    Magnetic sensors REED type

    Magnetic sensors HALL effect

    MAGNETIC SENSORSFOR CYLINDERS

    8

  • 8/10/2019 Signal Give Re

    2/7

    General

    The limit switches, or magnetic sensors, have to be mounted on cylinders with magnetic piston. These, when hitby the magnetic field generated by the piston as it approaches, close the circuit sending an electrical signal byrel solenoid valve control, etc. or converse with the controlling electronic system situaded on the machine.

    There are available magnetic sensor with ampulla Reed type and with Hall effect. The sensors are attached tothe cylinder by a proper clamp and havea Led insertion indicator.Themagnetic sensors with ampulla are made in 3 versions:- U (universal) functioning with continuous or alternate current, protected by varistor Led indicator.- U/1(universal) functioning with continuous or alternate current, with contact Reed only to avoid 3 volt tensiondrop caused by led.- D.C. for functioning with continuous current only, utilized for switching heavy loads since the contact Reedbecome the pilot of a semi-conductor power circuit.

    Note: The magnetic sensorsare according tothe Directive and following amendments.EMC89/336/CEE

    Magnetic sensors for cylinders

    8.0

    Instruction on how to use the sensors properly

    Particular attention must be paid not to exceed the working limits listed in the tables and that the sensor is neverconnectedto the mains without a load connectedin series; theseare theonly measures that if not observed canput the circuits out of order. In the case of direct current ( D.C.) connection polarities must be respected, that isthe brown wire to the positive load (+) and the blue to the negative (-). If these are inverted the sensor remainsswitched, the load connected and the ledturned off. However, this would not damage the circuit.For the"U" type sensors attention must be paid that the length of the cabledoesn't exceed 8 meters, with tensionabove 100 V. In this case a serialresistance is added to reduce the capacitive effectsof the line.

    Asan example 1000 per 100-130 V e 2000 per 200-240 V.

  • 8/10/2019 Signal Give Re

    3/7

    Cylinders andmicrocylinders

    Rodless cylinders

    1500.D.C.1500.U

    1500.U/1

    1600.D.C.1600.U1600.U/1

    Magnetic sensors for cylinders

    for cylinders and microcylinders for rodless cylinders

    8.1

    Ordering code

    Diagrams andconnections

    27 15,5

    14

    ,5

    27 12

    14

    ,5

    Maximum permanent current

    Maximum current (pulses of 0,5 sec.)

    Voltage range

    Maximum permanent power

    Working temperature

    Maximum voltage drop

    Cable section

    Degree of protection

    Connecting time

    Disconnecting time

    Average working period

    Repetition of intervention point

    Contact normally open

    1,2A

    1,5A

    12 48V

    57W

    3 250V

    20VA

    12 48V

    15W

    0 250V

    10VA

    0 48V

    8W

    3V

    2x0,35 mm

    IP 65

    2 ms

    1 ms

    10 cicles

    0,1 mm

    N.O.

    -20 C 70 C

    0V

    0,5A

    1A

    0,3A

    0,8A

    a.c.

    U U/1

    a.c.d.c.

    d.c. d.c. Type - d.c.

    bl

    bn

    Type - U

    bl

    bn

    Type U/1

    bl

    bn

    Sensors with 2 m. cable (REED type)

    8

    Technical characteristics

    Connection can be done either to negative or positive pole.

    These sensors can be used on cylinders series:

    1200 1260..F1280..F

    1306 - 1307 - 1308 1306.A1306.B1306.C

    1319 - 1320 1320.A1320.B1320.C

    1320.D1500

    1600 1600.A

    formicrocylind. with rolledend covers, with clampscodefor microcylind.withthreadedend covers, withclampscode for cylinders from16 to32

    brackets code for cylinders from 32 to 63for cylinders from 80to 125forcylinders from 160 and200

    brackets code for cylinders 32 and 40for cylinders 50and 63for cylinders 80and 100

    forcylinders 125directly on groove

    brackets code

    sensor for continuous current with ledsensor universal with led

    sensor universal without led (REED ampulla only)

    sensor for continuous current with ledsensor universal with ledsensor universal without led (REED ampulla only)

    7

    LOAD

    LOAD

    LOAD

  • 8/10/2019 Signal Give Re

    4/7

    These sensors can be used on cylinders series:

    1200 1260..F1280..F

    1306 - 1307 - 1308 1306.A1306.B1306.C

    1319 - 1320 1320.A1320.B1320.C1320.D

    1500

    1600 1600.A

    formicrocylind.withrolledend covers, with clampscodefor microcylind.with threadedend covers, withclampscode for cylinders from16 to32

    brackets code for cylinders from 32 to 63forcylinders from 80to 125forcylinders from 160 and200

    brackets code for cylinders 32 and 40forcylinders 50and 63forcylinders 80and 100for cylinders 125

    directly on groove

    brackets code

    Magnetic sensors for cylinders

    for cylinders and microcylinders for rodless cylinders

    8.2

    Diagrams and

    connections

    Tipo - UC

    bl

    bn

    Tipo - UA

    bl

    bn

    Tipo UA/1

    bl

    bn

    Sensors with connector (REED type)

    30 15,5

    29

    14

    ,5

    30 12

    29

    1

    4,5

    Ordering code

    3 250V

    20VA

    12 48V

    15W

    0 250V

    10VA

    0 48V

    8W

    3V

    N.O. o N.C. N.O.

    2x0,35 mm

    IP 65

    2 ms

    1 ms

    10 cicles

    0,1 mm

    -20 C 70 C

    0V

    0,5A

    1A

    0,3A

    0,8A

    a.c.U U/1

    a.c.d.c. d.c.

    Technical characteristics

    Cylinders and sensor universal with led normally open N.O.microcylinders sensor universal w ithout led N.O. ( REED a mpulla only)

    sensor universal with led normally closed N.C.sensoruniversal with ledN.O. with connectorand 2,5m. cablesensoruniversal without led N.O. with connectorand 2,5m. cable (REED ampulla only)

    sensoruniversal with led N.C. with connectorand 2,5m. cable

    Rodless cylinders sensor universal with led N.O.sensor universal without led N.O.sensor universal with led normally closed N.C.sensoruniversal with ledN.O. with connectorand 2,5m. cablesensoruniversal without ledN.O. with connectorand 2,5m. cable (REED ampulla only)sensoruniversal with ledN.C. with connectorand 2,5m. cable

    connector with 2,5m. cableconnector with 5 m. cableconnectorwith 10 m. cable

    RS.UARS.UA/1RS.UCRS.UAC1RS.UAC1/1

    RS.UCC1

    SRS.UASRS.UA/1SRS.UCSRS.UAC1SRS.UAC1/1SRS.UCC1

    C1C2C3

    7

    LOAD

    LOAD

    LOAD

    Maximum permanent current

    Maximum current (pulses of 0,5 sec.)

    Voltage range

    Maximum permanent power

    Working temperature

    Maximum voltage drop

    Cable section

    Degree of protection

    Connecting time

    Disconnecting time

    Average working period

    Repetition of intervention point

    Contact normally open

    Connection can be done either to negative or positive pole.

  • 8/10/2019 Signal Give Re

    5/7

    Cylinders and sensor Hall effect PNP with led, normally open N.O.microcylinders sensor Hall effect NPN with led, normally open N.O.

    sensor Hall effect PNP with led, normally closed N.C.sensor Hall effect NPN with led, normally closed N.C.

    Rodless cylinders sensor Hall effect PNP with led, normally open N.O.sensor Hall effect NPN with led, normally open N.O.sensor Hall effect PNP with led, normally closed N.C.sensor Hall effect NPN with led, normally closed N.C.

    1500.HAP1500.HAN

    1500.HCP1500.HCN

    1600.HAP1600.HAN1600.HCP1600.HCN

    8

    Magnetic sensors for cylinders

    for cylinders and microcylinders for rodless cylinders

    8.3

    Ordering code

    Diagrams and connections

    27 15,5

    14

    ,5

    27 12

    14

    ,5

    Maximum permanent current

    Voltage range

    Power (inductive load)

    Working temperatureCable section

    Degree of protection

    Connecting time

    Disconnecting time

    Average working period

    Repetition of intervention point

    Type of contact

    10W

    10 30V DC

    3x0,25 mm

    IP 65

    0,8 s

    0,3 s

    10 cicles

    0,1 mm

    N. O. o N.C.

    -20 C 70 C

    0,5A

    Sensors with 3 m. cable (HALL effect)

    Technical characteristics

    These sensors can be used on cylinders series:

    1200 1260..F1280..F

    1306 - 1307 - 1308 1306.A1306.B1306.C

    1319 - 1320 1320.A1320.B

    1320.C1320.D

    1500

    1600 1600.A

    for microcylind.withrolled end covers, with clampscodefor microcylind.withthreadedend covers, withclampscode for cylinders from16 to32

    brackets code for cylinders from 32 to 63forcylinders from 80to 125forcylinders 160 and200

    brackets code for cylinders 32 and 40forcylinders 50and 63

    forcylinders 80and 100for cylinders 125

    directly on groove

    brackets code

    9

    PNP

    brown

    blu

    black

    LOAD

    NPN

    brown

    blu

    black

    LOAD

  • 8/10/2019 Signal Give Re

    6/7

    Cylinders and sensor Hall effect PNP with led, normally open N.O.

    microcylinders sensor Hall effect NPN with led, normally open N.O.sensor Hall effect PNP N.O. with led, with connector and 2,5 m. cablesensor Hall effect NPN N.O. with led, with connector and 2,5 m. cable

    Rodless cylinders sensor Hall effect PNP with led, normally open N.O.sensor Hall effect NPN with led, normally open N.O.sensor Hall effect PNP N.O. with led, with connector and 2,5 m. cablesensor Hall effect NPN N.O. with led, with connector and 2,5 m. cable

    connector with 2,5 m. cable (3 wires)connector with 5 m. cable (3 wires)

    HS.PA

    HS.NAHS.PAC1HS.NAC1

    SHS.PASHS.NASHS.PAC1SHS.NAC1

    CH1CH2

    8.4

    6 30V DC

    6W

    3x0,25 mm

    IP 65

    0,8 s

    0,3 s

    10 cicles

    0,1 mm

    N. O.

    -20 C 70 C

    0,25A

    Technical characteristic

    9

    Diagrams and connections

    PNP

    brown

    blu

    black

    LOAD

    NPN

    brown

    blu

    black

    LOAD

    for cylinders and microcylinders for rodless cylinders

    Sensor with connector (Hall effect)

    30 15,5

    29

    14

    ,5

    30 12

    29

    14

    ,5

    Ordering code

    These sensors can be used on cylinders series:

    1200 1260..F1280..F

    1306 - 1307 - 1308 1306.A1306.B1306.C

    1319 - 1320 1320.A1320.B1320.C1320.D

    1500

    1600 1600.A

    for microcylind.with rolledend covers, with clamps codefor microcylind.with threadedend covers, withclampscode for cylinders from16 to32

    brackets code for cylinders from 32 to 63forcylinders from 80to 125forcylinders 160 and200

    brackets code for cylinders 32 and 40forcylinders 50and 63forcylinders 80and 100for cylinders 125

    directly on groove

    brackets code

    Magnetic sensors for cylinders

    Maximum permanent current

    Voltage range

    Power (inductive load)

    Working temperature

    Cable section

    Degree of protection

    Connecting time

    Disconnecting time

    Average working period

    Repetition of intervention point

    Contact normally open

  • 8/10/2019 Signal Give Re

    7/7

    These sensors can be used on cylinders series:

    1200 1280..FS

    1500

    microcylinders with threaded end covers, with clamps code

    - Shortstroke compact cylinders with sensor adapter cede1580.01F- Europecompact cylinders- directly on groovefrom 12 to 25

    - directly on grooveor with sensoradapter( code 1580.01F)from 32 to 50- with sensoradapter (code1580.01F) from 63to 100.

    1580.U1580.HAPMRS.UMHS.PMC1MC2MCH1MCH2

    Reed bulb sensor with led and 2.5 m cablePNP sensor Hall effect with led and 2.5 m cableReed bulb sensor with led and connectorPNP sensor Hall effect with led and connectorM8 in line connector with 2.5 m cable (2 wires)M8 in line connector with 5 m cable (2 wires)M8 in line connector with 2.5 m cable (3 wires)M8 in line connector with 5 m cable (3 wires)

    Sensor c/w 2.5 m. cable

    Sensor c/w M8 connector (300 mm cable)

    Ordering codes

    Type of contact

    Maximum current (pulses of 0,5 sec.)

    Maximum permanent current

    Maximum permanent power

    Voltage range A. C.

    Voltage range D. C.

    Working temperature

    Maximum voltage drop

    Cable section

    Degree of protection

    Connecting time

    Disconnecting time

    Average working period

    Repetition of intervention point

    Technical characteristics

    6VA

    3 30V

    3 30V

    4W

    /

    6 30V

    3V

    N.A.

    IP 65

    0,1

    2x0,14

    0,5 ms

    0,1 ms

    107

    3x0,14

    0,8 s

    0,3 s

    10

    9

    -20 C 70 C

    0,1A

    0,1A

    0,2A

    0,2A

    1580.U 1580.HAP

    NOTE : pay attention to the connected loads which should not exceed the recommendation

    Normal standard "PNEUMAX" sensors suitable for large slot are

    available for cylinders from 32 to 100 (see catalogue 4 section 8).

    MRS.U MHS.P

    Diagrams andconnections

    bl

    bn

    LOAD

    with Reed bulb

    Hall effect

    LOAD

    brown

    black

    blu

    Weight gr. 27

    Weight gr. 15

    6,5 5

    29

    4,3

    3

    26,5

    M8

    x1

    29 300 mm

    8.5

    Slot detail

    2,1

    5,5

    6,8

    5,2

    Series 1500Magnetic sensor for cylinders

    8