RWD heatpump controllersXavier Zabalegui/David Jefferson
1January 2003
Siemens Building Technologies
RWD Heat Pump controllers
RWD Heat Pump Controllers
RWD heatpump controllersXavier Zabalegui/David Jefferson
2January 2003
Siemens Building Technologies
Heat pump Controllers
Why?
Rapid growth in the use of heat-pump technology throughout North America
Sell applications, not components
Increase sales of valves and damper actuators
Wholesalers purchasing competitor’s controllers (T775, A350)
Increase RWD range
RWD suitable for commercial applications
RWD heatpump controllersXavier Zabalegui/David Jefferson
3January 2003
Siemens Building Technologies
RWD44U
• Standard RWD design• New LCD with clear heat/cool output status• New Digital input options• Alarm inputs• Suitable for Ni1000, Pt1000 or 0-10vdc
inputs• Heat/cool or reversing valve/compressor
config• Flexible output delay times• Usable defaults
Our standard solution Our standard solution for commercial heat for commercial heat pumps.pumps.
Easy and flexible Easy and flexible settingssettings
RWD heatpump controllersXavier Zabalegui/David Jefferson
4January 2003
Siemens Building Technologies
RWD Heat pump controllers
RWD44U
Standard RWD format with LCD Button or software tool parameter setting (4) digital outputs configurable Air to Air / Air to Water Heat-pumps Suitable for single, dual and triple compressor units Auxiliary functions applicable to Heat-pumps 24vac
RWD heatpump controllersXavier Zabalegui/David Jefferson
5January 2003
Siemens Building Technologies
RWD44U Internal diagram
“Removable terminals are also
labeled. Disconnect when
commissioning”
G D1 GND X1 M X2 M
G0 14 11 22 24 21 32 34 31 44 41
TOOL
RWD44Q1 Q2 Q3 Q4
RWD heatpump controllersXavier Zabalegui/David Jefferson
6January 2003
Siemens Building Technologies
Two-stage heating and cooling
RWD heatpump controllersXavier Zabalegui/David Jefferson
7January 2003
Siemens Building Technologies
Three stage (CR)compressor - (RV)reversing valve
S1= D/N C/O
X1= main sensor
X2= Remote setpoint
RWD heatpump controllersXavier Zabalegui/David Jefferson
8January 2003
Siemens Building Technologies
RWD44U/45U Aux Functions & Digital Input options
Auxiliary Functions
Remote setpoint
Compensation shift
Two sensor averaging
Winter/summer setpoint selection
Sensor select
Active input
Digital input options
Standby (on/off)
Alarm
Filter alarm
Day/night setpoints
# Refer to application chart for
combinations
RWD heatpump controllersXavier Zabalegui/David Jefferson
9January 2003
Siemens Building Technologies
RWD44U/45U Digital input options
Standby (on/off)
SEH62.1U
RWD heatpump controllersXavier Zabalegui/David Jefferson
10January 2003
Siemens Building Technologies
RWD44U/45U Digital input options
Alarm
External shutdown,
Flow switch, smoke,
Common alarm from heat pump
AlarmAlarm
RWD heatpump controllersXavier Zabalegui/David Jefferson
11January 2003
Siemens Building Technologies
RWD44U/45U Digital input options
Filter Alarm
Avoid heat pump breakdowns
Warning for maintenance personnel to change filter
RWD heatpump controllersXavier Zabalegui/David Jefferson
12January 2003
Siemens Building Technologies
RWD44U/45U Digital input options
Day & Night Setpoints
Keep internal temperatures within acceptable limits during unoccupied periods
SEH62.1U
RWD heatpump controllersXavier Zabalegui/David Jefferson
13January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
“Setpoint adjustment should be
mechanically limited”
Remote setpoint
RWD heatpump controllersXavier Zabalegui/David Jefferson
14January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
Compensation shift
Enhanced comfort and
energy savings
X2= SP= X2= SP=
RWD heatpump controllersXavier Zabalegui/David Jefferson
15January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
Sensor averaging
In some areas the temperature may vary from one location to another.
X1 X2
RWD heatpump controllersXavier Zabalegui/David Jefferson
16January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
Sensor Select
Flexible solution for special applications. Typical example is a general office area with a seldom used meeting room. Office area Meeting room
OR
X2 X1 X2 X1
RWD heatpump controllersXavier Zabalegui/David Jefferson
17January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
Winter/Summer setpoint selection
(Digital)
Heat pumps for 2-pipe systems (return water temperature control)
SP = 76° SP = 72°
RWD heatpump controllersXavier Zabalegui/David Jefferson
18January 2003
Siemens Building Technologies
RWD44U/45U Aux functions
Winter/Summer setpoint selection
(Analog)
Heat pumps for 2-pipe systems (return water temperature control)
SP = 72° SP = 76°
RWD heatpump controllersXavier Zabalegui/David Jefferson
19January 2003
Siemens Building Technologies
RWD45U
• Standard RWD44U design• Same auxiliary functions• LCD with monitoring of all inputs/outputs• Three universal inputs• New OpenAir™ economizer control• No need for hi/low limit thermostats• A single active O/A sensor can be used for a
group of controllers
““OpenAir™ economizer”OpenAir™ economizer”
oror
“ “RWD44U+ 2nd RWD44U+ 2nd independent universal independent universal
modulating loop”.modulating loop”.
RWD heatpump controllersXavier Zabalegui/David Jefferson
20January 2003
Siemens Building Technologies
RWD Heat pump controllers
RWD45U
Standard RWD44U format with LCD Button or software tool setting Air to Air / Air to Water Heat-pumps (4) DO’s and (1) AO configurable Suitable for single, dual and triple compressor units Economizer control or 2nd independent (Y) loop New OpenAir™ economizer sequence 24vac
RWD heatpump controllersXavier Zabalegui/David Jefferson
21January 2003
Siemens Building Technologies
RWD45U Internal diagram
G D1 GND X1 M X2 M
G0 14 11 22 24 21 32 34 31 44 41
X3 M TOOL
Y1 M
RWD45Q2 Q3 Q4Q1
RWD heatpump controllersXavier Zabalegui/David Jefferson
22January 2003
Siemens Building Technologies
RWD45U - OpenAir™ economizer control
Remember the days when you could just open a Remember the days when you could just open a window?window?
Why use cooling energy when the outside air temperature is suitable for cooling?
The OpenAir™ economizer feature simply shifts the 1st cooling stage and replaces it with a 0 -10vdc cooling output. This occurs only when cooling is required and the outside temperature is suitable.Introduce outside air via damper actuators.
Economizer control is not a new innovation, however the RWD45U OpenAir™ solution is an easily implemented and understood concept. “AffordableAffordable””
RWD heatpump controllersXavier Zabalegui/David Jefferson
23January 2003
Siemens Building Technologies
RWD45U - OpenAir™ economizer control
SP_C1 SP_C2SP_H2
Q3 Q4Q2Q1
SP_H1 Q
SP_C1 SP_C2
Q3 Q4Q2
SP_H1 Q0 V
10V
Normal Mode (Economy mode inactive)
Economy Mode Ymax
YminSP_H2
Q1
Xp
Y1
ON
OFF
ON
OFF
SD_C2SD_C1SD_H1SD_H2
3347d01
Economy mode is active only when cooling is required and the X2 temperature is within the maximum and
minimum limits.
Eco Parameters
Min X3 limit
Max X3 limit
Eco - Xp
Y min
Y max
RWD heatpump controllersXavier Zabalegui/David Jefferson
24January 2003
Siemens Building Technologies
RWD45U - OpenAir™ economizer controlMain benefits
Improved air quality
Reduced compressor running time
Reduced wear on compressor, condenser fan etc
Reduce installation costs:
1. Additional outside air limit thermostats not required
2. A single active outside air sensor could be used for multiple controllers
Reduced energy consumption - Save
We can offer our customers a complete We can offer our customers a complete packagepackage
RWD heatpump controllersXavier Zabalegui/David Jefferson
25January 2003
Siemens Building Technologies
Two-stage heating and cooling
RWD45
MD1
G0
G X2GND
AC 24V
X1 X2S1
G0
X1 M MX3
X3
TOOL Y1 M
,
C1
AC 24V
(N)
G0
11 21 31 41
14 22 24 32 34 44
Q
H2 H1 C2
PC
(L)
Y1
3347g03
B MMB B MMBGG
RWD heatpump controllersXavier Zabalegui/David Jefferson
26January 2003
Siemens Building Technologies
Three stage (CR)compressor - (RV)reversing valve
RWD45
B M
MD1
G0
G X2GND
AC 24V
X1 X2S1
G0
X1 M MX3
X3
TOOL Y1 M
,
CR2
AC 24V
(N)
G0
11 21 31 41
14 22 24 32 34 44
Q
RV CR1 CR3
PC
(L)
Y1
3347g02
MGB B M
G
RWD heatpump controllersXavier Zabalegui/David Jefferson
27January 2003
Siemens Building Technologies
RWD45U - Special applications (example)
Packaged water heat pump including supply water control valve via 2nd independent loop
X1 controls primary heat pump water temp with X3 controlling the supply water temp to the coils
Water system
RWD heatpump controllersXavier Zabalegui/David Jefferson
28January 2003
Siemens Building Technologies
RWD45U - Special applications (example)
Rooftop or split heat pump including air quality control via 2nd independent loop
X1 controls heat pump room temp with X3 controlling the CO2/VOC level within room Air / AQ
AQ processor
RWD heatpump controllersXavier Zabalegui/David Jefferson
29January 2003
Siemens Building Technologies
RWD45U - Special applications (example)
Rooftop or split heat pump including humidifier control via 2nd independent loop
X1 controls heat pump room temp with X3 controlling the humidifier output to room Air /
humidity
RWD heatpump controllersXavier Zabalegui/David Jefferson
30January 2003
Siemens Building Technologies
RWD45U - Special applications (example)
Stage control of heat pump including remote monitoring of X1 temperature
X1 controls heat pump room temp with Y1 supplying the equivalent signal in 0-10vdc format. Could also control remote SP and stop/start
Remote display
DDC
PLC
Alarm system
Input to another
controller
Air or Water
RWD heatpump controllersXavier Zabalegui/David Jefferson
31January 2003
Siemens Building Technologies
RWD for commercial applications
RWD must be recommended for commercial applications
Protection against unauthorized adjustment, equipment damage and nuisance service calls.
Optimum comfort and energy savings
MMI should not be available for occupants
Fan speed control should only be applied to residential or small room applications
RWD heatpump controllersXavier Zabalegui/David Jefferson
32January 2003
Siemens Building Technologies
RWD heat pump controllers
Inside a typical heat pump
Rooftop packaged unit Indoor packaged unit