SUBSTRATES FLOORS CEMENT SHEET CONCRETE WALLS BUILDING BOARD GYPSUM/CEMENT CONCRETE BRICK BLOCK CEMENT RENDER Shower Waterproofing System WATERPROOF SHOWER ALCOVES PRIOR TO TILING CONSTRUCTION CHEMICALS W1 Conforms to AS/NZS 4858 Class 3 DESCRIPTION A waterproofing kit for enclosed shower alcoves. Suitable for use on concrete, compressed cement sheeting and walls constructed of brick, block, render, cement sheeting and waterproof gypsum building board. COVERAGE (Approximate) 2 litre/m 2 at 1.5mm dry film thickness. CONTENTS OF KIT • 1 litre PRIMER AND GROUT ADDITIVE • 4 litre HYDRATHANE • 140mm REOMAT • 50mm Bond breaking tape • Brush APPLICATION SURFACE PREPARATION Waterproofing must be in accordance with AS3740 Surfaces to be waterproofed must be sound and free of dirt, dust, grease and other contaminants and allowed to dry before priming.The waste hole in compressed cement flooring must be cut no more than 5mm larger than the waste external diameter.Recess drainage flange.New concrete must have cured for 28 days. PRIMING Apply PRIMER & GROUT ADDITIVE with a brush to the prepared dry surface. When the surface becomes dry (after approximately 15-20 minutes) apply the HYDRATHANE – wash up with clean water. BOND BREAKER Place 50mm Bond Breaker at the floor/hob and wall/wall junctions and joins in sheeting equally to both surfaces. This will allow for greater movement accommodation,should it occur. JOINTS/CRACKS IN BUILDING SURFACES At junctions in building surfaces and over cracks place a bond breaker,tape or neutral cure silicone bead (as per ASNZ 4858/2004) and reinforce the first wet coat with 140mm REOMAT (to accommodate extremes in movement).Place the bond breaker/silicon bead and REOMAT centrally over the joint or crack. APPLY 1st COAT Apply a thick coat (1.5mm wet) of HDYRATHANE 75mm either side of the wall junctions and around tap outlets. Coat the remainder of the floor and wall.Take care to seal around the tap and faucet outlets. Recoat time: Two hours (depending on weather conditions). Application Temperature: Apply coating in ambient temperatures between 10°–30°C. APPLY a 2nd COAT Apply a 2nd coat of HYDRATHANE to the area to be tiled – recoat time is 2 hours. Apply the second coat of HYDRATHANE at 90° to all of the previous coat applying a thick coat (1.5mm wet) to ensure final dry thickness of 1.5mm. Clean up the uncured coating with clean water. THICKNESS Check the wet film thickness at 0.5 metre intervals and also at 0.5 metres along the bond breaking tape, with a wet film thickness gauge. ADHERE TILES Allow the membrane to cure for 72 hours before fixing tiles with KEMGRIP FLOOR AND WALL mixed with ELASTACRETE or KEMFLEX 2:1, GRIPFLEX, MONOFLEX.Tiles must be laid so that adequate fall is towards the floor waste. A cement screed can be used to achieve this. GROUTING Allow adhesive to cure 24 hours before grouting with KEMGROUT FLEXIBLE. COLOUR SEAL is applied to the surface at the junction of wall/wall, wall/floor and hob/floor, hob/wall in place of the grout. PRECAUTION Allow the HYDRATHANE to cure for 28 days before putting into use. It is advisable to flood test the shower after curing (approx. 72 hours 20°C 50 RH).This should be done before tiling commences. PACKAGING MIXING APPLICATION USES SAFETY PRECAUTIONS HYDRATHANE and PRIMER AND GROUT ADDITIVE are not harmful or toxic. Splashes on the skin and eyes must be washed away with clean water. Apply products in well ventilated areas. 037 MARCH 09

Transcript of Shower Waterproofing System

Page 1: Shower Waterproofing System

SUBSTRATES

FLOORSCEMENT SHEET

CONCRETE

WALLSBUILDING BOARDGYPSUM/CEMENT

CONCRETEBRICKBLOCK

CEMENT RENDER

Shower Waterproofing SystemWATERPROOF SHOWER ALCOVES PRIOR TO TILING

CONSTRUCTIONCHEMICALS

W1

Conforms to AS/NZS 4858 Class 3

DESCRIPTIONA waterproofing kit for enclosed shower alcoves. Suitable for use on concrete, compressed cement sheetingand walls constructed of brick, block, render, cement sheeting and waterproof gypsum building board.

COVERAGE (Approximate)2 litre/m2 at 1.5mm dry film thickness.

CONTENTS OF KIT• 1 litre PRIMER AND GROUT ADDITIVE • 4 litre HYDRATHANE• 140mm REOMAT • 50mm Bond breaking tape • Brush

APPLICATIONSURFACE PREPARATIONWaterproofing must be in accordance with AS3740Surfaces to be waterproofed must be sound and free of dirt, dust, grease and other contaminants and allowed to drybefore priming. The waste hole in compressed cement flooring must be cut no more than 5mm larger than the wasteexternal diameter. Recess drainage flange. New concrete must have cured for 28 days.

PRIMINGApply PRIMER & GROUT ADDITIVE with a brush to the prepared dry surface. When the surface becomes dry (afterapproximately 15-20 minutes) apply the HYDRATHANE – wash up with clean water.

BOND BREAKERPlace 50mm Bond Breaker at the floor/hob and wall/wall junctions and joins in sheeting equally to both surfaces. Thiswill allow for greater movement accommodation, should it occur.

JOINTS/CRACKS IN BUILDING SURFACESAt junctions in building surfaces and over cracks place a bond breaker, tape or neutral cure silicone bead (as per ASNZ4858/2004) and reinforce the first wet coat with 140mm REOMAT (to accommodate extremes in movement). Placethe bond breaker/silicon bead and REOMAT centrally over the joint or crack.

APPLY 1st COATApply a thick coat (1.5mm wet) of HDYRATHANE 75mm either side of the wall junctions and around tap outlets.Coat the remainder of the floor and wall.Take care to seal around the tap and faucet outlets. Recoat time: Twohours (depending on weather conditions). Application Temperature: Apply coating in ambient temperaturesbetween 10°–30°C.

APPLY a 2nd COATApply a 2nd coat of HYDRATHANE to the area to be tiled – recoat time is 2 hours. Apply the second coat ofHYDRATHANE at 90° to all of the previous coat applying a thick coat (1.5mm wet) to ensure final dry thickness of1.5mm. Clean up the uncured coating with clean water.

THICKNESSCheck the wet film thickness at 0.5 metre intervals and also at 0.5 metres along the bond breakingtape, with a wet film thickness gauge.

ADHERE TILESAllow the membrane to cure for 72 hours before fixing tiles with KEMGRIP FLOOR AND WALL mixed withELASTACRETE or KEMFLEX 2:1, GRIPFLEX, MONOFLEX.Tiles must be laid so that adequate fall is towards the floorwaste. A cement screed can be used to achieve this.

GROUTINGAllow adhesive to cure 24 hours before grouting with KEMGROUT FLEXIBLE. COLOUR SEAL is applied to thesurface at the junction of wall/wall, wall/floor and hob/floor, hob/wall in place of the grout.

PRECAUTIONAllow the HYDRATHANE to cure for 28 days before putting into use. It is advisable to flood test the shower aftercuring (approx. 72 hours 20°C 50 RH).This should be done before tiling commences.

PACKAGING

MIXING

APPLICATION

USES

SAFETY PRECAUTIONSHYDRATHANE and PRIMER AND GROUT ADDITIVE are not harmful or toxic. Splashes on the skinand eyes must be washed away with clean water. Apply products in well ventilated areas.

037 MARCH 09

Page 2: Shower Waterproofing System

CONSTRUCTIONCHEMICALS

l ADELAIDE 135 CORMACK RD (Cnr Davis St) WINGFIELD 5013 PH: (08) 8243 7888 FAX: (08) 8243 7800l BRISBANE 45 COULSON ST WACOL 4076 PH: (07) 3271 2944 FAX: (07) 3271 3892l MELBOURNE 11 GABRIELLE CT BAYSWATER NORTH 3153 PH: (03) 9761 4711 FAX: (03) 9761 4748l PERTH 11 COLLIE ST WELSHPOOL 6106 PH: (08) 9356 9999 FAX: (08) 9356 9955l SYDNEY 31-33 NEWTON RD WETHERILL PARK 2164 PH: (02) 9756 3533 FAX: (02) 9756 3534l AUCKLAND 16 CARPENTER RD EAST TAMAKI PH: (09) 273 5444 FAX: 0800 266 236 l KUALA LUMPUR LOT 2 JALAN KECAPI 33/2 ELITE INDUSTRIAL ESTATE OFF JALAN BUKIT KEMUNING

40000 SHAH ALAM PH: (603) 5122 2522 FAX: (603) 5122 2526

www.constructionchemicals.com.au

“The information contained in this technical publication is based on our current knowledge and experience and is provided as a guide only. In view of the many factors that may affect application it is the user’s soleresponsibility to ensure suitability for a specific purpose.”

APPLY BONDBREAKING TAPE TO

JOINTS

BOND BREAKER

TO HEIGHT OFTILE AREA

BOND BREAKER

BONDBREAKER

1.8m

DRAINAGEFLANGE

35-40mm WIDE HOLESFOR LEAK CONTROL

FLANGE

APPLY THE 2nd COAT TO FLOOR & WALLS

1.8m

COMPLETED SHOWER ALCOVE

1.8m

COLOUR SEAL

APPLY PRIMER APPLY 1st COAT TO THE WALL & FLOOR

1.8m

Waterproofing an Enclosed Shower

Floor waste in a concrete floor

Floor waste connected to timber or cement sheet flooring

Floor sheeting/Wall board Junction

Floor & Wall Junction

Floor & Wall Junction

Tap or Fitting Connection

Bond breaker

2 coats of HYDRATHANEapplied to a minimum finaldry film thickness of 1.5mm(ie. 2 @ 1.5mm wet coats)

Bond breaker

Floor

Wall2 coats ofHYDRATHANE appliedto a minimum final dryfilm thickness of 1.5mm(ie. 2 @ 1.5mm wetcoats)

Flooring

Drainage Flange

Waste

Drill hole no greater than5mm larger than the base

of the drainage flange

Ceramic Tiles

2 coats of HYDRATHANEapplied to a minimum finaldry film thickness of 1.5mm(ie. 2 @ 1.5mm wet coats)

Concrete floor

Drainage Flange

Waste

Ceramic Tiles

2 coats of HYDRATHANEapplied to a minimum finaldry film thickness of 1.5mm(ie. 2 @ 1.5mm wet coats)

Place silicone betweentile and flange of DripControl Flange

Tap Stem

Masonry wallgrooved toaccommodatetap body

Tap body

Wall

Ceramic Tiles

Wall Boardor Plaster

Drip Control Flange

2 coats of HYDRATHANE applied to aminimum final dry film thickness of1.5mm (ie. 2 @ 1.5mm wet coats)

Flooring

DrainageFlange

Ceramic tiles

Shower screen

1.8

m

HobGrate

COLOURSEAL

COLOURSEAL

Bond Breaker

Floor gradedto waste

Screed

Floor gradedto waste

2 coats ofHYDRATHANEto the wall

Apply 2 coats ofHYDRATHANE above or

below screed, applied to aminimum final dry film

thickness of 1.5mm to floorand 100mm up the

wall & hob (ie. 2@ 1.5mm wet coats)

Bond Breaker