Short form Manual ANALYST3Q and WinA3Q Contents:
1 Installation of WinA3Q.....................................................................................................1 2 Installation of PQDIF-Browser TOP 2000.....................................................................3 3 Recording of measurement data with ANALYST 3Q..................................................8 4 Reading of measured values ........................................................................................10 5 Evaluation of measurement data with TOP2000.......................................................14
1 Installation of WinA3Q Insert CD-ROM “WinA3Q” Double click “setup.exe” and follow the instructions on screen:
Oskar MELICHAR – PM PQP January 2002
Select a program folder:
Oskar MELICHAR – PM PQP January 2002
Installation is finished and WinA3Q can be launched immediately:
2 Installation of PQDIF-Browser TOP 2000 The actual version of TOP 2000 (The Output Processor) can be downloaded from:
http://www.pqsoft.com/top/ TOP2000 is a freeware PQDIF browser for comprehensive evaluation of measurement data acquired with ANALYST 3Q and other Power Quality measurement instruments. Start the installation wizard by double clicking setup.exe:
Oskar MELICHAR – PM PQP January 2002
Please read carefully the license agreement:
For a complete installation it is necessary to agree!:
Oskar MELICHAR – PM PQP January 2002
Read and accept the license agreement for TOP 2000:
There is some special information about the actual release:
Oskar MELICHAR – PM PQP January 2002
Follow the instructions on screen:
Oskar MELICHAR – PM PQP January 2002
Select the required import filters (PQDIF):
Oskar MELICHAR – PM PQP January 2002
3 Recording of measurement data with ANALYST 3Q
• Install the ANALYST 3Q on the measuring site, select function “PQ” for power quality measurements
• Wait until the flicker filters are initialised (appr. 2 minutes)
• Set the required averaging time with the menu functions e.g. 10 minutes for measurements compliant with EN50160. - The interval can be set between 1 s and 20.000 seconds.
• Press “Record” to start the measurement
• In function PQ ANALYST 3Q will record up to 9600 intervals based on the preset averaging interval. The test can be aborted any time by pressing button “Record” again.
Measuring periods:
Maximum recording period Meas. Function
Intervals max. Averaging interval
1s 10min 15min 20.000s
V/A/Hz 240 4min 40h (1d 16h) 60h (2d 12h) 55d 13h 12 min
W 240 4min 40h (1d 16h) 60h (2d 12h) 55d 13h 12 min
Flicker 240 4min 40h (1d 16h) 60h (2d 12h) 55d 13h 12 min
PQ 9600 2h 40min 66d 16h 100d appr. 6 years
Oskar MELICHAR – PM PQP January 2002
ANALYST 3Q will record the following parameters for each measuring interval:
Measuring function Stored parameters
Volts/Amps/Hertz
Voltages U1, U2, U3, RMS average, min, max values
Currents I1, I2, I3, RMS average, min, max values
Frequency, average, min, max values
W - Power
Currents I1, I2, I3, RMS average, min, max values
Active power P1, P2, P3, average, min, max values
Apparent power S1, S2, S3, average, min, max values
Reactive power Q1, Q2, Q3, average, min, max values
Distortion power D1, D2, D3, average, min, max values
Frequency, average, min, max values
Power factor PF1, PF2, PF3, average, min, max values
Events
Voltages L1, L2, L3, min, max of 10ms RMS values
Events, counters
Flicker
Pst L1, L2, L3, average, min, max
Plt L1, L2, L3, average, min, max
PQ
Voltages U1, U2, U3, RMS average values
Currents I1, I2, I3, RMS average values
Frequency, average values
Events L1, L2, L3, number of events per phase
Unbalance, average values
Flicker Pst L1, L2, L3, average values
Flicker Plt L1, L2, L3, average values
THD U L1, L2, L3, average values
THD I L1, L2, L3, average values
Active power P1, P2, P3, average values
Apparent power S1, S2, S3, average values
Reactive power Q1, Q2, Q3, average values
Distortion power D1, D2, D3, average values
Oskar MELICHAR – PM PQP January 2002
4 Reading of measured values
• Power on the ANALYST 3Q and make sure that it is in the HOLD mode (press Run/Hold once)
• Connect ANALYST 3Q to a serial port of your PC
• Run the WinA3Q software Select COM port ANALYST 3Q is connected to, the language and picture size for exporting screen shots
• Select menu File-Import:
Oskar MELICHAR – PM PQP January 2002
• WinA3Q displays an overview of all available screenshots and the recording file:
• Menu File:
Open opens a previously stored file from the PC Save saves the actual diagram (right side of window) to a file in format .bmp Print prints actual diagram on system printer Printer setup opens a dialog for definition of printer settings Import import measured values from the ANALYST 3Q Export exports recorded data to a file in PQDIF-format with the extension .pqd Exit exits WinA3Q
Oskar MELICHAR – PM PQP January 2002
• Menu Edit:
Copies the marked diagram to the Windows® clipboard for evaluation in other applications
• Menu settings:
Select the COM port for connection to ANALYST 3Q, the language of WinA3Q, the dimensions of the diagram which can be stored as bmp file.
Oskar MELICHAR – PM PQP January 2002
• Menu Help
Provides information about PQDIF browser:
and actual version of WinA3Q:
Normally you will copy screen shots to the Windows® clipboard, save them as .bmp file and export recordings to PQDIF files, which can be evaluated perfectly in the freeware PQDIF browser TOP 2000.
Oskar MELICHAR – PM PQP January 2002
5 Evaluation of measurement data with TOP2000
• Open TOP 2000 software
• Open a file you have exported with WinA3Q: TOP 2000 presents all available measurement rows. For a comprehensive evaluation select ALL and confirm with OK.
Oskar MELICHAR – PM PQP January 2002
Now all data are on the stack of TOP 2000 and we can create all required presentations:
Select the parameter for creation of a level time diagram:
Oskar MELICHAR – PM PQP January 2002
There are extensive functions: Tables:
Statistics, mathematical functions for calculations offer nearly unlimited evaluations. There are numerous settings to create the best type of presentation:
Oskar MELICHAR – PM PQP January 2002
Some examples:
For details see the comprehensive help documentation about TOP 2000 available on the internet.