Copyright @ Power Research & Development Consultants Pvt. Ltd SHORT CIRCUIT STUDIES 1

Transcript of SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @...

Page 1: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

SHORT CIRCUIT STUDIES

1

Page 2: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd2

Short circuit study

Requirements:

1. Determining the fault level at buses

2. Selection of breaker ratings

3. Protective device co-ordination

Page 3: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd3

Symmetrical components

Unbalanced system of „n‟ related phasors can be resolved to „n‟ system of balanced phasors.

In each balanced phasor, angle between two phasors andmagnitude of each phasor are equal.

Phase Quantities: Ia , Ib & Ic and

Sequence components are :

Ia1 stands for Positive sequence current.

Ia2 stands for Negative sequence current.

Ia0 stands for Zero sequence current.

Page 4: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd4

Sequence components

Ia1, Ib1 & Ic1 : Same phase sequence as Ia, Ib & Ic

Ia2, Ib2, & Ic2 :Opposite phase sequence as Ia, Ib and Ic

Ia0, Ib0, & Ic0 : All in-phase

Page 5: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd5

Ia

Ic

Ib

Ia1

Ic1

Ib1

120

120

120 Ia2

Ib2

Ic2

120

120

120

Ia0 Ib0

Ic0

Unbalanced current phasor

Positive sequence current

phasors

Negative sequence current

phasors

Zero sequence current phasor

Sequence components

Page 6: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd6

Similarly for voltages:

c0c2c1c

b0b2b1b

a0a2a1a

VVVVVVVVVVVV

++=++=++=

=

a0

a2

a1

2

2

c

b

a

VVV

1aa

1aa

111

VVV

Page 7: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd7

sequencetoPhaseps

aa

aa

T

phasetoSequencespand

aa

aa

aaT

ps

sp

111

1

1

3

1

12012401,1201

1

1

2

2

2

2

2

111

Page 8: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd8

Therefore no zero sequence exists in line voltagephasor.

Since phase voltage sum is not always zero, in thephase voltage phasor, the zero sequence voltageexists.

alwaysVVV

VVVV

V

V

V

aa

aa

V

V

V

LcLLbLLaL

cbaa

c

b

a

a

a

a

0

3

1

111

1

1

3

1

0

2

2

0

2

1

Page 9: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd9

I

I

I

a a

a a

I

I

I

I I I I

a

a

a

a

b

c

a a b c

1

2

0

2

2

0

1

3

1

1

1 1 1

1

3

Ia

a

b

Ib

Ic

c

Ia+ Ib + Ic= 0

Therefore no zero sequence current flows

into delta connection.

Sequence Currents:

Page 10: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd10

Ia a

Ib

Ic

b

c

Star connection Star grounded

Ia

I0 a

3I0

Ib

Ic

I0

I0

b

c

Ia+Ib+Ic = 0, There foreno zero sequence currentflows into star connection

Ia+Ib+Ic may not be zero.Hence path always exists forzero sequence currents.

Page 11: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd11

Transformer sequence

impedance diagram

Star - Delta +ve and -ve Zero

Page 12: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd12

Transformer sequence impedance diagram

+ve and -ve ZeroStar grounded-Delta

Page 13: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd13

Transformer Connection to reduce the 3rd

harmonic content (flow)

• Inrush current (Magnetising current)

• 3rd harmonic content : 40 to 50 % of fundamental.

• No 3rd harmonic current.

Page 14: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd14

Three winding Transformer

Page 15: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd15

Sequence Impedance

a

b

c

a’

b’

c’

Zaa

Zbb

Zcc

c

b

a

cccbca

bcbbba

acabaa

'

cc

'

bb

'

aa

I

I

I

ZZZ

ZZZ

ZZZ

V

V

V

Let Zaa = Zbb = Zcc = Zs and Zab = Zac = Zba = Zbc = Zca

= Zcb = ZmTsp Vs = [Z] . Tsp.Is

Page 16: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd16

V Z Z IV Z Z IV Z Zm I

a s m a

a s m a

a s a

1 1

2 2

0 02

Page 17: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd17

For Rotating Machines

Za,b,c is not symmetric. Even then, the Z1,2.0 is

diagonalized.

Exercise:

V

V

V

Z Z Z

Z Z Z

Z Z Z

I

I

I

a

b

c

s m m

m s m

m m s

a

b

c

1 2

2 1

1 2

Find the expression for Z1,2,0

and Prove that it is a diagonal matrix:

Page 18: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd18

Advantages of Sequence Component

De-couples the equation to +ve, -ve and zerosequence and hence easy to solve.

End conditions can be applied easily for fault studiesin sequence components.

Since the equations are de-coupled, same set ofsubroutines can be called for solving the +ve, -ve andzero sequence system.

Page 19: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd19

Steady State

a

b

c

Ia

Ib

Ic

Ea

Ec Eb

ZnIn

+

+ +

Page 20: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd20

Positive Sequence Network

c

a

b

Ia1

Ib1

Ic1

Ea

Ec Eb

Z1

Z1

Z1

Z1

EaVa1

Ia1

Reference Bus

Va1 = E a - I a1 Z1

a

+

-

Page 21: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd21

Negative Sequence Network

c

Ia2

Ib2

Ic2

Z2

Z2

Z2

Z2

Va2

Reference Bus

Va2 = - Ia2 Z2

a

b

a

Page 22: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd22

Zero Sequence Network

c

a

b

Ia0

Ib0

Ic0

Zg0

3Zn

Va0

Reference Bus

Va3 = - Ia0 Z0

a Zg0

Zg0

Zn 3Ia0 Zg0

Z0

Page 23: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd23

Generator impedance for fault study :

1.Transient (xd‟) or sub-transient ( xd”) is considered for positivesequence.

2. X2 i.e. Negative sequence which is close to xd”. (Approximately).

3. X0 is small 0.1 to 0.7 times xd”

Typical values on own rating :

Xd 100 to 200 %

Xq 60 to 200 %

Xd‟ 21 to 41 %

Xd” 13 to 30 %

X2 Xd”

Page 24: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd24

Transmission line :

Positive sequence impedance = Negative sequence impedance

Zero sequence impedance depends upon : Return path, Groundwires and Earth resistively.

Zero sequence reactance is approximately 2 - 2.5 times positivesequence impedance.

R0 is usually large. May be 5 to 10 times also.

B0 is 65 to 80 % of B positive sequence

Transformers :

All are equal i.e. Zpt = Znt = Zzt for transformer.

Zzt 90% of Zpt, if magnetising branch is neglected.

Page 25: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd25

Fault Representation:

Va1

Vf

Z1

Ia1

Va2

Z2

Ia2

Va1

Z0

Ia0

Va1 = Vf - Z1.Ia1 Va2 = -Z2 . Ia2 Va0 = - Z0 . Ia0

a0

a2

a1

0

2

1f

a0

a2

a1

I

I

I

Z00

0Z0

00Z

0

0

V

V

V

V

Page 26: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd26

Three phase fault representation:

a

b

c

a

b

c

Vab = 0 Va = 0 Va1 = 0Vbc = 0 Vb = 0 Va2 = 0Vca = 0 Vc = 0 Va0 = 0

a0

a2

a1

0

2

1f

I

I

I

Z00

0Z0

00Z

0

0

V

0

0

0

Page 27: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd27

Ia1 = Vf Z1 , Ia2 = 0 , Ia0 = 0

a0

a2

a1

2

2

c

b

a

I

I

I

1aa

1aa

111

I

I

I

Ia = Ia1

Ib = a2Ia1

Ic = aIa1

Ia = Ib = Ic

Three phase fault representation:

Page 28: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd28

Fault Through Impedance :

Zf

a

Zf

a

Zf

a

Z0

Zf

a

Zf

a

Zf

a

0I0IZZ

VI a0a2

f1

fa1

, ,

Page 29: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd29

Single Line to Ground Fault Representation

a

b

c

Ic

Ib

Ia

Va = 0

Ib = 0

Ic = 0

Page 30: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd30

2

2

11111

3

1aaaa

III

c

b

a

0

2

1

III

a

a

a

1 10

3II aa 2 ,

3II aa 1 ,

31 II aa 021 III aaa Q

0

2

1

0

2

1

0

2

1

000000

00

III

ZZ

ZV

VVV

a

a

af

a

a

a

111 IZVV afa 222 IZV aa 000 IZV aa

IZIZIZVVVV 002211021 aaafaaa

021 0VVVV aaaa Q

021

021

ZZZ

VIII

faaa

021

3

ZZZ

VI

f

a

Page 31: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd31

Fault Through Impedance :

a

b

c

Ia

Ic

Ib

Zf

f021

fa0a2a1

3zZZZ

VIII

Page 32: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd32

Line to Line Fault Representation:

Vb = Vc

Ia = 0

Ib = -Ic

a

b

c

Ic

Ib

Ia

c

b

a

2

2

a0

a2

a1

V

V

V

111

aa1

aa1

3

1

V

V

V

Va1 = 1/3 [Va+aVb+a2Vc] = 1/3 [Va+aVb +a2Vc]

Va2 = 1/3 [Va+a2Vb+aVc] = 1/3 [Va+a2Vb+aVc]

Va1 = Va2

Page 33: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd33

I

I

I

a a

a a

I

I

I

a

a

a

a

b

c

1

2

0

2

21

3

1

1

1 1 1

Ia0 = 1/3 (Ia +Ib +Ic) = 1/3 (Ib - Ib) = 0

Ia1 = 1/3 (aIb+a2Ic) = 1/3(aIb-a2Ib)

Ia2 = 1/3 (a2Ib + aIc) = 1/3 (a2Ib-aIb)

Ia1 = -Ia2

0

00

00

00

0

0 1

1

0

2

1

0

2

1

a

af

a

a

a

I

I

Z

Z

ZV

V

V

VVa1 = Vf - Z1Ia1

Va2 = Z2Ia2 = Va1 = Vf - Z1Ia1

Z2Ia1 = Vf - Z1Ia1

I

V

Z Zand I I I Va

f

a a a a11 2

2 1 0 00 0, ,

Page 34: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd34

Fault Through Impedance :

a

b

c

IcIb

Ia

Zf

I I

V

Z Z Za a

f

f

1 2

1 2

Page 35: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd35

Double Line to Ground Fault Representation:

a

b

cIcIb

Ia

Vb = 0

Vc = 0

Ia = 0

VVV

a a

a aV

a

a

a a

1

2

02

21

3

1

11 1 1

00

1 1 1V V V V V Va a a a a a1 2 03 3 3

, ,

V V Va a a1 2 0

Page 36: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd36

I

I

I

a a

a a I

I

a

a

a

b

c

1

2

0

2

21

3

1

1

1 1 1

0

Ia1 + Ia2 + Ia0 = Ia =0

Ia1 = 1/3 (aIb + a2Ic)

Ia2 = 1/3 (a2Ib + aIc)

Ia0 = 1/3 (Ib + Ic)

1/3(aIb + a2Ic) + 1/3(a2Ib + aIc) + 1/3(Ib +Ic) = 0

aIb + a2Ic + a2Ib + aIc + Ib + Ic = 0

V

V

V

V Z

Z

Z

I

I

I

a

a

a

f a

a

a

1

2

0

1

2

0

1

2

0

0

0

0 0

0 0

0 0

Va1 = Vf - Z1Ia1

Va2 = - Z2Ia2

Va0 = - Z0Ia0

Va1 = Va2 = Va0

Vf - Z1Ia1 = - Z2Ia2 - Z0Ia0

Page 37: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd37

V a0

Z1 Z

2Z

0

V f

Iao

V a2V a1

Ia2I a1

Fault Through Impedance:

a

b

c

ZfZf

Zg

IV

Z Z ZZ Z

Z Z Z

Z Z Z

Z Z Z Z

af

f

f

f g

1

12 0

2 0

1 1

2 2

0 0 3

'' '

' '

'

'

'

Page 38: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd38

Open Faults

Open in phase B & C

b

c

b’

c’

a a’

Ib = 0 and Ic = 0

V V Z I Z Iia

ka

aa a aa f ' '

I

I

I

a a

a a

I

I I I I I

a

a

a

a

a a a a f

1

2

0

2

2

1 2 0

1

3

1

1

1 1 1

0

0

1

3

1

3

Page 39: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd39

V

V

V

V Z

Z

Z

I

I

I

a

a

a

f a

a

a

1

2

0

1

2

0

1

2

0

0

0

0 0

0 0

0 0

V V Z I

V Z I

V Z I

V V V V V Z I Z I

V V

Z I V Z I Z I Z I

I I IV

Z Z Z Z

a f a

a a

a a

ka

la

kl kl kl zz f aa a

f kl

aa a kl a a a

a a aokl

aa

1 1 1

2 2 2

0 0 0

1 2 01

1 1 1 2 2 0 0

1 2

1 2 0

3

3

3

' '

'

'

Page 40: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd40

Vkl is the Thevenin equivalent voltage, once the line is removed, between buses k & l.

f

0

f

2

f

1f

'

aa

0

kl

0

lk

0

ll

0

kk0

2

kl

2

lk

2

ll

2

kk2

1

kl

1

lk

1

ll

1

kk1

ZZZZ3Z

ZZZZZ

ZZZZZ

ZZZZZ

Solution Methodology:

1. Do the load flow with the line isolated.

2. Then insert the line with two phase open.

Page 41: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd41

Open in phase A :

• Ia = 0• Similar type of analysis like double line fault.• Voltage is between two nodes, rather than between

node and ground.• Impedance is the Thevenin‟s equivalent impedance

between nodes.

IV V

ZZ Z

Z Z

fl k l

12 0

2 0

'' '

' '

.

Z Z Z Z Z Z

Z Z Z Z Z Z

Z Z Z Z Z Z

l

kk ll lk kl f

l

kk ll lk kl f

l

kk ll lk kl f

1

1 1 1 1 1

2

2 2 2 2 2

0

0 0 0 0 0

I IZ

Z Zf f

2 1 0

0 2

.

'

' 'I

I Z

Z Zf

f0

1

2

0 2

.'

' '

Page 42: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd42

Solution Methodology:

1. Form the Y bus for +ve, -ve and zero sequence.2. Do the LU factorisation for +ve, -ve and zero sequence.3. To find the driving point impedance-

In fault study, particular row or column of Z bus is required.

Consider, Yx = z

x=Y-1z

x= Z.z

Let z have 1 in pth location and 0, at all other location.

Page 43: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd43

x

Z Z Z Z

Z Z Z Z

Z Z Z Z

Z

Z

Z

Yx z

p n

p p pp pn

n n np nn

p

pp

np

11 12 1 1

1 2

1 2

10

1

0

L

L

M

L

M M

Pass in z, 1.0 for the desired bus and 0 else where.Call LU solution - x will be the desired column of Z bus.

4. Find the sequence fault current I1f, I2

f and I0f.

5. Determine the post fault bus voltage

Page 44: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd44

[Vf] = [Z] [If1]

= [Z] {[I0] - [If]}

= [Z] [I0] + [Z][-If]

= [V0] + [V]

V = [Z] [-If]

Y[V] = [-If]

Solve V using LU solution.

Above can be written as :

[Y]p[V]p = [-If]p , p: positive sequence and similarly for other sequences.

Page 45: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd45

For open fault, between k & l,

I k I

I

f p f

f

00

0

M

M

M

For faults other than open fault,

I If p f

p

0

0

0

:

:

Page 46: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd46

Example:

Page 47: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd47

Grounding Practice in Power System :

Advantages of ungrounded system :

• Ground connection normally doesn‟t carry current. Hence elimination saves the cost.

• Current can be carried in other phases, with fewer interruptions.

Page 48: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd48

Grounding Practice in Power System :

Limitations of ungrounded system :

• With the increase in voltage and line length current has increased and self clearing nature advantage couldn‟t be seen.

• Arcing ground : Phenomena of alternate clearing and re-striking of the arc, which cause high voltage (surge and transient).

• If grounded, the insulation can be graded in transformer from line to neutral, there by reducing the cost.

• In case of ungrounded system, influence on communication lines is more.

•Ground current can‟t be limited.

Page 49: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd49

Ungrounded System :a

b

c

3.01.73 1.73

0.0

Perfectly transposed line :Neutral of transformer is at zero potential.

Un-transposed line :Neutral is shifted.

Capacitance grounded :Perfectly transposed line.

Page 50: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd50

Resistance Grounded System:

The resistance to neutral limits ground current.

Selection of resistance value:

• Amount of ground fault current.

• Power loss in resistor during ground fault.

Power loss: usually expressed as a percentage of system rating.

Page 51: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd51

R

X

g

= 16 %X

g

= 8%

Z1 = 24% , Z2=24% , Z0=3R+j8

I

Z Z Z j j R j R j

Power Loss I RR j

R

f

f

3 3 100

24 24 3 8

300

3 56

300

3 56

1 2 0

2

2

*

Page 52: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd52

R

X

g

= 16 %X

g

= 8%

Z1 = 24% , Z2=24% , Z0=3R+j8

I

Z Z Z j j R j R j

Power Loss I RR j

R

f

f

3 3 100

24 24 3 8

300

3 56

300

3 56

1 2 0

2

2

*

Page 53: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd53

If : in pu, R : in puFor three phase system, power loss

=I R

percentage of phasesystemkVA ratingf2

33

R is in percent p.u.Maximum power loss = ?

Selection : How much be the value of ground fault current ?What should be the percent power loss in the ground resistance ?

Page 54: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd54

Effectively grounded system:

Solidly grounded : No impedance between neutral and earth

Effectively grounded : As per AIEE standard No.32, Section 32 - 1.05, May 1947 :

X system

X system

R

X system

o0

1 1

30 1 0 . .

X1 =X2 =25%

X1 =7%=X2=X0

X1 =34%X2 =120%

69 kV25 MVA

69 kV

B

A

Page 55: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd55

For fault atAX

X

For faultatBX

X

Grounded System

X

Xbut no resonance (resonancegrounding)

0

1

0

1

0

1

7

32

127

32 34

127

66

30

=

=+

=

Reactance :

. ;

If Xg = 50 at A , find the nature of grounding at A & B.

Effectively grounded system:

Page 56: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd56

Resonant - Grounded System :Capacitance current is tuned or neutralised by a neutral reactor or similar device.

0

0

I

I

I

0

I

I 2

Fault current is made zero by selecting the suitable tap on the ground reactor.

Page 57: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd57

Circuit Breaker Selection

1. Determine the symmetrical current (maximum) for any type of fault.

2. Multiply the current by factor obtained from standard tables depending on the duty cycle.

(2 cycles clearing, 5 cycles clearing etc.)

Use the above current to specify the interrupting current

Page 58: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd58

References

1. Stagg and A.H. El-Abiad, "Computer Methods in Power System Analysis", Mcgraw-Hill, 13th print, New Delhi,1988.

2. William D. Stevenson "Elements Of Power System Analysis", McGraw-Hill, Fourth edition, New Delhi, 1982.

3. George L. Kusic, "Computer Aided Power System Analysis",Prentice-Hall, International, N.J.,New Delhi, 1989.

4. J. Arrilllaga, C.P. Arnold and B.J.Harker ,"Computer Modeling of Electrical Power Systems", John Wiley and Sons,1983.

Page 59: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Queries & Discussions

59

Page 60: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd60

Thank You

Page 61: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

TRANSIENT STABILITY STUDIES

1

Page 62: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd62

Voltage stabilityRotor angle stability

Study period: 0-10

sec

Mid-term/long-term stability

Study period: seconds to

several minutes

(slow dynamics)

Small signal stability

Non-oscillatory

Sufficient synchronizing torqueOscillatory

Unstable control

action

Transient stability

Large disturbance

(First swing)

Stability

Page 63: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd63

Power System Operating States

f, v, loading acceptable, load met, n-1 or n-2 contingency acceptable

f, v, loading acceptable,load met n-1 or n-2 contingency not satisfied

f, v, loading not acceptable, load not met

Normal

Alert Restorative

Cascaded

system

syste

m In Extremis Emergency

Page 64: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd64

Pool control centre

System control centre

To other systemTo other system To other system

Transmission system Power plant

DS DS DS G G G

DS: Distribution System

G : Generator

Control Hierarchy

Page 65: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd65

Power System Subsystem & Controls

f Ptie Pgtotal

Schedule System generation control Load frequency control with

economic allocation

Other generating units and associated controls

Generating unit’s control

Prime mover & control

Excitation system and control

Generator f/N or

Pg Vt

If

Pm f/N

Transmission Controls Reactive power, Voltage control, HVDC transmission and others

Pg

f Ptie Pg.total

Page 66: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Stability classification

• Transient stability : Transmission line faults, sudden load change, loss of generation, line switching etc.

• Dynamic stability : Slow or gradual variations. Machine, governor-Turbine, Exciter modeling in detail.

• Steady state stability : Changes in operating condition. Simple model of generator.

66

Power System Stability

Ability of a power system to remain in synchronism. Classification of transients : Electromagnetic and Electromechanical

Page 67: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd67

Stable Unstable

Stable Unstable

t Sec. t Sec.

t sec.t Sec.

m2

m2

m1 m1

0 0

00

Transient Stability:First swing stability problemMulti-swing stability problem. (normal size)

Page 68: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd68

Assumptions :

Synchronous speed current and voltage are considered.

DC off set currents, harmonics are neglected.

Symmetrical components approach.

Generated voltage is independent of machine speed.

Circuit parameters are constant at nominal system

frequency.(Frequency variation of parameter neglected).

Page 69: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd69

Steady State Stability

Stable Unstable

Stable

Unstable

Page 70: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd70

Mechanical Equation :

J : Moment of inertia of rotor masses (kg-mt2 )

m : Angular displacement of rotor w.r.t. a stationary axis

(mechanical radians)

t : Time (seconds)

Tm : Mechanical or Shaft Torque ( N-m )

Te : Net electrical torque (N-m )

Ta : Net accelerating torque (N-m)

For generator, Tm and Te are +ve.

Jd

d tT T T N mm

a m e*2

2

Page 71: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd71

Reference Axis

Stationary

m

Reference axis at sm

sm

sm

Rotor axis at rotor

speed

m sm mt

m : Angular displacement of the rotor in mechanical radians.

Page 72: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd72

)(

.sec

2

2

2

2

2

2

2

2

2

2

ApproxPPdt

dM

wattsPPdt

dJ

perradiansinvelocityAngulardt

d

mNTTdt

dJ

dt

d

dt

d

dt

d

dt

d

emm

emm

m

mm

emm

mm

msm

m

Where M : Inertia constant = at synchronous speed in Joules-sec per mechanical radian.

Page 73: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd73

Constant is defined as the ratio of stored Kinetic Energyin Mega Joules at synchronous speed and machinerating in MVA

emm

sm

emm

sm

smsm

PPdt

dHS

wattsPPdt

dM

radianmechanicalperMJSH

M

MVAMJS

M

S

JH

2

2

2

2

2

2

2

/2

1

2

1

Page 74: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd74

em

s

emm

sm

emm

sm

PPdt

dH

puPPdt

dH

S

PP

dt

dH

2

2

2

2

2

2

2

2

2

Page 75: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd75

s

s

s

em

sem

s

em

em

HtIf

tH

pudt

dH

puPPLet

dt

dPP

dt

dH

puPPtd

d

f

H

reeselectricalinIf

EquationSwingpuPPdt

d

f

H

,2

2,1

2

1

2

180

deg

2

2

2

2

Page 76: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd76

Pm

Pe = 1 pu

At t = 0, breaker is opened.Initially Pe = 1 pu on machine rating Pm = 1pu and kept unchanged.

In 2H seconds, the speed doubles.

Page 77: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd77

MVASystem

ratingMachineHH

MVAsystemHRatingMachineH

RatingMachine

KEStoredH

mechsystem

systemmech

Inertia constant (H) is in the range 2 - 9 for varioustypes of machines. Hence H-constant is usuallydefined for machine.

Page 78: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd78

Relation between H constant and Momentof Inertia is given by:

machineS

NWR

H

Wattslbft

lbftNWR

KE

feetingyrationofRadiusR

poundsinpartrotationalofWeightW

ftlbWR

InertiaofMoment

6

22

22

22

10550

746

60

2

2.322

1

746sec/550

60

2

2.322

1

:

:

2.32

Page 79: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd79

Example :

Smach = 1333 MVA

WR2 = 5820000 lb - ft2

N = 1800 RPM

1333

60

18002

2.32

5820000

2

110

550

7462

6

H

= 3.2677575 pu (MJ/ MVA)

On 100 MVA base : H = 1333 / 100 = 43.56 (MJ /

MVA)

Page 80: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd80

G1 ,H1

Pe1 Pm1

G2 ,H2

Pm2 Pe2

112

1

2

1em PP

dt

d

f

H

222

2

2

2em PP

dt

d

f

H

21212

2

21eemm PPPP

dt

d

f

HH

Page 81: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd81

1 = 2 = ; since the machines swing together

PePtd

d

f

Hm

2

2

H = H1 + H2

Pm = Pm1 + Pm2

Pe = Pe1 + Pe2

G1 and G2 are called coherent machines.

Inertia Constant

HStored energy at rated speed in MWs

MVA rating

Page 82: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd82

MKS System

ratingMVA

RPMJ

ratingMVA

JH

RPMradianmechanicalinspeedRated

mkgininertiaofMomentJ

MWsJ

wattsJenergyKineticenergyStored

om

om

om

om

2

9

62

2

62

2

1048.510

2

1

60

2sec/:

:

102

1

2

1

Page 83: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd83

British Units

22

2

2

356.12.32

)(

mkgWR

J

ftlbgyrationofradiusofsquare

partrotatingofWeightWR

Given

Page 84: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd84

Example:

sec2

/)(

1048.5

77168.27547356.12.32

26

22

H

timestartingMechanical

MWsratingMVAH

energyStored

MVAMWsratingMVA

RPMJH

mtkgWR

J

MVA rating : 555 WR2 : 654158 lb-ft2

Page 85: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd85

Typical values

Unit Type H Constant

Hydo unit 2 to 4

Thermal unit

2 pole - 3600 RPM 2.5 to 6

4 pole - 1800 RPM 4 to 10

Non coherent machines

112

1

2

1 PePmdt

d

f

H

11

1

2

1

2

em PPH

f

dt

d

222

2

2

2em PP

dt

d

f

H

22

2

2

2

2

em PPH

f

dt

d

Page 86: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd86

21

2112

12

21

2112

12

21

21

12122

12

2

21

2112

21

2112

2

21

2

21

21

22

21

111

21

2

2

21

2

21

21

21

122112

2

21

2

22

2

11

1

212

2

,

1

1

1

HH

PHPHP

HH

PHPHP

HH

HHH

Where

PPtd

d

f

H

HH

PHPH

HH

PHPH

td

d

fHH

HH

PPHH

HPP

HH

H

td

d

fHH

HH

HH

HPPPPH

dt

d

f

PPH

fPP

H

f

dt

d

ee

e

mm

m

em

eemm

emem

emem

emem

Relative swing (with reference to one machine) is more important, rather than absolute swing.

Page 87: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd87

Swing Curves

Relative swing (with reference to one machine) is more important, rather than absolute swing.

Absolute Plot

1

o

2

3

T in sec.

4

Relative Plot (i-)

4

3

20

1

T in sec.

Page 88: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd88

Classical model : (Type 1) Constant voltage behind transient reactance.

E’ = Vt + (0 + jxd’) I

I

E’

Vt

jxd’ I

Ref.Vt

I

E’

jxd’+

-

Page 89: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd89

Power angle equation jXs

jXs

PE E

Xs

1 2 sin

E1 : Magnitude of voltage at bus1

E2 : Magnitude of voltage at bus2

: 1 - 2

Xs : Reactance

22 E11 E

Page 90: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd90

Machine Parameters

Synchronous : Steady state, sustained.

Transient : Slowly decaying

Sub-transient : Rapidly decaying

E=?

X=?

"'

"'

""'

0

qoqo

dod

dqqqd

TT

TT

XXXXX

Page 91: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd91

Parameter Hydro (pu) Thermal (pu)

xd 0.6 - 1.5 1.0 - 2.3

xq 0.4 - 1.0 1.0 - 2.3

xd’

0.2 - 0.5 0.15 - 0.4

xq’

------- 0.3 - 1.0

xd”

0.15 - 0.35 0.12 -0.25

xq”

0.2 - 0.45 0.12 -0.25

Td0’

1.5 - 9.0 s 3.0 -10.0 s

Tq0’

------- 0.5 - 2.0 s

Td0” 0.01 - 0.05 s 0.02 - 0.05 s

Tq0” 0.01 - 0.09 s 0.02 - 0.05 s

Ra 0.002 - 0.02 0.0015 - 0.005

Typical values

Page 92: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd92

Stability P

Pm

O

Pe=Pmax sin

u 90

0 s 180

0

Stable

• At s ; Pm = Pe ; net accelerating torque = 0.

• Let Pe decrease slightly.

increase (acceleration)

comes back to original position.

• Stable region . Hence s is stable operating point.

veisPPdt

d

f

Hem

2

2

Page 93: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd93

Unstable

· At u; Pm = Pe ; Net accelerating torque = 0

· Let Pe decrease slightly.

·

increases, (acceleration)

· Pe further decreases.

· Chain reaction never comes back to

normal value .

Hence u is unstable operating point.

veisPPdt

d

f

Hem

2

2

Page 94: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd94

Infinite bus

Generator connected to infinite bus.

· High inertia. H compared to other machines in the system.

· Frequency is constant.

· Low impedance. Xd‟ is very small.

· E‟ is constant and Vt is fixed.

· Infinite fault level symbol.

System

Page 95: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd95

Example :

200 MW

1.05 pu V

250 MVA 250 MVA Slack bus

1 pu - V

H = 3.2 , Z = 10% on own rating , Xd1 = 25% , tap = 1,

Ra = 0.0 and neglect R.

1. Establish the initial condition.

2. Perform the transient stability without disturbance.

3. Open the transformer as outage & do the study.

4. How long the breaker can be kept open before closing,

without loosing synchronism.

Page 96: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd96

Load Modeling

Page 97: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd97

Vary the tap.

Switch on the capacitor.

Determine the response (charge) in load.

Compute the parameters. P = P0 (CP + CI . V + CZ . V2) ( 1+Kf . f)

P varies with time, voltage and frequency.

P0 varies with time - can be constant at a given time of a day.

CP, CI, CZ & Kf are constants.

V & f are known at any time instant.

P is known from measurements.

Solve the non linear problem over a set of measurements.

fo

Po

frequency

Po

we

r

Page 98: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd98

Let the load be 10,000 MW. i.e. P0 = 10,000

Let for 1 Hz change in frequency, let the load change be 700 MW.

5.3

501100

7

:100

;

%7000,10

700

7001

700)(

)(700

p

f

p

f

p

foo

p

fo

C

baseMVAonthen

frequencyinchangeunitpertheisfpuinisPIf

C

numberpowerCffP

loadindecreaseCfP

What it implies :· Initial load 10,000 MW.· Loss of generation 700 MW· Increase in load 700 MW · Frequency 49 Hz.

Page 99: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd99

Load Model Parameters

Load model paraters

Measurement based approach

Input: Connected load

Measurement: P,V, f over a period

Out put: Parameters

Component based approach

Industrial

Commercial

residential

Agricultural

Page 100: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

100

Component pf P/V Q/V P/f Q/f

Air conditioner

3 p central heating0.90 0.088 2.5 0.98 -1.3

Arc furnace 0.7 2.3 1.6 -1.0 -1.0

Industrial Motors 0.88 0.07 0.5 2.5 1.2

Agricultural pumps 0.85 1.4 1.4 5.0 4.0

Residential

Summer 0.9 1.2 2.9 0.8 -2.2

winter 0.99 1.5 3.2 1.0 -1.5

Commercial

summer 0.85 0.99 3.5 1.2 -1.6

winter 0.9 1.3 3.1 1.5 -1.1

Industrial 0.85 0.18 6.0 2.6 1.6

Power plant 0.8 0.1 1.6 2.9 1.8

Page 101: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

101

Transducer

Regulator Exciter Generator

Limiter + relay

PSS

Excitation System Components

Ref.

Controller

Regulator

Power

amplifier

(Exciter) Plant

Feedback elements

Block Schematic

Et Efd

Vtr Ver

Vref

Page 102: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

102

Reactive Power Control

Synchronous generators

Overhead lines / Under ground cables

Transformers

Loads

Compensating devices

Page 103: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

103

Control Devices: Sources /Sinks --- Shunt capacitor, Shunt inductor

(Reactor), Synchronous condenser, and SVC.

Line reactance compensation --- Series capacitor

Transformer -----OLTC, boosters

Page 104: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

104

Speed Governor Systems :

AGC

Speed

changer

Speed

Governor Valve

/gate

Electrical

System

Energy Supply

steam or water

Turbine Generator

Speed

Tie line Power

Frequencies

Page 105: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

105

Types of Control: Primary Control : Governor action

Secondary Control : AGC, load frequency control (For selected generators)

1/R 1

1

T

T

ws

ws

1

T Kms D

speed

Turbine Droop(Goveror) Generator +

-

Speed

Ref.

Under Frequency operation:

Vibratory stress on the long low pressure turbine blades Degradation in the performance of plant auxiliaries say,

induction motor.

Page 106: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

106

Limitations: Only maximum spinning reserve can be achieved

Turbine pickup delay

Boiler slow dynamics

Speed governor delay

Page 107: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

107

Load Shedding:

Trip signal 49.5

0.4 Hz/s

48

10% load rejection

15% load rejection

50% load rejection

30% load rejection

1 Hz/s

4 Hz/s

2 Hz/s

Other measures:

* Fast valving

* Steam by-passing

Page 108: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

108

Modules in a Program:1. Data reading

2. Initialization

Steady state load flow

Control block parameter AVR, Gov., Machine, Motor, PSS, VDC, SVC.

3. Disturbance model

4. Control block modeling

5. Machine modeling

6. Load flow solution

7. Protective relay modeling

8. Special functions

Cyclic load

Arc furnace

Re-closure

9. Results output

Report

Graph

Page 109: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

109

Typical Swing Curve :

Time in seconds

AVR & PSS

Constant Efd

AVR with no PSS

65432

90

60

30

1

Page 110: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

110

Typical Swing Curve :

0.01

0.090

0.025

5 4 3 2 1

180

120

60

Time in Sec.

Rotor angle

degrees

Integration step size : Typical value : 0.01 seconds, Range : 0.005 to 0.02 seconds

Page 111: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

111

AVR : Type 1

1

1 1 sT

k

sT

1

21

s=f(Efd)

sk

sT

3

41

1

2 3k sT

PSS

+-

+

Vref

+

- EfdVT

Mapping Range

T1 Tr 0.01 -- 0.10T2 Ta 0.025 -- 0.2

T3 TE 0.5 -- 1.0

T4 TF1 0.5 -- 1.0

K1 KA 25 -- 200

K2 KE -0.5 -- 1.0

K3 KF 0.01 -- 0.1

Page 112: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

112

AVR : Type 2

Mapping Range

T1 TR 0.01 --- 0.05

T2 TA 0.01 --- 0.05

T3 TE 0.5 --- 1.0

T4 TF1 1.0

T5 TF2 0.1

k1 KA 50--200-400-600

k2 KE 1.0

k3 Kf 0.01 - 0.05

Efd1

1 1 sT

k

sT

1

21

s k

sT sT

3

4 51 1

Vs

+-

+

Vref

SE

1

2 3k sT+

-VT

VRmax

VRmin

-

Page 113: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

113

AVR TYPE – 5

VT 1

1 0 01 . s

k sT sT

sT sT

1 2 3

4 5

1 1

1 1

( )

+

- +

Vref VRmax

VRmin

Efdmax

Efdmin

1

1 1 sT

Mapping Range

0.01 Tr 0.01 -- 0.025

T1 Ts 0.025

T2 TE 1.0

T3 TF1 0.06

T4 TA 40.0

T5 TF2 0.024

k1 kA 200.0

Page 114: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

114

Steam Turbine Governing System

ref

+

1/T31/S

+Pref

P5

Pmax

C min

P-up

P-dn

1+sT2

0 k1(1+sT1)

-

+

- Pmin

C max

K1 : 0.05 - 0.04 Pmax : 1.0

T1 : 0.1 Pmin : 0.0

T2 : 0.03 Pup : 0.1

T3 : 0.4 Pdn : -1.0

Page 115: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

115

P

1/(1+sT1 ) 1/(1+sT2)

k1+k2 k3+k4

(1/1+sT3) (1/1+sT4)

k5+k6 k7+k8

Ps

T1 : 0.26 k1 : 0.2760 k1 + k2 : VHP

T2 : 10.0 k3 : 0.324 k3 + k4 : HP

T3 : 0.5 k5 : 0.4 k5 + k6 : IP

T4 : 99.9 k7 : 0.0 k7 + k8 : LP

Turbine Model

Page 116: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

116

Hydro Governor

+

1

1 1 sT

-

+

-

1

2T

Pmin

Pmax

Ps

ksT

sT1

3

31.

k2

Transient Droop Compensator

Permanent Droop Compensator

ref

+

+

Cmin P-dn

Cmax

1

s

P-up

k1 : 0.36 Pmax : 1.1 T2 : 0.2

k2 : 0.04 Pmin : 0.0 T3 : 5.0

T1 : 0.05 Pup : 0.1 Pdown : -

1.0

Page 117: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

117

Hydro Turbine

Ps1-sT1

1+0.5sT1

DM

T1 (T) : 1.0

Page 118: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

118

Transient Stability Enhancement

Philosophy :

1. Minimize the disturbance influence by minimizing the fault severity and duration.

2. Increase the restoring synchronizing forces.

3. Reduce accelerating torque.

Page 119: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

119

Transient Stability Enhancement

Methods :

1. High speed fault clearing.

2. Reduction of transmission system reactance.

3. Regulated shunt compensation.

4. Dynamic Braking.

5. Reactor switching.

6. Independent pole operation of circuit breaker.

7. Single pole switching

8. Fast valaving.

9. Generator tripping.

10.Controlled system separation and load shedding.

11.High speed excitation systems.

12.HVDC transmission link control.

Page 120: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

120

Major references used in the development of Transient Stability Studies Module

1. Dommel, N. Sato “Fast Transient Stability Solutions”, IEEE Transactions on Power Apparatus and Systems, 1972, PP 1643 -1650.

2. W. Dommel, “Digital computer solution of electromagnetic transients in single and multiphase networks”, IEEE Transactions on Power Apparatus and Systems, April 1969, Vol. PAS-88, PP 388 - 399.

3. IEEE Committee Report, “Dynamic Models for Steam and Hydro Turbines in Power System Studies”, IEEE PES Winter Meeting, New York, Jan./Feb. 1973. (Paper T 73 089-0).

4. IEEE Committee Report, “Proposed Excitation System Definitions for Synchronous Machines”, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-88, No. 8, August 1969.

5. IEEE Committee Report, “Computer representation of excitation systems”, IEEE Transactions Power on Apparatus and Systems, June 1968, Vol. PAS-87, PP 1460 - 1464.

Page 121: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Queries & Discussions

121

Page 122: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

122

Thank You

Page 123: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Introduction to Power System Protection

1

Page 124: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

124

Topics for Discussion Protective relaying

Need for protection

Types of Protection

General Philosophy

Over-Current Relays

Distance Relays

Page 125: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

125

Introduction

Page 126: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

126

Protective Relaying Safeguard equipment from damage during

abnormal operating conditions.

Protective Relaying should:

Ensure normal operation

Prevent equipment failure

Limit the effects of disturbances

Page 127: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

127

Need for Protection Loss of equipment (Permanent or Partial damage)

Loss of production

Revenue loss

Fire hazard, loss of life

Loss of confidence level in using electricity as a commodity

Page 128: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

128

Functions of Protection Primary function - Prompt removal of faulty

element suffering a short circuit, or when it startsto operates in an abnormal manner

Secondary function, to provide indication oflocation and type of failure

Page 129: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

129

Types of Protection

Over voltage protection – Lightning/Surgearrestors, Insulation co-ordination

Fault protection (over loading/current) -Application of Relays

Protection for human (safety) – Earthing andEarth mats, clearances, insulation

Page 130: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

130

Protection Philosophy

Cricket Protection

Position the fielders Designs the system

and sets the relays

Delivers the ball Charges the system

Batsman hits the ball Fault occurs

Mid-off stops/fails Primary relay

operates/ fails

Long-off stops/ fails Backup relay

operates / fails

Match lost ? Loss of

Power/Revenue

Page 131: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

131

Protection FeaturesSensitive – detection of short circuit or abnormalcondition

Selectivity – ensure that only the unhealthy part ofthe system is disconnected

Speed – to prevent or minimize damage and risk ofinstability of machines

Reliability – to ensure proper action even after longperiods of inactivity and also after repeatedoperations under severe conditions

Page 132: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

132

Protection System Design

Design of circuit breakers and isolating devices

Transducer (sensing devices)

Relay design

Relay application and co-ordination

Simulation and testing

Battery

Trip Coil

CB

Aux.

Switch

Relay

Relay Contacts

C T

Page 133: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

133

Protection Statistics Correct and Undesired

Operation as per the settings.

Settings are wrong, not updated

Human Error

Leaving the trip circuit open after test

Open circuited trip coils

Mechanical failure of circuit breaker

Page 134: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

134

Causes of Protection Failure Current or voltage supply to the relays

DC-tripping voltage

Protective relays

Tripping circuit or breaker mechanism

Circuit breaker

Page 135: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

135

Equipment Selection Relay selection

Selecting a relay scheme to recognize the existence of a fault within a given protective zone

Initiate circuit breaker operation

Circuit breaker selection

Determine the interruption requirement

Normal current and voltage rating

Selection of breakers and location

Page 136: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

136

Fault Characteristics

Magnitude

Frequency

Phase angle

Duration

Rate of change

Direction or order of change

Harmonics or the wave shape

Page 137: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

137

Protection Scheme Design

Divide the system into zones

Design appropriate breakers

Minimize the amount of load being disconnected

Page 138: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

138

Types of Relays

Page 139: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

139

Schematic of a Static Relay

COM T NOT AR

TRIPOver-Current :

FCRICT

CT

PP

Page 140: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

140

Schematic of an NR

Page 141: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

141

Over-Current Relays

Page 142: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

142

Basics

Relays operate based on the current sensed.

Can be used as primary or backup protection

May be directional or non-directional

Operation time depends on curve selected

Settings involve selecting the plug setting and the time setting

Page 143: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

143

Definitions Plug Setting

Plug setting is that value of current abovewhich the relay should operate.

Time dial setting

The time dial setting of the relay provides thediscrimination between the primary and backuprelay.

Page 144: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

144

Standard Curves

Page 145: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

145

Curve Equations

Page 146: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

146

Relay Co-ordination Identification of main and backup relays

Steady state analysis

Determination of plug setting

Determination of definite time setting

Determination of time dial setting

Page 147: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

147

Distance Relays

Page 148: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

148

Basics*Distance relays are the most widely used relays fortransmission lines protection.

*The relay measures the distance in terms ofimpedance by measuring the voltage and current.

*Major advantage is that relay acts as primary aswell as remote back up.

*The present digital distance relays offer morefunctionalities in terms of protection, monitoring andcontrol rather than just impedance measurement

Page 149: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

149

Types of Characteristics Mho

Quadrilateral

Lentical

Quadra-Mho

Elliptical Characteristics

Circular

Page 150: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

150

Mho Characteristic

X

Roffset

Zone-3

Zone-2

Zone-1(R3X3)(R2X2)

(R1X1)

Page 151: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

151

Quadrilateral Characteristics

Page 152: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

152

Impedance Calculation

Relays operate if the impedance seen is withinthe set characteristics known as zones.

Separate zones are present for phase and earthloops.

Page 153: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

153

PhilosophyZone Direction Protected Reach Time Setting (s)

Zone 1 Forward 80 % of the PL Instantaneous

Zone 2(for 400kV and above)

Forward

For Single Circuit –120 % of the PL

0.35

For Double Circuit –150 % of PL

0.5 to 0.6 – If Z2 reach overreaches 50% of the shortest line;0.35 – otherwise

Zone 2 (for 220kV and below

Forward120% of PL or100% of PL + 50% of ASL

0.35

PL: Protected Line, ASL: Adjacent Shortest Line, ALL: Adjacent Longest Line

Page 154: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

154

PhilosophyZone Direction Protected Reach Time Setting (s)

Zone 3 Forward 120% 0f (PL + ALL) 0.8 to 1.0

Zone 4 Reverse

10% for the Long line (>100 km)20% for short line (<100 km)

0.5 if Z4 overreaches 50% of reverse shortest line0.35: otherwise

Note : Z2 reach should not encroach the next lower voltage level: If Z3 reach encroaches next voltage level (after considering in feed), Z3 time must

be coordinated: If utility uses carrier blocking scheme, then the Z4 reach may be increased as the

requirement. It should cover the LBB of local bus bar and should be coordinated with Z2 time ofthe all other lines.

Page 155: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

155

Zone 1 Instrument Transformer errors

Transmission line is not completely balanced

Hence apparent impedance is susceptible to an error of 20%.

Zone 1 is under reached to prevent incorrect operation for fault on next line (Eg. Close to adjacent bus)

Zone 1 reach

Who covers the Remaining

?

Page 156: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

156

Zone 2 for single circuit line To provide coverage to remaining portion of

protected line

Over reach margin should be min 20% (for reason

discussed in Zone1)

Zone 1 reach

Zone 2 reach What about backup

protection for fault here ?

Page 157: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

157

Zone 2 for double circuit line

Zone 1 reach

Zone 2 reach What about backup

protection for fault here ?

Page 158: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

158

Zone 3 Zone 3 protection is backup protection for fault on

adjacent line.

Need to reach the PL + ALL

Zone 1 reach

Zone 2 reach

Considering Errors

Zone 3 reach

Page 159: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

159

Resistive Reach (Zone 1)

Earth

Should provide maximum coverage considering fault resistance, arc resistance and tower footing resistance.

Should be <4.5 * X1 (X1=Zone 1 reach)

Phase

Reach should be set to provide coverage against all types of anticipated phase to phase faults subject to check of possibility against load point encroachment

Should be <3*X1

Page 160: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

160

Resistive Reach (Zone 2 and Zone 3)

The philosophy used for Zone 1 is applicable herealso.

Additionally

Due to in-feeds, the apparent fault resistanceseen by relay is several times the actual value,this should be considered before arriving at thesetting.

Page 161: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Queries and Discussions

161

Page 162: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

162

Thank You

Page 163: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Protection Case Studies

1

Page 164: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

164

Topics for Discussion Overcurrent Relays

Distance Relays

Differential Relays

Page 165: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

165

Overcurrent relays

Page 166: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

166

Relay coordination sample

• Generator data

• Generator fault level :

• Maximum : 1000 MVA

• Minimum : 500 MVA

Transmission Line Details

Sl. No From Bus To Bus Impedance(pu)

1 1 2 0.1

2 2 3 0.1

3 3 4 0.1

4 4 5 0.1

~

R1

R2

R3

R4

B-1

B-2

B-3

B-4

B-5

Page 167: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

167

Relay data

Sl No Relay Name

MaximumLoad Current(A)

CT ratingRelay

Characteristics

1 R1 800 800/1 3s

2 R2 400 400/1 3s

3 R3 200 200/1 3s

4 R4 100 100/1 3s

Relay Pairs

Sl No Primary Relay Backup Relay

1 R4 R3

2 R3 R2

3 R2 R1

Page 168: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

168

Fault Studies results

Relay Impedance Fault Bus Fault MVAFault Current

in A

R1 0.1 1 1000 52486.388

R2 0.2 2 500 26243.194

R3 0.3 3 333.33 17495.288

R4 0.4 4 250 13121.590

SlNo

PrimaryRelay

Backup Relay

Fault Bus

Backup Relay Current in A

1 R4 R3 413121.590

2 R3 R2 3 17495.288

3 R2 R1 5 26243.194

Page 169: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

169

Plug setting computationFor Relay R4

% Setting Primary Setting Remarks

50 50 < Load Current

75 75 < Load Current

100 100 = Load Current

RelayLoad

CurrentCT Rating % Setting

Primary Current

R1 800 800/1 100 800

R2 400 400/1 100 400

R3 200 200/1 100 200

R4 100 100/1 100 100

Page 170: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

170

Time setting computation

Page 171: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

171

Time setting computation

Page 172: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

172

Final relay settingsRelay Plug Setting TMS

R1 800 0.6

R2 400 0.47

R3 200 0.29

R4 100 0.05

Operating times for a fault at Bus 5, with a fault current of 10, 500 A

R1 ≈ 1.61 s

R2 ≈ 1.00 s

R3 ≈ 0.51 s

R4 ≈ 0.07 s

Page 173: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

173

Co-ordinated Curves

Page 174: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

174

Application

• Backup to distance relays (220/132 kV andbelow)

• HV and LV side of ICT as backup to differentialrelays

• DEF is used in 400 kV line as protection for highimpedance earth faults.

• Non directional OC is also used in 400kV lineunder fuse fail condition

Page 175: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

175

DOC Setting Philosophy• For 220 kV and 132 kV line with only one main distance

protection, DOC must be set in such a way that for fault at remote bus the DOC (IDMT) is coordinated with Zone 2 time typically 1.1 s

• For DOC at 400 kV side of ICT, it is to be set such that for fault at remote end bus (longest line), DOC (IDMT) is coordinated with Zone 3 time

• Instantaneous DOC can be used at 400 kV side of ICT, set such that

– It does not pickup for fault on 220 kV bus

– It does not pickup for transformer charging current

– Time setting of 0.05 s to 0.1 s can be considered.

Page 176: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

176

DEF Setting Philosophy• For 220 kV and 132 kV line with only one main distance

protection, DEF (IDMT) must be set in such a way that it is coordinated with Zone 2 time

• For 400 kV line or where two main distance protection is used, DEF is used only for protection against high impedance faults and is coordinated with Zone 3 time

• For DEF at 400 kV side of ICT, it is to be set such that for fault at remote end bus (longest line), DEF (IDMT) is coordinated with Zone 3 time

• Instantaneous DEF can be used at 400 kV side of ICT, set such that

– It does not pickup for fault on 220 kV bus

– It does not pickup for transformer charging current

– Time setting of 0.05 s to 0.1 s can be considered.

Page 177: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

177

Instantaneous Setting calculation

15000 MVA

315 MVA

Zps=0.12 pu

Zebra

55 km

3φ Fault

Ia = 3225 A

3000 MVA

R2

• Reflected Current = 1.3 * 3225 = 4195 A• Inrush Current = 8*450 = 3600 A• Ip>> = Highest of the above two = 4200 A (Set

value).

Page 178: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

178

Distance relays

Page 179: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

179

179

• Sample SystemR1 = 0.0297 Ω/kmX1 = 0.332 Ω/kmR0 = 0.161 Ω/kmX0 = 1.24 Ω/kmZm = 0.528 Ω/km

G

400 kV Station 1 400 kV Station 2 220 kV Station 2

130 km

Twin Moose

80 km

Twin Moose

200 km

Twin Moose

162 km

Twin Moose

4x315 MVA

Z=0.12 pu

21

CCVT input

CT input

Station 5

Station 4

Station 3

Other Lines89 km

Twin Moose

Station 6

Page 180: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

180

Zone 1• Primary referred

• X1_prim = 0.332 *130*0.8 = 34.5 Ω

• Secondary referred

• X1_sec = 34.5*CTR/PTR, CTR:CT Ratio, PTR: PT Ratio

• Operating Time: Instantaneous

Page 181: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

181

Zone 2• Protected line is single circuit

• Adjacent Shortest Line: 80 km to Station 5

• X2_Prim = 0.332*130*1.2 = 51.79 Ω (130+26 km)

• X2 covers only 32% of Adjacent Shortest Line.

• Operating Time : 0.35s

Page 182: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

182

Zone 3• Adjacent Longest Line is 200 km to Station 4

• X3_Prim = 0.332*(130+200)*1.2 = 131.47 Ω

• That is 130 km PL + additional 266 km

• Time Setting

• Check if Zone 3 of PL encroach Zone 3 of adjacentline protection

• Zone 3 of Station 2- Station 5 line is 202.8 km.

• The Two Zone 3 are overlapping and hence must betime coordinated.

• Time = 0.8+ 0.06 (tcb)+0.03 (treset)+0.06 (tsf)= 0.95(set 1s)

• tcb, treset and tsf values are as per CEA report

Page 183: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

183

Points to be Considered• Obtain the actual line parameters from line impedance

test results. If not available, consider the standard values.

• Check Relay Setting type

• Primary or secondary referred values

• RX or Z

• Computation of Zero sequence compensation factor. (K0, Kn or Kr-Kx

Page 184: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

184

Points to be Considered• Note the shortest and longest line emanating from

the adjacent substation, along with impedance values

• For double circuit lines, check if it is two single circuit tower or one double circuit tower

• If necessary, carry out system study to study the effect of in feed, mutual coupling, power swing to achieve coordinated setting.

Page 185: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

185

Load Encroachment Consideration

• Basic Check

• Rated V = 63.5 V and Rated I = 1 A. (Secondary Referred)

• Phase Impedance = (0.85*V)/(1.5*I) = 36 Ω

• R reach must always be less than 36 Ω

Page 186: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

186

Operating Time coordination

• Zone 1 is primary protection, hence instantaneous operation

• Zone 2 is a overreach zone and hence needs to be delayed.

• If errors involved is less, then Zone 2 can trigger for Zone 1 fault of adjacent line. Hence Zone 2 is to be coordinated with Zone 1.

0

0.35

Tim

e (

s)

Page 187: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

187

Operating Time Coordination• For fault at 80% of segment B, Segment B zone 1 can

also under reach by 20%

• Hence only Zone 2 of Segment B pick up

• Segment A Zone 2 can also pickup.

• Hence segment A Z2 to be coordinated with segment B Z2

Tim

e (

s)

0

0.35

0.5 to 0.6

Segment A Segment B

Page 188: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

188

Operating Time coordination

• For 220 kV and below, if Zone 2 of PL can encroach the Zone 2 of ASL, then coordination is achieved by reducing the Zone 2 reach of PL to coordinate with Zone 2 reach of ASL.

Tim

e (

s)

0

0.35

Segment A Segment B

Reduced Zone 2 reach for coordination purpose

Page 189: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

189

Operating Time coordination• Zone 3 is the backup protection and hence needs to

be operate after Zone 1 or Zone 2 has failed to clear the fault.

• Zone 3 is coordinated with Zone 2 time of adjacent line relay.

Tim

e (

s)

0

0.35

0.5 to 0.6

Segment A Segment B

0.8 to 1.0

Page 190: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

190

Load Encroachment Consideration• Reach setting is given considering the various “under

reach” effect that can occur. This makes the resistivesetting “high”

• Phase loop measures the phase impedance and hencehas to be set such that it does not trip for abnormal oremergency system loading condition

• Emergency loading condition is to be used to decide theload encroachment point.

Page 191: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

191

Load Encroachment Consideration• Following criteria may be considered

• 1.5 times the thermal rating of line

OR

• 1.5 times associated bay equipment rating(minimum of all equipment)

• Minimum voltage of 0.85 pu to be considered

Load encroachment angle can be considered as 30(approx. 0.85 pf)

Page 192: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

192

Power Swing Blocking• During power system disturbances, unbalance

exist between generators which cause theoperating point to oscillate

• R-X trajectory might enter the zones of protection

• Blinder schemes are traditionally used to detectswings and prevent unnecessary tripping

• The rate of change of impedance is used todifferentiate between power swings and faults

Page 193: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

193

Power Swing Blocking Schemes

Page 194: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

194

PSB Options

No power swing blocking

Block all zones

Block zone 2 and higher

Block all zones but allow OST

Page 195: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

195

Stability Studies for PSB Settings

• Identify the generators which are prone to instabilityand the lines where power swings are observed.

• Determine the location where system should beseparated

• Time and reach settings are calculated

• Outermost zone reach should be within the innerboundary

• Outer boundary should be less than load impedance

Page 196: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

196

Carrier Aided Protection

Transfer

Unblocking

Direct

Blocking

Permissive

Page 197: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

197

Permissive Under-Reach

A BZ1

Z2

Z1

Z2

Close to A

Page 198: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

198

Permissive Over-Reach

A BZ1

Z2

Z1

Z2

Close to A

Page 199: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Queries & Discussions

199

Page 200: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

200

Thank You

Page 201: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Principles of Unit Protection

1

Page 202: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

202

Topics for Discussion

Introduction to Unit Protection

Differential Protection – Simple, Percentage Biased and High Impedance

Applications

Setting Examples

Page 203: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

203

Meaning

Protection which responds to faults onlyin one zone

No need for time grading

Normally fast acting – not affected byfault severity

Operates based on the comparison ofboundary conditions

Introduction

Page 204: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

204

Types of Unit Protection

Differential Protection

Utilizes Current

Over-Fluxing Protection

Utilizes Voltage and Frequency

Backup-Impedance Protection

Utilizes Current and Voltage

Page 205: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

205

Simple Differential Protection

Differential Protection

Page 206: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

206

Setting Consideration The effect of magnetizing inrush during initial

energization should be considered.

Correction for possible phase shift across thetransformer windings (phase correction)

The effects of different earthing and windingarrangements (filtering of zero sequence currents)

Correction for possible unbalance of signals fromcurrent transformers on either side of the windings(ratio correction)

Page 207: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

207

Phase Correction and Zero

Sequence Filtering

Page 208: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

208

Ratio Correction

Page 209: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

209

Biased Differential Relay

Page 210: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

210

Requirement of Biased

RelaysErrors which vary proportionally with the operatingconditions such as:

– Errors due to transformer taps

– CT errors

– Ratio Mismatch – Difficulty in obtaining exactlysimilar currents in both secondaries

Transient Errors

– CT Saturation

Page 211: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

211

Operating Characteristics

Page 212: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

212

CT

Satu

ration

• During CT saturation magnetizing impedance = zero

• Infinite magnetizing current will flow in the shorted path.

• Secondary of the network acts as open circuit.

• During this situation secondary current Is = zero

Page 213: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

213

High Impedance Differential Protection

Page 214: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

214

Comparison of Differential Schemes

Low Impedance High Impedance• Identical CTs not required

• Not stable for CTSaturation for externalfaults

• No protection for over-voltage required

• Stable for CT saturation forexternal faults

• Identical CTs are preferredfor sensitive operation

• May require an MOV toprotect Relay againstvoltage developed duringexternal faults

Page 215: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

215

Restricted Earth Fault Protection

Page 216: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

216

Amplification of Neutral

Current

Page 217: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

217

Currents During External Faults

Page 218: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

218

Currents During an Internal

Fault

Page 219: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

219

Transformer Protection

Differential Relays

Mainly percentage biased relays

2nd and 5th harmonic restraints are provided

High Set may be provided on HV winding

Restricted Earth Fault Relay

High Impedance Schemes are popular

Applications

Page 220: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

220

Modern Day Transformer Protection

Page 221: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

221

Line/Cable Protection

Differential Protection

– Percentage biased schemes are used

– Inrush currents are considered

– Major challenge was the distance between two ends

Pilot Wire Protection

– Measurements communicated over the pilot wire

– Balanced voltage as well as circulating current schemes are used

Page 222: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

222

Balanced Voltage Scheme

Page 223: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

223

Comparison of Pilot Wire

Schemes

Balanced Voltage Circulating Current Works on the tripping

principle

Interruption to the pilotwires causes blocking

Short circuit of pilot wiresleads to tripping

Overcurrent protectionrequired to preventincorrect tripping due toshort circuit of pilot wires

Works on blocking principle

Interruption of the pilotwires causes tripping

Short circuit of pilot wiresleads to blocking

Overcurrent protectionrequired to block operationfor large currents due topilot wire interruption

Page 224: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

224

Bus-Bar Protection

Differential Schemes

Incoming and outgoing currents are balanced

Multiple CT connections

Both High and Low Impedance Schemes are used

Partial Bus Bar Relay

Retention of supply to healthy portion of the network

Page 225: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

225

Partial Bus Bar Relay Example

225

Page 226: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

226

Overall Differential

Protection

Page 227: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

227

Sample Network

Setting Examples

Page 228: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

228

General Parameters

Parameter Value Unit

Mid tap Voltage in % 0

Primary side Full load Current at Mid tap Voltage

262.4319405 A

Secondary side Full load current 2624.319405 A

Page 229: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

229

Secondary Ratio

Compensation

Parameter Value Unit

Secondary side Full load Current on CT secondary 0.874773135 A

Secondary side ratio compensation 1.143153533

Secondary Full load CT secondary current with ratio correction

1 A

Page 230: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

230

Primary Side Ratio

Compensation

Parameter Value Unit

Primary full Load current At Maximum tap Voltage 249.9351815 A

Primary full Load current At Minimum tap Voltage 276.2441479 A

Primary side Full load Current on CT secondary side at Mid tap Voltage 0.874773135 A

Primary full Load current on CT secondary side At Maximum tap Voltage 0.833117272 A

Primary full Load current on CT secondary side At Minimum tap Voltage 0.920813826 A

Primary side ratio compensation 1.143153533

Page 231: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

231

Differential Current

Computation

Parameter Value Unit

Primary full Load current on CT secondary with ratio correction At Maximum tap Voltage

0.952380952 A

Primary full Load current on CT secondary with ratio correction At Minimum tap Voltage

1.052631579 A

Differential current at maximum tap 0.047619048 A

Differential current at minimum tap 0.052631579 A

Page 232: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

232

Restraint Current

Calculation

Parameter Value Unit

Restraint current at maximum tap 0.976190476 A

Restraint current at minimum tap 1.052631579 A

Setting Error at maximum tap 4.87804878 %

Setting Error at minimum tap 5.00 %

Page 233: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

233

Relay Settings

Setting Value Unit

Min Current 0.15 A

Slope 1 Start 0.75 A

Slope 1 20

Slope 2 Start 1.33 A

Slope 2 75

High Set 12.5 A

Page 234: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

234

Relay Characteristics

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

0 0.5 1 1.5 2 2.5

I dif

fere

nti

al o

n C

T Se

con

dar

y

I restraint on CT Secondary

Page 235: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

235

REF - CT Selection The voltage across the stabilizing resistor at maximum through fault

current is given by

Vs = k*Ikmax*(RCT + 2. RL)/ n volts

Where:

RCT= current transformer secondary winding resistance

RL = One way maximum lead resistance from the CT to the relaying point

Ikmax = maximum external fault current

k = stabilizing factor used to account for the distorted voltage wave due to faults.

n = transformation ratio of the CT

The knee point voltage of the CTs should be chosen at least 2 times the stability voltage setting

Page 236: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

236

REF - Voltage Settings

Considerations

Always, relay operating voltage should be less than Vk/2 but more than Vs.

If stability voltage increases beyond Vk, CT enters saturation region for which there is infinite Magnetization (Current), but voltage remains at the same level (no huge change in voltage). This condition is seen as open circuited on the secondary.

Vset >Vs, such that relay will not operate for external fault with CT saturation condition.

Page 237: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

237

REF - Stabilizing Resistor Design The value of the Iprim at which the relay operates at certain settings

can be calculated as follows:Iprim = n * (Ir + m*(Vs/Vk)*Io) AWhere,n = the transformation ratio of the current transformerIr = the current value representing the relay settingm = the number of current transformers included in the

protectionIo = the magnetizing current of one current transformer at knee

point voltage, Vk. The relay setting current Ir can be computed as

Ir = (Iprim / n) - m*(Vs/Vk)*Io A

The setting of the stabilizing resistor (Rs) must be calculated in the following manner, where the setting is a function of the required stability voltage setting (Vs) and the relay current setting (Ir).

Stabilizing Resistor value, Rs = Vs/Ir

Page 238: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

238

REF - Metrosil Requirement

The following equations should be used to estimate the peaktransient voltage that could be produced for an internal fault.

Vp = 2 * sqrt(2. Vk(Vf – Vk)) voltsVf = If *(RCT + 2.RL + Rs) voltsWhere:Vp = Peak voltage developed by the CT under internal fault

conditions.Vk = Current transformer knee-point voltage.Vf = Maximum voltage that would be produced if CT saturation

did not occur.If = Maximum internal secondary fault current.RCT = Current transformer secondary winding resistance.RL = One way maximum lead burden from current transformer to

relay.Rs = Stabilizing resistor.

Page 239: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

Queries & Discussions

239

Page 240: SHORT CIRCUIT STUDIES - ERPCerpc.gov.in/wp-content/uploads/2016/09/An-Overview... · Copyright @ Power Research & Development Consultants Pvt. Ltd 3 Symmetrical components Unbalanced

Copyright @ Power Research & Development Consultants Pvt. Ltd

240

Thank You