Short Circuit Stress Calculation in Power Transformer · PDF file ·...
Transcript of Short Circuit Stress Calculation in Power Transformer · PDF file ·...
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
301
Short Circuit Stress Calculation in Power Transformer Using
Finite Element Method on High Voltage Winding Displaced
Vertically Ashfaq Ahmad
1, Iqra Javed
2, Waseem Nazar
3
1,3The University of Lahore Department of Electronics
2 University of Management and Technology Department of Informatics and Systems
Abstract The objective of this research is to compute the
mechanical stresses in power transformer resulting from the
currents more than rated value during its operation. Due to
this high fault current, mechanical stresses are produced
indifferent directions which may cause the damage of winding
insulation. Various techniques have been adopted to analyze
the stresses on transformer windings. For the
accomplishment of research, FEM (Finite Element Method) is
utilized for the calculation of short circuit forces. All
mechanical generated in transformers are calculated
mathematically and verified through software. For the
verification of results, real time measurements on 20MVA 132
/11.5KV power transformer are made. Various failure
mechanisms due to these forces have been discussed.
Moreover, design parameters which determine the maximum
stresses in different parts of the transformer are also the part
of research. Effects of asymmetrical current and forces in
various parts of transformer have also been narrated.
Moreover, Different properties of materials have been studied
and the usage of proper material for withstanding the
dynamic effects of short circuits is discussed. Workmanship
errors on short circuit withstand capability have also been
elucidated. Finally, a complete model for the study of dynamic
effects of short-circuits in a power transformer and
comparison with forces calculated with FEMM soft ware [13].
Keywords Finite element method; Power transformer; Short circuit stress; Mechanical Stresses; Axial and Radial
Stresses.
I. INTRODUCTION
Due to continuous growth in demand of electricity,
Government and utility companies have started expansion
of generation stations which include interconnections of
national grids. Due to these additions, the short circuit
current of the system has increased where many sources of
power are available to feed faulty location on the
occurrence of event. All the components in the system are
affected by this change including transformers which have
to bear heavy currents. A large number of transformers in
power system have been reported to fail due to prolonged
heavy current.
Data collected from the High Voltage testing laboratory
shows that one fifth of the transformers under test are failed
due to weak insulation which ultimately bear short-circuit
current. It is important to mention that the transformers
which have to undergo this test, are manufactured with
almost and special care in the manufacturers premises
[9, 10]. Lack of insulation strength of transformers imposed
by manufacturers can cause severe damages to the
transformer as well as the system. System disruption
include following effects;
Deformation of LV and HV windings
Broken pressure plates on windings
Bending of clamping structure
Bulging of tank body
Collapse of bushings
Short-Circuited tapping leads
Rest of the paper organized as follows;
Section-II discusses types of short circuits in power
system, section III narrates the forces which are produced
due to short circuit current while remaining sections
include axial and radial forces acting on windings, and last
section describes the fem calculations results of forces
acting on transformer windings [5].
II. SHORT CIRCUIT CURRENTS
Almost all types of faults cause the sudden rise of
current in power system which results in malfunction and
inconsistent operation of installed equipment along with
severe effect on transformer insulation.
Usually, the three-phase faults are the most severe of all;
hence the transformer should be designed to withstand the
effects of symmetrical three phase faults. It must be
mentioned here that in some cases (Where a tertiary
connected winding is present), the single-phase to line fault
short-circuit current can be higher than the three-phase
fault on those windings, since it is related to very special
cases, emphasis is made on symmetrical three-phase faults
only.
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
302
A. Value of symmetrical short-circuit current
For three-phase transformers with two separate
windings, the r.m.s value of the symmetrical short-circuits
current I shall be calculated as in equation (i) [1].
(i)
Where:
U: is the rated voltage of the winding under
consideration, in Kilovolts
Zt: is the short-circuit impedance of the transformer
referred to the winding under consideration, in ohms per
phases
Zs: is the short-circuit impedance of the system, in ohms
per phase
As mentioned above, due to addition of more and more
generating stations within an interconnected system, the
source impedance Zs is very small and generally neglected
for calculations purpose.
B. Nature of short-circuit current
Consider the circuit given alternate voltage source.
Assuming that the below with an switch is closed at t=0
instant, which simulates the short-circuit, the expression for
the current i(t) can be written as follows:
Fig 1A Sinusoidal voltage source switched on to an RL network
i(t) = Imax[sin(t-)]
Where:
Imax: Maximum value of the current i
t: Time, in seconds
: Phase angle of the circuit impedance [tan-1(L/R)]
: Time constant [L/R]
The plot of this current expression with respect to time is
as under:
Fig.2 A Sinusoidal voltage source switched on to an RL network
The mechanical strength of the transformer windings
should be such that it shall withstand the highest short-
circuit forces generated which correspond to the first
current peak in the figure above, since this current peak has
the highest magnitude due to presence of DC component in
the current pattern.
C. Thermal withstand during short-circuit
During short-circuit, a very high current flows within the
windings of the transformer. However, the duration of
short-circuit is very small, the temperature of the windings
generally do not rise high enough to damageable values.
Hence, this effect can generally be neglected.
IEC 60076-5 however, gives a formula for the
calculation of temperature rise during short-circuits. This
formula assumes that all the heat produced by the winding
during short-circuits stays in it and none is dissipated. This
is a poor assumption, but since the limit of allowable temperature rise is high (250
oC), almost all the
transformers qualify this requirement during short-circuit
testing.
According to IEC 60076-5, the average temperature
1attained by the winding after short circuit is calculated
by the equation (ii) [2].
(ii)
Where
o: is the initial winding temperature, in degrees
Celsius
J: is the short-circuit current density,
t: is the duration, in seconds (s)
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 3, Issue 11, November 2013)
303
III. SHORT-CIRCUIT FORCES
When a current carrying conductor lies in a magnetic
field, a force is produced upon that current carrying
conductor, whose magnitude is given by equation (iii).
F=B.I.L sin (iii)
Where:
B: flux density, in Tesla
I: Current in the conductor, in Amps
L: length of current carrying element, in meters
: angle between flux density vector and current vector
This force is called the electromagnetic force because
it is produced both by combined effect or electric current
and magnetic flux. [12] The direction of this force can be
easily computed using the well-Known Left-hand rule.
A. Electromagnetic Forces
In transformers, electromagnetic forces may have three
components if we model it in 3D cylindrical coordinates.
r-component
z-component
-component
The r-component of the electromagnetic forces results in
the radial forces that act on the windings [8]. The z-
component is the originator of the axial forces that act on the windings. Finally, the -component can cause twisting
motion of the windings, but it is never present because the
center axis of the windings is always coinciding with each
other.