Short Circuit Fault Calculator V62
Transcript of Short Circuit Fault Calculator V62
Job NamePersonalize by entering the 'Job Name' and 'Your Company Name' Utility Fault Current
Company Name
Available Fault Current Calculation0 amperes kVA = E = trans. FLA = 300 0 0 Step 1b: by:John Sokolikboth the kVA Insert rating and impedence of transformer. (Note: When you insert
I = kVA x 1000 = trans. FLA 0 Isca = trans. FLA current ampere rating fault x 100 = from transformer Z local utilityIsca = ampere short-circuit current RMS symmetrical.
Step 1a: Insert available
the kVA rating and impedence you must select a voltage from the select the Voltage and Phase from dropdown box before the value will be calculated.)
or Isca
Z
= =
0 3 % 0 amperesSelect Voltage & Phase
Point to Point Method Step 2: Select type of (distance) Length conductor and conduit 2xLxI (ASC) 'f ' factor =
N x C x E L-N
# conductors per phase
Phase conductor constant Step 3: Insert the LengthVoltone to Line of Line conductor Neutral conductor constant Multiplier Volt Line to Neutral Step 4: Insert the number of M = conductors per phase. 1 1+f Line to Line Line to Neutral Fault Current at Service Equipment
L = Isca = N = C = EL-L = f = C = EL-N = f =
150 Select Conductor & Raceway 0 1 2/0 0 Phase Conductor 0 Volt 0.000 0 Neutral Conductor 2 0 Volt 0.000
Step 5a: Select phase M = 1.000 conductor size size. M = 1.000
Step 5b: Select neutral conductor size.
Finished product Isca x M = fault current at terminals of main disconnect L- L = CALCULATED FAULT CURRENT Isca x M = fault current at terminals of main disconnect L- N =
0 amperes 0 amperes
Fault Current from Service disc. to panel "_____" Single Phase Feeder Length (distance) 2xLxI (ASC) 'f ' factor = N x Cby entering next point x E L-N # conductors per phase Continue to point Phase conductor constant Volt Line to Line Neutral conductor constant Volt Line to Neutral Multiplier M= 1 Line to Line L =
Select Conductor & Raceway
Single Phase
Isca = N = C = EL-L = f = C = EL-N = f = M =
0 Phase 0 Phase Conductor
0AWG
0 Volt0.000 0 Neutral Conductor 0 Volt 0.000 1.000AWG
1+f
Line to Neutral
M
=
1.000
Isca x M = fault current at terminals of the panel L- L = Isca x M = fault current at terminals of the panel L- N = Calculation does not include motor contribution
0 amperes 0 amperes
Branch Circuit Fault from Single Phase Branch 2xLxI 'f ' factor =
Point to Point Length (distance) (ASC)# conductors per phase
Select Conductor & Raceway
L
= 0 Phase 0 Phase Conductor
Single Phase
N x C x E L-N
Phase conductor constant Volt Line to Line Neutral conductor constant Volt Line to Neutral Multiplier M= 1 1+f Line to Line Line to Neutral
Isca = N = C = EL-L = f = C = EL-N = f = M M = =
0AWG
0 Volt0.000 0 Neutral Conductor 0 Volt 0.000 1.000 1.000AWG
Isca x M = fault current at terminals of the panel L- L = Isca x M = fault current at terminals of the panel L- N = Calculation does not include motor contribution
0 amperes 0 amperes
on
1b: Insert both Ver. 4.00 the kVA ng and impedence of ormer. (Note: When you insert
ating and impedence you must voltage from the select the Voltage se from dropdown box before the l be calculated.)
Voltage & Phase
Conductor & Raceway
2/0
2
ep 5b: Select neutral conductor size.
Conductor & Raceway
Single Phase
NeutralAWG
AWG
Conductor & Raceway Single Phase
NeutralAWG
AWG
Job Name Your Company Name
Available Fault Current Calculationby:John Sokolik
Ver. 6.3
Utility Fault Current
23,132 amperes
I = kVA x 1000 = trans. FLA E x 1.732 Isca = trans. FLA x 100 transformer Z
kVA = E = trans. FLA =
208 0
Three Singl in PVC AWG ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### 400 kcmil 500 kcmil 600 kcmil 750 kcmil 1000 kcmil
=Isca =
0 % 0 amperes Three Phase 208/120 FEET
Isca = ampere short-circuit current RMS symmetrical.
Point to Point Method 'f ' factor = Length (distance) 1.732 x L x I (ASC) L = Isca = N = C = EL-L = f = C = EL-N = f = M M = =
N x C x E L-N
# conductors per phase
Phase conductor constant Volt Line to Line Neutral conductor constant Volt Line to Neutral M= 1 1+f
Multiplier
50 Copper in Nonmetallic Raceway 23,132 1 500 kcmil 26,706 Phase Conductor 208 Volt 0.361 26,706 Neutral Conductor 500 kcmil 120 Volt 0.625 0.735 0.615
Line to Line Line to Neutral Fault Current at Service Equipment
Isca x M = fault current at terminals of main disconnect L- L = Isca x M = fault current at terminals of main disconnect L- N =
17,001 amperes 14,234 amperes### ###
Neutral
Fault Current from (example FROM SERVICE EQUIP TO PANEL) Three Phase Feeder 1.732 x L x I 'f ' factor = Length (distance) (ASC)# conductors per phase
Copper in Nonmetallic Raceway Three Phase
N x C x E L-N
Phase conductor constant Volt Line to Line Neutral conductor constant Volt Line to Neutral Multiplier M= 1 1+f Line to Line Line to Neutral
L = Isca = N = C = EL-L = f = C = EL-N = f = M M = =
100 17,001 Phase 14,234 Neutral 1 7,493 Phase Conductor 1 208 Volt 1.889 7,493 Neutral Conductor 1 120 Volt 2.742 0.346 0.267
### ### ### ###
### Isca x M = fault current at terminal of the panel L- L = Isca x M = fault current at terminal of the panel L- N = Calculation does not include motor contribution
5,884 amperes 3,804 amperes### ###
AL/PVC CU/MET AL/MET