Shop Practice

download Shop Practice

of 24

Transcript of Shop Practice

  • 7/31/2019 Shop Practice

    1/24

    NATIONAL ELECTRICAL CODE (NEC) AND PHILIPPINES ELECTRICAL CODE (PEC)

    RULES AND REGULATIONS ON DIFFERENT WIRING METHODS

    I. NON METALLIC RACEWAY OR WOODEN MOLD WIRING

    A. Definition

    Non metallic raceway or wooden mold wiring is a

    wiring method where conductors are installed in a surface

    container which lay out along the surface of ceiling and

    walls and not concealed (or not hidden).

    B. Use

    The use of this wiring shall be permitted only in dry

    locations (places not affected by rain or moisture). It

    shall not be used, however:

    1. When or where concealed.

    2. Where subject to severe physical damage unless approved

    for the purpose.

    3. When voltage is more than 300V between conductors.

    4. In hoist ways.

    5. In hazardous location.

    6. Where subject to ambient temperature exceeding 50C.

    C. Size of Conductors

    No conductor larger than that for which the raceway is

    design shall be installed in non metallic surface raceway.

    D. Number of Conductors in Raceway

  • 7/31/2019 Shop Practice

    2/24

    The number of conductors installed in any raceway

    shall be no greater than the number for which the raceway

    is designed.

    E. Fittings for Taps and Joints

    Any junction point requiring joints and taps shall use

    porcelain tee or porcelain cross with base. When junction

    points come from one direction from top or from below, the

    run wire porcelain tee is used. Where taps come from both

    direction, porcelain cross is used.

  • 7/31/2019 Shop Practice

    3/24

    F. Need for Porcelain Tube or Flexible Circular Loom

    Where conductors are entering switches, convenience

    outlet, lamp socket, cutout box, and safety switch shall be

    protected by circular loom.

    If the wire or wires passing through walls porcelain

    tube or circular loom may be used. Where circular loom or

    mica tube is used at the end of the wooden mold or raceway

    a V cut or M cut must be made the molding end.

    G. Wall Switch, Convenience Outlet and Lamp Holder

    Wall switch and convenience outlet used must be of the

    surface type. In case of the wall switch is must be mounted

    on a switch base when installed. The lamp holder used must

    be of the cleat type.

  • 7/31/2019 Shop Practice

    4/24

    II. OPEN WIRING OR INSULATOR OR EXPOSED KNOB AND TUBE WIRING

    A. Definition

    Open wiring or insulators is a wiring method usingknob tubes, cleats and flexible tubing for the protection

    and support of insulated conductors run is and on building

    and not concealed by the building structure.

    B. Use

    1. The wiring method may be used for or outside the

    building.

    a. Exposed work, either inside or outside the building.

    b. In wet or dry location

    c. When subject to corrosive

    2. This wiring method, however shall not be used

    a. Commercial garage

    b. In theater or movie houses

    c. In motion picture studios

    d. In hazardous location

    C. Conductors

    Any conductors shall be insulated. Only single

    conductor may be used on a knob (split or solid) or tubing

    hence conductor such as TW, THW, RW, RHW, etc. are

    permitted.

    In figuring the ampacities (meaning current carrying

    capacity of wire) allowed, the table for copper or aluminum

    conductor must be consulted.

    D. Supports

  • 7/31/2019 Shop Practice

    5/24

    1. Conductor must be separated or must not take contact with

    any object over than its insulating supports. The

    supports shall be non combustible and non absorptive.

    a. Under ordinary conditions and conductor support shall

    not be more than 4 feet apart or closer as the

    condition warrants.

    b. Conductors of number 8 or larger that are installed

    across open space where they are not liable to be

    disturbed may have the support spaced is feet apart.

    However, non combustible, non absorptive support

    shall be speed at interval not to exceed 4 feet apart

    and a minimum spacing of 2 inch between conductors.

    c. In buildings of mill constructions where feeders of

    number 8 or longer are used and a minimum spacing 6

    between conductors maintained the conductors may be

    supported at the timbers only.

    2. Exceptions:

    a. Approved flexible non metallic tubing may be used to

    cover the conductor in a continuous length not to

    exceed is 15feet when not exposed to physical damaged

    and in a dry location and shall be secured by straps

    not more than 4 feet apart.

    b. Conductors of number 8 or larger that are installedacross open spaced wire. They are not liable to be

    disturbed may have the support spaced is feet apart.

    However, non combustible, non absorptive support

    shall be speed at interval not to exceed 4 feet apart

    and a minimum spacing of 2 inch between conductors.

    c. In buildings of mill constructions where feeders of

    number 8 or larger are used and a minimum spacing of

    6 between conductors maintained the conductors may be

    supported at the timbers only.

    E. Conductor Separation

    1. For voltage not exceeding 300V between conductors

    a. A minimum of 2 inches separation between conductors.

  • 7/31/2019 Shop Practice

    6/24

  • 7/31/2019 Shop Practice

    7/24

    J. Protection from Physical Damage

    Open conductors exposed to physical damage they shall

    be separated by any of the following:

    a. By guard strip not less than inch in thickness and as

    high as the insulating support place on each side.

    b. By substantial running board at least inch thick or by

    wooden molds.

    c. By metal strips or metal mold.

    d. By conduit pipe in continuous length.

    K. Entering Spaces Subject to Dampness

    All conductor of open wiring that enter or leave a

    damp wet or corrosive space shall have drip loops and the

    tube entering the walls shall be non combustible and non

    absorptive mounted on a slope so that the moisture will

    not enter other parts of the building.

  • 7/31/2019 Shop Practice

    8/24

    III. CONCEALED KNOB AND TUBE WIRING

    A. Definition

    Concealed knob and tube wiring is a wiring methodusing knobs, tube and flexible non metallic tubing for

    the protection and support of insulated conductor concealed

    or hidden in hallow spaces of walls and ceilings of

    buildings.

    B. Use

    This type of wiring shall be use in hallow spaces of

    walls and ceilings it shall not be use in:

    1. The commercial garage

    2. Theaters

    3. Motion picture studios

    4. Hazardous location

    C. Conductors

    The same provision as that in open wiring or

    insulator.

    D. Supports

    The same provision as that in open wiring or

    insulator.

    E. Conductive Separation

    a. Conductor shall be separated at least 3 and maintained

    at least 1 from the surface wired over.

    b. At distributing center outlets, switches or other places

    where spaces are limited each conductor shall be encased

    in a continuous length of flexible tubing.

  • 7/31/2019 Shop Practice

    9/24

    F. Separation from Other Objects and Protections

    The same provision as that in open wiring or

    insulator.

    G. Boxes of Insulating Materials

    The use of non metallic boxes is permitted. Provided

    that the conductors are supplied with in 8 inches of the

    box.

    H. Switches

    The same provision as that in open wiring or

    insulator.

  • 7/31/2019 Shop Practice

    10/24

    IV. METAL MOLD OR SURFACE METAL RACEWAYS

    A. Definition

    Surface metal raceways provide in wiring method thathas many advantages. This wiring method not intended for

    new construction, but is quite valuable in additions to

    existing wiring systems that must be expanded without

    cutting into the existing building to add conduit and other

    component surface metal raceway have been use for many

    years and have been found quite satisfactory for the

    purpose for which they are intended.

    B. Use

    Surface metal raceways may be installed in dry

    location in most any case except the following:

    1. Where concealed except that it may be used for under

    paster extensions when approved for that purpose.

    2. Where exposed to severe physical damage unless approved

    for that purpose.

    3. Where the voltage between conductors exceed 300V.

    4. Where subject to corrosive vapors.

    5. In hoist ways.

    6. In hazardous areas.

    C. Grounding Metal Enclosures

    Metal raceways, boxes, cabinets and fittings shall be

    grounded.

    D. Electrical Continuity of Metal Raceways Enclosures

    Metal raceways or metal enclosures for conductors

    shall be metallically joined together into a continuous

    electrical conductor.

  • 7/31/2019 Shop Practice

    11/24

    E. Secured Place

    All raceways, boxes, cabinets and fittings shall be

    securely fastened in place with approved screws.

    F. Mechanical Continuity of Raceways and Conductors

    Raceways and other assemblies shall be continuous from

    outlet to outlet and from fitting conductors shall be

    continuous between outlet and devices. No splices shall be

    permitted in raceways.

  • 7/31/2019 Shop Practice

    12/24

  • 7/31/2019 Shop Practice

    13/24

    V. ARMORED CABLE OR BX WIRING

    A. Definition

    Armored cable wiring is a wiring method using afabricated assembly of insulated conductors in a flexible

    metallic enclosure.

    B. Use

    Armored cable wiring may be use in the following:

    1. For dry location

    2. Under plastic extensions

    3. Embedded in plaster finish

    4. Embedded in brief or other masonry except in wet or damp

    location.

    5. May be run or fish in air void, of masonry block of the

    walls that are not exposed to moisture or dampness are

    below grade lines.

    6. In damp places and where exposed to oil or other

    conditions that might deteriorate the insulation if thearmored cable is of the ACL type (lead - covered)

    Armored Cable may not be use in:

    1. Theaters

    2. Motion pictures studios

    3. Any hazardous locations

    4. Crane or hoists

    5. Storage battery rooms

    6. Where exposed to corrosive vapors

    7. To hoist ways of elevators

    8. Commercial garage

  • 7/31/2019 Shop Practice

    14/24

    C. Types

    There are numbers of types of armored cable such as

    type AC, type ACL, type ACI, etc.

    Armored cables are for branch circuits. This cable are

    made of flexible metal type but an internal strips of

    bonding composed of copper or aluminum shall be continue

    throughout the length and

  • 7/31/2019 Shop Practice

    15/24

    D. Conductors

    The insulated conductors shall be of the following

    types:

    1. Rubber

    2. Thermoplastic

    3. Varnished cloth

    4. Asbestos varnished cloth

    5. Special type approved for the purpose

    E. Supports

    All supports for armored cable must be of the approved

    type and must be installed so as not to damage the cable.

    Armored cable shall be secured at interval not to

    exceed 4 feet and within 12 may be extended to not over

    24 at terminal where there is a necessity for flexibility.

    F. Bends

    All bends are to be made so as not to damage the

    cable.

    The bend radius shall not be less than 5 times the

    diameter of the cable.

    G. Electrical Continuity of Armored Cable and Enclosures

    The armor of armored cable shall be metallically

    joined together into a continuous electrical conductor. The

    armor covering shall be securely and effectively connected

    to boxes fittings and cabinets locknuts and connectors

    supply this continuity.

    H. Mechanically Continuity of Armored Cable

  • 7/31/2019 Shop Practice

    16/24

  • 7/31/2019 Shop Practice

    17/24

  • 7/31/2019 Shop Practice

    18/24

    D. Wet Locations

    All supports volts straps concrete shall be of

    corrosion resistant materials or protected against

    corrosion by approve corrosion resistant materials. In

    exposed work under wet or damp location it is required that

    a air space between the conduit system (including boxes

    and fittings and the surface wired over).

    E. Minimum Sizes

    For practical purposes inch trade size rigid conduit

    is the smallest allowable however for under plaster

    extensions conduit with a minimum inside diameter of 5/16

    is permitted in some cases.

    F. Number of Conductors in Conduit

    A table for a minimum number of conductors in table

    sizes of conduit shall be consulted. Example is given below:

    Wire

    Type

    Conductors

    Size

    1/2 3/4 1 1/4 2 2

    TW,

    THW

    14 9 15 25 44 99 142

    RW,

    RHW

    10

    12

    8

    7

    5

    2

    12

    9

    4

    19

    15

    7

    35

    26

    12

    78

    60

    28

    111

    85

    40

  • 7/31/2019 Shop Practice

    19/24

    VII. Non Metallic Sheated or Loomex Cable Wiring

    A. Definition

    Non metallic sheated, which is commonly termed asloomex cable is a factory assembly of two or more insulated

    conductors having an outer sheat or moisture resistance,

    flame retardant or sometimes corrosion resistant, non

    metallic material.

    B. Use

    This type of wiring either for exposed or concealed

    wiring it maybe regarded as a substitute for open wiring on

    insulator or exposed knob and tube work, and has the

    advantages that continuous protection is provided over the

    entire length of the conductor. In addition to the

    insulation supplied to ordinary thermoplastic were in the

    case of armored cable no insulating supports are required

    and only one hole need be bared when the cable passes

    through a timber.

    Insulating bushing or grommets shall be used where the

    cable passes through holes in metal part or similar members.

    C. Types

    Non metallic sheated cable are manufacture in the

    following types, type NM which has an overall covering of

    the flame retardant materials and the type NMC which has an

    overall covering of flame retardant, moisture resistance,

    fungus resistant and corrosion resistant materials.

    Both types are emitted to be used in one and two

    familiar dwelling and other structure exceeding three

    floors.

    Type NM, non metallic sheated cables are permitted

    to be installed for exposed and concealed work in normally

    dry location. It is also permissible to be ferned in air

    voids, in masonry blocks on tiles, walls where such walls

    are not expose on suggested to excessive moisture or

    dampness. This cable (type NM) shall not be installed in

  • 7/31/2019 Shop Practice

    20/24

  • 7/31/2019 Shop Practice

    21/24

    Both types however shall not be use at

    1. Service entrance cable

    2. In commercial garage

    3. In theaters

    4. Motion picture studios

    5. Hoist ways

    6. Hazardous location

    7. Embedded in poured cement or concrete

    D. Supports

    Non metallic sheated cable shall be seaved by wire

    staple strap or similar fittings so designed and installed

    as not to injured, the cable shall be secured in place at

    interval not exceeding 4ft. and within 12 from every

    cabinet, box or fittings.

    E. Bends

    Bends in cable shall be made so that the protective

    covering of the loomex not allowed the cable must be

    injured. No bends shall have the radius less than five

    times the diameter of the cable.

  • 7/31/2019 Shop Practice

    22/24

    RULES AND REGULATION ON SERVICE ENTRANCE INSTALLATION

    1. Service conditions supplying a building or other structureshall not pass through the other interior or another

    building.

    2. Service conductors shall normally with stand exposure to

    atmospheric and other condition of use without deter mental

    lockage of current.

    3. Ungrounded conductors of service entrance for limited loads

    of a single branch ckt. shall be number 12 or number 1 but

    it is no case smaller than the branch ckt. conductors.

    4. Service entrance conductor shall not have be splice.

    5. Service raceways or tubing shall be equipped with a rain

    tight or weather head.

    6. Drip loops shall be formed on end service entrance

    conductor to prevent entrance of water and moisture.

    7. Any service entrance raceway tubing or cable shall

    terminate at the

  • 7/31/2019 Shop Practice

    23/24

    RULES AND REGULATION ON SERVICE, SWITCH FEEDER AND DISTRIBUTION

    BOARD INSTALATION

    1. Conductors and bus bars on a distribution board shall be located

    as to be free from physical damage and shall be held firmly in

    place.

    2.The arrangement of bus bars and conductors shall be such as to

    avoid over heating due to inductive effect.

    3.Feeder conductor shall have an ampacity not lower than required

    to apply the load.

    4.Feeder conductor shall not be smaller than number 10 where the

    load supplies consist of the following number and types of

    circuit

    a. Two or more two wire branch circuit supplied by a two wire

    feeder.

    b. More than two wire branch ckt. supplied by three wire feeder.

    c. Two or more three wire branch ckt. supplied by three wire

    feeders.

    5. Feeder conductors ampacity shall not be lower than that of

    the service entrance conductor.

    6. Service switch, containing the main protective devices such

    as fuse or circuit breaker must be installed as near as

    possible to the point of entrance.

  • 7/31/2019 Shop Practice

    24/24