SHEET LIST - weaverandjacobs.com · roof top mechanical unit on plan beam bottom chord bracing on...
Transcript of SHEET LIST - weaverandjacobs.com · roof top mechanical unit on plan beam bottom chord bracing on...
RTU___#
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
R
S
T
U
V
W
TYPICAL STRUCTURAL ABBREVIATIONS
WB-1
TRUSS
TYPICAL SYMBOLS LEGEND TYPICAL PLAN NOTES:
CAST IRON C.I.
APPROVED APPD.
W.I.WD.W.P.W/WDW.W.L.WBW.W.M.WPFG.WS.
PRE-ENGINEERED
WROUGHT IRONWOODWORK POINTWITHWINDOWWIND LOADWIND BRACEWELDED WIRE MESHWATERPROOFING
WATERSTOP
VERT.VERTICAL
UNLESS NOTED OTHERWISE U.N.O.
TSTR.T.O.W.T.O.S.C.T.O.S.T.R.W.T.O.P.C.T.O.P.T.O.F.T.O.B.
T & BT & GTHK.TERR.TTEMP.
TUBE STEELTREADTOP OF WALLTOP OF STRUCTURAL CONCRETETOP OF STEELTOP OF RETAINING WALLTOP OF PIER CAPTOP OF PIERTOP OF FOOTINGTOP OF BEAM
TOP AND BOTTOMTONGUE & GROOVETHICKTERRAZZOTENSIONTEMPERATURE
SUPT(S).SUBCONTR.SYM.STRUCT'L.STRUCT.STIR.STR.STIFF.STL.STD.S.F.SPEC'D.SPEC(S)SPA.SIM.SW.SHT.VSECT.SCHED.
SUPPORT(S)SUBCONTRACTORSYMMETRICALSTRUCTURALSTRUCTURESTIRRUPSSTRAIGHTSTIFFENERSTEELSTANDARDSQUARE FOOT (FEET)SPECIFIEDSPECIFICATION(S)SPACESIMILARSIDEWALKSHEETSHEARSECTIONSCHEDULE(D)
RND.RM.RF. OPNG.R.D.RF.RIS.REQ'D.RET. SYS.REQ.REM. OR RREINF.RCPR
ROUNDROOMROOF OPENINGROOF DRAINROOFRISERREQUIREDRETENTION SYSTEMREQUIREREMAINDERREINFORCE(ING) (ED) (MENT)REINFORCED CONCRETE PIPERADIUS
PROJ.PRELIM.PREFAB.
P/CP.S.I.P.S.F.PT.PL.PC.PERP.
PARTN.PAR.P
PROJECTIONPRELIMINARYPREFABRICATED
PRECAST CONCRETEPOUNDS PER SQUARE INCHPOUNDS PER SQUARE FOOTPOINTPLATEPIECEPERPENDICULAR
PARTITIONPARALLELPAN
OSTG.O.D.O.F.O.H.OPP.OPNG(S).O.C.
OUTSTANDINGOUTSIDE DIAMETEROUTSIDE FACEOPPOSITE HANDOPPOSITEOPENING(S)ON CENTER
NO. OR #N.T.S.N.I.C.N.S.NOM.N.F.
NUMBERNOT TO SCALENOT IN CONTRACTNON-SHRINKNOMINALNEAR FACE
M.C. ORMMISC.MIN.MID.MEZZ.MECH.MAX.MAT.M.O.MFR.
MOMENT CONNECTION(S)MOMENTMISCELLANEOUSMINIMUMMIDDLEMEZZANINEMECHANICALMAXIMUMMATERIALMASONRY OPENINGMANUFACTURE(R)
L.P.LLVLLHLONG.LLLWT. CONC.
LOW POINTLONG LEG VERTICALLONG LEG HORIZONTALLONGITUDINALLIVE LOADLIGHTWEIGHT CONCRETE
KSFKLFk
KIP PER SQUARE FOOTKIP PER LINEAR FOOTKIPS (1000 LBS)
JST(S).JT(S).
JOIST(S)JOINT(S)
INTERM.INT.I.F.I.D.INFO.
INTERMEDIATEINTERIORINSIDE FACEINSIDE DIAMETERINFORMATION
HK.HORIZ.
H.P.HT.H.S.
HOOKHORIZONTAL
HIGH POINTHEIGHTHEADED STUDS
GR. BM.GR.GOVT.GEN. CONTR.
G.S.G.I.GALV.GA.
GRADE BEAMGRADEGOVERNMENT
GENERAL CONTRACTORGALVANIZED STEELGALVANIZED IRONGALVANIZEDGAGE OR GAUGE
FDN.F.D.FL.FLG.FP.FIN. FL.FIN.
F.S.FABR.F. TO F.
FOUNDATIONFLOOR DRAINFLOORFLANGEFIREPROOF(ING)FINISHED FLOORFINISH(ED)
FAR SIDEFABRICATORFACE TO FACE
X-STR.EXT.EXIST.E.J.EXP.EQUIP.EQ.ENT.ENGR.ELEV.EL.ELEC.
E.W.E.F.EA.
EXTRA STRONGEXTERIOREXISTINGEXPANSION JOINTEXPANSIONEQUIPMENTEQUALENTRANCEENGINEERELEVATORELEVATIONELECTRICAL
EACH WAYEACH FACEEACH
DWL(S).DBL.DWG(S).DS.DVTL.DIM(S).DIA.DIAG.D.B.A.DLDET.
DOWEL(S)DOUBLEDRAWING(S)DOWNSPOUTDOVETAILDIMENSION(S)DIAMETERDIAGONALDEFORMED BAR ANCHORDEAD LOADDETAIL
COV. PL.COR.C.J.CONST.CT.J.CONTR.CONT.CONN(S).CMUCONC.C OR COMP.COL.CLR.CC. TO C.C.G.C.L.CLG.C.I.P.
COVER PLATECORNERCONSTRUCTION JOINTCONSTRUCTIONCONTROL JOINTCONTRACTORCONTINUOUSCONNECTION (S)CONCRETE MASONRY UNITCONCRETECOMPRESSIONCOLUMNCLEAR OR CLEARANCECHANNELCENTER TO CENTERCENTER OF GRAVITYCENTER LINECEILINGCAST-IN-PLACE
B.L.BLDG.BRDG.B.L.E.
BRACKET BRKT.BOT.B.O.BLKG.BLK.BEV ('D)BTWN.BFFBRG.BM.BSMT.B. TO B.B.F.
BUILDING LINEBUILDINGBRIDGINGBRICK LEDGE ELEVATION
BOTTOMBLOCK-OUTBLOCKINGBLOCKBEVEL (ED)BETWEENBELOW FINISH FLOORBEARINGBEAMBASEMENTBACK TO BACKBACK FACE
AHUA/C@
ARCH'L.ARCH.APPROX.
L&A.B.ALT.
AIR HANDLING UNITAIR CONDITIONERAT
ARCHITECTURALARCHITECTAPPROXIMATE
ANGLEANDANCHOR BOLTALTERNATEAGGREGATE AGGR.ADJACENT ADJ.ADDITIONAL ADDN'LABOVE FINISH FLOOR AFF
EDGE ANGLE OFFSET E.A.O.
ARCH'L. FINISH SURFACE A.F.S.
FIELD VERIFY (F.V.)
TAPERED BEAM T.B.
ARE NOT NECESSARILY USED
PENETRATION PEN.
CANTILEVER CANT.
TOP OF T.O.
TYPICAL TYP.
ALL ABBREVIATIONS SHOWN
HOLLOW STRUCTURAL SHAPE HSS
BUILDING MANUFACTURER PEBMPRE-ENGINEEREDMETAL BUILDING PEMB
TYPICAL ABBREVIATIONS, SYMBOLS AND PLAN NOTES AS-1
SUBSTITUTIONS
DESIGN LOADS
A.F.S.
INDICATES TRUSS - SEE TRUSS ELEVATIONS.
INDICATES THAT COLUMN STOPS AT THIS LEVEL.
INDICATES THAT COLUMN STARTS UPWARD FROM THIS LEVEL.
INDICATES WIND BRACE - SEE WIND BRACE ELEVATIONS.
CAST-IN-PLACE CONCRETE
STRUCTURAL PRECAST CONCRETE
SAND GRAVEL, OR LOW P.I. FILL
EARTH
ROCK
ARCHITECTURAL PRECAST CONCRETE
NON-SHRINK GROUT
SAND CEMENT GROUT
C.M.U.
BRICK
EXISTING
STRUCTURAL STEEL
WOOD (CONTINUOUS)
WOOD (NON-CONTINUOUS)
GLUE LAMINATED LUMBER (GLU-LAM)
ARCHITECTURAL FINISHED SURFACE
PLYWOOD
MICRO LAMINATED LUMBER (MICRO-LAM)
3. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF FLOOR DROPS, FLOOR SLOPES, CURBS,MISCELLANEOUS ELEVATIONS, DETAILS AND DIMENSIONS NOT SHOWN ON PLAN.
4. SEE ARCH'L. DWGS. FOR SIZES & LOCATIONS OF ROOF OPENINGS.
5. REPETITIVE MEMBERS SUCH AS BEAM PURLINS SHALL BE EQUALLY SPACED BETWEEN DIMENSIONEDPOINTS, U.N.O.
6. NOTE TO CONTRACTOR:FIELD VERIFY ALL EXISTING DIMENSIONS & ELEVATIONS PRIOR TO FABRICATION OF MATERIALSAND CONSTRUCTION.
ROOF TOP MECHANICAL UNIT ON PLAN
BEAM BOTTOM CHORD BRACING ON PLAN
THE FOLLOWING GENERAL NOTES CONSTITUTE A MAJOR PART OF THE PLANS AND SPECIFICATIONS. STRICTCOMPLIANCE WITH THESE NOTES IS ESSENTIAL TO THE PROPER CONSTRUCTION OF THE BUILDING.
1. REFER TO THE PLAN NOTES, LOCATED IN THESE GENERAL NOTES, FOR APPLICATION OF DETAILS WHICH AREDESIGNATED AS "TYPICAL DETAILS" IN THIS SET OF DRAWINGS.
2. SLEEVES AND BLOCKOUTS REQUIRED FOR PASSAGE OF DUCTWORK, PIPING, DRAINS, CONDUIT, ETC., ANDANCHORS REQUIRED FOR ANCHORING EQUIPMENT AND PIPING ARE NOT GENERALLY INDICATED ON THESTRUCTURAL DRAWINGS. THE CONTRACTOR SHALL DETERMINE SUCH REQUIREMENTS FROM OTHER SERIESDRAWINGS, SUBCONTRACTORS, AND SUPPLIERS AND SHALL COORDINATE THE LOCATIONS AND DETAILS FORTHESE ITEMS PRIOR TO FABRICATION OR CONSTRUCTION OF THE STRUCTURE. ANY CONFLICTS BETWEEN THESEITEMS AND THE BUILDING STRUCTURE SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FORRESOLUTION.
3. VERIFY, OR ESTABLISH, LOCATIONS AND DIMENSIONS OF ALL FRAMED OPENINGS RELATED TO EQUIPMENT ORDUCTWORK, INCLUDING INSULATION, IF ANY. WHERE SUBSTANTIAL RELOCATION OR RECONFIGURATION ISREQUIRED, SUBMIT A DRAWING TO THE ARCHITECT FOR REVIEW.
4. LOCATE EXISTING REINFORCEMENT, USING APPROPRIATE IMAGING EQUIPMENT, PRIOR TO CUTTING OR DRILLINGINTO EXISTING CONCRETE. DO NOT CUT OR DAMAGE EXISTING REINFORCEMENT. IF THE REQUIRED OPERATIONSMAKE DAMAGING EXISTING REINFORCING UNAVOIDABLE, INFORM ARCHITECT SO THAT THE CONDITION MAY BEEVALUATED AND ALTERNATIVE DIRECTIONS GIVEN.
5. MATERIALS OR PRODUCTS SUBMITTED FOR APPROVAL WHICH ARE NOT AS SPECIFIED IN THE DOCUMENTSSHALL BE ACCOMPANIED BY A CURRENT ES REPORT (BY ICC EVALUATION SERVICE, INC.) OR ICBO REPORT (BYINTERNATIONAL CONFERENCE OF BUILDING OFFICIALS). MATERIALS OR PRODUCTS THAT DO NOT HAVE AN ESOR ICBO REPORT INDICATING THE SUBSTITUTED MATERIAL OR PRODUCT TO BE EQUAL TO THAT SPECIFIED, WILLNOT BE CONSIDERED.
1. ALL REQUESTS FOR SUBSTITUTIONS OF MATERIALS OR DETAILS SHOWN IN THE CONTRACT DOCUMENTS SHALLBE SUBMITTED FOR APPROVAL DURING THE BIDDING PERIOD. ONCE BIDS ARE ACCEPTED, PROPOSEDSUBSTITUTIONS WILL BE CONSIDERED ONLY WHEN THEY ARE OFFICIALLY SUBMITTED WITH AN IDENTIFIEDSAVINGS TO BE DEDUCTED FROM THE CONTRACT.
INDICATES MOMENT CONNECTION -SEE MOMENT CONNECTION DETAILS.
INDICATES STEEL BEAM SPLICE -SEE STRUCTURAL STEEL SIMPLE BEAM CONNECTION DETAILS SBX-1.
STRUCTURAL SYMBOLSTHE FOLLOWING SYMBOLS ARE USED TO REPRESENT THE MATERIALS SHOWN ON THESTRUCTURAL DRAWINGS. SEE SPECIFICATIONS AND GENERAL NOTES FOR MATERIALQUALITIES REQUIRED.
1. SEE ARCHITECTURAL DRAWINGS FOR ACTUAL SEA LEVEL ELEVATION RELATED TO DATUM ELEVATION =100'-0" SHOWN ON DRAWINGS.
- SEE PLAN FOR TOP OF STRUCTURAL CONCRETE (T.O.S.C.) ELEVATION.- T.O.S. EL. = BOTTOM OF METAL DECK ELEVATION SEE PLAN FOR TOP OF STEEL (T.O.S.) ELEVATION.
2. SHEET INDEX:THE DETAILS IN THE DRAWINGS, INCLUDING THOSE DRAWINGS REFERENCED BY THIS INDEX, WHICH AREDESIGNATED AS "TYPICAL DETAILS", APPLY GENERALLY TO THE CONSTRUCTION IN ALL AREAS WHERETHE CONDITIONS ARE SIMILAR TO THOSE DESCRIBED IN THE DETAILS, REGARDLESS OF WHETHER OR NOTTHE DETAILS ARE SPECIFICALLY REFERENCED IN THE DRAWINGS.
G.C.
GENERAL
EXISTING CONDITIONS1. FIELD VERIFY ALL RELEVANT DIMENSIONS AND CONDITIONS AT EXISTING STRUCTURES PRIOR TO STARTING
SHOP DRAWINGS AND THE CONSTRUCTION PROCESS IN THOSE AREAS. SUBMIT APPROPRIATE PLANS ANDDETAILS REFLECTING THE FIELD VERIFIED EXISTING CONDITIONS FOR THE ARCHITECT'S USE
.2. EXISTING CONDITIONS WHICH REQUIRE MODIFICATIONS TO THE DESIGN OF THE PROPOSED CONSTRUCTION SHALL
BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT.
3. THE TESTING LABORATORY SHALL EXAMINE AND REPORT ON THE CONDITION OF PORTIONS OF THE EXISTINGSTRUCTURE WHICH WILL BE ALTERED OR WHICH WILL SUPPORT NEW FRAMING, WITH SPECIAL EMPHASIS ON THEFOLLOWING:
A. EXISTING BOLTED CONNECTIONS: IDENTIFY MISSING, DAMAGED OR OTHERWISE DETERIORATED BOLTS ANDCONNECTION PLATES.
B. EXISTING WELDED CONNECTIONS: VERIFY THAT WELDS WERE COMPLETED AND ARE STILL IN GOOD CONDITION, SUITABLE FOR SUPPORT OF ADDITIONAL LOADS SHOWN ON DRAWINGS.
C. GENERAL CONDITION OF FRAMING IN AREAS TO BE LOADED OR ALTERED. CONFIGURATION AND EVIDENCEOF EXCESSIVE CORROSION OR OTHER DAMAGE SHALL BE REPORTED.
1. DEAD LOADS INCLUDE THE WEIGHT OF THE STRUCTURAL COMPONENTS AND ALLOWANCES FORPERMANENT PARTITIONS, PERMANENT FIXTURES, FINISHES, ROOFING, MECHANICAL, ELECTRICAL,PLUMBING AND FIRE PROTECTION MATERIALS SHOWN OR SPECIFIED.
2. LOADINGS FOR MECHANICAL ROOMS ARE BASED ON THE WEIGHTS OF ASSUMED EQUIPMENT, ASINDICATED ON THE MECHANICAL DRAWINGS (INCLUDING THE WEIGHT OF CONCRETE PADS, WHEREINDICATED). ANY CHANGES IN TYPE, SIZE, LOCATION OR NUMBER OF PIECES OF EQUIPMENT SHOULD BE REPORTED TO THE ARCHITECT FOR VERIFICATION OF THE ADEQUACY OF SUPPORTING MEMBERS PRIOR TO THE PLACEMENT OF SUCH EQUIPMENT.
3. DESIGN LIVE LOADING IS AS FOLLOWS:ROOF ..................................................................................................................................................... 20 PSFOFFICES (NOT INCLUDING NON-PERMANENT PARTITIONS)................................................................. 50 PSFPARTITION ALLOWANCE IN OFFICE AND CLASSROOM AREAS......................................................... 20 PSFEXTERIOR BALCONIES.......................................................................................................................... 100 PSFSTAIRWAYS.......................................................................................................................................... 100 PSFPUBLIC CORRIDORS.............................................................................................................................. 100 PSFCORRIDORS ABOVE FIRST FLOOR....................................................................................................... 80 PSFALL SLABS-ON-GRADE........................................................................................................................ 100 PSFSTORAGE (LIGHT).................................................................................................................................. 125 PSFSTORAGE (HEAVY)............................................................................................................................... 250 PSFCATWALKS............................................................................................................................................ 40 PSFMECHANICAL ROOM (MIN.).................................................................................................................... 150 PSFELEVATOR MACHINE ROOM.................................................................................................................. 150 PSFHANDRAIL IMPACT LOAD...................................................................................................................... 50 PLF
4. LIVE LOAD REDUCTIONS, WHERE PERMISSIBLE, ARE COMPUTED IN ACCORDANCE WITH THE BUILDING CODE.
5. DESIGN WIND LOADING IS AS FOLLOWS (NOTE: PER ASCE 7-10, WIND LOADS ARE ULTIMATE.SERVICE LOADS MAY BE OBTAINED BY DIVIDING THE STATED LOADS BY 1.6.):
WIND DESIGN OPTION....................................................................................................... DIRECTIONAL PROCEDUREor ENVELOPE PROCEDURE
BASIC WIND SPEED (3-SECOND GUST)............................................................................................ 130 MPHRISK CATEGORY............................................................................................................................... IIEXPOSURE CATEGORY..................................................................................................................... CINTERNAL PRESSURE COEFFICIENT.................................................................................................0.18
ROOF PRESSURE(+)/ SUCTION(-) LOADS (NET – INCLUDING INTERNAL PRESSURE – LOADS MAY BE LINEARLY INTERPOLATED BETWEEN VALUES FOR THE GIVEN TRIBUTARY AREAS)
INTERIOR ZONES – MORE THAN 22’ FROM EDGE, HIP, OR RIDGE (ZONE 1) (10 SQ.FT. OF TRIBUTARY AREA)................................ +19.00 / -47.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA).............................. +16.00 / -43.00 PSF END ZONES - WITHIN 22’ OF EDGE, HIP, OR RIDGE (ZONE 2)
(10 SQ.FT. OF TRIBUTARY AREA)................................. +19.00 / -78.00 PSF(100 SQ.FT. OF TRIBUTARY AREA)............................... +16.00 / -51.00 PSF
CORNER ZONES - WHERE ZONE 2 AREAS OVERLAP (ZONE 3)(10 SQ.FT. OF TRIBUTARY AREA)................................. +19.00 / -118.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA)............................... +16.00 / -51.00 PSF
ON CANOPIES AND OVERHANGS ENDS (ZONE 2) (10 SQ.FT. OF TRIBUTARY AREA)............................. -74.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA)............................... -71.00 PSF CORNERS (ZONE 3) (10 SQ.FT. OF TRIBUTARY AREA)................................. -118.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA)............................... -40.00 PSF
CURTAINWALL DESIGN PRESSURE/SUCTIONINTERIOR ZONE (ZONE 4) (10 SQ.FT. OF TRIBUTARY AREA).......................... +43.00 / -47.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA)........................ +36.00 / -41.00 PSFEXTERIOR ZONE (ZONE 5) (10 SQ.FT. OF TRIBUTARY AREA)...........................+43.00 / -57.00 PSF
(100 SQ.FT. OF TRIBUTARY AREA)....................... +36.00 / -45.00 PSF
FM GLOBAL REQUIREMENT: MULTIPLY ABOVE VALUES BY 1.6 FOR MINIMUM FM APPROVED WIND CLASSIFICATION RATING NEEDED FOR THE ENTIRE ROOF ASSEMBLY. USE ULTIMATE WIND RATING OF 180PSF MINIMUM.
RELIABLE ROOF DEAD LOAD TO RESIST WIND UPLIFT....................................................................... 5 PSFINTERIOR PRESSURE ON STRUCTURAL ELEMENTS............................................................................. 8 PSF
6. SEISMIC DESIGN DATA (IBC):
RISK CATEGORY.............................................................................................................. IIMAPPED SPECTRAL RESPONSE ACCELERATIONS, SS & S1..........................................0.074 / 0.030SITE CLASS...................................................................................................................... DSPECTRAL RESPONSE COEFFICIENTS SDS /SD1............................................................0.079 / 0.048SEISMIC DESIGN CATEGORY........................................................................................... ABASIC SEISMIC-FORCE-RESISTING SYSTEM...........................................STEEL ORDINARY CONCENTRICALLY
BRACED FRAMESDESIGN BASE SHEAR....................................................................................................... 215kSEISMIC RESPONSE COEFFICIENT, CS.............................................................................0.025RESPONSE MODIFICATION FACTOR, R............................................................................3.25ANALYSIS PROCEDURE USED........................................................... EQUIVALENT LATERAL FORCEDEFLECTION AMPLIFICATION FACTOR.............................................................................3.25
7. SNOW LOADING (ASCE 7, SECTION 7):
GROUND SNOW LOAD..................................................................................................... 5 PSF
8. ELEVATORS: SUPPORTING ELEMENTS FOR ELEVATORS ARE BASED ON PUBLISHED DATA FOR THEFOLLOWING ELEVATOR TYPES:
SCHINDLER 3300 TRACTION ELEVATOR
SUBMIT FINAL LOAD DATA FROM MANUFACTURER SUPPLYING ELEVATORS, PRIOR TO FABRICATION OFSUPPORTING MATERIALS.
9. STACKS OF MATERIALS OR OTHER CONSTRUCTION LOADS PLACED ON THE STRUCTURE SHALL NOT EXCEEDTHE STATED DESIGN LIVE LOAD FOR THE AREA AFFECTED UNLESS ADEQUATELY SHORED.
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:3
9 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S1.01
ABBREVIATIONS,SYMBOLS, AND TYPICALPLAN NOTES
15134
SHEET LISTSHT. NO. SHEET NAME
S1.01 ABBREVIATIONS, SYMBOLS, AND TYPICAL PLAN NOTES
S1.02 GENERAL NOTES
S2.01 BASEMENT FOUNDATION PLAN
S2.02 FIRST FLOOR FRAMING PLAN
S2.03 SECOND FLOOR FRAMING PLAN
S2.04 THIRD FLOOR & LOW ROOF FRAMING PLAN
S2.05 HIGH ROOF FRAMING PLAN
S3.01 CONCRETE SECTIONS AND DETAILS
S4.01 SIMPLE BEAM CONNECTION DETAILS
S4.02 COMPOSITE STEEL BEAM DETAILS
S4.03 COMPOSITE STEEL BEAM DETAILS
S4.04 STEEL SECTIONS AND DETAILS
S4.05 STEEL SECTIONS AND DETAILS
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
CONCRETE MIX
1. CONSTRUCTION JOINTS IN BEAMS, SLABS AND WALLS SHALL ONLY OCCUR WITHIN 2'-0" OF MIDSPAN BETWEENSUPPORTS. SUBMIT A DIAGRAM OF ALL PROPOSED CONSTRUCTION JOINTS WHICH ARE NOT SPECIFICALLYSHOWN ON THESE DRAWINGS (REFER TO SPECIFICATIONS).
2. SLEEVES, MECHANICAL OPENINGS, CONDUITS, PIPES, RECESSES, DEPRESSIONS, CURBS AND ALL EMBEDDEDITEMS SHALL BE PROVIDED FOR AS SHOWN ON THE ARCHITECTURAL AND MECHANICAL DRAWINGS AND ASREQUIRED BY EQUIPMENT MANUFACTURERS. MINIMUM CONCRETE BETWEEN SLEEVES SHALL BE 6".INSTALLATION OF THESE ITEMS SHALL BE COORDINATED WITH SHOP DRAWINGS OF TRADES REQUIRING THESEITEMS.
3. SET FORMS TO FOLLOW SLOPES AND GRADES DEFINED ON PLAN, KEEPING MEMBER DEPTHS CONSTANT ATDEPTHS DETAILED OR SCHEDULED, UNLESS NOTED OTHERWISE. SLOPE UNIFORMLY BETWEEN ELEVATIONSGIVEN. BUILD IN CAMBER WHERE SPECIFIED.
4. DUE TO THE THIN CONCRETE SLABS ON THIS PROJECT, NO CONDUIT OR PIPE IS PERMITTED TO BE CAST IN THESLAB. MINOR CONDUIT MAY BE INSTALLED IN THE SLAB IF SUBMITTED IN ADVANCE TO THE ARCHITECT FORAPPROVAL.
5. FLOORS ARE NOT DESIGNED TO SUPPORT FORMWORK AND WET CONCRETE WEIGHT OF NEXT LEVEL.CONTRACTOR SHALL DESIGN AND PROVIDE RESHORING TO PREVENT OVERSTRESSING THE STRUCTURE.
6. PROVIDE 40 CUBIC YARDS OF ADDITIONAL CONCRETE TO BE USED IN THE FIELD AS DIRECTED BY THEARCHITECT/ENGINEER. LABOR FOR PLACEMENT AND FINISHING SHALL BE INCLUDED. ANY UNUSED PORTION OFTHIS QUANTITY SHALL BE CREDITED TO THE OWNER AT THE RATE OF $150 PER CUBIC YARD FOR A TOTAL OF$6,000.00
CAST-IN-PLACE CONCRETE
1. LAYOUT NEW OR TEMPORARY FLOOR OPENINGS, CORES, AND COLUMN BASE PLATE ANCHOR LOCATIONS ASSHOWN ON THE DRAWINGS.
2. AFTER PROPOSED OPENINGS, SLEEVES, AND ANCHORS HAVE BEEN LOCATED, ENGAGE TESTING LABORATORYTO LOCATE AND MARK LINES OF REINFORCING ON THE SLAB AT THOSE LOCATIONS. NOTIFY STRUCTURALENGINEER AND ARCHITECT TO SITE OBSERVE, UNLESS ALL PROPOSED MODIFICATIONS MEET THE CONDITIONS INPARAGRAPHS 5 AND 6, BELOW. MODIFY OPENING LOCATIONS IF REQUIRED.
3. TO AVOID CUTTING REINFORCING BEYOND THE EDGE OF THE OPENINGS, CORNERS OF SQUARE ORRECTANGULAR OPENINGS MAY NOT BE OVERCUT. WHEN REINFORCING IS ALLOWED TO BE CUT, IT MAY BE CUTONLY WITHIN THE LIMITS OF THE NEW OPENINGS.
4. CORNERS OF OPENINGS MAY BE CORE DRILLED AND CUT BETWEEN CORES, OR CORES MAY BE CUT ALONGEDGES OF OPENING. CONCRETE MAY THEN BE CHIPPED OUT OF THE CENTER OF THE OPENING.
5. DO NOT CORE OR CUT THROUGH BEAMS OR JOISTS.
6. WHERE THE FOLLOWING CONDITIONS ARE MET, CORING IS STRUCTURALLY ACCEPTABLE WITHOUT FURTHERRESERVATION. OTHER RESTRICTIONS MAY APPLY WHICH ARE BEYOND THE SCOPE OF THE STRUCTURALCRITERIA:
A. SLAB CORES WITH A MAXIMUM DIAMETER OF 6” THAT ARE LOCATED 1” CLEAR OF ALL EMBEDDED REINFORCING AND ARE ALIGNED WITH AND SPACED AT LEAST 6” CLEAR OF ADJACENT CORES (PARALLELOR PERPENDICULAR TO THE SLAB SPAN) AND 12” CLEAR OF EXISTING OPENINGS IN BOTH DIRECTIONS. SEETYPICAL CORING DETAIL.
B. WHERE SLAB CORES ARE NOT ALIGNED PARALLEL OR PERPENDICULAR TO SLAB SPAN, THEY SHALL BESPACED AT LEAST 6” CLEAR OF OTHER CORES IN BOTH DIRECTIONS AND 12” CLEAR OF EXISTING OPENINGS. SEE TYPICAL CORING DETAIL.
7. AFTER SETTING FLOOR DRAINS IN PLACE, FILL ALL VOIDS AROUND DRAINS SOLID WITH FLOWABLE HIGH-STRENGTH, NON-SHRINK, GROUT. GROUT TO CONFORM TO ASTM C1107.
8. WATERPROOF OR SEAL CONCRETE AND GROUT AROUND FLOOR DRAINS SO WATER CANNOT SEEP INTO JOINTSOR PENETRATE CONCRETE TO AVOID CORROSION OF ANY REINFORCING THAT HAS BEEN CUT.
CHIPPING, CUTTING, OR CORING INTO EXISTINGCONCRETE CONSTRUCTION
1. WHERE FIELD DRILLED EXPANSION BOLTS ARE PROPOSED FOR AN APPLICATION OR LOCATION NOT SHOWN ONTHESE DRAWINGS, THE PRODUCT AND ITS INTENDED APPLICATION SHALL BE SUBMITTED FOR APPROVAL.
2. EXPANSION BOLTS SHALL BE ONE OF THE FOLLOWING (NO SUBSTITUTIONS):
STRONG-BOLT 2, SIMPSON STRONG-TIE CO., PLEASANTON, CAPOWER-STUD+SD1, POWERS FASTENERS, BREWSTER, NYKWIK BOLT TZ, HILTI FASTENING SYSTEMS, TULSA, OK
3. ONLY ONE LENGTH OF BOLT SHALL BE PRESENT ON THE JOBSITE FOR EACH BOLT DIAMETER, UNLESSOTHERWISE SPECIFIED ON THE DRAWINGS.
4. EXPANSION BOLTS, OF THE DIAMETER AND EMBEDMENT SHOWN ON THE DRAWINGS, SHALL BE INSTALLED BYPERSONNEL TRAINED TO INSTALL EXPANSION BOLTS AND SHALL BE INSTALLED IN ACCORDANCE WITH THECONTRACT DOCUMENTS AND THE MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS (MPII). WHEREPROVISIONS OF THE ABOVE REFERENCED DOCUMENTS ARE IN CONFLICT, THE MOST STRINGENT REQUIREMENTSHALL GOVERN.
5. ALL POST-INSTALLED ANCHORS SHALL BE INSPECTED BY A SPECIAL INSPECTOR IN ACCORDANCE WITH THEBUILDING CODE. INSTALLATION OF EXPANSION BOLTS SHALL BE CONTINUOUSLY INSPECTED BY THE TESTINGLABORATORY, TO ENSURE THAT HOLES ARE OF PROPER DIAMETER AND LENGTH, THAT MINIMUM INSTALLATIONTORQUES ARE OBTAINED, AND THAT BOLTS ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’SPRINTED INSTALLATION INSTRUCTIONS (MPII).
6. BOLTS SHALL BE INSTALLED PERPENDICULAR TO THE FACE OF THE CONCRETE. THE MAXIMUM DEVIATION FROMPERPENDICULAR SHALL BE 6 DEGREES. ALL BOLTS INSTALLED OUTSIDE OF THE SPECIFIED TOLERANCE SHALLBE CONSIDERED UNACCEPTABLE.
7. THE CONTRACTOR SHALL CREATE A TEMPLATE FOR EACH BOLT GROUP PRIOR TO FABRICATING HOLES INCONNECTION PLATES. TEMPLATES SHALL BE MADE AFTER LOCATING EXISTING REINFORCING STEEL WITHFERROSCAN OR SIMILAR NON-DESTRUCTIVE REINFORCING IMAGING DEVICE. POSITION BOLT HOLES SO AS NOTTO CONFLICT WITH THE EXISTING REINFORCING. BOLT POSITIONS MAY BE ADJUSTED IN THE FIELD A MAXIMUMOF 1 1/2" FROM THE DIMENSIONS SHOWN ON THE DETAILS, TO AVOID CONFLICTS WITH THE EXISTINGREINFORCING STEEL.
8. SUBMIT DRAWINGS OF TEMPLATES SHOWING HOLE LOCATIONS PRIOR TO FABRICATION OF CONNECTIONPLATES.
9. HOLES SHALL BE DRILLED IN A CONTINUOUS OPERATION AVOIDING FREQUENT REMOVAL OF THE DRILL FROMTHE HOLE. AFTER DRILLING, ALL DUST AND OTHER FOREIGN MATTER SHALL BE BLOWN OUT OF THE HOLE WITHCOMPRESSED AIR.
10. HOLES DRILLED IN THE CONCRETE SHALL BE SAME NOMINAL DIAMETER AS THE BOLT. USE THE BIT TYPE ANDSIZE RECOMMENDED BY THE BOLT MANUFACTURER. HOLES SHALL NOT BE ENLARGED OR REDIRECTEDANYWHERE ALONG THEIR LENGTH.
11. ALL ABANDONED HOLES DRILLED IN THE CONCRETE SHALL BE COMPLETELY FILLED WITH EPOXY GROUT.
12. TIGHTEN NUTS AGAINST SMOOTH WASHERS TO THE MINIMUM TORQUE RECOMMENDED BY THE MANUFACTURER.
13. HOLES IN CONNECTION PLATES SHALL BE NO MORE THAN 1/16" LARGER THAN THE BOLT DIAMETER. IF LARGERDIAMETER HOLES ARE NECESSARY FOR ERECTION PURPOSES THE CONTRACTOR SHALL PROVIDE PLATEWASHERS SUFFICIENTLY WELDED TO THE CONNECTION PLATE TO TRANSFER THE SPECIFIED LOAD.
FIELD DRILLED EXPANSION BOLTS IN CONCRETE
1. FIELD DRILLED DOWELS AND ANCHOR RODS TO BE SET IN HARDENED CONCRETE SHALL BE ONE OF THESYSTEMS LISTED HERE.
SET-XP EPOXY ANCHORING SYSTEM, SIMPSON STRONG-TIE CO., PLEASANTON, CAPE1000+ STANDARD SET ADHESIVE ANCHORING SYSTEM, POWERS FASTENERS, BREWSTER, NYHIT/HY200 ADHESIVE ANCHORING SYSTEM, HILTI FASTENING SYSTEMS, TULSA, OKHIT-RE500-SD ADHESIVE ANCHORING SYSTEM, HILTI FASTENING SYSTEMS, TULSA, OK
2. DOWELS AND THREADED RODS, OF THE SIZE, TYPE, AND EMBEDMENT SHOWN ON THE DRAWINGS, SHALL BEINSTALLED BY PERSONNEL TRAINED TO INSTALL ADHESIVE ANCHORS AND SHALL BE INSTALLED INACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII) AND AS INDICATED ONTHE DRAWINGS. A MANUFACTURER’S REPRESENTATIVE SHALL BE PRESENT DURING INITIAL INSTALLATION TOPROVIDE ONSITE TRAINING OF INSTALLERS.
3. WHERE INSTALLATION OF ADHESIVE ANCHORS IS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORTSUSTAINED TENSION LOADS, THE INSTALLING PERSONNEL SHALL BE CERTIFIED IN ACCORDANCE WITH THEACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM, OR EQUIVALENT.
4. AT CORED HOLES, WET HOLES, OR HOLES DEEPER THAN 18 INCHES, SUBSTITUTE A SLOW CURE EPOXYADHESIVE OR OTHER APPROPRIATE PRODUCT RECOMMENDED BY THE MANUFACTURER FOR THE SPECIALAPPLICATION.
5. ALL POST-INSTALLED ANCHORS SHALL BE INSPECTED BY A SPECIAL INSPECTOR IN ACCORDANCE WITH THEBUILDING CODE. INSTALLATION OF GROUTED DOWELS AND RODS SHALL BE CONTINUOUSLY INSPECTED BY THETESTING LABORATORY, TO ENSURE THAT HOLES ARE OF PROPER DIAMETER AND LENGTH, ARE PROPERLYCLEANED, AND THAT DOWELS AND RODS ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’SPRINTED INSTALLATION INSTRUCTIONS (MPII).
6. ANCHORS SHALL BE INSTALLED PERPENDICULAR TO THE FACE OF THE CONCRETE, UNLESS OTHERWISEINDICATED ON THE DRAWINGS.
7. THE CONTRACTOR SHALL CREATE A TEMPLATE FOR EACH ANCHOR ROD GROUP PRIOR TO FABRICATING HOLESIN CONNECTION PLATES. TEMPLATES SHALL BE MADE AFTER LOCATING EXISTING REINFORCING STEEL WITHFERROSCAN OR SIMILAR NON-DESTRUCTIVE REINFORCING IMAGING DEVICE. POSITION ANCHOR HOLES SO ASNOT TO CONFLICT WITH THE EXISTING REINFORCING. ANCHOR POSITIONS MAY BE ADJUSTED IN THE FIELD AMAXIMUM OF 1 1/2" FROM THE DIMENSIONS SHOWN ON THE DETAILS, TO AVOID CONFLICT WITH THE EXISTINGREINFORCING STEEL.
8. SUBMIT DRAWINGS OF TEMPLATES FOR ANCHOR ROD GROUPS SHOWING HOLE LOCATIONS PRIOR TOFABRICATION OF CONNECTION PLATES.
9. HOLES SHALL BE DRILLED WITH A HAMMER DRILL. CORED HOLES ARE NOT PERMITTED. DIAMETER OF HOLESDRILLED IN THE CONCRETE SHALL BE THE SIZE RECOMMENDED BY THE MANUFACTURER FOR THE RESPECTIVEANCHOR SIZE.
10. IMPORTANT: AFTER DRILLING, ALL DUST AND OTHER FOREIGN MATTER SHALL BE BLOWN OUT OF THE HOLEWITH COMPRESSED AIR. DO NOT FLUSH WITH WATER. CLEAN SIDES OF HOLE AS RECOMMENDED BYMANUFACTURER. HOLES MUST BE DRY.
11. ALL ABANDONED HOLES DRILLED IN THE CONCRETE SHALL BE COMPLETELY FILLED WITH NONSHRINK GROUT.
12. HOLES IN CONNECTION PLATES SHALL BE NO MORE THAN 1/16" LARGER THAN THE ANCHOR DIAMETER. IFLARGER DIAMETER HOLES ARE NECESSARY FOR ERECTION PURPOSES, THE CONTRACTOR SHALL PROVIDEPLATE WASHERS SUFFICIENTLY WELDED TO THE CONNECTION PLATE TO TRANSFER THE SPECIFIED LOAD.
FIELD DRILLED DOWELS AND ARCHOR RODS IN CONC.
1. STRUCTURAL BEAMS SUPPORTING THE ELEVATOR BEAMS ARE SHOWN FOR A SCHWDLER 3300 TRACTIONELEVATOR. IF AN ELEVATOR OF ANOTHER MODEL OR MANUFACTURER IS USED, SUPPORTING BEAMS DESIGNSHALL BE VERIFIED BY THE CONTRACTOR.
2. PROVIDE BLOCKOUT IN ELEVATOR PIT SLAB FOR HYDRAULIC CYLINDER. COORDINATE SIZE AND LOCATION WITHELEVATOR MANUFACTURER.
ELEVATOR FRAMING
1. ROOF MOUNTED MECHANICAL UNIT LOCATIONS AND DESIGN WEIGHTS ARE SHOWN ON THE ROOF FRAMINGPLANS. CONTRACTOR SHALL NOTIFY THE ENGINEER IF ACTUAL SIZES, WEIGHTS, OR LOCATIONS DIFFER FROMTHOSE SHOWN ON THE ROOF FRAMING PLANS. PROVIDE ADDITIONAL STEEL FRAMING, AS DETAILED, FORSUPPORT OF RTU CURBS AND PROVIDE DECK SUPPORT ANGLES AT ALL ROOF OPENINGS.
ROOF MOUNTED MECHANICAL UNITS
CODES & DESIGN SPECIFICATIONS1. BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE.
2. STRUCTURAL STEEL: AISC 360-10 "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS" AND AISC 341-10 "SEISMICPROVISIONS FOR STRUCTURAL STEEL BUILDINGS."
3. STRUCTURAL CONCRETE: "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-14)," THEAMERICAN CONCRETE INSTITUTE.
4. S TRUCTURAL MASONRY: "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-11)," THEAMERICAN CONCRETE INSTITUTE.
5. FM GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS 1-28, 1-29 AND 1-54.
1. PROVIDE CONCRETE HAVING THE FOLLOWING GENERAL CHARACTERISTICS:
28-DAY MAX.STRENGTH SLUMP AGG. SIZE
CLASS (PSI) (IN) TYPE (IN.) USAGEA 3000 3-5 HDRK 1 GRADE BEAMS, SLABS-ON-GRADEB 4000 3-5 HDRK 1 FORMED SLABS, BEAMS, WALLSC 3000 3-5 HDRK 3/4 SLABS ON METAL DECK, TOPPING SLABS
2. WORKABILITY ADMIXTURES MAY BE UTILIZED, PROVIDED THAT BATCH PROPORTIONS ARE DETERMINED IN THEMANNER DESCRIBED IN THE SPECIFICATIONS.
3. FLY ASH WILL NOT BE PERMITTED IN ARCHITECTURALLY EXPOSED CONCRETE. FLY ASH MAY BE USEDELSEWHERE, WITHIN THE SPECIFIED PROPORTION LIMITS, BUT THE CONTRACTOR SHALL FIRST VERIFYCOMPATIBILITY WITH CURING COMPOUNDS, SEALERS, BOND BREAKER, FLOORING ADHESIVES AND OTHERMATERIALS PROPOSED TO BE IN CONTACT WITH THE CONCRETE.
4. PROVIDE FIVE PERCENT (PLUS OR MINUS 1 1/2 PERCENT) AIR ENTRAINMENT IN CONCRETE PERMANENTLYEXPOSED TO THE WEATHER AND IN ALL LIGHTWEIGHT CONCRETE. USE OF AIR ENTRAINMENT, ANDCORRESPONDING REDUCTION OF THE WATER/CEMENT RATIO, MUST BE NOTED ON THE MIX DESIGNS. DO NOTUSE AIR IN SLABS WHICH HAVE A TROWEL FINISH.
5. USE OF ACCELERATING OR SET-RETARDING ADMIXTURES REQUIRES PRIOR APPROVAL OF THE ARCHITECT. INGENERAL, USE OF CALCIUM CHLORIDE WILL NOT BE PERMITTED.
6. CEMENT SHALL BE TYPE I OR TYPE III (ASTM C 150), EXCEPT AS FOLLOWS:
CLASS OF CEMENTCONCRETE TYPEA I/II
7. MAXIMUM WATER-CEMENT RATIO FOR CONCRETE SLABS SHALL BE 0.40. CONTRACTOR SHALL USE LOWERWATER-CEMENT RATIO IF IT IS DETERMINED THAT THIS IS NEEDED TO PLACE FLOORING AS SCHEDULED.
8. LIGHTWEIGHT CONCRETE SHALL HAVE A MAXIMUM CURED DENSITY OF 120 POUNDS PER CUBIC FOOT.
9. SLUMP LIMITS APPLY AT THE TRUCK AT THE TIME OF DISCHARGE EXCEPT THAT PUMPED CONCRETE SHALL BESAMPLED AT THE DISCHARGE END OF THE HOSE. WHEN A SUPERPLASTICIZER IS USED, THE SLUMP SHALL BEMEASURED AT THE TRUCK BEFORE INTRODUCING THE SUPERPLASTICIZER. STRENGTH TESTS SHALL BE MADEON CONCRETE AS PLACED WITH ALL ADDITIVES.
1. REINFORCING STEEL SHALL BE NEW OR RECYCLED DOMESTIC DEFORMED BILLET STEEL, CONFORMING TO ASTMA 615, GRADE 60.
REINFORCING STEEL SHOWN IN SECTIONS OF BEAMS AND WALLS IS SCHEMATIC INDICATION THAT REINFORCINGEXISTS. SEE SCHEDULES, SECTION NOTES, AND GENERAL NOTES FOR ACTUAL REINFORCING REQUIRED.
2. DETAIL REINFORCING BARS AND PROVIDE BAR SUPPORTS AND SPACERS IN ACCORDANCE WITH THE ACIDETAILING MANUAL.
3. WHERE BAR TYPES FROM THE BAR BENDING DIAGRAM ARE SPECIFIED, PROVIDE BARS ACCORDINGLY.OTHERWISE, DETAIL BARS IN BEAMS, COLUMNS, SLABS, AND WALLS AS FOLLOWS:
A. RUN TOP AND BOTTOM BARS CONTINUOUS, WITH SPLICES AND HOOKS AS DESCRIBED BELOW.B. PROVIDE STANDARD 90 DEGREE HOOK ON TOP BARS AT CANTILEVER ENDS.C. SPLICE TOP AND INTERMEDIATE BARS AT THE CENTER LINE BETWEEN MEMBER SUPPORTS, UNLESS NOTED
OTHERWISE.D. SPLICE BOTTOM BARS DIRECTLY OVER MEMBER SUPPORTS, UNLESS NOTED OTHERWISE.E. SPLICE VERTICAL BARS IN WALLS ONLY AT FLOOR LINES, UNLESS NOTED OTHERWISE. HORIZONTAL BARS
SHALL BE SPLICED AS SPECIFIED FOR TOP, BOTTOM, AND INTERMEDIATE BARS OF BEAMS.F. CENTER BARS NOTED AS "AT SUPT'S." OVER MEMBER SUPPORTS, AND CENTER BARS NOTED AS "BTWN.
SUPT'S." BETWEEN SUPPORTS.G. PLACE BARS NOTED AS "2ND LAYER" BELOW THE PRIMARY TOP BARS (OR ABOVE THE PRIMARY BOTTOM
BARS) AND PROVIDE #11 SPACER BARS PLACED AT INTERVALS OF 4'-0" BETWEEN THE TWO LAYERS OFBARS.
H. ALL BAR SPLICES IN BEAMS, SLABS, AND WALLS SHALL BE 40 BAR DIAMETERS, EXCEPT THAT SPLICES INHORIZONTAL WALL BARS AND INTERMEDIATE BEAM BARS SHALL BE 75 BAR DIAMETERS.
I. PROVIDE CORNER BARS FOR EACH HORIZONTAL BAR AT THE INSIDE AND OUTSIDE FACES OF INTERSECTINGBEAMS OR WALLS.
4. BARS SHOWN IN THE SCHEDULE TO HOOK AT DISCONTINUOUS ENDS SHALL HAVE THE HOOK PLACEDHORIZONTALLY AT EXTERIOR CORNERS.
5. PROVIDE NO. 3 DOWELS X 2'-0" AT 1'-6" ON CENTER, WITH A 90 DEGREE HOOK AT ALL EDGES OF CONCRETESLABS, UNLESS DETAILED OTHERWISE.
6. PROVIDE FOUNDATION DOWELS TO MATCH MASONRY WALL REINFORCEMENT. DOWELS SHALL EXTEND AMINIMUM OF 60 BAR DIAMETERS ABOVE AND 30 BAR DIAMETERS BELOW TOP OF FOUNDATION.
7. CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS FOLLOWS, MEASURED TO NEAREST BAR, STIRRUP ORTIE:
A. AT SLABS-ON-GRADE, BEAM AND WALL SURFACES DEPOSITED AGAINST THE GROUND (WITH OR WITHOUTVAPOR RETARDER): 3".
B. AT FORMED FACES OF BEAMS AND WALLS EXPOSED TO RAIN OR IN CONTACT WITH THE GROUND: 2".C. AT FORMED FACES OF BEAMS NOT EXPOSED TO RAIN OR SOIL: 1 1/2”.D. AT FORMED FACES OF COLUMNS NOT EXPOSED TO RAIN OR SOIL: 1 3/4".E. AT INTERIOR AND PROTECTED EXTERIOR FACES OF WALLS: 1".F. FORMED SURFACES OF SLABS:
INTERIOR EXPOSURE: 1"#5 BAR AND SMALLER, EXPOSED TO WEATHER: 1 1/2"#6 BAR AND LARGER, EXPOSED TO WEATHER: 2"
G. TOP STEEL IN SLABS:INTERIOR EXPOSURE: 1"EXPOSED TO WEATHER: 2"
H. TOP STEEL IN BEAMS:INTERIOR EXPOSURE: 1 1/2"EXPOSED TO WEATHER: 2"
8. MAINTAIN THE SPECIFIED COVER DIMENSION WITHIN A TOLERANCE OF PLUS OR MINUS 3/8" EXCEPT FOR SLABS-ON-GRADE AND SOIL-FORMED MEMBERS, WHERE 5/8" TOLERANCE IS PERMITTED. EXTRA COVER WEAKENS THEMEMBER AND REDUCED COVER LEADS TO CORROSION.
9. REFER TO TYPICAL STEEL CONNECTION DETAIL SHEET (S4.01) FOR ADDITIONAL REINFORCING REQUIRED ATSTEEL BEAM CONNECTION EMBED PLATES.
10. PROVIDE 2 TONS OF ADDITIONAL REINFORCING STEEL (#3 BARS AND LARGER) TO BE USED IN THE FIELD ASDIRECTED BY THE ARCHITECT/ENGINEER. LABOR FOR DETAILING, CUTTING, BENDING, AND PLACEMENT SHALL BEINCLUDED. ANY UNUSED PORTION OF THIS QUANTITY SHALL BE CREDITED TO THE OWNER AT THE RATE OF$2,000 PER TON FOR A TOTAL OF $4,000.00
CONCRETE REINFORCEMENT
1. TOPPING SLABS SHALL BE MINIMUM 2" THICK, REINFORCED WITH 4X4-W4.0XW4.0 WELDED WIRE MESH.
2. LAP REINFORCING MESH 1'-0" AT SPLICES. MESH SHALL BE FURNISHED IN FLAT SHEETS AND SUPPORTED ONCONTINUOUS BAR CHAIRS TO MAINTAIN PROPER COVERAGE OF 1" BELOW THE TOP SURFACE. CUT ALTERNATEWIRES DIRECTLY BENEATH CONTROL JOINTS.
3. PROVIDE #3 X 4’-0" DIAGONAL MIDDLE OF TOPPING AT ALL RE-ENTRANT CORNERS.
4. CONTRACTOR SHALL LIMIT POURS TO 10,000 SQUARE FEET, WITH 3-DAY LAPSE BETWEEN POURS. SUBMITTOPPING POUR SEQUENCE FOR REVIEW.
COMPOSITE TOPPING SLABS
5. ALL MOMENT CONNECTIONS SHALL BE FULL WELDED CONNECTIONS DESIGNED TO DEVELOP THE FULL CROSS-SECTION OF THE MEMBER. STIFFENER PLATES, WHERE SHOWN, ARE MANDATORY AND MAY NOT BE OMITTED.MOMENT CONNECTIONS ARE INDICATED ON THE PLANS BY A TRIANGULAR BULB ON THE END OF THE BEAM, ORBY THE LETTERS "MC".
6. CANTILEVER BEAMS MOMENT CONNECTED TO THE FRAME SHALL BE THE SAME SIZE AS THE BACK-UP SPAN IFNO SIZE IS GIVEN.
7. ALL BOLTS SHALL BE TIGHTENED TO A "SNUG TIGHT" CONDITION.
8. BACK TO BACK CHANNELS OR DOUBLE ANGLES ACTING AS COMPRESSION MEMBERS SHALL BE CONNECTED TOEACH OTHER AT THIRD POINTS ALONG THE LENGTH BY WELDING IN SPACER PLATES OF EQUAL THICKNESS TOTHE GUSSET PLATES. UNEQUAL LEG ANGLES SHALL BE ORIENTED LONG LEG DOWN UNLESS NOTEDOTHERWISE.
9. TEMPORARY CONSTRUCTION BRACING OF STRUCTURAL STEEL FRAME SHALL REMAIN IN PLACE UNTIL AFTERALL PERMANENT BRACING COMPONENTS HAVE BEEN COMPLETED. THE LATERAL-LOAD-RESISTING SYSTEM OFTHE BUILDING INCLUDES MOMENT-CONNECTED RIGID FRAMES, DESIGNATED WIND BRACES, CONCRETE SHEARWALLS, REINFORCED MASONRY SHEAR WALLS, AND CONNECTING DIAPHRAGM ELEMENTS. THE METAL ROOFDECK AND COMPLETED CONCRETE FILL ON METAL FLOOR DECK ARE ESSENTIAL DIAPHRAGM COMPONENTS OFTHE PERMANENT BRACING SYSTEM.
10. WIND BRACES IN THE VERTICAL PLANE ARE DENOTED BY "WB" ON THE PLAN. SEE WIND BRACE DETAILS FORCONFIGURATIONS.
11. CONNECT MISCELLANEOUS STEEL MEMBERS USING FILLET WELDS SUFFICIENT TO DEVELOP THE TENSILESTRENGTH OF THE SMALLER MEMBER AT THE JOINT UNLESS SHOWN OTHERWISE.
12. ALL STEEL SHALL BE FURNISHED WITH SHOP COAT OF RUST INHIBITIVE PRIMER.
13. WHERE ANGLES ARE NOTED TO BE CONTINUOUS, PROVIDE FULL BUTT WELD AT SPLICES.
14. PROVIDE 3 TONS OF ADDITIONAL STRUCTURAL STEEL TO BE USED IN THE FIELD AS DIRECTED BY THEARCHITECT/ENGINEER. LABOR FOR DETAILING, FABRICATION, AND ERECTION SHALL BE INCLUDED. ANY UNUSEDPORTION OF THIS QUANTITY SHALL BE CREDITED TO THE OWNER AT THE RATE OF $3,200 PER TON FOR A TOTALOF $9,600.00
STRUCTURAL STEEL (CONT.)
METAL ROOF DECK (TYPICAL U.N.O.)
1. FIELD DRILLED DOWELS AND ANCHOR RODS TO BE SET IN HARDENED CONCRETE SHALL BE ONE OF THESYSTEMS LISTED HERE.
SET-XP EPOXY ANCHORING SYSTEM, SIMPSON STRONG-TIE CO., PLEASANTON, CAPE1000+ STANDARD SET ADHESIVE ANCHORING SYSTEM, POWERS FASTENERS, BREWSTER, NYHIT/HY200 ADHESIVE ANCHORING SYSTEM, HILTI FASTENING SYSTEMS, TULSA, OKHIT-RE500-SD ADHESIVE ANCHORING SYSTEM, HILTI FASTENING SYSTEMS, TULSA, OK
2. DOWELS AND THREADED RODS, OF THE SIZE, TYPE, AND EMBEDMENT SHOWN ON THE DRAWINGS, SHALL BEINSTALLED BY PERSONNEL TRAINED TO INSTALL ADHESIVE ANCHORS AND SHALL BE INSTALLED INACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII) AND AS INDICATED ONTHE DRAWINGS. A MANUFACTURER’S REPRESENTATIVE SHALL BE PRESENT DURING INITIAL INSTALLATION TOPROVIDE ONSITE TRAINING OF INSTALLERS.
3. WHERE INSTALLATION OF ADHESIVE ANCHORS IS HORIZONTALLY OR UPWARDLY INCLINED TO SUPPORTSUSTAINED TENSION LOADS, THE INSTALLING PERSONNEL SHALL BE CERTIFIED IN ACCORDANCE WITH THEACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM, OR EQUIVALENT.
4. AT CORED HOLES, WET HOLES, OR HOLES DEEPER THAN 18 INCHES, SUBSTITUTE A SLOW CURE EPOXYADHESIVE OR OTHER APPROPRIATE PRODUCT RECOMMENDED BY THE MANUFACTURER FOR THE SPECIALAPPLICATION.
5. ALL POST-INSTALLED ANCHORS SHALL BE INSPECTED BY A SPECIAL INSPECTOR IN ACCORDANCE WITH THEBUILDING CODE. INSTALLATION OF GROUTED DOWELS AND RODS SHALL BE CONTINUOUSLY INSPECTED BY THETESTING LABORATORY, TO ENSURE THAT HOLES ARE OF PROPER DIAMETER AND LENGTH, ARE PROPERLYCLEANED, AND THAT DOWELS AND RODS ARE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’SPRINTED INSTALLATION INSTRUCTIONS (MPII).
6. ANCHORS SHALL BE INSTALLED PERPENDICULAR TO THE FACE OF THE CONCRETE, UNLESS OTHERWISEINDICATED ON THE DRAWINGS.
7. THE CONTRACTOR SHALL CREATE A TEMPLATE FOR EACH ANCHOR ROD GROUP PRIOR TO FABRICATING HOLESIN CONNECTION PLATES. TEMPLATES SHALL BE MADE AFTER LOCATING EXISTING REINFORCING STEEL WITHFERROSCAN OR SIMILAR NON-DESTRUCTIVE REINFORCING IMAGING DEVICE. POSITION ANCHOR HOLES SO ASNOT TO CONFLICT WITH THE EXISTING REINFORCING. ANCHOR POSITIONS MAY BE ADJUSTED IN THE FIELD AMAXIMUM OF 1 1/2" FROM THE DIMENSIONS SHOWN ON THE DETAILS, TO AVOID CONFLICT WITH THE EXISTINGREINFORCING STEEL.
8. SUBMIT DRAWINGS OF TEMPLATES FOR ANCHOR ROD GROUPS SHOWING HOLE LOCATIONS PRIOR TOFABRICATION OF CONNECTION PLATES.
9. HOLES SHALL BE DRILLED WITH A HAMMER DRILL. CORED HOLES ARE NOT PERMITTED. DIAMETER OF HOLESDRILLED IN THE CONCRETE SHALL BE THE SIZE RECOMMENDED BY THE MANUFACTURER FOR THE RESPECTIVEANCHOR SIZE.
FIELD DRILLED DOWELS AND ARCHOR RODS IN CONC.
FIELD DRILLED DOWELS AND ARCHOR RODS IN CONC.(CONT.)
1. ROOF DECK SHALL BE 3" DEEP, 20 GAUGE, DEEP RIB, GALVANIZED METAL DECK, WITH 8" RIB SPACING, MEETINGTHE REQUIREMENTS OF THE STEEL DECK INSTITUTE.
2. ROOF DECK SHALL BE CONTINUOUS OVER THREE OR MORE SPANS.
3. TYPICAL DECK CONNECTIONS SHALL BE AS FOLLOWS:
IN PERIMETER ZONE, WITHIN 22 FEET OF BUILDING PERIMETER, PUDDLE WELDS AT 8" ON CENTER ALONG EACHSUPPORT. AT SIDE LAPS, SCREWS EQUALLY SPACED BETWEEN SUPPORTS, NOT TO EXCEED 9" ON CENTER.
IN CORNER ZONE, WHERE PERIMETER ZONES OVERLAP AT BUILDING CORNERS, TWO 3/4" PUDDLE WELDS INEVERY RIB AT SUPPORTS FOR 1-75 AND 1-90 RATINGS. AT SIDE LAPS, SCREWS EQUALLY SPACED BETWEENSUPPORTS, NOT TO EXCEED 9" ON CENTER.
IN INTERIOR ZONE, PUDDLE WELDS AT 8" ON CENTER ALONG EACH SUPPORT. AT SIDE LAPS, SCREWS EQUALLYSPACED BETWEEN SUPPORTS, NOT TO EXCEED 12" ON CENTER.
4. SCREWS SHALL BE "TEKS" #12-14X3/4" HWH #2.
5. PUDDLE WELDS SHALL BE FULL-FUSION, 5/8" DIAMETER (MINIMUM) WELDS, MADE THROUGH WELD WASHERS.METAL AROUND WELDS SHALL BE COMPLETELY INTACT AFTER WELDING.
6. THE METAL ROOF DECK ON THIS PROJECT IS REQUIRED TO PERFORM AS A STRUCTURAL DIAPHRAGM, WITHSHEAR LOADS OF 427 POUNDS PER FOOT AT PERIMETER ZONES, AND 347 POUNDS PER FOOT AT INTERIORZONES. ALL WELDS AND SCREWS ARE CRITICAL TO THE SUCCESSFUL PERFORMANCE OF THE DIAPHRAGM.
7. SUSPENDED CEILING, LIGHT FIXTURES, DUCTS OR OTHER UTILITIES SHALL NOT BE SUPPORTED BY THE STEELDECK.
10. IMPORTANT: AFTER DRILLING, ALL DUST AND OTHER FOREIGN MATTER SHALL BE BLOWN OUT OF THE HOLEWITH COMPRESSED AIR. DO NOT FLUSH WITH WATER. CLEAN SIDES OF HOLE AS RECOMMENDED BYMANUFACTURER. HOLES MUST BE DRY.
11. ALL ABANDONED HOLES DRILLED IN THE CONCRETE SHALL BE COMPLETELY FILLED WITH NONSHRINK GROUT.
12. HOLES IN CONNECTION PLATES SHALL BE NO MORE THAN 1/16" LARGER THAN THE ANCHOR DIAMETER. IFLARGER DIAMETER HOLES ARE NECESSARY FOR ERECTION PURPOSES, THE CONTRACTOR SHALL PROVIDEPLATE WASHERS SUFFICIENTLY WELDED TO THE CONNECTION PLATE TO TRANSFER THE SPECIFIED LOAD.
1. COORDINATION OF THE ROOF STRUCTURE AND THE ARCHITECTURAL SECTIONS AND ELEVATIONS IS CRITICAL TOPROPER STRUCTURAL STEEL FABRICATION. ELEVATIONS OF TOP OF STRUCTURAL STEEL ARE SHOWN ON THEARCHITECTURAL PLANS AND SECTIONS. REFER TO THESE SECTIONS AND DETAILS TO SET THE STEELELEVATIONS AND TO UNDERSTAND THE ARCHITECTURAL INTENT.
2. TOLERANCE REQUIREMENTS - STRUCTURAL DRAWINGS INDICATE MISCELLANEOUS STEEL ELEMENTS SUCH ASSHELF ANGLES, LINTELS, SUPPORT MEMBERS FOR CURTAIN WALLS OR MASONRY, AND EDGE ANGLES FOROPENINGS AND PERIMETER CONDITIONS WHICH ARE INTENDED TO SUPPORT OR BE COORDINATED WITHMATERIALS FURNISHED BY OTHER TRADES. IT IS THE INTENT OF THESE DRAWINGS THAT THESE ELEMENTS BEFIELD ATTACHED BY FIELD WELDING OR BOLTING TO MEET THE TOLERANCES REQUIRED BY OTHER TRADES,WHICH MAY BE MORE STRINGENT THAN A.I.S.C. TOLERANCES FOR STRUCTURAL STEEL. CONTRACTOR SHALLCOORDINATE TRADES AND FIELD INSTALL MISCELLANEOUS STEEL ELEMENTS AND THE STRUCTURAL STEELFRAME TO COMPLY WITH THE TOLERANCE CRITERIA FOR PROPER INSTALLATION OF MATERIALS BY OTHERTRADES.
3. STRUCTURAL STEEL MATERIAL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS:
WIDE FLANGE (W) SHAPES AND TEES A 992 (50 KSI YIELD)OTHER ROLLED SHAPES, PLATES AND RODS A 36 (36 KSI YIELD)HOLLOW STRUCTURAL SHAPES (HSS OR TS) A 500, GRADE C (42 KSI YIELD ROUND/46 KSI YIELD SQUARE)PIPE A 53, GRADE B (35 KSI YIELD)BOLTS FOR CONNECTIONS A 325NANCHOR BOLTS (ANCHOR RODS) F 1554 (36 KSI YIELD)
4. PREDESIGNED BEAM CONNECTION DETAILS ARE SHOWN ON SHEET S4.01. OTHER TYPICAL CONNECTIONS ARESHOWN IN TYPICAL DETAILS. CONNECTIONS WHICH ARE NOT SPECIFICALLY DETAILED SHALL BE DESIGNED BYTHE FABRICATOR IN ACCORDANCE WITH THE CONNECTION NOTES AND SPECIFICATIONS.
STRUCTURAL STEEL
1. PROVIDE SHOP DRAWINGS SHOWING PLUMBING LINE LOCATIONS, PIPE SIZES AND INVERT ELEVATIONS OF PIPES.LAYOUT TO MINIMIZE TRENCHING AS MUCH AS POSSIBLE.
2. LAYOUT PLUMBING LINE AND FLOOR DRAIN LOCATIONS ON EXISTING SLABS.
3. ENGAGE A TESTING LABORATORY TO USE X-RAY OR OTHER SENSING DEVICES TO LOCATE AND CLEARLYMARK LINES OF TOP LEVEL REINFORCING ON THE SLAB AT THOSE LOCATIONS. IF POSSIBLE ALSO LOCATEBOTTOM LEVEL REINFORCING WITH A DIFFERENT COLOR MARKER.
4. ADJUST TRENCHES TO LOCATE BETWEEN PARALLEL LINES OF REINFORCING CUTTING OUT ONLY ONELONGITUDINAL BAR IF POSSIBLE.
5. NOTIFY STRUCTURAL ENGINEER FOR REVIEW PRIOR TO CUTTING AND TRENCHING.
6. SAWCUT SLABS EACH SIDE OF TRENCH PER DETAIL A AND CHIP-OUT EXISTING CONCRETE. DEPTH OF TRENCHSHALL INCORPORATE HEIGHT OF ADDITIONAL TOPPING.
7. AFTER INSTALLATION OF PIPES, DRILL AND GROUT NEW DOWELS PER DETAIL A.
8. PIPES LOCATED BELOW THE SLAB ARE TO BE BACKFILLED WITH SPECIFIED PIPE BEDDING MATERIAL AND HANDCOMPACTED TO BOTTOM OF EXISTING SLAB.
9. DRILL AND GROUT DOWELS INTO SIDES OF TRENCH PER DETAIL A.
10. INSTALL SYNKO-FLEX WATERSTOP ALONG BOTTOM EDGES OF TRENCH.
11. FILL TRENCH AND VIBRATE WITH CLASS ‘B’ CONCRETE.
PLUMBING TRENCHES IN EXISTING SLABS
1. LAYOUT PLUMBING LINE LOCATION FOR CORING ON FACE OF EXISTING BEAM OR WALL.
2. ENGAGE A TESTING LABORATORY TO USE X-RAY OR OTHER SENSING DEVICES TO LOCATE AND CLEARY MARKLINES OF TOP LEVEL HORIZONTAL AND VERTICAL REINFORCING ON THE BEAM OR WALL AT THOSE LOCATIONS.
3. INSTALL SYNKO-FLEX IN CORE AROUND PIPE IF CORE IS BELOW LEVEL OF SLAB.
CORE DRILLING THRU EXIST. BEAMS OR WALLS
3" O
R 5
"
12"
OR
18"
NEW CONC. TOPPPING
AVOID CUTTING BOTTOMREINF. WHERE POSSIBLE
EXIST. CONC. SLAB
SPECIFIED BEDDINGMATERIAL
NEW PLUMBING LINE
1'-4" MAX.
EXCAVATION/CUTLINE AS REQUIRED
EXIST. REINF.
CONT. SYNKO-FLEXWATERSTOP ATBOTTOM OF SLAB
PIPE TRENCH INSTALLATION IN EXISTING SLABNO SCALE
LOCATE REINF. IN BEAM ORWALL PRIOR TO CORING
PIPE, SEE PLUMBING
CORE THRU WALL
EXISTING SLAB
NEW CONCRETE TOPPING
EXIST. BEAM OR WALL
EXISTING SLAB
SYNKO-FLEX WATERSTOP ATPERIMETER IF UNDER SLAB
PIPE CORE THRU BEAM OR WALLNO SCALE
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
0 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S1.02
GENERAL NOTES
15134
1 1/2" = 1'-0" A
1 1/2" = 1'-0" B
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
Fa Fa
F F
E E
D D
C C
B B
3
3
4
4
5
5
6
6
3a
EXIST. SUMPTO REMAIN ATEL. 91'-6" +/-
EXIST. ELEVATORPIT AT EL. 94'-6" +/-.FILL W/ SAND &COVER W/ SLAB
EXIST. BSMT. WALL
9'-0
" +/
-20
'-0"
+/-
23'-0
" +/
-20
'-0"
+/-
13'-0
" +/
-
6'-9" +/- 13'-3" +/- 20'-0" +/- 20'-0" +/-
EXIST. TURBINE FOUNDATIONCOLUMNS TO REMAIN
2/S3.01
1
S3.01
T.O.S.C. EL.= 99'-8 1/2"
T.O.S.C. EL.= 99'-2" AT SUMP
T.O.S.C. EL.= 99'-11 1/2"
T.O.S.C. EL.= 99'-10 1/2"
8'-6"
7'-8
"
DIAGONAL BARS AT ALLREENTRANT CORNERSPER 11/S3.01, TYP.
5
S3.01
REMOVE (3) 6"X6"STEEL ELEVATORCOLUMNS
8"X8" BUILDINGCOLUMN TO REMAIN
@ SUMP PIT INSLAB ABOVE
TYP.
SEE 13/S3.01 FORPIT SLAB ABOVE
NEW 8" CMU
FACE OF EXIST.CMU WALL
EXIST. TUNNEL
T.O.S.C. EL.= 99'-3 1/2"
T.O.S.C. EL.= 99'-3 1/2"
T.O.S.C. EL.= 99'-2"
20
S3.01
PLAN NORTHTRUE NORTH
NEW HARD ROCK CONCRETE TOPPING. MINIMUM 2"THICK AND SLOPES 1/8" / FT. TO EXISTING SUMP.SEE TOPPING NOTES ON S1.02 FOR REINFORCING.
LEGEND
PLAN NOTES:1. ALL GRID DIMENSIONS ARE BASED ON EXISTING DRAWINGS, AND
MUST BE FIELD VERIFIED.
2. THE EXISTING FLOOR AT EL. = 99'-0" (+/-) SLOPES 2" TO VARIOUSFLOOR DRAINS AT EL. 98'-10" (+/-)
3. REMOVE ALL UN-NEEDED PROJECTING ANCHOR BOLTS PRIOR TOPLACING TOPPING.
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
1 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S2.01
BASEMENT FOUNDATIONPLAN
15134
3/16" = 1'-0"
1 BASEMENT FOUNDATION PLAN
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
Fa Fa
F F
E E
D D
C C
B B
A A
1
1
2
2
3
3
4
4
5
5
6
6
3a
Aa
24'-0" +/- 20'-0" +/- 20'-0" +/- 20'-0" +/- 20'-0" +/-
12'-3
" +/
-11
'-9"
+/-
9'-0
" +/
-20
'-0"
+/-
23'-0
" +/
-20
'-0"
+/-
13'-0
" +/
-
24'-0" +/- 20'-0" +/- 6'-9" +/- 13'-3" +/- 20'-0" +/- 20'-0" +/-
24'-0
" +/
-9'
-0"
+/-
20'-0
" +/
-23
'-0"
+/-
20'-0
" +/
-13
'-0"
+/-
(EX
.) W
18X
45
(EX
.) W
16X
40
(EX.) W18X55
(EX
.) W
18X
45
(EX.) W16X36 CONT. (F.V.)
(EX.) W8X17
(EX.) W8X17
(EX
.) W
14X
30
(EX
.) W
14X
30
(EX.) C6X8.2
(EX.) W12X27
(EX.) C18x42.7
(EX.) W24X68 (EX.) W24X68
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX.) W24X68 (EX.) W27X84
(EX
.) W
16X
40
(EX
.) W
18X
45
(EX
.) W
16X
40
(EX
.) W
16X
40
(EX
.) W
18X
45
(EX
.) W
16X
40
(EX.) W27X84
(EX
.) W
12X
53 +
18C
42.
5
(EX
.) W
27X
84
(EX
.) W
24X
76
(EX
.) W
24X
68
(EX.) C6X8.2
(EX.) C6X8.2
(EX.) C10X15.3
(EX.) C10X15.3
(EX.) C6X8.2
(EX.) C10X15.3
(EX.) C10X15.3
(EX
.) W
21X
55
(EX.) W12X27
(EX.) W12X27
(EX.) W12X27
(EX.) W14X30
(EX.) W12X27
(EX.) W16X36
(EX
.) W
12X
27
(EX
.) C
8X11.
5
(EX
.) C
6X
8.2
(EX
.) W
8X17
(EX
.) C
6X
8.2
(EX.) C8X11.5
(EX
.) C
6X
8.2
(EX.) W12X27
(EX
.) W
12X
27
(EX.) W8X17
(EX.) W24X68
(EX
.) W
12X
53
(EX
.) W
16X
36
(EX
.) W
18X
50
(EX
.) W
18X
45
(EX.) W8X17
(EX
.) W
10X
21
(EX
.) W
10X
21
(EX.) W10X21
(EX
.) W
8X17
(EX.) W8X17
(EX.) W8X17
(EX.) C6X8.2 (EX.) C6X8.2
(EX
.) W
10X
21
(EX.) W12X27
(EX
.) C
6X
8.2
(EX
.) C
8X11.
5
(EX.) W12X27
(EX
.) C
6X
8.2
(EX
.) C
8X11.
5
(EX
.) C
10X
15.
3
W12X26 (18)
OPEN
T.O.S.C. EL. = 111'-3"
FORM AND FILL-IN ALLEXIST. SLAB OPENINGSWITH CONCRETE
EXIST.CHASE
NEW ELEVATOROPENING
W12X19 (18)
(EX.) W12X27
1
S4.02
TYP.
SEE S4.01 FOR TYPICALBEAM CONNECTIONS
11
S4.02
TYP.
W8X15
NEW STAIR
7
S3.01
TYP.
6
S3.0110
S3.01
RELOCATEEXIST. W10X21AND DEMOLISHEXIST. W8X17
11
S4.03
12
S4.0311
S4.03
TYP.
13
S4.03
14
S4.03
6
S3.01
8
S3.01
9
S3.01
10
S3.01
9
S3.01
12k12k
8k 8k
13k 13k
TYP.
4/S4.01
DIAGONAL BARS AT REENTRANTCORNERS PER 11/S3.01, TYP.
5"
NE
W W
B-4
11/S
4.0
4
NEW WB-29/S4.04
ADD 1/4" FILLET WELDALL-AROUND TO ALLEXISTING BEAM TO COL.CONNECTIONS ALONGGRIDLINE 6, TYP.
REMOVE (3) 6"X6"STEEL ELEVATORCOLUMNS
3
S4.02
3
S4.02
5/S4.03
11/S3.01
TYP.
14
S3.01
TYP.
8'-6"
7'-8
"
17
S3.01
16
S3.01
18
S3.01
15
S3.01
12
S3.01
12
S3.01
12
S3.01
12
S3.01SLO
PE
SLOPE
1'-6
"8'
-1"
HSS5X5X1/4
7A
S3.01
7A
S3.01
1'-3
1/2
"5'
-0"
7'-0" 5'-1 1/2" 9'-10 1/2"
19
S3.01
TYP.
7A
S3.01
SLO
PE
SIM.
A
S1.02
TYP.B/S1.02
TYP.
PLAN NORTHTRUE NORTH
3" +/- CONCRETE TOPPINGOVER EXIST. CONC. SLAB
LEGEND
2 1/2" CONC. OVER 2", 20GAUGE, TYPE VLI, GALV. DECK(4 1/2" TOTAL) AFTERREMOVAL OF 1 1/2" GRATING
5" +/- CONC. TOPPING OVEREXIST. CONC. SLAB AFTERREMOVAL OF QUARRY TILE &GROUT BED
PLAN NOTES:1. ALL GRID DIMENSIONS ARE BASED ON EXISTING DRAWINGS, AND
MUST BE FIELD VERIFIED.
2. EXISTING SLAB ELEVATIONS AS NOTED ARE BASED ON ORIGINALDRAWINGS AND MAY VARY.
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
2 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S2.02
FIRST FLOOR FRAMINGPLAN
15134
3/16" = 1'-0"
1 FIRST FLOOR FRAMING PLAN (FFE 111'-3")
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
Fa Fa
F F
E E
D D
C C
B B
A A
1
1
2
2
3
3
4
4
5
5
6
6
3a
Aa
(EX
.) W
10X
21
(EX.) C8X11.5
(EX.) C8X11.5
(EX
.) W
10X
21
(EX
.) W
8X24
(EX.) W18X45(EX.) W18X50
(EX
.) W
16X
40
(EX.) W21X55
(EX
.) W
16X
40
(EX.) W14X43 (EX.) W18X45 (EX.) W18X50
(EX
.) W
16X
40
(EX
.) W
16X
36
(EX
.) W
16X
36
(EX
.) W
16X
40
(EX
.) W
16X
40
(EX.) W27X84
(EX
.) W
21X
55
(EX
.) W
16X
40
(EX.) W21X68 (EX.) W21X68
(EX
.) W
16X
40
(EX
.) W
16X
40
(EX
.) W
16X
40
(EX
.) W
16X
40
(EX.) W8X24 (EX.) W16X40 (EX.) W16X40
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX
.) W
12X
27
(EX.) C12X20.7
(EX
.) C
12X
20.
7
(EX
.) C
10X
15.
3
(EX.) C10X15.3
(EX.) W6X15.5
(EX.) W8X17
(EX
.) W
24X
68(E
X.)
W21X
55(E
X.)
W12X
27
(EX.) W24X100
(EX.) W24X68
(EX.) W16X36
(EX.) W18X50
(EX.) W24X68
(EX
.) W
24X
76
(EX
.) W
27X
102
(EX
.) W
27X
94
(EX.) W24X68 (EX.) W21X55 (EX.) W16X36
(EX
.) W
16X
36
(EX
.) W
18X
50
(EX
.) W
16X
36
(EX.) W18X45 (EX.) W21X55
(EX
.) W
14X
30
(EX
.) W
14X
30
(EX.) W21X55 (EX.) W14X43
(EX
.) W
16X
36
(EX.) W12X27(EX
.) W
12X
27(E
X.)
W8X
17
(EX
.) W
8X17
(EX
.) W
8X17
(EX
.) W
18X
50
(EX
.) W
18X
50
(EX.) W16X36
(EX
.) W
16X
36
(EX
.) W
10X
21
(EX
.) W
10X
21
(EX.) W21X55
(EX.) W18X45
(EX
.) W
18X
45(EX
.) W
10X
21
(EX.) W8X17
(EX.) W16X36
(EX.) W18X45
(EX.) W18X45
(EX.) W16X40
(EX
.) W
21X
62
(EX
.) W
21X
62
(EX
.) W
16X
36
(EX
.) W
18X
50
(EX
.) W
16X
50
(EX.) W16X36(EX.) W16X36
(EX.) W6X15.5
(EX.) W6X15.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) W
8X17
(EX
.) W
8X17
(EX.) C8X11.5
(EX.) W18X45
(EX.) C4X7.2
(EX.) C8X11.5
(EX.) W8X17
(EX.) W8X17
(EX
.) C
8X11.
5
(EX
.) C
10X
15.
3
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5 (EX
.) C
8X11.
5
(EX
.) C
10X
15.
3
(EX.) W18X45
(EX
.) W
24X
68
(EX.) W16X36
(EX
.) W
27X
94
(EX.) W16X36
(EX.) W16X36
(EX.) W16X36
(EX.) W12X27 (EX.) W12X27
(EX
.) W
27X
84
(EX
.) W
24X
68
(EX.) W12X27 (EX.) W12X27
(EX.) W12X27 (EX.) W12X27
(EX.) W12X27 (EX.) W12X27
(EX.) W16X36
(EX.) W12X27
(EX
.) W
10X
21
(EX.) C8X11.5
(EX
.) C
8X11.
5
(EX
.) C
6X
8.2
(EX
.) C
8X11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5
(EX
.) C
6X
8.2
(EX.) C6X8.2
(EX
.) C
8X11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5(E
X.)
C8X
11.
5
(EX
.) C
8X11.
5(E
X.)
C6X
8.2
(EX
.) C
6X
8.2
(EX
.) W
14X
30
24'-0" 20'-0" 20'-0" 20'-0" 20'-0"
12'-3
"11
'-9"
9'-0
"20
'-0"
23'-0
"20
'-0"
13'-0
"10
1/2
"
24'-0" 20'-0" 6'-9" 13'-3" 20'-0" 20'-0"10 1/2"
24'-0
"9'
-0"
20'-0
"23
'-0"
20'-0
"13
'-0"
W16
X26
(18)
W14X22 (18)
W14X22 (18)
W14X22 (18)
W14
X22
(14)
W10
X17
(10)
W12
X19
(18)
W16X31 (27)
W16X31 (27)
W10
X17
(10)
W10
X17
(10)
W14
X22
(18)
W14
X22
(18) OPEN
OPEN
T.O.S.C. EL. = 123'-0"
FORM & FILL-IN SLABOPENINGS WITHCONCRETE, TYP.
W8X15
GLASS FLOORSEE ARCH'L
REMOVE EXISTING STAIR LANDINGAND SUPPORT BEAM BELOW
3
S4.02
W8X
15W
8X15
1
S4.02
1
S4.02
TYP.
3 EQ. SPA.
(EX.) W16X36
25k25k
8k8k8k 8k
12k
17k
17k
17k
17k
12k
18k 18k
SEE SHEET S4.01 FORTYPICAL BEAM CONNECTIONS
10/S4.01
TYP.
4/S4.01
TYP.
10/S4.01
TYP.
9k9k
(EX.) C12X20.7
(EX.) C12X20.7
16k
16k
10k
16k
16k
10k
18k
18k
NE
W W
B-4
11/S
4.0
4
NEW WB-29/S4.04
NE
W W
B-3
10/S
4.0
4
9
S4.03
TYP.
10
S4.03
TYP.
1
S4.02
TYP.
2"
DIAGONAL BARS AT REENTRANTCORNERS PER 11/S3.01, TYP.
15
S4.03
TYP.
NE
W W
B-1
8/S
4.0
4
17
S4.03
FOLDING PARTITIONABOVE, SEE ARCH'L
16
S4.03
TYP.
10
S4.03
AD
D 1
/4"
FIL
LET
WE
LD A
LL-A
RO
UN
D T
OE
XIS
T B
EA
M T
O C
OL.
CO
NN
EC
TIO
N
4/S4.01
TYP.
COVER PL. BOT. FLANGEOF BEAM PER 18/S4.03
4/S4.01
TYP.
NEW ELEVATOROPENING
3
S4.02 5/S4.03
11/S3.01
TYP.
REMOVE (3) 6"X6"STEEL ELEVATORCOLUMNS
ABOVE
REMOVE EXIST. BMS.
REMOVE EXIST. BMS.
REMOVEPERIM.PLATE
REMOVE STONERUBBLE AND FILLW/ CONCRETE, TYP.
(EX
.) C
8X11.
5(E
X.)
C8X
11.
5
NOTE: FULL PENETRATION WELD C12 FLANGESTO W16 AND FILLET WELD ANGLE CONNECTION
12
S4.05
W8X
15
SLOPENEW CANOPY
1'-6
"
10
S4.05
15'-10" +/-
10'-1
" +/
-
W10
X17
(10)
20
S4.03
9
S4.05
7
S4.05
6
S4.05
TYP.
TYP.
8/S4.05
19
S4.03
TYP.
19
S3.01
TYP.
REMOVEEXIST. BEAMS
9
S4.05
10
S4.05
W10
X17
(10)
C8X
11.
5
HANGER PER 12/S4.05
10 1
/8"
6"
8k8k
W8X15
C8X11.5
W10
X17
(10)
PLAN NORTHTRUE NORTH
2 1/2" +/- CONC. TOPPING OVEREXIST. CONC. SLAB AFTERREMOVAL OF QUARRY TILE &GROUT BED
LEGEND
2 1/2" CONC. OVER 2", 20GAUGE, TYPE VLI, GALV. DECK(4 1/2" TOTAL) AFTER REMOVALOF 1 1/2" GRATING
PLAN NOTES:1. ALL GRID DIMENSIONS ARE BASED ON EXISTING DRAWINGS, AND
MUST BE FIELD VERIFIED.
2. EXISTING SLAB ELEVATIONS AS NOTED ARE BASED ON ORIGINALDRAWINGS AND MAY VARY.
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
3 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S2.03
SECOND FLOORFRAMING PLAN
15134
3/16" = 1'-0"
1 SECOND FLOOR FRAMING PLAN (FFE 123'-0")
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
Fa Fa
F F
E E
D D
C C
B B
A A
1
1
2
2
3
3
4
4
5
5
6
6
3a
W14X22 (22)
W14X22 (22)
W14X22 (22)
W14X22 (22)
W14X22 (22)
W16X26 (22)
W30
X90
(62
) c=
1 1/4
"
W12
X19
(10)
W16
X26
(22)
W18
X40
(24)
W14X22 (22)
W14X22 (22)
W14X22 (22)
W14X22 (22)
W14X22 (22)
(EX.) W12X27
(EX.) W12X27
(EX.) W16X36
(EX.) W12X27
(EX.) W10X21
(EX.) W10X21
(EX.) W10X21
(EX.) W12X40
(EX.) W10X21
(EX.) W10X21
(EX.) W10X21
(EX.) W12X40
(EX.) W10X21
(EX.) W10X21 (B.U.)
(EX.) W12X40
(EX
.) W
16X
36
(EX
.) W
16X
36
(EX
.) W
16X
36
(EX
.) W
16X
36
(EX
.) W
16X
36(E
X.)
W8X
17(E
X.)
W18X
45(E
X.)
W18X
55(E
X.)
W10X
33
(EX.) W21X62 (EX.) W21X62 (EX.) W21X55
(EX
.) W
18X
50
(EX.) W18X45(EX.) W18X45(EX.) W8X24
(EX
.) W
8X24
(EX
.) W
18X
45
(EX
.) W
18X
45
(EX
.) W
18X
50
(EX
.) W
18X
45
(EX
.) W
12X
27
(EX
.) W
12X
27(E
X.)
W8X
17
(EX
.) W
8X40
(EX
.) W
21X
62
(EX
.) W
12X
36
(EX
.) W
21X
62
(EX
.) W
12X
27
(EX
.) W
18X
45
(EX
.) W
18X
50
(EX
.) W
21X
55
(EX
.) W
18X
50
(EX.) W30X108
(EX.) W18X45
(EX.) W18X45
(EX.) W18X45
(EX.) W18X45
(EX.) W18X45
(EX.) W18X45
(EX.) W24X68 (EX.) W21X62 (EX.) W18X45 (EX.) W18X45
(EX
.) W
18X
55(E
X.)
W18X
45(E
X.)
W18X
45
(EX.) W12X27(EX.) W12X27(EX.) W12X27(EX.) W16X36
T.O.S.C. EL. = 135'-9 1/2"
NEW COMPOSITEBEAMS W/ 3/4" DIA. X 5"HEADED STUDS, TYP.
3 1/2" CONC. OVER 2"-20GAUGE, TYPE VLI, GALV.COMPOSITE FLOOR DECK(5 1/2" TOTAL), TYP.
NEW 16 GAUGE EDGEFORM AT PERIM. TYP.
12'-0
"12
'-0"
9'-0
"20
'-0"
23'-0
"20
'-0"
13'-0
"
24'-0" 20'-0" 6'-9" 13'-3" 20'-0" 20'-0"
24'-0
"9'
-0"
20'-0
"23
'-0"
20'-0
"13
'-0"
24'-0" 20'-0" 20'-0" 20'-0" 20'-0"
W27X84 (20)
11
S4.02
TYP.
W12X19 (20)
W12X19 (20)
W14X22 (16)
W14X22 (16)
W14
X22
(16
)
1
S4.02
7
S4.02
TYP.
3
S4.02
12/S4.02
TYP.
7/S4.03
TYP.
1
S4.02
TYP.
1
S4.02
TYP.
1
S4.023
S4.02
8/S4.03
TYP.
W21X44
2
S4.04
NOTE 2
TYP.
3
S4.04
TYP.
NOTE 2
3
S4.04
TYP.
NO
TE
2
NO
TE
2
2
S4.04
3
S4.02
4
S4.04
5
S4.04
W12
X19
6
S4.04
7
S4.04
W14X22
2
S4.04
TYP.
W12
X19
(EX.) W8X17 (EX.) W8X17 (EX.) W8X17 (EX.) W8X17 (EX.) W8X17 (EX.) W8X17
(EX
.) W
8X17
(EX.) W8X17
(EX.) W8X17(EX.) W8X17
(EX.) W8X17
(EX.) W8X17
(EX.) W8X17
(EX.) W8X17
(EX.) W8X17 (EX.) W8X17(EX.) W8X17(EX.) W12X27(EX.) W12X27
(EX.) W8X17(EX.) W8X17
(EX
.) W
8X17
(EX
.) C
8X11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5(E
X.)
C8X
11.
5(E
X.)
W8X
17
(EX
.) C
8X11.
5
(EX
.) C
4X
5.4
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
8X11.
5
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
8X11.
5
(EX
.) C
4X
5.4
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C4X5.4
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) C8X11.5
(EX.) W8X17
(EX.) W8X17
(EX.) C8X11.5
(EX.) C8X11.5 (EX.) C8X11.5
(EX.) C8X11.5
(EX
.) C
8X11.
5
W14
X22
(10)
8k8k
W12
X19
(8)
20k
20k
19k
16k
16k16k
16k
19k
20k
20k
W30
X11
6 (6
2) c
=1
1/4
"87
k65
k
31k 45k
W24
X76
(40
) c=
3/4"
32k
29k
W14X22
W12
X19
W12X19
9k
11k
15k
9k
10k
15k
15k
15k
15k
46k
25k
10k 10k
48k
65k
20k 20k
20k
20k
20k
20k
20k
20k
16k
16k
16k
16k
28k
28k
26k
26k
9k9kNE
W W
B-4
11/S
4.0
4
NEW WB-29/S4.04
NE
W W
B-3
10/S
4.0
4
NE
W W
B-1
8/S
4.0
4
H=
8k
H=
8k
H=10k
H=
10k
H=8k
H=
10k
H=10k
6
S4.03
SIM.
REMOVE W10X21 BEAMAND X-ROD BRACE
4"
NEW ELEVATOROPENING
5/S4.03
11/S3.01
TYP.
11/S3.01
TYP.
4/S4.01
TYP.
10/S4.01
TYP.
1,100# 1,100#
200# 200#
17
S4.03
BELOW
1,700#
TYP.
17 OR19/S-4.04
1,100#500#
600#
500#
200#
200#
1,100#
1,100#
3/S4.05
TYP.
EXIST. AWNINGFRAMING TO REMAIN
2'-0 1/2" 5'-6 3/8" 4"WB-5
5/S4.05
20/S4.05
A.5 A.5
INSTALL NEW W21IMMEDIATELYUNDER EX. W12
13
S4.05SLO
PE
1"
EXIST. STEEL X-BRACINGBELOW TO BE REMOVED
TYP.
20/S4.04
TYP.
20/S4.04
10 1/2"
PLAN NORTHTRUE NORTH
LEGEND3 1/2" CONC. OVER 2", 20 GAUGE,TYPE VLI GALV. COMPOSITE FOORDECK (5 1/2" TOTAL), TYP.
PLAN NOTES:1. ALL GRID DIMENSIONS ARE BASED ON EXISTING DRAWINGS,
AND MUST BE FIELD VERIFIED.
2. REMOVE EXISTING ROOF DECK AND REPLACE WITH 3", 20 GADECK
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
5 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S2.04
THIRD FLOOR & LOWROOF FRAMING PLAN
15134
3/16" = 1'-0"
1 THIRD FLOOR & LOW ROOF FRAMING PLAN (FFE 135'-9 1/2")
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
F F
E E
D D
C C
B B
2
2
3
3
4
4
5
5
6
6
(EX
.) W
12X
27
(EX.) W12X27 (EX
.) W
27X
84
(EX
.) W
27X
84
(EX
.) W
27X
84
(EX
.) W
27X
84
(EX.) W8X24 (EX.) W8X24 (EX.) W8X24 (EX.) W8X24
(EX.) W8X24 (EX.) W8X24
(EX.) W8X24
(EX.) W8X24
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21(EX.) W10X21
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21(EX.) W10X21
(EX
.) W
10X
21(E
X.)
W8X
17
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21 (EX.) W10X21
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21 (EX.) W10X21
(EX.) W10X21 (EX.) W10X21 (EX.) W10X21 (EX.) W10X21
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX.) W6X15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) W
6X15
.5(E
X.)
W6X
15.5
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
6X
8.2
(EX
.) C
4X
5.4
(EX.) C4X5.4
(EX.) W8X17 (EX.) W8X17 (EX.) W8X17 (EX.) W8X17
EXIST. X-RODS TO REMAIN
1
S4.04
TYP.
NO
TE
2
DE
CK
SP
AN
1
S4.04
TYP.
20'-0" 20'-0" 20'-0" 20'-0"
12'-0
"9'
-0"
20'-0
"23
'-0"
20'-0
"
20'-0" 20'-0" 20'-0" 20'-0"
9'-0
"20
'-0"
23'-0
"20
'-0"
NE
W W
B-1
8/S
4.0
4
H=10k
H=10k
H=
10k
H=
10k
*
*
*
*
*
*
*
*
*
*
*
*TYP.
1/S4.05
1,100#
1,100#
1,700#
1,100#
1,100#
TYP.
17 OR19/S4.04
3/S4.05
TYP.
W10
X12
W8X10 HOIST BM.
SIM.
5/S4.03
2
S4.05
WB-55/S4.05
A.5 A.5
3 EQ. SPA.
SLO
PE
1/4
" / 1
2"
T.O.S. EL. = 145'-4 1/4" @ GRID A.5
3" 2'-1 1/2" 20'-0" 3 3/8"
W14X22
W12
X26
W10
X19
W10
X19
W10
X19
3" METAL DECK
19/S4.05 18/S4.05
10/S4.01
HOLD 2" BELOWROOF DECK
W12X19
W10
X19
7k7k7k
7k7k 7k
7k7k
7k7k
7k 7k
7/S4.03
PLAN NORTHTRUE NORTH
PLAN NOTES:1. ALL GRID DIMENSIONS ARE BASED ON EXISTING DRAWINGS,
AND MUST BE FIELD VERIFIED.
2. REMOVE EXISTING ROOF DECK AND REPLACE WITH 3", 20 GADECK
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
6 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S2.05
HIGH ROOF FRAMINGPLAN
15134
3/16" = 1'-0"
1 HIGH ROOF FRAMING PLAN
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
TYPICAL DETAILNO SCALE
NOTE:1. SEE 13/S3.01 FOR ELEVATOR PIT SLAB.2. SEE 2/S3.01 FOR SUMP PIT INFO.3. SEE 3/S3.01 FOR ELEVATOR SILL INFO.4. SEE 4/S3.01 FOR ELEVATOR GUIDE RAIL
SUPPORT INFO.
EL. VARIESSEE PLAN
EXIST. SLABEL. = 99'-0" (+/-)
NEW CONC. TOPPING,THICKNESS VARIES
EXISTING TOPPING SLAB
EXISTING MAT FOUNDATION
8"
NEW 8" CMU
DRILL & GROUT #4X3'-6" DWLS.@ CORNERS & 24" O.C. BTWN.
ELEVATOR PIT WALL
TYPICAL DETAILELEVATOR SUMP PIT
SEE 13/S3.01SEE 13/S3.01
2'-0" X 2'-0" X 2'-0" DEEPSTAINLESS STEEL SUMPPAN. SET IN SLAB OPENINGAND MORTAR BED OF WALL.
BLOCKOUT SLAB FOR SUMP.CUT OUT DECK AFTERCONCRETE HAS SET.
NO SCALE
SHAFT OPENINGREFER TO PLAN
ELEVATOR MFR. TO DETERMINE IFSTEEL SILL ANGLE IS REQUIRED.INSTALL W/ 3/4" DIA. 0'-6"EXPANSION BOLTS @ 1'-0"
FACE OF PIT WALLOR FLOOR BEAM
ELEVATOR DOOR SILL
TYPICAL DETAIL
DIM
.3" TY
P
PROJECTION2" MAXIMUM
TYPICAL DETAIL
PL.1/2X4X1'-0"W/2-3/4" DIA. EXP.OR EPOXY BOLTS
HSS 6X4X3/16ELEVATOR GUIDE RAIL SUPPORTCOLUMN EA. SIDE OF PIT.
ELEVATOR GUIDE RAIL SUPPORT
NO SCALE
N.S
. GR
OU
T1/
2" H
.S.
5"
3"
3/16
T.O.S.C. EL. = 111'-3"
3" CONC. TOPPING
NO WALL AT 7ANEW CONCRETE TOPPING
T.O.S.C. EL.= 111'-3"
EXIST. SLAB
EXIST. BM. BEYOND
EXIST. CONC. WALL
T.O.S.C. EL.= 111'-3"
EXIST. CONC.
2" DECK WELD TOEXIST. EMBED
#4 X 5'-0" @ 12" O.C.,CENTERED ON JOINT3" CONC. TOPPING
T.O.S.C. EL. = 111'-3"T.O.S.C. EL. = 111'-3"
3" CONC. TOPPING
3/16 2-12
NEW L3X3X1/4 CONT.
#4 X 5'-0" @ 12" O.C.,CENTERED ON JOINT
3" 8"
EXIST. TOPPINGSLAB
5" +
/-
EXIST. MAT
SAND INFILL
SLAB REINF. #5@12" E.W.BOT. LAYER E-W DIRECTION
5"
DRILL & GROUT OR EPOXY#4X3'-0" DWLS. @ 12"
SAWCUT FOR LEDGE
NO SCALE
BLOCKOUTS
CORNERS
GRADE BEAM,CONSTRUCTIONJOINT OR RECESS
PROVIDE 2#4X4'-0"DIAGONAL BARS1" BELOW TOP OF SLAB
NOTE:FABRICATOR TO LOCATE THESEBARS ON THE SHOP DRAWINGS.
RE-ENTRANT CORNER REINFORCING
TYPICAL DETAIL
45.00°
1" 1"
EQ
.
1/2" EXPANSIONJOINT MATERIAL
CONCRETEWALK SEE CIVIL
THICKEN WALKAS REQUIRED
SEE CIVIL FORSUBSLAB PREPARATION
DRILL & GROUT #4 X 3'-0"@ 12" AT DOORS
SEE SECTIONSFOR CONCRETE
EXTERIOR WALK TO GRADE BEAM
TYPICAL DETAIL
SLOPE
8"
CONNECTION OF MASONRY WALL TO STEEL BEAM
SEE PLAN FOR BEAM
L6X3-1/2X5/16 X 0'-6"LLV @ EACH BOLT
3" VERTICALSLOTTED HOLE INANGLE, 1 1/2" MIN.FROM EDGE
3/4" DIA. THRU - BOLTX 0'-11" @ 4'-0"
8X8 TROUGH TILEW/ 2#4 CONT.
WALL REINFORCINGCONTINUOUS TO TOPCOURSE, SEE GENERALNOTES FOR SIZE ANDSPACING
TYPICAL DETAIL
3" M
AX
.2"
MIN
.
3/16 1 1/2TYP.
T.O.S.C. EL.VARIES
1'-0
"
SEE 16/S3.01
SEE 16/S3.018"
#3X @ 12"W/ 2#5 CONT.TOP & BOT.
2'-0"
8"
4"
10"
5" SLAB-ON-GRADE,REINF. W/ #3@12" E.W.
T.O.S.C. EL.VARIES
BE
LOW
GR
AD
E1'
-0"
MIN
.
5'-0"
CLE
AR
HO
LD 2
"
2#4 CONT. TOP & BOT.W/ #3 SITR. @ 8" O.C.
3
10"
1'-0
" M
IN.
6" 6"
EL. = 111'-3"
SEE 16/S3.01
SEE 16/S3.01
COLUMN, SEE PLAN
5/16
EMBED. PL. 1"X10"X0'-10" W/(4)3/4" DIA. X 8" H.S. GALV.
6"6"
6"
1'-0" 1'-0"
1 1/2"
EL. = 111'-3"
1"
2#4 EA.TREAD
SEE 16/S3.01
C.L. COLUMBEYOND
#4X @ 12"1'-6"
8"
T.O.S.C. EL.SEE PLAN
8"
PL. 3/8"X4" X CONT. W/1/2" DIA. X 4" H.S. @ 12"
8" CONT. TROUGH BEAM.REINF. W/ 1#4 TOP AND BOT.
2" METAL DECK
CMU FACE SHELL
#4X @ 24"3'-0"
3'-0
"
REINF.
ELEVATOR PIT SLAB
TYPICAL DETAIL
, 7A
≤ 2'-0" EXISTING SLAB
T.O.S.C. EL.SEE PLAN
4" +
/-
2 1/
2" +
/-
1/2"
CLR
.
ADDN'L #3@12" BOT.
CHIP & ROUGHENTOP 3" ALONG EDGES
FORMED SOFFIT
SMALL OPENING IN-FILL
TYPICAL DETAIL
1" C
LR.
SAWCUT & ROUTE OUT 4"WIDE X 2" DEEP TRENCHIN EXIST. 5" SLAB
C.L. TUNNEL
T.O.S.C. EL.VARIESSEE PLAN
CONCRETETOPPING
LEVELINGCOMPOUND,SEE SPECS.
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:4
7 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S3.01
CONCRETE SECTIONSAND DETAILS
15134
1 1" = 1'-0" 2 3 4
3/4" = 1'-0" 7 1" = 1'-0" 6 1" = 1'-0" 10 3/4" = 1'-0" 8 1" = 1'-0" 9
1 1/2" = 1'-0" 5
11 12 14 3/4" = 1'-0" 15
3/4" = 1'-0" 16 3/4" = 1'-0" 17 1 1/2" = 1'-0" 18
1" = 1'-0" 13
3/4" = 1'-0" 19 1 1/2" = 1'-0" 20
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
THIS CONNECTION SHALL BE USED ONLY WHEN CONNECTING BEAMS TOCOLUMNS OR WHEN CONNECTING BEAMS TO GIRDERS WHERE GIRDER HASBEAM CONNECTION ON ONE SIDE ONLY. IF USED AT LOCATIONS WHERE ABEAM CONNECTION IS OPPOSED BY A BEAM CONNECTION ON THE OTHERSIDE OF THE SUPPORTING MEMBER, AN OSHA-APPROVED METHOD MUST BEUSED FOR TEMPORARY ERECTION SUPPORT OF BOTH MEMBERS.
WIDEFLANGE
BEAMSIZE
#BOLTS
PERVERT.ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
WELDED TOBEAMWEB
BOLTED TO BEAMWEB
REDUCTIONFOR COPED
BOTTOM
MIN.ANGLE
LENGTH(IN.)
MAX REACTION (KIPS)
3/4 " DIA.
BOLTS
7/8 " DIA.
BOLTS
3/4 " DIA.
BOLTS
7/8 " DIA.
BOLTS
W8 TO W12 2 .230 29 29 14 13 4 5 1/2
W12 TO W18 3 .235 51 51 25 23 4 8 1/2
W16 TO W24 4 .250 82 82 42 39 5 11 1/2
W18 TO W30 5 .300 104 120 63 59 6 14 1/2
W21 TO W40 6 .350 124 148 87 82 7 17 1/2
W24 TO W44 7 .395 145 172 115 108 8 20 1/2
W30 TO W44 8 .470 165 197 156 147 -- 23 1/2
W33 TO W44 9 .550 185 221 185 194 -- 26 1/2
W36 TO W44 10 .600 205 245 205 235 -- 29 1/2
W40 TO W44 11 .630 226 269 226 269 -- 32 1/2
W44 12 .710 246 294 246 294 -- 35 1/2
CONNECTION LOAD CAPACITYANGLES WELDED TO BEAM
ANGLES BOLTED TO BEAM
BOLTS
SECT. "A"
SECT. "A"
NO SCALE TYP.
VERTICAL ROWS
DOUBLE ANGLESL4x3 1/2x5/16 FOR3/4" BOLTSL4x3 1/2x3/8 FOR 7/8" BOLTS
GIRDER WEB,COL. WEB,OR FLANGE
SEE "ANGLESBOLTED TO BEAM"DETAIL BELOW FORMORE NOTES
OPTIONALCOPED TOP
GIRDER WEB, COL.WEB, OR FLANGE
L4x4x3/8 ERECT. CLIPWHERE BEAMSFRAME TO BOTHSIDES OF COLUMNWEB TYP.
STD. HOLES OR HORIZ.SHORT SLOTS
OPTIONAL COPEDBOTTOM, REDUCECAPACITY ASSHOWN IN TABLE
NOTE: VALUES IN THE COLUMNS LABELED "BOLTED TO BEAM WEB" MAY BE INCREASED BY THE RATIO OFTHE ACTUAL BEAM WEB THICKNESS TO THE MINIMUM BEAM WEB THICKNESS TABULATED. FOR THISCALCULATION THE BEAM WEB THICKNESS MAY NOT BE TAKEN MORE THAN 0.43" FOR 3/4" DIA. BOLTS ORMORE THAN 0.62" FOR 7/8" DIA. BOLTS.
TYPICAL DOUBLE ANGLE CONNECTION
1/2" MAX.
3 1/2"
3" T
YP
.3"
4"
TY
P.
1 1/
4" M
IN.
3" T
YP
.
3 1/2"
"A"
1/43 SIDES
1 1/4" 1 1/4"
MIN
1 1
/2"
CO
PE
1 1/
2" M
AX
3"
TY
P
3"
NOTE:LARGER BM. REACTION MUSTBE LESS THAN 3 TIMESSMALLER BM. REACTION
WIDEFLANGE
BEAM SIZE
3/4 " DIA.
BOLTS
7/8 " DIA.
BOLTS
W8x10 2 .170 14 14
W10x12 2 .190 14 20
W12x14 3 .200 26 29
W12x16 3 .220 26 32
W8 TO W12 2 .230 14 20
W12 TO W18 3 .235 26 34
W16 TO W24 4 .250 37 51
W18 TO W30 5 .300 48 65
W21 TO W44 6 .350 59 78
W24 TO W44 7 .395 70 91
W30 TO W44 8 .470 81 104
W33 TO W44 9 .550 91 117
W36 TO W44 10 .600 102 130
W40 TO W44 11 .630 112 143
W44 12 .710 123 156
CONNECTION LOAD CAPACITY(X = 3" MAX.)
BOLTS
SECT. "A"COLUMN
PL. TO MATCH BEAM WEBTHICKNESS, 3/8" MINIMUM.
TYP. SINGLEPLATEBOLTEDCONNECTIONFOR BEAMS ONBOTH SIDES ONLY
# BOLTSPER
VERT. ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
MAX REACTION(KIPS)
MAX.X= 3"
TYP.
1 1/4" @ 3/4" DIA. BOLTS1 1/2" @ 7/8" DIA. BOLTS,
1/43 SIDES
MIN
1 1/
2"M
IN3"
WIDE FLANGEBEAM SIZE 3/4 " DIA. BOLTS 7/8 " DIA. BOLTS
W8 TO W12 2 9 12
W12 TO W18 3 18 23
W16 TO W18 4 29 39
W18 5 41 56
(NOT PERMITTED FOR BEAMS DEEPER THAN 18")
CONNECTION LOAD CAPACITY (X = 3" MAX.)
PL.3/8"
SECT. "A"
BOLTS
COLUMN
SHEAR TAB BOLTEDCONNECTION
FOR BEAMS ON ONE SIDE ONLY
# BOLTS PERVERT. ROW
MAX REACTION (KIPS)
"A"
MAX.X= 3"
TYP.
1 1/4" @ 3/4" DIA. BOLTS1 1/2" @ 7/8" DIA. BOLTS
5/16
MIN
1 1/
2"M
IN3"
WIDEFLANGE
BEAMSIZE
3/4 " DIA. BOLTS 7/8 " DIA. BOLTS
1 ROW 2 ROWS 1 ROW 2 ROWS
W8x10 2 .170 4 2 5 3
W10x12 2 .190 4 3 5 4
W12x14 3 .200 8 10 11 11
W12x16 3 .220 8 13 11 15
W8 TO W12 2 .230 4 6 5 8
W12 TO W18 3 .235 8 16 11 18
W16 TO W24 4 .250 16 28 21 33
W18 TO W30 5 .300 24 41 32 55
W21 TO W44 6 .350 33 56 45 77
W24 TO W44 7 .395 43 73 59 100
W30 TO W44 8 .470 54 92 74 126
W33 TO W44 9 .550 65 113 89 154
W36 TO W44 10 .600 77 134 105 183
W40 TO W44 11 .630 88 155 120 212
W44 12 .710 100 178 136 233
CONNECTION LOAD CAPACITY (X = 7" MAX.)
BOLTS
COL. WEB
SECT. "A"
SIM.
AT GIRDERAT COLUMN
STIFFENER TYP.
PLATE:5/16" @ 3/4" DIA. BOLTS3/8" @ 7/8" DIA. BOLTS
PLATE:5/16" @ 3/4" DIA. BOLTS3/8" @ 7/8" DIA. BOLTS
1 OR 2 VERT. ROWS
SINGLE PLATE BOLTED CONNECTION
#BOLTS
PERVERT.ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
MAX REACTION (KIPS)
"A"
MAX.X=7"
"A"
MIN
.3"
MIN
.1
1/2"
MAX.X=7"
1/41/4
MIN
1 1/
2"
MIN3"
WIDEFLANGE
BEAMSIZE
#BOLTS
PERVERT.ROW
WELDED TO GIRDER BOLTED TO GIRDER MIN.ANGLE
LENGTH(IN.)
MAX REACTION (KIPS)
3/4 " DIA.
BOLTS
7/8 " DIA.
BOLTS
3/4 " DIA.
BOLTS
7/8 " DIA.
BOLTS
W8 TO W12 2 21 22 10 14 5 1/2
W12 TO W18 3 31 35 21 28 8 1/2
W16 TO W24 4 42 48 32 44 11 1/2
W18 TO W30 5 53 61 43 59 14 1/2
W21 TO W40 6 63 74 55 75 17 1/2
W24 TO W44 7 74 86 66 90 20 1/2
W30 TO W44 8 84 98 77 105 23 1/2
W33 TO W44 9 95 110 88 120 26 1/2
W36 TO W44 10 106 123 99 134 29 1/2
W40 TO W44 11 117 135 110 149 32 1/2
W44 12 127 147 120 164 35 1/2
CONNECTION LOAD CAPACITY
WELDED TO GIRDER
BOLTED TO GIRDER SECT. "B"
BOLTS
SECT. "A"
PURLIN
GIRDER
PLAN VIEW
WELD SIZE "W" IS 1/4" FOR3/4" DIA. BOLTS AND 5/16"FOR 7/8" DIA. BOLTS
SINGLEANGLE:L4x4x3/8
SINGLE ANGLE:L4X3X3/8
SINGLE ANGLES MUST STAGGER ASSHOWN WHEN CONNECTIONTO GIRDER IS A FIELD CONNECTION
TYPICAL SINGLE ANGLE CONNECTION
3" 4"
1 1/4" 1 1/4""A"
TY
P.
3"M
IN.
1 1/
2"
TY
P.
1 1
/4"
"B"
4"
1 1/4" 1 1/4"
TY
P.
1 1
/4"
4"
TY
P.
3"
MIN
.1
1/2"
TO BEAM C.L. 2 1/2" TO
2 1/2"
W 2WRETURN
W
C.L. SUPPORT
C.L. SKEWED BEAM
TWO ANGLES TWO BENT ANGLES
C.L. SUPPORT
C.L. SKEWED BEAM
C.L. SKEWED BEAM
TWO BENT PLATESSINGLE BENT PLATE
SKEWED SIMPLE FRAMING CONNECTIONS - BEAM TO BEAM
C.L. OF BOLT
C.L. OF BOLT
NOTE:DESIGN SINGLE BENT PLATE CONNECTIONFOR SINGLE SHEAR AND ECCENTRICITYREFER TO CONNECTION "E"
CO
NT
RA
CT
OR
TO
SE
T T
HIS
DIM
EN
SIO
N T
O A
LLO
WP
RO
PE
R IN
ST
ALL
AT
ION
OF
BO
LTS
WH
ER
E B
OLT
ED
CO
NN
EC
TIO
NS
AR
E U
SE
D
CONTRACTOR TO SETTHIS DIMENSION TOALLOW PROPERINSTALLATION OF BOLTSWHERE BOLTEDCONNECTIONS ARE USED
TYPICAL DETAIL
UP TO 1
12
OVER 1 TO 8
1212
OVER 8
OVER 4
12
90°
.
.
REACTION IS CALCULATED FROM THE DROP-IN SPAN. WIDE FLANGE SIZEIS THE SMALLER OF THE DROP-IN BEAM OR THE SUPPORTING BEAM.
WIDEFLANGE
BEAMSIZE
W8x10 2 .170 15 14
W10x12 2 .190 18 24
W12x14 3 .200 30 29
W12x16 3 .220 33 32
W8 TO W12 2 .230 18 20
W12 TO W18 3 .235 36 34
W16 TO W24 4 .250 53 51
W18 TO W30 5 .300 70 67
W21 TO W44 6 .350 97 92
W24 TO W44 7 .395 126 119
W30 TO W44 8 .470 150 187
W33 TO W44 9 .550 173 234
W36 TO W44 10 .600 195 261
W40 TO W44 11 .630 217 287
W44 12 .710 238 313
7/8" DIA. BOLTS
X = 3 3/4"
BOLTS
3/4" DIA. BOLTS
X = 3 1/4"
BOLTS
CONNECTION LOAD CAPACITY
SECT. "A"
BOLTS
PROVIDE SHORT-SLOTTED HOLESIN PLATE AT DROP-IN SIDE FORADJUSTMENT
DROP-IN SIDE
1 1/4" @ 3/4" DIA.BOLTS 1 1/2" @7/8" DIA. BOLTS,TYP.
OPTIONAL COPED BOTTOMON DROP-IN SIDE ONLY
:NOTE:SLOTS NOT ALLOWEDWHERE H=_ IS USED
3/8" THICK SHEARPLATES BOTHSIDES
TYPICAL SHEAR
SPLICE CONNECTION
#BOLTS
PERVERT.ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
MAX REACTION(KIPS)
"A"
MAX.X=3 1/4"
MIN
.3"
MIN
.1
1/2"
TYP. 1 1/4".
WIDEFLANGE
BEAMSIZE
3/4" DIA. BOLTS 7/8" DIA. BOLTS
1 ROW 2 ROWS 1 ROW 2 ROWS
W8x10 2 .170 19 19 19 19
W10x12 2 .190 20 22 25 25
W12x14 3 .200 31 34 35 35
W12x16 3 .220 31 34 38 38
W8 TO W12 2 .230 20 23 26 26
W12 TO W18 3 .235 31 34 39 39
W16 TO W24 4 .250 41 46 52 52
W18 TO W30 5 .300 52 57 65 65
W21 TO W44 6 .350 62 69 78 78
W24 TO W44 7 .395 72 80 91 91
W30 TO W44 8 .470 83 92 104 104
W33 TO W44 9 .550 93 103 117 117
W36 TO W44 10 .600 104 115 130 130
W40 TO W44 11 .630 114 127 143 143
W44 12 .710 124 138 156 156
CONNECTION LOAD CAPACITY
PLATE:5/16" @ 3/4" DIA. BOLTS3/8" @ 7/8" DIA. BOLTS
SEE TABLE IN DETAIL "D" IFCOLUMN SIZE FORCES "X" DIM TOBE LARGER THAN 5" BUT NOT MORETHAN 7".
INTERSECTING BEAMS AT PIPE COLUMNELEVATION
CENTER LINE OFCOLUMN AND BEAM
SEE PLAN FORBEAM
SECTION "A"
DETAIL K1/4 @ 3/4" DIA.BOLTS5/16 @7/8" DIA.BOLTS
SLOT COLUMNFOR PLATES ASSHOWN
#BOLTS
PERVERT.ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
MAX REACTION (KIPS)
THROUGHPLATE
CONNECTIONAT TUBECOLUMN
MAX.
X = 5"
MIN
.A
/2A
"A"
MIN
.A
/2
MAX. 2"
3/16TYP
WIDEFLANGE
BEAMSIZE
3/4" DIA. BOLTS
(3/16" WALL THK)
W8x10 2 .170 16 19
W10x12 2 .190 16 25
W12x14 3 .200 25 35
W12x16 3 .220 25 38
W8 TO W12 2 .230 16 26
W12 TO W18 3 .235 25 39
W16 TO W24 4 .250 34 52
W18 TO W30 5 .300 43 65
W21 TO W44 6 .350 51 78
W24 TO W44 7 .395 59 91
W30 TO W44 8 .470 67 104
W33 TO W44 9 .550 75 117
W36 TO W44 10 .600 83 129
W40 TO W44 11 .630 91 141
W44 12 .710 100 153
19
20
31
31
20
31
42
53
63
74
84
94
103
111
118
3/4 " DIA. BOLTS
(1/4" WALL THK)
7/8" DIA. BOLTS(5/16" WALL
THK)
CONNECTION LOAD CAPACITY
Leh = 1 1/2" FOR 3/4" DIA. 1 3/4" FOR 7/8" DIA
Lev = 1 1/4" FOR 3/4" DIA. 1 1/2" FOR 7/8" DIA.
PLATE:1/4" @ 3/4" DIA. BOLTS (3/16" TUBE WALL THICK. MIN.)5/16" @ 3/4" DIA. BOLTS (1/4" TUBE WALL THICK. MIN.)3/8" @ 7/8" DIA. BOLTS (5/16" TUBE WALL THICK. MIN.)
3/16 @3/4" DIA. BOLTS w/ 3/16" TUBE WALL1/4 @3/4" DIA. BOLTS w/ 1/4" TUBE WALL5/16 @7/8" DIA. BOLTS w/ 5/16" TUBE WALL
TUBE COL.-WALL THICKNESS MIN.,3/16" @ 3/4" DIA. BOLTS(REDUCED CAPACITIES)1/4"@3/4" DIA. BOLTS5/16"@7/8" DIA. BOLTS
1/4@3/4" DIA. BOLTS5/16@7/8" DIA.BOLTS
SINGLEPLATE
CONNECTIONAT COLUMN
#BOLTS
PERVERT.ROW
MINIMUMBEAMWEB
THICKNESS(IN.)
MAX REACTION (KIPS)
TYP
TYP
MIN
Lev
MIN
Lev
3" MAX
TY
P
3"
MINLeh
MINLeh
MIN
Leh
MIN
Leh
MINLeh
MINLeh
MIN3"
MIN 3"
PRE-ENGINEERED CONNECTION DETAILS ARE PROVIDED TO ASSIST THE DETAILER AND FABRICATOR. WHERETHESE PRE-ENGINEERED DETAILS ARE USED THEN NO DESIGN WORK IS REQUIRED BY THE FABRICATOR AND NOCALCULATIONS ARE REQUIRED TO BE SUBMITTED. WHERE THESE PRE-ENGINEERED DETAILS ARE USED, ALLASPECTS OF THE CONNECTIONS MUST CONFORM TO THE PRE-ENGINEERED DETAILS.
THE FABRICATOR MAY, AT HIS OPTION, SUBMIT ALTERNATE CONNECTION DETAILS FOR USE ON THE PROJECT.ALTERNATE CONNECTION DETAILS MUST CONFORM TO THE CONCEPTS SHOWN IN THE PRE-ENGINEEREDCONNECTION DETAILS. SUBMITTALS CONTAINING ALTERNATE CONNECTION DETAILS MUST INCLUDE DESIGNCALCULATIONS SEALED BY A REGISTERED ENGINEER PER THE SPECIFICATIONS.
BEAMS OF VARIOUS WEB THICKNESSES ARE GROUPED BASED ON THEIR DEPTH. NUMBER OF BOLTS SHOWNARE THEREFORE BASED ON THE THINEST WEB IN EACH GROUP.
CONNECTIONS SHOWN IN THE DRAWINGS WHICH ARE NOT COVERED BY THE PRE-ENGINEERED DETAILS SUCHAS TRUSS CONNECTIONS, WIND BRACE CONNECTIONS OR OTHER NON TYPICAL CONNECTIONS MUST BEDESIGNED BY THE FABRICATOR AND SUBMITTED WITH DESIGN CALCULATIONS SEALED BY A REGISTEREDENGINEER PER THE SPECIFICATIONS. NUMBER OF ROWS OF BOLTS IN SIMPLE BEAM CONNECTIONS SHALL NOTBE LESS THAN THE NUMBER FOUND BY DIVIDING THE SMALLER BEAM DEPTH (IN INCHES) BY SIX, AND ROUNDINGUP ANY FRACTION TO THE NEXT HIGHER NUMBER.
NOTES:1. FABRICATOR SHALL SELECT TYPICAL BEAM CONNECTIONS FROM THESE DETAILS USING LOAD
REACTIONS GIVEN ON THE PLAN (AS _K) OR SCHEDULE. WHERE NOT GIVEN ON PLAN, BEAMREACTION AT EACH END SHALL BE ASSUMED TO BE 55 PERCENT OF THE MAXIMUM TOTALALLOWABLE (ASD) UNIFORM LOAD FOR THE BEAM SIZE AND SPAN GIVEN IN THE 50 KSI TABLESIN PART 2 OF THE AISC STEEL CONSTRUCTION MANUAL, THIRTEENTH EDITION.
2. ALL BEAM REACTIONS ARE IN KIPS, AT SERVICE LOADS (UNFACTORED).
3. TABULATED CONNECTION CAPACITIES ARE UNFACTORED AND ARE BASED ON GRADE 50 BEAMS,A36 PLATES AND ANGLES, A325N BOLTS (BEARING TYPE) AND E70XX ELECTRODES. FOR CONNECTIONS TOEXISTING A36 BEAM AND COLUMNS, CAPACITIES SHALL BE REDUCED ACCORDINGLY.
4. SLOTTED HOLES ARE NOT PERMISSIBLE EXCEPT WHERE SHOWN.
5. WHERE HORIZONTAL FORCES ARE SHOWN ON THE PLAN (AS H=_K), THE FABRICATOR SHALLSIZE THE CONNECTION TO TRANSFER THE HORIZONTAL FORCE IN ADDITION TO THE REQUIREDVERTICAL REACTION (CONNECTION CAPACITY=V+H). SLOTTED HOLES ARE NOT PERMITTED.
6. FOR EXISTING CONNECTIONS WITH H=_k, SIZE AND ADD FILLET WELD TO EXISTING BEAM TO COLUMNCONNECTION TO TRANSFER THE HORIZONTAL FORCE. SEE DETAIL 7/S4.01
7. COMPLY WITH AISC MIN. EDGE DISTANCES.
EXISTING BEAM
EXISTING COLUMN
1/4
WELD FOR H=_k AT EXISTING
TYPICAL DETAIL
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:5
0 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S4.01
SIMPLE BEAMCONNECTION DETAILS
15134
1 23 4
5 6
89 10
1 1/2" = 1'-0" 7
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
5 1/2"
16 GA. 14 GA. 12 GA. 10 GA.
EDGE FORM GAGE
THICKNESS
SLAB
MAXIMUM SLAB OVERHANG - "A"
NO SCALE
EDGE CONDITION
METAL FLOOR DECK
3'-0"
4" 6" 9" 11"
#3X4" @ 18" O.C.W/ 1#4 CONT.
METAL EDGE FORM.SEE SCHEDULE ABOVE
TYPICAL DETAIL
NOTE:IF DIMENSION "A" EXCEEDS TABLEMAXIMUMS, PROVIDE ANGLESUPPORT PER DETAIL 14/S4.02 WHENDECK RUNS PARALLEL TO BEAM ANDPER DETAIL 14/S4.02 WHEN DECKRUNS PERPENDICULAR TO BEAM.
PLAN
SEE
TH
ICK
NE
SS
SLA
B
"A"
2" MIN.
1-12
4 1/2" 6" 7" 10" 12"
EDGE OF SLAB
4'-0"
L1-1/2X1-1/2X3/16 @ 4'-0"
#3 X 4"@ 12" TOP W/#3 CONT.EDGE FORM:
16 GAGE TO1'-6" CANTILEVER14 GAGE TO2'-0" CANTILVER
TYPICAL DETAIL
2 LEGS
SEE PLANCANTILEVER
1-8
NO SCALE NO SCALE
SLAB EDGE WITH OUTRIGGER
BENT PL. 1/4"X3"X0'-5 1/2" LLV
DECKFILLER ASREQUIRED
WT4X5 ATEACH PURLIN
L _ AT EACHPURLIN
#3 X 4"@ 12" TOP W/#3@9" CONT.
PURLIN, SEE PLAN
L3X3X1/4X0'-4"WELDED TOBOTH BEAMS
CONDITIONS ATEXTERIOR COLUMNS
TYPICAL DETAIL
3/16
3/16
3/16
3/163/16
3/16
3/16 4
SEE PLAN
NO SCALE
CANTILEVERED SLAB EDGE
#3 @ 9" CONT.
16 GAGE EDGE FORM
_-_"
#_ X @ __" O.C.
TYPICAL DETAIL
4"3'-0" MAX.
SEE PLAN
NO SCALE
BENT PL. 1/4"X4 1/2" OR 5 1/2"X_CONT. W/ 3/8" DIA. X 18" WELDEDDEFORMED BAR ANCHOR @ 12".COORD. W/ NEW STAIR ATTACHMENT.
SILL ANGLE ATELEVATOR PERMANUFACTURER
EDGE CONDITION AT STAIR STRINGERS AND ELEVATOR SILL
EDGE OF SLABDIM. SEE PLAN
TYPICAL DETAIL
PLAN
SEE
1/4 2-12PLATE TO BEAM
1. COMPOSITE STEEL BEAMS ARE INDICATED ON THE PLANS THUS (EXAMPLE):
W16X31 (28) C = 2 3/4"
WHERE 28 IS THE TOTAL NUMBER OF SHEAR STUDS BETWEEN SUPPORTS AND 2 3/4" IS THEBEAM CAMBER (IF ANY). END REACTIONS FOR SIZING CONNECTIONS ARE SHOWN AT EACHEND IN KIPS - SERVICE LEVEL). DO NOT USE AISC SPAN TABLES FOR DETERMINING ENDREACTIONS. HERE NO REACTION IS GIVEN, DESIGN CONNECTION TO DEVELOP THE FULLSHEAR CAPACITY OF THE WEB, OR CONTACT THE ENGINEER.
2. COMPOSITE STEEL BEAMS DO NOT REQUIRE SHORING TO SUPPORT THE WET WEIGHT OFCONCRETE. BEAMS WILL BE HIGHLY STRESSED AS CONCRETE IS PLACED AND MUST BEPOSITIVELY BRACED BY THE METAL DECK CONNECTIONS. DO NOT EXCEED CONCRETETHICKNESSES SHOWN.
3. WARNING: IN NONSHORED CONSTRUCTION, EXCESSIVE CONCRETE WEIGHT DURING CASTINGCAN CAUSE SUPPORTING BEAMS TO COLLAPSE. DO NOT, UNDER ANY CIRCUMSTANCES,EXCEED THE DESIGN SLAB THICKNESS BY MORE THAN 3/4 INCH. CAREFULLY CHECK BEAMCAMBERS AND RETURN ANY FOUND TO BE OUT OF TOLERANCE TO THE SHOP FORCORRECTION (SEE SPECIFICATION SECTION 05 12 00).
4. PRIOR TO ERECTING THE FIRST COMPOSITE BEAMS, THE CONTRACTOR SHALL CALL ASPECIAL PRE-CONSTRUCTION MEETING WITH APPLICABLE SUBCONTRACTORS, TESTINGLABORATORY, ARCHITECT AND STRUCTURAL ENGINEER TO REVIEW ALL REQUIREMENTS ANDESTABLISH A QUALITY CONTROL PROCEDURE.
5. THE FINISHED COMPOSITE FLOOR SHALL NOT BE LOADED WITH CONSTRUCTION MATERIALSBEFORE THE CONCRETE HAS ATTAINED 75 PERCENT OF ITS SPECIFIED STRENGTH.
6. ALL SHEAR STUDS SHALL BE FIELD APPLIED, UNLESS OTHERWISE NOTED. SIZE SHALL BESELECTED FROM THE FOLLOWING TABLE DEPENDING ON DECK AND SLAB DIMENSIONS:
DECK SLAB SHEAR STUDS2" 3.5" 3/4" DIA. X 5"2' 2.5" 3/4" DIA. X 4"
7. PLACE THE INDICATED NUMBER OF SHEAR STUDS ALONG THE LENGTH OF THE BEAM OR BEAMSEGMENT AS SHOWN IN THE SHEAR STUD PLACEMENT DIAGRAMS.* STUDS SHALL BE EQUALLY SPACED IN A SINGLE ROW WHERE POSSIBLE, ALLOWING ASINGLE STUD IN THE DECK FLUTES, WHERE APPLICABLE.* PLACE STUDS IN THE MIDDLE OF THE RIB, IF POSSIBLE. WHERE THE STUD MUST BE OFFSETFROM THE MIDDLE OF THE RIB, SHIFT THE STUD AWAY FROM THE BEAM MIDSPAN, ORTOWARD THE CLOSEST SUPPORT (11/S4.02).* WHERE ADDITIONAL STUDS ARE REQUIRED TO OBTAIN THE SPECIFIED NUMBER OF STUDS INA LENGTH OF BEAM, PLACE STUDS IN TANDEM PAIRS PER THE SHEAR STUD PLACEMENTDIAGRAM AND 6/S4.02.* THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING PROPER STUD LAYOUT FOREACH BEAM PRIOR TO INSTALLATION OF STUDS IN THE FIELD. REFER TO TYPICAL DETAILSFOR PLACEMENT OF SHEAR STUDS ON BEAMS.
9. PROVIDE ADDITIONAL STUDS AS REQUIRED TO SATISFY THE MAXIMUM SPACINGS SHOWN IN5/S4.02. WHERE NO STUDS ARE CALLED FOR ON A BEAM SEGMENT SUPPORTING METALFLOOR DECK, PROVIDE A MINIMUM NUMBER TO SATISFY THE FOLLOWING MAXIMUM STUDSPACINGS PER DETAIL 5/S4.02.
10. PROVIDE CAMBER IN MEMBERS WHERE INDICATED. SPECIFIED CAMBER APPLIES ATJOBSITE, JUST PRIOR TO ERECTION, LYING DOWN FLAT SO THAT MEMBER WEIGHT HAS NOEFFECT. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT ORCOMPENSATE FOR CAMBER LOSS DURING SHIPMENT. MEASURED CAMBER IN MEMBERS UPTO 50'-0" LONG SHALL BE WITHIN A TOLERANCE OF -0" TO +1/2" FROM AMOUNT SPECIFIED.FOR MEMBERS GREATER THAN 50'-0" LONG, BOTH POSITIVE AND NEGATIVE TOLERANCE MAYINCREASE 1/8" FOR EVERY 10'-0" OF LENGTH IN EXCESS OF 50'-0". MEMBERS WITH A FIELDMEASURED CAMBER OUTSIDE OF SPECIFIED TOLERANCE SHALL BE RETURNED TO SHOP.
11. THE CONTRACTOR SHALL MEASURE AND RECORD CAMBER OF ALL BEAMS UPON ARRIVALAND BEFORE ERECTION FOR COMPLIANCE WITH THE SPECIFIED CAMBER. MEASURE LYINGFLAT WITH WEB HORIZONTAL. MEMBERS OUTSIDE THE CAMBER TOLERANCE SHALL BERETURNED TO THE SHOP FOR CORRECTION. CAMBERS MEASURED BY THE CONTRACTORARE TO BE VERIFIED BY THE OWNER'S TESTING LABORATORY.
12. SET HORIZONTAL MEMBERS WITH THEIR NATURAL CAMBER (OR SPECIFIED CAMBER) UP.
COMPOSITE STEEL FLOOR FRAMING NOTES
8. WHERE MULTIPLE NUMBERS OF STUDS ARE SHOWN FOR A BEAM, PLACE EACH QUANTITY OFSTUDS IN THE CORRESPONDING BEAM SEGMENT WHERE THE NUMBER IS SHOWN.
14. DECK SHALL BE INSTALLED IN THREE SPAN LENGTHS AT ALL POSSIBLE LOCATIONS. TWOSPAN AND SINGLE SPAN LENGTHS OF DECK SPANNING MORE THAN 9'-5" AND 7'-5"RESPECTIVELY SHALL BE HEAVIER GAUGE DECK, PROPERLY SIZED FOR THE REQUIRED SPAN.
16. INTERMEDIATE SHORING OF THREE SPAN LENGTHS OF DECK TO SUPPORT CONSTRUCTIONLOADS AND WET CONCRETE IS NOT REQUIRED, UNLESS SHOWN OTHERWISE ON THEDRAWINGS.
17. REINFORCE THE SLAB OVER THE METAL DECK WITH WELDED WIRE MESH, FURNISHED IN FLATSHEETS. USE 6x6 - W2.1xW2.1
18. PLACE AN EXTRA LAYER OF WIRE MESH 6'-0" WIDE IN THE TOP OF THE SLAB ABOVE ALLINTERIOR GIRDERS WHICH RUN PARALLEL TO THE DECK SPAN.
20. PLACE SUPPORTS FOR WIRE MESH ON METAL DECK, SO THAT THE MESH IS MAINTAINED INPOSITION 3/4" BELOW THE TOP OF SLAB.
21. METAL DECK SHALL, IN GENERAL, BE FASTENED TO STEEL FRAMEWORK BY WELDING SHEARSTUDS THROUGH THE DECK. IF FIELD WELDED SHEAR STUDS THROUGH METAL DECK ARENOT CALLED FOR IN SCHEDULE OR ON DRAWINGS, DECK SHALL BE WELDED TO STEELFRAMEWORK BY PUDDLE WELDS NOT LESS THAN 3/4" DIAMETER, SPACED NOT MORE THAN1'-0". WHERE SHEAR STUD SPACING EXCEEDS SPECIFIED MAXIMUM DECK WELD SPACING,USE ADDITIONAL PUDDLE WELDS AT 1'-0" BETWEEN STUDS. WHERE 2 UNITS ABUT, EITHEREND TO END OR SIDE TO SIDE, EACH SHALL BE SO FASTENED TO STEEL FRAMING.
22. SIDES OF ADJACENT UNITS SHALL BE JOINED BY WELDING 1" LONG FUSION WELDS OR BUTTONPUNCHING AT A MAXIMUM SPACING OF 3'-0" BETWEEN SUPPORTS.
23. UNLESS OTHERWISE INDICATED IN THE DETAILS, METAL EDGE FORM SHALL BE 14 GAUGECOLD FORMED STEEL, WELDED AT SUPPORTING BEAM FLANGE AT 12" ON CENTER.
24. DEFLECTION OF DECK AND/OR STEEL WILL TAKE PLACE WHEN CONCRETE IS POURED. * THE SPECIFIED CONCRETE SLAB THICKNESS SHALL BE MAINTAINED AT COLUMN LOCATIONS.* SLAB THICKNESS AWAY FROM THE COLUMNS WILL VARY DUE TO BEAM AND DECK DEFLECTIONS.* MINIMUM THICKNESS OF CONCRETE REQUIRED MUST BE PROVIDED, AND TOP SURFACES OFSLABS MUST BE CONSTRUCTED WITHIN SPECIFIED TOLERANCES.* WHERE THERE IS RESIDUAL CAMBER IN STEEL BEAMS, FINISHED CONCRETE SURFACESHALL FOLLOW CAMBER OF BEAMS, BUT FINISHED SURFACE SHALL NOT VARY BY MORE THAN1/4" FROM ONE BEAM TO ANOTHER ADJACENT BEAM, NOR 1/2" TOTAL FOR LENGTH OF FLOOR.* CAMBERED BEAMS ARE INTENDED TO DEFLECT TO APPROXIMATELY A STRAIGHT LINEUNDER FULL WEIGHT OF CONCRETE SLAB, IF ALL TOP OF STEEL ELEVATIONS AND CAMBERSARE AS SPECIFIED IN THE DRAWINGS.* THE CONTRACTOR SHALL BE FAMILIAR WITH THE CONDITIONS OF THE PROJECT ANDFURNISH THE MATERIALS REQUIRED TO CREATE THE SPECIFIED FLOOR ELEVATION. NOADJUSTMENT WILL BE MADE TO CONTRACT PRICE FOR ADDITIONAL CONCRETE REQUIREDBECAUSE OF DEFLECTION OF DECK OR STEEL OR DUE TO DIFFERENTIAL CAMBER.
25. ANTICIPATED MEMBER DEFLECTION:UNCAMBERED BEAMS: 1"METAL DECK: 1/2"
19. PLACE #4 x 4'-0" DIAGONAL BAR NEAR TOP OF SLAB AT ALL CORNERS OF ALL OPENINGSLARGER THAN 6". PROVIDE 2 #4 x 4'-0" DIAGONAL BARS AT ALL RE-ENTRANT CORNERS.
15. FILLER STRIPS SHALL NOT BE USED AT DECK EDGES UNLESS SHEAR STUDS ARE APPLIED TOTHE SUPPORTING ELEMENT AT SPACINGS NOT GREATER THAN THE REQUIREMENTS OF DETAIL5/S4.02 ON THIS SHEET.
13. DESIGN OF COMPOSITE STEEL BEAMS AND DETAILS FOR CONSTRUCTION ARE BASED ON THEFOLLOWING DECK SYSTEM: COMPOSITE METAL DECK - VULCRAFT DIVISION OF NUCORCORPORATION.
TYPE: VLI YIELD STRENGTH: 50 KSIDEPTH: 2 GAUGE: 20
B
C
A
D
E
N/2
12" O.C.
SHEAR STUD PLACEMENT DIAGRAM
NO SCALE
N/2 N/2
N/2 N/2
N
NOTE: N = SCHEDULED NUMBER OF STUDS
PLAN OF BEAM
N
12" O.C.N/2
END OF BEAM
WHEREVER THE NUMBER OF STUDSREQUIRED IN A GIVEN BEAM SEGMENT ISMORE THAN WILL FIT IN ONE ROW ATTHE MINIMUM SPACING, PLACE THEEXTRA STUDS IN PAIRS BEGINNING ATEACH END OF THE BEAM AS SHOWN.
STUD SPACING:
DECK PERPENDICULAR TO BEAMS
SPC'G OF DECK FLUTES, MIN
24" MAXIMUM
DECK PARALLEL TO BEAMS
4 1/2" MINIMUM
32" MAXIMUM
TYPICAL DETAIL
3" M
IN
NO SCALE
SHEAR STUD
BEAM BEAM
SHEAR STUDSEE SPECIFICATIONS
SHEAR STUDS,SEE SPECIFICATIONS
TYPICAL DETAIL
B
B/2 B/2
B
B/4, 1 1/2" MIN.B/4, 1 1/2" MIN.
FINISHED SLAB
COMPOSITEMETAL DECK
NO SCALE
DECK PARALLEL TO BEAM
EXTRA LAYER OF WELDEDWIRE MESH, SEE NOTES.
WELDED WIRE MESH,SEE GENERAL NOTES
CLOSURE PLATEWHERE REQUIRED
NOTE:DECK MAY RUN CONTINUOUS OVER GIRDERPROVIDED THAT STUDS CAN BE POSITIONED ASSPECIFIED.
TYPICAL DETAIL
3/4"
CLR
.
COMPOSITE METAL DECK
FINISHED SLAB
NO SCALE
DECK PERPENDICULAR TO BEAM
SHEAR STUDS
WELDED WIRE MESH, SEEGENERAL NOTES. SUPPORTWITH CHAIRS AS REQUIREDTO MAINTAIN IN POSITION
TYPICAL DETAIL
METAL FLOOR DECK
MID-SPAN (OR POINTOF MAXIMUMMOMENT WHEREIDENTIFIED ON BEAM)
PLACE STUDS LEFTOF CENTER RIB INDOWN FLUTE (IF ANY)
PLACE STUDS RIGHTOF CENTER RIB INDOWN FLUTE (IF ANY)
CENTER RIB INDOWN FLUTE
NOTE:PROVIDE DIAGONAL ANGLES FORSUPPORT WHERE STEEL DECK EXISTSAROUND ANY CORNER OF ANY COLUMN,INCLUDING EXTERIOR COLUMNS.
L3X2X1/4 L.L.H.
STEEL COLUMN
STEEL BEAMS
NO SCALE
METAL DECK SUPPORT AT COLUMN
PLAN
TYPICAL DETAIL
3/16 2TYP. EACH END
NO SCALE
SPANS TO 3'-6": L4X3X1/4 L.L.V.SPANS 3'-6" TO 6'-0": C5X6.7SPANS 6'-0" TO 10'-0": W8X10NON-COMPOSITE: WELD TO DECK
@ 2'-0" O.C. MAX.
REMOVE METAL DECKAFTER SLAB HAS CURED
W8X10 NON-COMPOSITE
LARGE MECHANICAL OPENING IN COMPOSITE SLAB
BLOCK OUT FOROPENING PRIOR TOPOURING DECK SLAB
TYPICAL DETAIL
#4 x 4'-0" DIAG.EACH CORNER TOP
SECTION "A"
STEEL BEAMPLAN
SP
AN
DE
CK
STEEL BEAM
NO SCALE
#4x6'-0" EA. SIDEPERP. TO DECK RIBSBLOCK OUT FOR
OPENING PRIOR TOPOURING DECKSLAB 1#6 IN BOTTOM OF FIRST
FLUTE ON EACH SIDE OFOPENING, EXTEND TO BEAMAT EACH END
REMOVE DECKAFTER SLAB HASCURED
NOTE:REINFORCING NOT REQUIRED AT OPENINGS LESSTHAN 6" WIDE UNLESS DETAILED OTHERWISE. FOROPENINGS LARGER THAN 2'-0" WIDE, PROVIDE BEAMFRAMING. PER J/SCS-1
SMALL MECHANICAL OPENING IN COMPOSITE SLAB
SEE SECTION "A"FOR REINF.PARALLEL TODECK RIBS
#4X4'-0" EA.CORNER TOP
TYPICAL DETAIL
"A" 10
'-0"
MA
X.
2'-0" MAX.
10'-6
" M
AX
.
FLOOR STRENGTHENING AT PLUMBING CHASE
PLAN
FLOOR BEAM
SP
AN
DE
CK
FLOOR BEAM
W8X10
NO SCALE
3#4 @ 6" EACH SIDE OFCHASE CENTERED INSLAB
CHASE PARALLELTO DECK SPAN
CHASEPERPENDICULARTO DECK SPAN
NOTE:PLACE W8X10'S UNDER DECKRIBS AND CONNECT TOFLOOR BEAMS WITHSTANDARD DOUBLE ANGLECOPED CONNECTIONS. WELDTO DECK AT 1/3 POINTS (NOHEADED STUDS REQUIRED).
W8X10UNDER ADJ.DOWN FLUTE
TYPICAL DETAIL
MAX. 1'-0"
1'-6" MAX.
MAX. 1'-0"
MAX.
4'-0"1'-0" TYP.
GIRDER
TYP.
C.J.
PU
RLI
N
TY
P.
PLAN PLAN
1ST POUR2ND POUR
CONSTRUCTION JOINT -PARALLEL TO GIRDER
CONSTRUCTION JOINT -PARALLEL TO PURLINSCOMPOSITE SLAB CONSTRUCTION JOINTS
NO SCALE
C.J
.
1S
T P
OU
R IF
GIR
DE
RU
ND
ER
1S
T P
OU
R IS
CA
MB
ER
ED
GIRDER TYP.
PU
RLI
N T
YP
.
TYPICAL DETAIL
-/=
1/4
PU
RLI
N
EQ EQ
1ST
PO
UR
IFG
IRD
ER
UN
DE
R1S
T P
OU
R IS
NO
TC
AM
BE
RE
D
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:5
1 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S4.02
COMPOSITE STEEL BEAMDETAILS
15134
1
14 15
2 3
5 6 7
11 12 13
17 18 20
10
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
PERIMETER EMBED
CUT OUT EDGE FORMAND TACK WELDANGLE TO EDGE FORM
SEE DETAIL 2/S4.02FOR EDGE FORM
TYPICAL DETAIL
.
SEE PLAN
NO SCALE
POCKET FOR RECESSED BEARING
BENT PLATE 3/8 x _ LONGWITH 3/8" END CLOSUREPLATES
3/8" DIA. x 18" DEFORMEDBAR ANCHOR WELDED TOEND PLATE
NOTE:CONTRACTOR COORDINATELOCATION WITH PRECASTSHOP DRAWINGS.
SEE DETAIL B/SCS-1FOR EDGE FORM
#3 xWELDED TO PLATE
TYPICAL DETAIL
SEE PLAN
NO SCALE
TYPICAL DETAILSLAB RECESS AT COMPOSITE STEEL FLOOR
T.O.S.C. EL.SEE PLAN
L4X3X1/4CONT. (LLV)
T.O.S.C. EL.SEE PLAN
3/16 2-12
SEE ARCH'L
NO SCALE
TYPICAL DETAILSLAB RECESS AT COMPOSITE STEEL FLOOR
T.O.S.C. EL.SEE PLAN
T.O.S.C. EL.SEE PLAN
14 GA.CLOSURE
SEE ARCH'L
NO SCALE
T.O.S.C. EL.
C.L. COL.
ELEVATOR GUIDE RAIL SUPPORT
C.L. BEAM
HSS6X4X1/4
PL.1/2X4X1'-0" W/(2)3/4" DIA. EXP. OREPOXY BOLTS
NEW BEAMSEE PLAN
L6X3-1/2X5/16 LLV EA.SIDE W/ 13/16"X2-1/2"VERTICAL SLOTTEDHOLE
3/4" DIA. THRU - BOLT.GREASE, FINGER TIGHTEN &BURR THREADS
NOTE:VERIFY LOCATION OF VERTICALTUBES WITH ELEVATOR MFR.PRIOR TO PLACEMENT.COORD. WITH FIRE-RATEDSHAFTWALL ASSEMBLIES.
1/4" STIFFENER PLATE
FACE OFHOISTWAY
TYPICAL DETAIL
3/16
3/16 3
PLAN
SEE
SEE ____
NO SCALE
N.S
. GR
OU
T1"
H.S
.3
1/2"
___
1 1/4"
1 3/
8"
ERECTIONBOLTS
STRAP PLATE TO HAVE MINIMUMCROSS-SECTIONAL AREA EQUALTO AREA OF BEAM FLANGE.GRADE OF PLATE TO MATCHGRADE OF BEAM. LENGTH OFPLATE TO BE AS REQUIRED TODEVELOP FILLET WELD.
WEB PLATE, SIZED BYFABRICATOR FORERECTION AND BACKUPPLATE FOR WELDING
MOMENT CONNECTION DIFFERENT DEPTH BEAMS
TYPICAL DETAIL
TYP
SIZE WELD TODEVELOP FULLSTRENGTH OFBEAM FLANGE
TC-U4a BEAM TOBEAM WELDAFTERFLANGES, TYP.
TC-U4a TYP.
T.O.S.C. EL.SEE PLAN
SEE S4.02 FOR STUDS,REINF. & ADDN'L INFO.
SEE PLAN FOR BEAMS, TYP.SEE S4.01 FOR TYP.BEAM CONN. DETAILS
TYPICAL DETAIL
7 1/2" +/-
T.O.S.C. EL.= 111'-3"
EXIST. BEAMAND PL. CONT.
1/S4.02
SIM.
TACK ONEDGE FORM
7 1/2" +/-
T.O.S.C. EL.= 111'-3"
REMOVE EXIST.GRATING
EXISTING BEAMS
EXIST.CONC.WALL
7 1/2" +/-
TOPPING SLAB
EXIST. PL. CONT.
EXIST. BEAM
T.O.S.C. EL.= 111'-3"
EXISTING SLAB
SEE 12/S4.03
REMOVE EXIST. 2"QUARRY TILE &GROUT BED
5" +
/-
EXIST. CONCRETE
REMOVE EXIST.1 1/2" GRATING
NEW 2" DECK
EXIST. BEAM
T.O.S.C. EL. = 111'-3"
T.O.S.C. EL. = 110'-10 1/2"
#4 X 5'-0" @ 12" O.C.CENTERED ON BEAM
EXISTINGSTL. BM.
NEW PL. 1/2" CONT. X AS SHOWN(GRADE 36)
3/16 1 1/2-6
12" CONT.AT EA. END
TYP.1/2"
REINFORCEMENT OF EXISTING BEAM
TYPICAL DETAIL
EXISTING OR NEWFLOOR, SEE PLAN
TYPICAL DETAIL
L3X2-1/2X1/4 CONT. LLH
REMOVE QUARRY TILE &GROUT BED, AND REPLACEW/ CONC. TOPPING
2 1/
2"4"
+/-
EXIST. CONCRETE EXIST. CHANNEL
NEW SLAB AND DECKAFTER REMOVAL OF 1 1/2"GRATING, SEE PLAN
3/16 2-12
#4 X 5'-0" @ 12" O.C.CENTERED ON BEAM
2'-6"
3/16 3
L3X3X1/4 X 0'-8" @ 3'-0"
HSS3X2X3/16 CONT. LSH
T.O.S.C. EL.SEE PLAN
NEW SLAB ANDDECK, SEE PLAN
3/16 3
2 1/
2"2"
EXIST. SLAB
EXIST. BEAM
2 1/
2"
4" +
/-
REMOVE 2" QUARRY &GROUT BED, AND REPLACEW/ CONC. TOPPING
TYPICAL DETAIL
#4 X 5'-0" @ 12" O.C.
2'-6"
NO SCALE
TYP.
3/16
EXIST. STEELBEAM, SEE PLAN
23/16
C.L. OF CURTAIN & WT
23/16
FOLDING PARTITION SUPPORT- PARALLEL TO BEAMS
2
T.O.S.C. EL.
NOTE:1. ADD 1 BAY OF ANGLE X-BRIDGING
PARALLEL TO PARTITIONL2-1/2X2-1/2X3/16 @ 6'-0" O.C.SPACE 2 AT 3'-0' O.C. ATCLOSEST END.
WT4X12 CONT.W/ BOLT HOLES
REFER TO ARCH'L.FOR BRACKET & BOLTS
EXIST. SLAB
TYPICAL DETAIL
EXIST.STEEL BEAM,SEE PLAN
T.O.S.C. EL.SEE PLAN
NEW BEAM, SEE PLAN
EXIST. SLAB
EXIST. BEAM
REMOVE 2" QUARRY TILE &GROUT BED, AND REPLACE W/CONC. TOPPING, SEE GENERALNOTES
2 1/
2"4"
+/-4
1/2"
SEE PLAN FORDECK DIRECTION
3/16 4
L3X3X1/4 CONT. NOTCH VERT.LEG @ BEAMS AS REQ'D
4/S4.01
TYPICAL DETAIL
2'-6"
#4 X 5'-0" @ 12" O.C.
T.O.S.C. EL.SEE PLAN
EXIST. SLAB
EXIST. BEAM
REMOVE 2" QUARRY TILE &GROUT BED, AND REPLACEW/ CONC. TOPPING
TRIM EXIST. ANGLELEG AS SHOWN
4" +
/-2
1/2"
3/16 2-12
NEW L3X2-1/2X1/4 CONT. LLH
NEW SLAB AND DECK AFTERREMOVAL OF 1 1/2" GRATING
TYPICAL DETAIL
#4 X 5'-0" @ 12" O.C.CENTERED ON BEAM
CHANGE IN DECK DIRECTION
TYPICAL DETAIL
T.O.S.C. EL.SEE PLAN
S4.01
EXIST. SLAB
4" +
/-
2 1
/2"
EXIST. BEAM
NEW TOPPING
CONTRACTOR TO FIELD MEASUREAND COORDINATE EXIST.CONDITIONS WITH STAIR MFR.AFTER REMOVAL OF EXIST. STAIR.
NEW STAIR
EXIST. SLAB
10 1/2" +/-
EXIST. BENTPL. AND BEAM
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:5
3 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S4.03
COMPOSITE STEEL BEAMDETAILS
15134
1 2 3 4 5
7 8
1 1/2" = 1'-0" 11 1 1/2" = 1'-0" 12 1 1/2" = 1'-0" 13 1" = 1'-0" 14
1816
10
17
1 1/2" = 1'-0" 9
1 1/2" = 1'-0" 15
1" = 1'-0" 6
1" = 1'-0" 20 1" = 1'-0" 19
SET ISSUE DATES
# DATE ISSUE
09/22/2016 50% CD REVIEW
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
EXISTINGBENT PL. 1/4"
EXISTING BEAM
FIELD VERIFY
T.O.S. EL.VARIES
REMOVE EXISTING ROOFDECK AND REPLACE W/NEW 3" ROOF DECK, SEENOTES ON S1.02.
SEE PLAN FOR DIRECTIONOF DECK SPAN
10 1/4" +/-
T.O.S. EL.VARIES
EXISTING BENT PL.& ANGLE, CONT.
EXISTING BEAM
REMOVE EXISTING ROOFDECK AND REPLACE W/NEW 3" ROOF DECK, SEENOTES ON S1.02.
SEE PLAN FOR DIRECTIONOF DECK SPAN
NEW SLAB AND DECK
T.O.S.C. EL.= 135'-9 1/2"
EXIST. T.O.S. EL.= 135'-4" +/-
SEE PLAN FORDIRECTION OFDECK SPAN
EXIST. BEAM
NEW 3" ROOF DECK.SEE PLAN FORDIRECTION OF SPAN.
CUT AND REMOVE TOPOF EXIST. BENT PL.'SAND ANGLES, CONT.
NEW L3X3X3/16 CONT.
3/16 2-12
NEW SLAB AND DECK
T.O.S.C. EL.= 135'-9 1/2"
EXIST. T.O.S. EL.= 135'-4" +/-
SEE PLAN FORDIRECTION OFDECK SPAN
SEE PLAN FORDIRECTION OFDECK SPAN
EXISTING BEAM
5 1/
2"
NOTE:REMOVE TOP OF EXIST.BENT PL.'S AND ANGLESAT PASSAGEWAYS.
NEW ROOF DECK
T.O.S.C. EL.= 135'-9 1/2"
5 1/
2"
COMPOSITE SLAB ON DECK
NEW BEAM, SEE PLAN
FENCE POST, SEE ARCH'L.WELD TO EDGE ANGLE PRIORTO PLACING CONCRETE.
SIM.
6/S4.04
1'-2 1/4"
EXIST. BEAM
T.O.S.C. EL.VARIES
EXIST. BM. EL.VARIES
VA
RIE
S
L3X3X3/16 CONT.
3/16 2-24
STAGGER@ 12"
15/S4.02
BENT PL. 1/4"X3"X0'-4 1/2"LLV CONT.
SEE 5/S4.04
4
4"
NEW L3X3X3/16 CONT.
NEW ROOF DECK
EXISTING BEAM
3/16 2-12
A.5
CB
1 3/4" DIA X-RODS W/TURNBUCKLE
T=42
kT=42k
Level 3111'-3"
EL. = 127'-1 1/2"
EL. = 135'-7"
EXIST. ANGLESTO REMAIN
NEW 1 1/2" DIA.X-RODS W/TURNBUCKLE
NOTE:REMOVE EXIST.ANGLE X-BRACINGBELOW EL. 127'-1 1/2"
Level 2111'-0"
Level 3123'-0"
43a
1" DIA X-RODS W/TURNBUCKLE
1 1/4" DIA X-RODS W/TURNBUCKLE
T=15
k
T=25k
T=15k
T=25k
Level 4135'-9 1/2"
Level 3123'-0"
FaF
1 1/2" DIA X-RODSW/ TURNBUCKLE
T=35k T=35k
Level 4135'-9 1/2"
Level 3123'-0"
C BLevel 5156'-0"
W12X19 (10)
NEW BEAM
1 3/4" DIA RODS W/TURNBUCKLES
T=48
k T=48kT=48kT=
48k
Level 4135'-9 1/2"
S4.0412
TYP.
PROVIDE HEAVY GAUGEWIRE TIE AT RODINTERSECTION
RODS (1" DIAMETER OR LESS)
TYPICAL DETAILNO SCALE
"A"
"B"
NOTES:1. DESIGN WELDS TO CARRY MINIMUM BRACE FORCES SHOWN ON WB ELEVATIONS ON S4.042. MINIMUM WELD LENGTHS TO BE 4" EA. SIDE.3. WELDS SHALL BE BALANCED ABOUT THE CENTROID OF THE BASE.4. USE DOUBLE-THREADED TURNBUCKLES WITH RODS TO BRING BRACE TO SNUG CONDITION.5. GUSSET PLATES DO NOT NEED TO BE SLOTTED FOR RODS LESS THAN 1 1/4" DIA.
NO SCALE
SLOT GUSSET TORECEIVE ROD
MIN. ROD DIA.
NOM. WELD SIZE
TYPICAL DETAIL
DETAIL "A" WELD TYPE: FLARE BEVELGROOVE
MINIMUM RODDIAMETER
ALLOWABLE LOAD(K/IN.)
4.1
4.9
5.7
1" 6.5
DETAIL "B" WELD TYPE: FILLET
ALLOWABLE LOAD (K/IN.)
7.6 9.6 11.2
8.0 10.4 12.8
8.4 11.2 13.6
8.8 11.6 14.0
5/8"
3/4"
7/8"
1 1/4"
1 1/2"
1 3/4"
2"
3/16" 1/4" 5/16"
LAP ROD OVERGUSSET
2 SIDES
4 SIDES
WIND BRACE CONNECTION ELEVATIONS
NO SCALE
WORK POINT
WORK POINT
CONNECTION TO BEAM AND COLUMN
ADD DOUBLE ANGLEIF REQUIRED TOSATISFY COMBINEDREACTION
CENTROID OF WELDAND GUSSET PLATE.
DESIGN WELD FORECCENTRICITY "e"TYP.
WIND BRACE DESIGN NOTES:1. DESIGN CONNECTION FOR FORCES SHOWN ON WIND BRACE ELEVATIONS.2. SIZE WELDS FOR SHEAR, TENSION AND ECCENTRICITY OF C.G. WELD AND C.G. FORCE.3. AT BEAM TO COLUMN CONNECTIONS, SIZE ATTACHMENT TO COLUMN FOR COMBINED
GRAVITY LOAD SHEAR PLUS VERTICAL SHEAR COMPONENT DUE TO LATERAL LOAD.4. CHECK NET TENSILE AND SHEAR CAPACITY OF GUSSET PLATES.
TYPICAL DETAIL
e
NEW OREXIST. BEAM
EXIST. COLUMN
1/41/4
EXIST. COLUMN
NEW 1/2" PL.'S
RODS (GREATER THAN 1" DIA.)
TYPICAL DETAILNO SCALE
PL. 3/8"
TURNBUCKLES
PLAN
RTU CURBOVER L6
RTU CURBOVER L6
DUCT
L6x4x5/16 LLH
DUCT OPENINGSWHERE APPLICABLE
L6x4x5/16 LLH
SCHEMATIC ARRANGEMENT OF RTUMISC. METAL SUPPORT ANGLES
NOTE:CONTRACTOR TO PROVIDE MISC. METALS COORDINATED WITH THEEQUIPMENT FURNISHED. ARRANGEMENT SHOWN IS SCHEMATIC ONLYAND A FINAL ARRANGEMENT IS TO BE DESIGNED BY THE CONTRACTOR.STRENGTHEN JOIST AS REQ'D. TO COMPLY WITH THIS TYPICAL DETAIL.
JOIST, SEEPLAN (TYP.)
L6X4X5/16 LLH
DUCT OPENINGSWHERE APPLICABLE
JOIST - SEEPLAN (TYP.)
L6x4x5/16 LLH
SEE MECHANICALDRAWINGS FOR SIZE ANDLOCATION OF ROOF-TOPUNIT
NOTE:USE THIS DETAIL IF RTU SYSTEMREQUIRES DUCTS TO LINE UP WITHINSIDE OF CURB
ROOF DECK, EXTENDACROSS OPNGS. CUTOUT ONLY AS REQ'D.
RTU PERPENDICULAR TO BEAMS
RTU BETWEEN BEAMS
MECHANICAL UNIT CURB BEARING ON BEAMS
TYPICAL DETAIL
DECK UNDER RTU AWAYFROM DUCT OPENINGS TOREMAIN INTACT, TYP.
IF ANGLE IS WITHIN 6" OF PANEL POINTNO ADDITIONAL SUPPORT REQUIRED
6'-0" MAX
3/16
NOTCHHORIZONTALLEG OF ANGLEAND WELDVERTICAL LEGTO BEAM WEB
MC8X21.4 X 0'-6"OVER BEAMS OR @L6 INTERSECTIONSFOR CURB SUPPT.
ANGLE, SEE PLANSIN THE DETAIL
EXIST. BEAM
A B
ROOF DECK
MECHANICAL UNIT CURB SUPPORTED BETWEEN BEAMS
ROOF DECK
6'-0" MAX.
NOTE:USE THIS DETAIL WHERE MECHANICAL UNIT CURB OCCURS BETWEEN BEAMS, OR WHERE CURBS AREDISCONTINUOUS OR CANNOT DELIVER LOAD DIRECTLY TO SUPPORTING PRIMARY ROOF FRAMING(SUCH AS AT SOME ISOLATION CURBS) AND LOADS APPLIED TO THE CHANNELS EXCEED THE LIMITSGIVEN FOR THE DETAIL ABOVE. SERVICE LOADS APPLIED TO THE VERTICALLY ORIENTED CHANNELSSHALL BE LIMITED TO THE FOLLOWING VALUES: FOR UP TO A 8'-0" SIMPLE SPAN, 1500 PLF UNIFORMLOAD OR A 4500 POUND CONCENTRATED LOAD APPLIED AT MIDSPAN. ALL CHANNELS MUST SPANBETWEEN ROOF JOISTS OR BEAMS.LONGER SPANS REQUIRE ADDITIONAL ANALYSIS WHICH WILLRESULT IN LARGER MEMBERS OR SMALLER LOAD LIMITS.
NOTE:USE THIS DETAIL WHERE MECHANICAL UNIT CURBS EXTEND ACROSS TWO OR MORE BEAMS.CURBS MUST BE CONTINUOUS AND DESIGNED TO DELIVER EQUIPMENT LOADS DIRECTLY TOSUPPORTING PRIMARY ROOF FRAMING EXCEPT AS FOLLOWS. WHERE CURBS AREDISCONTINUOUS (SUCH AS AT SOME ISOLATION CURBS) OR CANNOT DELIVER LOAD DIRECTLYTO THE PRIMARY ROOF FRAMING, SERVICE LOADS APPLIED TO THE FLAT CHANNELS SHALL BELIMITED TO THE FOLLOWING VALUES: FOR UP TO A 8'-0" SIMPLE SPAN, 200 PLF UNIFORMLOAD OR A 775 POUND CONCENTRATED LOAD APPLIED AT MIDSPAN. ALL CHANNELS MUSTSPAN BETWEEN PRIMARY ROOF FRAMING ELEMENTS. LONGER SPANS REQUIRE ADDITIONALANALYSIS WHICH WILL RESULT IN LARGER MEMBERS OR SMALLER LOAD LIMITS.
SEE MECHANICAL DRAWINGSFOR SIZE AND LOCATIONOF ROOF-TOP UNIT
MC8X21.4 AT ROOF-TOPMECHANICAL UNITCURBS. BEAR 4" MINIMUMON EACH BEAM.
NOTES:1. IF CURB IS GREATER THAN 1'-0"
FROM C.L. OF BEAM EXTENDCHANNEL TO NEXT BEAM.
2. SEE 4/S4.05 FOR DECK SUPPORTFRAMING AT OPENINGS.
MECHANICAL UNIT CURB SUPPORTED DIRECTLYON TWO OR MORE BEAMS
SEE MECHANICAL DRAWINGSFOR SIZE AND LOCATION OFROOF-TOP UNIT
C8X11.5 BETWEEN BEAMS ATROOF-TOP MECHANICAL UNITCURBS. SPACE AT 8'-0" O.C. MAX.NOTCH C8 OR ADD 3/8" WEBPLATE AND WELD TO BEAM. ORUSE MC8X21.4 @ 8'-0" O.C. ONTOP OF DECK LIKE DETAIL A.COORDINATE INTERMEDIATEMEMBERS TO MISS OPENINGS.
TYPICAL DETAIL
1 1/2@6
3/16
1 1/2@6
3/16 2
EXIST. BEAM
EXIST. BEAMMECHANICALSCREENSUPPORT
T.O.S. EL.
METAL WALL PANEL,SEE ARCH'L
L3X3X3/16 X CONT. GALV.
HSS4X4X1/4 GALV.@ 6'-0" MAX.
L3X3X3/16 GALV. CONT.NOTCH HORIZ. LEG @ TUBE
CAP PL. 1/8" GALV.
SE
E A
RC
H'L
SE
E A
RC
H'L
FO
R H
EIG
HT
1/4
1/4 ANGLE & TUBE
TYP. BTWN.
VA
RIE
S
1 1/2
EXIST. BEAM, SEE PLAN
NEW WEBSTIFFENER PL. 3/8"
3/16
MC8 SUPPORT BTWN. BMS.
1/4
SEE 19/S4.04
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:5
5 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S4.04
STEEL SECTIONS ANDDETAILS
15134
1 1/2" = 1'-0" 1 1 1/2" = 1'-0" 2 1 1/2" = 1'-0" 3 1 1/2" = 1'-0" 4 1 1/2" = 1'-0" 5
1 1/2" = 1'-0" 6 1 1/2" = 1'-0" 7
3/16" = 1'-0"
11 NEW WB-4
3/16" = 1'-0"
9 NEW WB-2 3/16" = 1'-0"
10 NEW WB-3 3/16" = 1'-0"
8 NEW WB-1
14 1512 13
19 1" = 1'-0" 17 20
SET ISSUE DATES
# DATE ISSUE
11/18/2016 95% CD REVIEW
11/30/2016 100% CD REVIEW
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017
3 3a
T.O.S.C. EL.SEE PLAN
3" 20 GA. METALROOF DECK
C8X11.5 CONT.AT PERIMETER
1/4" 12"
19/S4.05
L3X3X3/16 CONT.
BEAM BEYOND
L3X3X3/16 CONT.
3/16 2-12
1/4 4
3/16
ERECTION BOLT
PL. 3/8"X4"X0'-8"
GALV., TYP.
NOTE:ALL EXPOSED STEEL MEMBERSSHALL BE GALVANIZED.
REMOVE EXIST. C4
NEW GLASS BLOCKFLOOR, SEE ARCH'L
3/16 2-12
NEW HSS3X1-1/2X3/16LSH CONT.
EXIST. CONC. WALL
EXIST. BEAM
11 1/2" +/-1/2" +/-
NEW TOPPING
T.O.S.C. EL.SEE PLAN
L6X3-1/2X5/16 CONT. LLVW/ 3/4" DIA. EXP. OREPOXY BOLTS @ 24"
EXIST. CONC. WALL
NEW SLAB ON DECK
REMOVE EXIST.CONT. PL.
NEW TOPPING
4 1/
2"
SEE PLAN FORDIRECTION OFDECK SPAN
ADDN'L #3 X 3'-0" TOP
6"
3"
T.O.S.C. EL.SEE PLAN
L6X3-1/2X5/16 CONT. LLVW/ 3/4" DIA. EXP. OREPOXY BOLTS @ 24"
EXIST. CONC. WALL
NEW SLAB ON DECK
REMOVE EXIST.CONT. PL.
NEW TOPPING
SEE PLAN FORDIRECTION OFDECK SPAN
DRILL & GROUT#3X @ 12" TOP
6"
THOROUGHLY CLEAN ALLCONCRETE & RUBBLE 3'-0"
4 1/
2"
6"
T.O.S.C. EL.SEE PLAN
4 1/
2"
NEW BEAM
EXIST. CONC. WALL
NEW SLAB ON DECK
REMOVE EXIST.CONT. PL.
NEW TOPPING
ELE
VA
TIO
N
PL. 3/4"X12"X1'-4"
ELEVATION
8"
3"5"
5"3"
(6)1/2" DIA. EXP. BOLTS
6"
4" M
IN.,
TY
P.
"A"
PLANDRAIN RING
L2 1/2X2 1/2X1/4
EXIST. C8X11.5 OR C6X8.2
NOTE:REFER TO ARCHITECTURAL ORMECHANICAL DRAWINGS FORROOF DRAIN SIZE AND LOCATION.
C.L. ROOF BEAM
INSTALL DECKCONTINUOUSOVER FRAME.CUT OPENINGWHEN REQUIRED
ROOF DRAIN FRAMING
SECTION "A"
TYPICAL DETAIL
3/16
EXIST. BEAMEXIST. CHANNEL
ROOF OPENING FRAMING
T.O.S. EL.
SEE PLAN FORJOIST ORBEAM SIZES ROOF DECK
SUPPORTL3X3X1/4
L5X3X5/16 L.L.V.EACH SIDE OF OPENING.
INSTALL DECK CONT.OVER FRAME. CUTOPNG. WHEN REQ'D.
NOTES:1. REFER TO ARCHITECTURAL OR
MECHANICAL DRAWINGS FOR OPENINGSIZE AND LOCATION.
2. OPENINGS LESS THAN 6"x6" OR 6" DIA. INSIZE DO NOT REQUIRE ANGLE FRAME.
NOTES:1. THIS DETAIL ALSO OCCURS AT ALL
ROOF TOP MECHANICAL VENTSSHOWN ON MECHANICAL ROOFPLANS.
2. PROVIDE L6X6X3/8 WHERE SHIPS -LADDER MOUNTS TO ANGLE ATROOF HATCH. COORD. W/ ARCH'L.
TYPICAL DETAIL
3/16TYP.
3/16TYP.
3/16TYP.
EXIST. ROOF BEAM
3/16
NEW 3" METAL ROOF DECK
2"
L4X3X1/4
NEW HOIST BEAM.REFER TO ELEVATORMFR. FOR LOCATION.
3/4" DIA. THRU-BOLT INCENTER OF 2 1/2"VERTICAL SLOT. FINGERTIGHTEN NUT OVERGREASED WASHERSAND BURR THREADS
1
1
3/16TYP
NEW ROOF DECK
GIRDER FLANGE BRACING
TYPICAL DETAIL
GUSSET PL. 3/8", TYP.
TYP
NOTE:USE THIS DETAIL ONLY WHEREREFERENCED ON PLANS BY THESYMBOL
*
EXISTING BEAM
L3X3X1/4
#3X @ 12" W/1#3 CONT. TOP & BOT.
2'-6"
4"
EXISTING BEAM
T.O.S.C. EL.SEE PLAN
L3X3X1/4 CONT.W/ 1/2" DIA. X 6"H.S. @ 2'-0"
FORM SOFFIT
GLASS BLOCKFLOOR, SEE ARCH'L
REMOVE TOP BAR
4 5
1" DIA. X-RODSW/ TURNBUCKLE
T=13k T=13k
ERECTION SEAT AS REQ'D
W24X76
NEW BEAM
EXIST. W12X40
REMOVE EXIST. BENTPLATES AND ANGLES
T.O.S.C. EL.SEE PLAN
EL. = 135'-3 3/4" +/-
SEE PLAN FOR BEAM
NO SCALE
NOTES:
1. SEE ROOF PLAN FOR ROOF SLOPE. SLOPE CAP PLATES ACCORDINGLY.
2. STIFFENER PLATE SHALL BE EQUAL IN THICKNESS TO THE COLUMN WALL THICKNESS OR BEAM WEB THICKNESS, WHICHEVER IS GREATER.
3. CONNECT INTERSECTING BEAMS TO STIFFENER PLATES USING BOLTS IN SINGLE SHEAR DESIGNED FOR ECCENTRIC BEAM REACTION.
1/2" CAP PLATE CENTEREDON COLUMN AND
2-3/4" DIA. BOLTS
STIFFENER PLATEEACH SIDE
COLUMN, SEESCHEDULEOR PLAN
CAP PLATE - BOLTED CONNECTION
TYPICAL DETAIL
1/16" SMALLERTHAN BEAM WEBTHICKNESS,3/16"MINIMUM
3/16
TYP
3"
SEE PLAN FOR BEAM
NO SCALE
NOTES:
1. SEE ROOF PLAN FOR ROOF SLOPE. SLOPE CAP PLATES ACCORDINGLY.2. STIFFENER PLATE SHALL BE EQUAL IN THICKNESS TO THE COLUMN WALL THICKNESS OR BEAM WEB THICKNESS, WHICHEVER IS GREATER.3. CONNECT INTERSECTING BEAMS TO STIFFENER PLATES USING BOLTS IN SINGLE SHEAR DESIGNED FOR ECCENTRIC BEAM REACTION.
STIFFENER PLATEEACH SIDE
COLUMN, SEESCHEDULE OR PLAN
2-3/4" DIA. BOLTS,STAGGERED ON EACHSIDE OF BEAM WEB
1/2" CAP PLATECENTERED ON COLUMNAND BEAM
CAP PLATE - BOLTED CONNECTION
3/4" DIA. BOLT, TYP.
FOUR HOLES ARE PERMISSIBLEIN THE CAP PLATE. ONLY TWOHOLES ARE PERMISSIBLE IN THEBEAM FLANGE.
BOTTOM FLANGE OF BEAM.
COLUMNCAP PLATE
WEB STIFFENERPLATE, TYP.
PLAN VIEW
PLAN - BEAM/COLUMN CONNECTION DETAIL
NO SCALE
TYPICAL DETAIL
3/16
1/16" SMALLERTHAN BEAM WEBTHICKNESS,3/16" MIN.
TYP
3"
SEE PLAN FOREXIST. BEAM
NO SCALE
NOTES:1. STIFFENER PLATE SHALL BE EQUAL IN THICKNESS TO THE COLUMN WALL THICKNESS OR BEAM THICKNESS, WHICHEVER IS GREATER.
1/2" BASE PLATECENTERED ONCOLUMN AND BEAM
STIFFENERPLATE EACHSIDE
COLUMN, SEE SCHEDULEOR PLAN
BASE PLATE - BOLTED CONNECTION
BOTTOM FLANGEOF EXIST. BEAM.
COLUMNCAP PLATE
WEB STIFFENERPLATE, TYP.
PLAN VIEW
PLAN - BEAM/COLUMN CONNECTION DETAIL
NO SCALE
TYPICAL DETAIL
3/16
3/16
1/16" SMALLERTHAN BEAM WEBTHICKNESS,3/16" MIN.
3"
CONSTRUCTION
DOCUMENTS
2849 FM 447Nursery, TX 7797
TP
NM/GS
13-05
G3 POWERPLANT
DRAWN BY:
CHK'D BY:
3702 S. Interstate 35, Suite 109New Braunfels, TX 78132830-620-0778 Office
CgM and AssociatesArchitects
CGM AND ASSOCIATES3702 S. INTERSTATE 35, SUITE 109.NEW BRAUNFELS, TX 78132
830-620-0778 P830-620-0778 F
ARCHITECT
DATUM ENGINEERS, INC5929 BALCONES DRIVE, STE. 100AUSTIN, TX 78731
512-469-9490 P
STRUCTURAL ENGINEER
BARKER AND ASSOCIATES, INC.824 BROADWAY ST. SUITE 201SAN ANTONIO, TX 78215
210-826-9191 P210-223-9194 F
MEP ENGINEER
FPCG_FIRE PROTECTION CONSULTING GROUP339 SANDALWOOD LANESAN ANTONIO, TX 78216
210-835-2389 P
LIFE SAFETY_FIRE PROTECTION
PROJECT NO:
FILE PATH:
COPYRIGHT:CGM & ASSOCIATES ARCHITECTS, INC2016
PORTIONS OF THIS DRAWING MAY NOT BE TO SCALE. THEREFORE, THIS DRAWING SHALL NOT BE SCALED. COPYRIGHT © 2017 DATUM ENGINEERS, INC.
15134 _STEC-G3.rvt
Datum Engineers IncorporatedWWW.DATUMENGINEERS.COM | CO REG. NO. F-2819
Datum Project No.
Dallas San Antonio214-358-0174 210-858-2869
Austin512-469-9490
South Texas Electric
Cooperative
2/1
0/2
017 1
1:0
9:5
6 A
MC
:\U
sers
\Tony.D
AT
UM
\Docum
ents
\Local R
evi
t F
iles\
Revit
2016 L
oca
l\15134 _
ST
EC
-G3_T
ony.
rvt
S4.05
STEEL SECTIONS ANDDETAILS
15134
1" = 1'-0" 12
1" = 1'-0" 10 1" = 1'-0" 6 1" = 1'-0" 7 1" = 1'-0" 8
3 4 1" = 1'-0" 2 1 1/2" = 1'-0" 1
1" = 1'-0" 9
3/16" = 1'-0"
5 WB-5
1" = 1'-0" 13
18 19 20
SET ISSUE DATES
# DATE ISSUE
02/08/2107 CONSTRUCTION DOCUMENTS
12/16/2014
GALEN G. SCHROEDER
44999L I C E N SE D
STAT E OF T EXA
S
PR
OF
E
SS
I O N A L E NG
I
NE
ER
��
��
.....................................
.....................................
.......
.........................
..
.....................
......
.......
02/08/2017