MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
ELECTRICAL SYMBOL LEGEND
ABBREVIATIONS
AMPERE
HEIGHT ABOVE FINISHED FLOOR, MEASURED TO BOTTOM
HEIGHT ABOVE FINISHED GRADE
ELECTRIC WATER COOLER
EXPLOSION PROOF
GROUND FAULT CIRCUIT INTERRUPTER
HORIZONTALLY MOUNTED
ISOLATED GROUND
KILOWATT
NOT IN CONTRACT
NON-FUSED
POLEPHASE
SURGE PROTECTION
TWIST LOCK
UNLESS NOTED OTHERWISE
VOLT AMPERE (WATTAGE)
WALL MOUNTEDW
VA
TL
SP
G, GFCI
A, AMP
UNO
PHP
H
NF
NIC
KW
IG
EWC
AFG
AFF
EXP
EWH ELECTRIC WATER HEATER
WEATHERPROOF ENCLOSUREWP
FACP
FAAP
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
NIGHTLIGHTNL
TYPICAL TYPICAL FOR ALL SIMILAR DEVICES, FIXTURES, ITEMS,SYMBOLS SHOWN ON THE PLANS.
1. ABSOLUTELY NO SPLICES WILL BE ALLOWED IN ANY SYSTEMS WIRES.PROVIDE FULL LENGTH WIRING BETWEEN DEVICES AND TERMINALS.
2. HEIGHTS REQUIRED BY EQUIPMENT SUPPLIERS TAKE PRECEDENCE OVERALL OTHER DIMENSIONS.
3. ALL HEIGHTS INDICATED ARE FROM FINISHED FLOOR OR GRADE TO TOPOF EXPOSED PORTION OF ITEM (i.e. COVERPLATE, HOUSING, ORENCLOSURE).
4. ITEMS IN TILE SURFACES SHALL BE INSTALLED AS CLOSE AS POSSIBLE TOTHE DIMENSION GIVEN AND SHALL BE HORIZONTALLY AND VERTICALLYCENTERED AND ALIGNED WITH THE TILE JOINTS.
5. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUITCONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TOANY DEVICE ON THE CIRCUIT IS 0-100 FEET FROM THE PANEL, ARE TO HAVE#12 MINIMUM BRANCH CIRCUIT WIRING THROUGHOUT CIRCUIT. (CONDUITSIZE PER SPEC AND NEC.)
6. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUITCONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TOANY DEVICE ON THE CIRCUIT IS 101-175 FEET FROM THE PANEL, ARE TOHAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROMPANEL CIRCUIT BREAKER TO FIRST DEVICE AND #12 BRANCH CIRCUITWIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (CONDUIT SIZEPER SPEC AND NEC). FIRST 75 FT. OF COMBINED HOMERUN AND BRANCHCIRCUIT TO BE MINIMUM #10 WIRE (3/4"C.).
7. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUITCONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TOANY DEVICE ON THE CIRCUIT IS 176-225 FEET FROM THE PANEL, ARE TOHAVE #10 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (3/4"C.) FROMPANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUITWIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.).
8. 120 VOLT BRANCH CIRCUITS, WHERE THE LENGTH OF CIRCUITCONDUCTORS COMPLETE FROM CIRCUIT BREAKER IN SOURCE PANEL TOANY DEVICE ON THE CIRCUIT IS 226 FEET OR MORE FROM THE PANEL, ARETO HAVE #8 MINIMUM BRANCH CIRCUIT WIRING HOMERUN (1"C.) FROMPANEL CIRCUIT BREAKER TO FIRST DEVICE AND #10 BRANCH CIRCUITWIRING THROUGHOUT THE REMAINDER OF THE CIRCUIT (3/4"C.). FIRST 125FT. OF COMBINED HOMERUN AND BRANCH CIRCUIT TO BE MINIMUM #8WIRE (1"C.).
9. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, THE CONTRACTORSHALL PROVIDE NEW CONDUIT FOR ALL CONDUCTORS THAT AREINSTALLED AS A PART OF THIS PROJECT. INSULATED PLASTIC BUSHINGSARE TO BE PROVIDED ON ALL CONDUIT STUB-OUTS AND STUB-UPS.
10. ALL BREAKERS THAT PROVIDE POWER TO FIRE ALARM CONTROL PANELS,POWER SUPPLIES OR OTHER FIRE ALARM DEVICES OR EQUIPMENT SHALLBE FURNISHED, INSTALLED, CONNECTED AND IDENTIFIED IN ACCORDANCEWITH 2010 NFPA 72-5.2.5.2.
11. UNLESS SPECIFICALLY INDICATED AS EXISTING, ALL EQUIPMENT, CONDUIT,WIRE AND ALL ACCESSORIES, REQUIRED AS PART OF THE INSTALLATION,AND USE OF STATED EQUIPMENT, SHALL BE PROVIDED BY THECONTRACTOR AS A PART OF THIS PROJECT.
12. WHERE THE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENTROUTINGS OF CONDUIT, DIFFERENT LOCATIONS OF EQUIPMENT, ETC., THECONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE RAMIFICATIONS OFTHE PROPOSED CHANGE THAT ARE NOT INCLUDED IN HIS PROPOSAL, BUTBECOME APPARENT AT A LATER DATE, AND SHALL BEAR THECONSEQUENCES OF CORRECTING ANY AND ALL CONFLICTS, DEFICIENCIESOR OTHER PROBLEMS AT NO INCREASE IN COST OR INCREASE INCONSTRUCTION TIME ALLOTTED.
13. THE INSTALLATION OF ALL DEVICES, INCLUDING MOUNTING HEIGHTS,SHALL BE COMPLIANT WITH 2014 FBC ACCESSIBILITY CODE.
14. THE CONTRACTOR SHALL INCLUDE IN HIS SCOPE; (1) THE LABOR ANDMATERIALS REQUIRED FOR CREATING OPENINGS FOR CONDUITPENETRATIONS THROUGH WALLS, SLABS AND ROOF STRUCTURES; ASWELL AS THE SEALING OF THESE PENETRATIONS; (2) THE ROUTING OFCONDUITS AROUND INPENETRATABLE OBSTACLES, SUCH ASPOURED-IN-PLACE BEAMS, COLUMNS, LINTELS AND SIMILAROBSTRUCTIONS AND; (3) THE SEALING OF PENETRATIONS OF CONDUITSINTO WHICH NEW WIRE IS PULLED AS A PART OF THIS PROJECT, TOINCLUDE FIREPROOFING WHERE NECESSARY.
15. IF THE INTENT OF THE ARCHITECT/ENGINEER WITH REGARD TO ANYDETAIL IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONEINTERPRETATION, SUCH MATTERS SHALL BE BROUGHT TO THE A/E INWRITING BEFORE THE SUBMISSION OF BIDS, AND THE A/E SHALL ISSUECORRECTION OR CLARIFICATION IN WRITING. OTHERWISE, NO EXTRACOSTS OR EXTENSIONS OF TIME WILL BE BE ALLOWED FOR THE WORK ORMATERIAL THAT THE A/E WILL REQUIRE, PROVIDED THAT IT COMES WITHINA REASONABLE INTERPRETATION OF THE DRAWINGS ANDSPECIFICATIONS.
16. WHERE THE CONTRACTOR DETERMINES THAT HIS SYSTEM WILL REQUIREADDITIONAL 120VAC POWER SUPPLIES IN LOCATIONS OTHER THAN AT THEFIRE ALARM CONTROL PANEL, HE SHALL COORDINATE THESEREQUIREMENTS FOR ADDITIONAL POWER AND ALL COSTS FOR NEWBREAKERS, CONDUIT, WIRE, SURGE SUPPRESSORS AND ANY OTHERREQUIREMENTS SHALL BE INCLUDED IN THIS CONTRACTORS BID.
17. THE CONTRACTOR SHALL THOROUGHLY CLEAN ALL EQUIPMENT TO BECOMPLETELY FREE OF INTERNAL DEBRIS AND EXTERIOR PAINT, MARKS,DIRT AND ALL SCRATCHES SHALL BE TOUCHED UP.
18. MINIMUM 3/4" CONDUIT FOR CIRCUIT HOMERUNS.
19. ALL EMPTY/SPARE CONDUITS SHALL HAVE PULL STRINGS WITH LABELINGTAGS AT EACH END.
20. ALL PVC RACEWAYS SHALL HAVE A BARE COPPER GROUNDINGCONDUCTOR INSTALLED.
21. ALL CONDUCTORS SHALL BE COPPER.
22. ALL METALLIC RACEWAYS SHALL HAVE AN INSULATED COPPEREQUIPMENT-GROUNDING CONDUCTOR.
23. CONDUIT FITTINGS SHALL BE STEEL.
24. FLEXIBLE METALLIC CONDUIT SHALL BE STEEL.
25. ELECTRICAL NONMETALLIC CONDUIT (ENT) SHALL NOT BE USED.
26. EXPANSION FITTINGS SHALL BE PROVIDED IN EXPOSED CONDUIT RUNSOVER 100 FEET, AT BUILDING EXPANSION JOINTS AND IN CONDUIT RUNSBETWEEN BUILDINGS.
27. DEVICES SHALL BE SPECIFICATION GRADE 20 AMPS, RATED MINIMUM.
28. EXTERIOR TERMINAL CABINETS SHALL HAVE LOCKABLE COVERS.
29. DESIGN MEETS FLORIDA BUILDING CODE 2017 AND NEC 2011.
30. SEAL ALL PENETRATIONS. REFER TO DETAILS SHEET.
31. PAINT AND PATCH SURFACES AS REQUIRED WHERE EXISTING DEVICES,SURFACE RACEWAYS, AND EQUIPMENT ARE REMOVED AS PART OF THEPROJECT. REFER TO PAINTING SPECIFICATION.
32. ALL TRENCHING TO BE BY HAND.
33. ALL BURIED CONDUITS TO BE 24" BELOW GRADE TO TOP OF CONDUIT.
34. PROVIDE ORANGE BARRIER FENCE WITH DRIVEN RODS AROUND OPENTRENCHES.
35. PROVIDE STAINLESS STEEL BLANK PLATES FOR ALL ABANDONED FIREALARM AND INTERCOM BOXES.
36. TAP-CONS ARE NOT PERMITTED, USE PLASTIC ANCHORS WITH STAINLESSSTEEL SCREWS IN EXTERIOR APPLICATIONS.
37. PROVIDE SLEEVE ANCHOR WITH STAINLESS STEEL BOLTS FOR IN-GROUNDPULL BOX COVER.
38. DESIGN COMPLIES WITH NFPA 72 2013.
39. UPON ACTIVATION OF THE KITCHEN HOOD ANSUL SYSTEM THE CAMPUSWIDE FIRE ALARM SYSTEM SHALL BE ACTIVATED.
40. UPON ACTIVATION OF THE ALARM SYSTEM ALL AIRHANDLER UNITS WILLSHUTDOWN.
GENERAL NOTES(NOTE: NOT ALL SYMBOLS SHOWN ON LEGEND ARE NECESSARILY USED ON FLOOR PLANS)
ELECTRICAL SCOPE OF WORK1. PROVIDE FOR THE DEMOLITION AND RENOVATION OF EXISTING INTERCOM AND FIRE
ALARM SYSTEM. EXISTING FIRE ALARM AND INTERCOM SHALL REMAIN OPERATIONALFOR THE DURATION OF THE PROJECT. CONTRACTOR SHALL PHASE PROJECT TO MEETTHIS REQUIREMENT. FIRE ALARM AND INTERCOM WORK IS EXCLUDED FROM THEPORTABLE CLASSROOMS. PORTABLE CLASSROOMS WILL BE DISCONNECTED ANDRECONNECTED TO NEW EQUIPMENT VIA EXISTING CONDUCTORS. THIS IS A BRIEFDESCRIPTION OF ELECTRICAL WORK REQUIRED. REFER TO SPECIFICATIONS BOOK ANDCOMPLETE PLANS FOR ENTIRE SCOPE OF WORK. PROVIDE DEDICATED POWER CIRCUITSFOR FA AND IC PROVIDE ADDITIONAL GROUNDING.
2. PROVIDE CEILING TILES TO MATCH EXISTING TILES WHERE CEILING SPEAKERS HAVEBEEN DELETED.
3. REMOVE ALL EXISTING DUKANE DIGITAL CLOCK SYSTEM, INCLUDING CLOCKS, POWERSUPPLIES, WIRING AND RACEWAY COMPLETE. PROVIDE BLANK COVER PLATES ANDPAINT TO MATCH EXISTING WALL. EXISTING RACEWAYS THAT ARE IN GOOD CONDITIONAND PROPERLY SUPPORTED MAY BE REUSED FOR FIRE ALARM AND INTERCOM.
UNDER CABINETUC
S
INTERCOM DEVICES
CEILING MOUNTED INTERCOM SPEAKER
INTERCOM EQUIPMENT RACK
INTERCOM TERMINAL CABINET
SURFACE MOUNTED INTERCOM SPEAKER
INTERCOM CALL-IN STATION 48" AFF
ADMINISTRATIVE PHONEA
STAFF STATIONINTERCOM WIRE LEGENDa = WEST PENN #355 4-CONDb = WEST PENN #220 2-COND
c = WEST PENN #AQC355 4-COND EXTERIOR USEd = WEST PENN #290 2-CONDe = CAT 5 FOR VOIP ADMIN PHONE/DISPLAY
ICER
ICTC
ICTBINTERCOM TERMINAL BOARD
S
NOTE:PROVIDE FIRE STOPPING FOR ALL CONDUIT PENETRATIONS OF FLOORS, WALLS AND CEILINGS WEATHER RATEDOR NOT. REFER TO FIRE SYSTEMS ON E8.01. WHERE SLEEVES ARE INSTALLED, THEY SHALL BE SUPPORTEDFROM THE ASSEMBLY THROUGH WHICH THEY PASS. SEAL THE SLEEVE ANULAR PENETRATION AND THE SLEEVEAFTER THE INSTALLATION OF CABLING.
FIRE ALARM SYSTEM
MANUAL FIRE ALARM PULL STATION. 48" TO ACTUATOR HANDLE
FIRE ALARM CONTROL UNIT "FACU"
FIRE ALARM ANNUNCIATOR PANEL "FAAP"
FIRE ALARM TERMINAL CABINET "FATC", NEMA 1 RATED
135° HEAT DETECTOR
SMOKE DETECTOR
CONTROL MODULE RELAY
MONITOR MODULE
FIRE ALARM CEILING MOUNTED STROBE, 75 CANDELA MINIMUM
FIRE ALARM CONTROL PANEL "FACP"
FIRE ALARM HORN - WALL MOUNTED
DUCT SMOKE DETECTOR - PROVIDE LED SUPERVISORY INDICATOR FORBOTH DETECTORS IN AN ACCESSIBLE LOCATION AND CLEARLYLABELED.
"R" = RETURN"S" = SUPPLY
FIRE ALARM COMBINATION HORN/STROBE DEVICE - 80" TO BOTTOM OFILLUMINATION DEVICE (75 CANDELA MINIMUM, 110 CANDELA WHERENOTED)
FIRE ALARM STROBE ONLY, 75 CANDELA MINIMUM - 80" TO BOTTOM OFILLUMINATION DEVICE
NOTE:PROVIDE PULL STRINGS IN ALL RACEWAYS WHERE EXISTING FIRE ALARM AND INTERCOM CONDUCTORS AREREMOVED. PROVIDE IDENTIFICATION LABEL TO INDICATE OPPOSITE END LOCATION. FOR IN-GROUNDPULLBOXES, PROVIDE CARLON FLEX SIZED AS REQUIRED TO PROVIDE SEPARATION BETWEEN FIRE ALARM ANDINTERCOM SYSTEMS. ABOVE GRADE, PROVIDE SEPARATE PULL OR JUNCTION BOXES.
IC
IC
FIRE ALARM CEILING MOUNTED COMBINATION HORN/STROBE DEVICE (75CANDELA MINIMUM, 110 CANDELA WHERE NOTED)
POWER DEVICES
J JUNCTION BOX
PB PULL BOX
DUPLEX RECEPTACLE
CEILING RECEPTACLE
GROUND ROD
EXTERIOR WALL MOUNTED ONE DIRECTION INTERCOM SPEAKER (HORN)WITH SINGLE HORN WIRE GUARD. VALCOM WIRE GUARDS POWDERCOATED WHITE PAINT. PROVIDE STAINLESS STEEL SCREWS FORMOUNTING.
EXTERIOR WALL MOUNTED TWO DIRECTION INTERCOM SPEAKER (HORN)WITH DOUBLE HORN WIRE GUARD. VALCOM WIRE GUARDS POWDERCOATED WHITE PAINT. PROVIDE STAINLESS STEEL SCREWS FORMOUNTING.
194° HEAT DETECTOR ATTIC
FIRE ALARM COMBINATION HORN/STROBE DEVICE CEILING MOUNTED,INSTALLED WITH SAFETY TECHNOLOGY INTERNATIONAL 1200 SERIESWEATHERPROOF PROTECTIVE COVER.
WEATHERPROOF LOUDSPEAKER SURFACE MOUNTED BOX TYPEWP
FIRE ALARM PULL STATION INSIDE SIGN
WALL TELEPHONE OUTLET.
MICROPHONE OUTLET - WALL MOUNTED
P
MICROPHONE OUTLET - FLOOR MOUNTEDM
TV
INTERCOM HANDSET WITH PAGE MUTE RELAYICS
PROJECTOR OUTLET CEILING MOUNTED. ORIENT PROJECTORPLATE WITH ELECTRICAL AND DATA KNOCK OUTS FURTHESTFROM SCREEN.
M
TELEVISION OUTLET MOUNTED AT 84" ABOVE FINISHED FLOOR.PROVIDE 4" SQUARE BACKBOX, SINGLE GANG P-RING, 1" CONDUITTO ACCESSIBLE CEILING SPACE, AND (2) CAT-6 CABLE TOCLOSEST IDF ROOM. DUCT DETECTOR REMOTE INDICATOR
KNOX BOX
DUCT DETECTOR REMOTE TEST SWITCH
FIRE ALARM CEILING MOUNTED SPEAKER DEVICE (75 CANDELA MINIMUM,110 CANDELA WHERE NOTED)
135° HEAT DETECTOR ROR
ROR RATE OF RISE
FIRE ALARM WALL MOUNTED SPEAKER/STROBE DEVICE (75 CANDELAMINIMUM, 110 CANDELA WHERE NOTED)
TYP.
CLOCK
NOTE:ROUTE ALL NEW FIRE ALARM AND INTERCOM RACEWAYS TO FACILITATE INSTALLATION OF NEW MECHANICALEQUIPMENT INCLUDING AIR HANDLERS AND CHILLED WATER.COORDINATION WITH MECHANICAL PROJECT WILL BE REQUIRED, INCLUDING PHASING WITH MECHANICALWORK.
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
NO TERMINAL CABINET NO TERMINAL CABINETS
FATC-11
1204
AG
ICTC-17FATC-17
1602
BUILDING 17
BUILDING 14
BUILDING 13 BUILDING 12
BUILDING 11
BUILDING 16
BUILDING 15BUILDING 10
BUILDING 7 BUILDING 8
BUILDING 9
BUILDING 4
BUILDING 5
BUILDING 3BUILDING 2 BUILDING 1
FATC-16 ICTC-16
FATC-15ICTC-15
FATC-13ICTC-13
ICTC-11
FATC-12
ICTC-12
FATC-10ICTC-10
ICTC-9FATC-9
FACP
FATC-8
ICTC-8
FATC-7
ICTC-7
FATC-7
FATC-4ICTC-4
FATC-7
1
1
5TYP.
5TYP.
5TYP.
ICTC-2
2
2
TELECENTERRACK
6
6
6
6
6 6
6
6
7 EXISTING PORTABLE BUILDINGS
7 EXISTING PORTABLE BUILDINGS
7 EXISTING PORTABLE BUILDINGS
ICTC-5
9
9
10
5
8
3
3
PLAN KEY NOTES:1. EXISTING GAS METER
2. NO EXISTING FA OR ICTC CABINETS CAN BE LOCATED
3. FIRE ALARM AND INTERCOM APPEARS TO BE FED OVERHEADFROM BLDG 17.
4. RACEWAY ROUTING AS SHOWN TAKEN FROM EXISTING AS-BUILTDOCUMENTS AND FEILD INVESTIGATION.
5. EXISTING CANOPIES BETWEEN BUILDINGS AS SHOWN.
6. REMOVE EXISTING FIRE ALARM CABLING BETWEEN EXISTING FIREALARM TERMINAL CABINETS. EXISTING RACEWAYS TO REMAIN.PROVIDE NEW FIRE CONDUCTORS IN RENOVATION PHASE. REFERTO RENOVATION PLANS FOR ADDITIONAL REQUIREMENTS.
7. EXISTING PORTABLE BUILDINGS ARE NOT IN SCOPE OF WORK.MAINTAIN EXISTING INTERCOM AND FIRE ALARM CIRCUITS WITHNEW SYSTEMS. REFER TO RENOVATIONS PLANS FOR ADDITIONALREQUIREMENTS.
8. EXISTING CHILLED WATER ENCLOSED CHASE BETWEEN BLDG 11AND 13.
9. EXISTING INGROUND ELECTRICAL BOXES LABELED "ELECTRICAL".
10. EXISTING INGROUND BOX NOT IDENTIFIED POSSIBLE CHASE WAYBETWEEN BUILDINGS FIRE ALARM AND INTERCOM.
#
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
f. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
g. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
h. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
i. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
j. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
k. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
SYSTEMS SITE EXISTING PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
1 2
INTERCOM HORNAT CANOPY
PANEL 1-102
IC
1
IC
IC
IC
C
3
C
110 CD
110 CD
2
IC
PANEL 1-101
IC
IC
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. EXISTING DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED
ABOVE. REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. REMOVE OLD DUKANE MASTER CLOCK SYSTEM COMPLETE ANDPOWER SUPPLY. BACK BOX FOR SPEAKER AND CALL BUTTON TOREMAIN.
3. PULL STATION INSIDE SIGN TO BE REMOVED.
#
BUILDING 1 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FACP
1
PANEL2-101
A
AUTO CALL FACP
AC OVERRIDE
DUKANE PANEL
IC IC IC IC IC
IC IC IC IC
12
3
DUKANEPS 2
ICTC-24
SEC, SEC,RADIO, PS
ACPOWER
FIRE ALARMBATTERY
AUTOFIRE
AUTO CALLFIRE
6
8
A8
PANEL L2 480V A8
A8
CODE YELLOW
IC
7
5
5
5
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. EXISTING DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED
ABOVE. REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. REMOVE OLD DUKANE MASTER CLOCK SYSTEM COMPLETE, POWERSUPPLY AND WIRING.
3. REMOVE HVAC OVERIDE PANEL COMPLETE.
4. EXISTING ICTC-2 TO REMAIN AND BE REUSED. REMOVE EXISTINGINTERCOM CONDUCTORS.
5. REMOVE DUKANE CLOCK. EXISTING ANALOG CLOCKS TO REMAIN.
6. EXISTING KEY VAULT TO BE REUSED IN RENOVATION.
7. REMOVE EXISTING LOUD SPEAKER HORN AT CANOPY.
8. EXISTING ADMIN PHONE WITH KEY PAD.
#
BUILDING 2 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
2
2
2
2
2
1
TVTC-D
1
IC
IC
IC
IC
IC
IC
IC
PNL 3-101
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOVE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
#
BUILDING 3 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
WP
WP
WP
WP
WP WP
333
2 2 2 2 2
1
FATC
FARP
CATV ICTC-4
FA EVAC
MATCHLINE E204MATCHLINE E204
PANEL 4-102
GYM PASYSTEM
1 1 1 1 1
1 1
WG
IC
IC
IC IC
IC
GAS BOILER
TTB
CLOCK PS
IC
IC
IC
5
9 9
6
6
PNL L1
PNL 4-101 PNL PA1
PNL Z-1
INTERCOMSPEAKER ATCANOPY
4
8
WPWP
WP WP
333
333
333
2
2
2
1
1
1
MATCHLINE E204MATCHLINE E204
INTERCOMSPEAKER ATCANOPY
WG
IC IC
33
33
7
7
PLAN KEY NOTES:1. REMOTE SMOKE DETECTOR/ALARM
INDICATING LIGHT AND TEST SWITCHSTATION. EXISTING DUCT DETECTORS ANDMECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATEDMECHANICAL MEZZANINE HEAT DETECTORS.
2. FAN SHUT-DOWN RELAY.
3. CEILING MOUNTED NOTIFICATION APPLIANCESPEAKER.
4. EXISTING ICTC-4 TO REMAIN AND BE REUSED.REMOVE EXISTING INTERCOM CONDUCTORS
5. PA SYSTEM TO REMAIN.
6. REMOVE LOUD SPEAKER HORN AT CANOPY.
7. REMOVE WALL MOUNTED LOUD SPEAKERHORN.
8. REMOVE EXISTING DUKANE CLOCK POWERSUPPLY.
9. EXISTING DUKANE CLOCK TO BE REMOVEDBACK BOX TO REMAIN. REMOVECONDUCTORS.
#
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE
REMOVED. PROVIDE, INSTALL ANDTERMINATE ALL SYSTEMS AND FIREALARM EQUIPMENT INCLUDING, BUTNOT LIMITED TO, RACEWAYS, WIRECABLE, CIRCUIT BREAKERS, MODULES,RELAYS (LISTED FOR USE WITH FIREALARM) ETC. NECESSARY TO SHUTDOWN SUPPLY FANS, FAN TERMINALBOXES (FTB) DAMPERS, AND OTHERDEVICES REQUIRED TO BECONNECTED TO THE FIRE ALARMSYSTEM BUT NOT SPECIFICALLYSHOWN ON THE DRAWINGS.COORDINATE THE EXACT LOCATIONSOF DEVICES WITH OTHER DIVISIONSAS NECESSARY PRIOR TO ROUGH-IN.REFER TO SPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOKSPECIFICATIONS, RISER DIAGRAMSHEETS, DETAIL SHEETS, AND THEINSTRUCTIONAL STATION DETAIL FORALL REQUIREMENTS.
c. DEVICES ARE SHOWN INAPPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARESHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BEREMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDINGSPEAKERS, CALL BUTTONS, ADMIN.PHONES, STAFF STATIONS, GATEWAYSAND WIRING.
f. FIRE ALARM AND INTERCOM WORKSHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLYOPERATIONAL FOR THE DURATION OFTHE PROJECT. THE ONLY EXCEPTIONWILL BE DURING THE CHANGE OVERAFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINALCABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARMAND INTERCOM CABLING COMPLETEBELOW GRADE.
i. REMOVE ALL FIRE ALARM ANDINTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
BUILDING 4 SECTION A DEMO SYSTEMS PLAN
BUILDING 4 SECTION B DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FATC-5
1
22
2
IC
IC IC
ICIC
STAFF ICPHONE
PNL5-107
PNL5-102
WP3
ICTC-5
TV
4
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. REMOVE OLD DUKANE MASTER CLOCK SYSTEM COMPLETE ANDPOWER SUPPLY. COMBINATION SPEAKER/DIGITAL CLOCK,WALL-FLUSH. MOUNTED REMOVE EXISTING DUKANE DIGITAL CLOCKAND SPEAKER EXISTING BACK BOX TO REMAIN REFER TORENOVATION PLAN.
3. REMOVE WALL MOUNTED LOUDSPEAKER HORN.
4. EXISTING ICTC-5 TO REMAIN AND BE REUSED.
#
BUILDING 5 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
TV
FATC-7
1
1
2
2 2
2
2
ICTC-7
PANEL MAI
PANEL L3
PANEL PA2
PANEL7-101
FATCTTB
IC
IC
IC
IC IC
IC
3
4
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
3. EXISTING ICTC-7 CABINET TO REMAIN AND BE REUSED, REMOVEEXISTING INTERCOM CONDUCTORS.
4. EXISTING STAFF PHONE TO BE REMOVED AND REPLACED WITH CALLBUTTON.
#
BUILDING 7 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
3. EXISTING ICTC-8 CABINET TO REMAIN AND BE REUSED, REMOVEEXISTING INTERCOM CONDUCTORS.
4. EXISTING TELECENTER IV TO BE REMOVED AND REPLACED. REFERTO RENOVATION PLANS.
#
11
2
2
2
ICTC-8
IC RACK TELECENTER IV
IC
IC
IC
IC
IC
ICIC
PANEL 8-101
4
FATC-8
3
TTB
BUILDING 8 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
FATC-9
TVTC-I
ICTC-92
2
2
22
22
2
IC
1
ICIC
IC IC
IC
IC IC ICPANEL L-4
PANEL 9-101
3
DUKANE CLOCK P.S. 4
A
TO PORTABLES(2) 1 1/4 DOWN
5
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
3. EXISTING ICTC-9 CABINET TO REMAIN AND BE REUSED, REMOVEEXISTING INTERCOM CONDUCTORS.
4. REMOVE EXISTING DUKANE CLOCK SYSTEM POWER SUPPLY.REMOVE CONDUCTORS.
5. EXISTING ADMIN INTERCOM PHONE WITH KEY PAD.
#
BUILDING 9 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
FATC-10
TVTC-K
ICTC-10
2
22
IC
IC
2
IC
2
IC
2
IC
IC IC
IC
3
3
4
4
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
3. EXISTING ICTC-10 CABINET TO REMAIN AND BE REUSED, REMOVEEXISTING INTERCOM CONDUCTORS.
4. EXTERIOR WALL MOUNTED LOUD SPEAKER HORN.
#
BUILDING 10 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
2
2
1
TVTC-M
FATC-11
MC-1
3
MC-2
ICTC-11
WPS
3
3IC
IC
IC
1 1
IC
IC
IC
IC
IC
IC
WPS
4
5
5
6
6
PNL 11-101
5
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. CEILING MOUNTED FIRE ALARM STROBE.
3. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
4. EXISTING ICTC-11 CABINET TO REMAIN, REMOVE EXISTING INTERCOMCONDUCTORS.
5. EXISTING LOUDSPEAKER HORN TO BE REMOVED.
6. EXISTING LOCAL SOUND SPEAKER TO REMAIN.
#
BUILDING 11 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FATC-12
TVTC-N
1
WPS
2
ICTC-12
2
IC
IC
IC
IC
IC
PANEL 12-101
1
1
1
1
3 5
S
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
3. EXISTING ICTC-12 CABINET TO REMAIN AND BE REUSED. REMOVEEXISTING INTERCOM CONDUCTORS.
4. EXISTING LOUDSPEAKER HORN TO BE REMOVED.
5. BLANK OFF OLD CLOCK BACK BOX.
#
BUILDING 12 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
MATCHLINE E212MATCHLINE E212
1
TVTC-L
FATC-13
ICTC-13
3
MC-3
4
1
IC
IC IC
IC IC
PNL
IC
6
13-101
SS
88
7
99
3
MATCHLINE E212MATCHLINE E212
2
1
3IC
IC
IC IC
1 1
IC
S
S
IC
5
PNL 13-103
PNL 13-102
PNL13-105
PNLL-104
PNLL-7
10 GASH.W.
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED.
PROVIDE, INSTALL AND TERMINATE ALL SYSTEMSAND FIRE ALARM EQUIPMENT INCLUDING, BUTNOT LIMITED TO, RACEWAYS, WIRE CABLE,CIRCUIT BREAKERS, MODULES, RELAYS (LISTEDFOR USE WITH FIRE ALARM) ETC. NECESSARY TOSHUT DOWN SUPPLY FANS, FAN TERMINALBOXES (FTB) DAMPERS, AND OTHER DEVICESREQUIRED TO BE CONNECTED TO THE FIREALARM SYSTEM BUT NOT SPECIFICALLY SHOWNON THE DRAWINGS. COORDINATE THE EXACTLOCATIONS OF DEVICES WITH OTHER DIVISIONSAS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOKSPECIFICATIONS, RISER DIAGRAM SHEETS,DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATELOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN INTHEIR APPROXIMATE LOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED.PROVIDE A COMPLETE NEW INTERCOM SYSTEMINCLUDING SPEAKERS, CALL BUTTONS, ADMIN.PHONES, STAFF STATIONS, GATEWAYS ANDWIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BEPHASED SO THAT FIRE ALARM AND INTERCOMARE FULLY OPERATIONAL FOR THE DURATION OFTHE PROJECT. THE ONLY EXCEPTION WILL BEDURING THE CHANGE OVER AFTER HOURS ANDWEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAYBE REUSED IF ADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM ANDINTERCOM CABLING COMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOMCABLING ABOVE CEILING. REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE
DETECTOR. EXISTING DUCT DETECTORS ANDMECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATEDMECHANICAL MEZZANINE HEAT DETECTORS.
2. KITCHEN HOOD FIRE SUPPRESSION ACTIVATIONSWITCH.
3. COMBINATION SPEAKER/DIGITAL CLOCK,WALL-FLUSH. MOUNTED REMOVE EXISTINGDUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATIONPLAN.
4. AUDITORIUM SPEAKER
5. EXISTING NATURAL GAS SUPPLY METER. REFER TOSITE PLAN FOR EXACT LOCATION.
6. EXISTING ICTC-13 CABINET TO REMAIN AND BEREUSED. REMOVE EXISTING INTERCOMCONDUCTORS.
7. AUDITORIUM SOUND SYSTEM RACK.
8. AUDITORIUM SPEAKERS TO REMAIN.
9. EXISTING LOCAL SOUND SYSTEM SPEAKER TOREMAIN.
10. REMOVE EXISTING DUKANE CLOCK BACK BOX TOREMAIN.
#
BUILDING 13 SECTION A DEMO SYSTEMS PLANBUILDING 13 SECTION B DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
IC
1
2
1
4
4
3
3 TYP
3 TYP EXISTING POLE
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOVE DEVICE AND TRACE OUT SOURCE OF FIRE ALARM CIRCUIT.
2. REMOVE INTERCOM DEVICE AND TRACE OUT SOURCE OF INTERCOMCIRCUIT.
3. EXISTING POLE MOUNTED LOUDSPEAKER HORN AIMED AT PORTABLECLASSROOMS.
4. EXISTING REMOTE INDICATOR AND KEY TEST SWITCH.
#
BUILDING 14 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR. EXISTING
DUCT DETECTORS AND MECHANICAL MEZZANINE LOCATED ABOVE.REMOVE DUCT DETECTORS AND ASSOCIATED MECHANICALMEZZANINE HEAT DETECTORS.
2. FLASHING LIGHT ALARM.
3. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
4. EXISTING ICTC-15 CABINET TO REMAIN AND BE REUSED. REMOVEEXISTING INTERCOM CONDUCTORS.
5. EXISTING LOUDSPEAKER HORNS TO BE REMOVED.
#
1
2
TVTC-J
FATC-15
3
ICTC-15
3
IC
IC
2
IC
IC
IC
1
IC
3IC
3IC
3IC
IC
3IC
3IC
3IC
3IC
TTB
4
IC
BUILDING 15 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
3
IC
IC
TVTC-J
IC
IC
FATC-16IC
IC
ICTC-16
TTC
IC
PNL LP2
PNL PP2
PNL PP3
3
IC
3
IC 3
IC
3
IC
3
IC
3
IC
3
IC
3
IC 3
IC
1
4
2
CABINETS NOT GROUNDED
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. EXISTING LOUDSPEAKER HORN TO BE REMOVED.
3. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
4. EXISTING ICTC-16 CABINET TO REMAIN AND BE REUSED. REMOVEEXISTING INTERCOM CONDUCTORS.
#
BUILDING 16 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
3IC
EMS
IC
IC
IC
IC3
3IC
ICTC-17
TELEPHONE
TVTCFATC
-17
LP-1
PP-1
4
(NO GROUND)
2
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
f. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
g. EXISTING FIRE ALARM TERMINAL CABINETS MAY BE REUSED IFADEQUATE.
h. REMOVE ALL EXISTING FIRE ALARM AND INTERCOM CABLINGCOMPLETE BELOW GRADE.
i. REMOVE ALL FIRE ALARM AND INTERCOM CABLING ABOVE CEILING.REPLACE WITH NEW.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. MECHANICAL UNIT ABOVE.
3. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. MOUNTEDREMOVE EXISTING DUKANE DIGITAL CLOCK AND SPEAKER EXISTINGBACK BOX TO REMAIN REFER TO RENOVATION PLAN.
4. EXISTING ICTC-17 CABINET TO REMAIN AND BE REUSED. REMOVEEXISTING INTERCOM CONDUCTORS.
#
BUILDING 17 DEMO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FATC-11
1204
AG
ICTC-17FATC-17
1602
BUILDING 17
BUILDING 14
BUILDING 13 BUILDING 12
BUILDING 11
BUILDING 16
BUILDING 15BUILDING 10
BUILDING 7
BUILDING 8
BUILDING 9
BUILDING 4
BUILDING 5
BUILDING 3 BUILDING 2BUILDING 1
FATC-16 ICTC-16
FATC-15ICTC-15
FATC-13ICTC-13
ICTC-11
FATC-12
ICTC-12
FATC-10ICTC-10
ICTC-9 FATC-9
FACP-2
FATC-8
ICTC-8
GATEWAY #1
FATC-7
ICTC-7
FATC-7
FATC-4ICTC-4
FATC-7
1
1
ICTC-2
GATEWAY#3
GATEWAY#2
GATEWAY#5
12
12
12
11
4
13
13
10 EXISTING PORTABLE BUILDINGS
8
FACP-55
97
9
8
FACP-112
9 9
9
7
9
88
FACP-4 6
7
8
8
8
FACP-311
11
13
10 EXISTING PORTABLE BUILDINGS
10 EXISTING PORTABLE BUILDINGS
ICTC-5
GATEWAY #412
13
FA TO PORTABLES
8
FATC-2ICTC-3FATC-3
ICTC-3ICTC-3
14
14
4
BUILDING 8
TYPICAL
18
16
13
15
17
13
PLAN KEY NOTES:1. EXISTING GAS METER REFER TO DETAIL 2 SHEET E-804.
2. PROVIDE NEW FIRE ALARM CONTROL PANEL (FACP) NODE. NODETO SUPPORT BUILDINGS 1,2 AND 3. REFER TO BUILDING FLOORPLAN AND FIRE ALARM RISER DIAGRAM.
3. PROVIDE NEW FIRE ALARM CONTROL PANEL (FACP) NODE. NODETO SUPPORT BUILDINGS 7, 8, 16 AND 17. REFER TO BUILDINGFLOOR PLAN AND FIRE ALARM RISER DIAGRAM.
4. PROVIDE NEW FIRE ALARM CONTROL PANEL (FACP) NODE. NODETO SUPPORT BUILDING 9, 10, 11, 12 AND PORTABLE BUILDINGS.REFER TO BUILDING FLOOR PLAN AND FIRE ALARM RISER DIAGRAM.
5. PROVIDE NEW FIRE ALARM CONTROL PANEL (FACP) NODE. NODETO SUPPORT BUILDING 4 AND 5. REFER TO BUILDING FLOOR PLANAND FIRE ALARM RISER DIAGRAM.
6. PROVIDE NEW FIRE ALARM CONTROL PANEL (FACP) NODE. NODETO SUPPORT BUILDING 13 AND 15. REFER TO BUILDING FLOOR PLANAND FIRE ALARM RISER DIAGRAM.
7. PROVIDE NEW (2) 2” CONDUIT WITH TWO (2) SIX (6) STRANDINDOOR/OUTDOOR RATED FIBER OPTIC CABLE. ROUTE ONE CABLETO THE INTERCOM FIBER PATCH PANEL AND ONE CABLE TO THEFIRE ALARM FIBER PATCH PANEL.
8. EXISTING CONDUITS TO BE REUSED WITH NEW FIRE ALARM CABLE.PROVIDE ALTERNATE PRICING IN THE EVENT THAT THE EXISTINGCONDUITS ARE NOT USABLE.
9. EXISTING CONDUITS NOT BEING USED IN RENOVATION SHALL BEEMPTIED OF EXISTING CABLES.
10. EXISTING PORTABLE BUILDINGS ARE NOT IN SCOPE OF WORK.MAINTAIN EXISTING INTERCOM AND FIRE ALARM CIRCUITS WITHNEW SYSTEMS. REFER TO RISER DIAGRAMS AND NOTES ABOVEFOR ADDITIONAL REQUIREMENTS.
11. NEW FIRE ALARM NODE.
12. NEW INTERCOM GATEWAY.
13. ROUTE FIBER VIA EXISTING CANOPIES BETWEEN BUILDINGS.PROVIDE SEPARATE RACEWAY FOR FIRE ALARM AND INTERCOMFIBER.
14. PROVIDE 1" CONDUIT WITH FIRE ALARM CIRCUITS.
15. PROVIDE 1 1/2" CONDUIT FOR INTERCOM BETWEEN BUILDING 10ICTC AND BUILDING 11 ICTC ROUTE VIA CANOPY SHROUD ASSHOWN.
16. PROVIDE 1 1/2" CONDUIT FOR INTERCOM BETWEEN BUILDINGBUILDING 8 ICTC AND BUILDING 16 ICTC. ROUTE VIA CANOPYSHROUD AS SHOWN.
17. PROVIDE 1" CONDUIT FOR INTERCOM BETWEEN BUILDING 13 ICTCAND BUILDING 12 ICTC. ROUTE VIA CANOPY SHROUD AS SHOWN.
18. PROVIDE 1 1/2" CONDUIT FOR INTERCOM BETWEEN BUILDING 2 ICTCAND BUILDING 3 ICTC. ROUTE OVERHEAD.
#
GENERAL NOTES:a. ALL EXISTING FIRE ALARM TO BE REMOVED. PROVIDE, INSTALL AND
TERMINATE ALL SYSTEMS AND FIRE ALARM EQUIPMENT INCLUDING,BUT NOT LIMITED TO, RACEWAYS, WIRE CABLE, CIRCUIT BREAKERS,MODULES, RELAYS (LISTED FOR USE WITH FIRE ALARM) ETC.NECESSARY TO SHUT DOWN SUPPLY FANS, FAN TERMINAL BOXES(FTB) DAMPERS, AND OTHER DEVICES REQUIRED TO BE CONNECTEDTO THE FIRE ALARM SYSTEM BUT NOT SPECIFICALLY SHOWN ON THEDRAWINGS. COORDINATE THE EXACT LOCATIONS OF DEVICES WITHOTHER DIVISIONS AS NECESSARY PRIOR TO ROUGH-IN. REFER TOSPECIFICATIONS.
b. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISERDIAGRAM SHEETS, DETAIL SHEETS.
c. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.
d. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
e. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
f. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
g. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
h. ALL EXISTING INTERCOM IS TO BE REMOVED. PROVIDE A COMPLETENEW INTERCOM SYSTEM INCLUDING SPEAKERS, CALL BUTTONS,ADMIN. PHONES, STAFF STATIONS, GATEWAYS AND WIRING.
i. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
j. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
k. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
KEY:
UNDERGROUND
OVERHEAD
SYSTEMS SITE RENO PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
1 3
INTERCOM HORNAT CANOPY
PANEL 1-102
IC
1
IC
IC
2C
2
C
110 CD
110 CD
ICTC-1
FATC-1
2IC
5
5
6
4C C
C C
WP WP
WPWP
78TYP
IC
5
IC
48
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDE 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. PROVIDE PULL STATION INSIDE SIGN REFER TO DETAIL 4 ON SHEETE-802.
3. PROVIDE METAL COVER PLATE, SCREWS AND CLIPS TO COVEREXISTING BACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTED SPEAKER.PROVIDE NEW CALL BUTTON. PAINT METAL COVER PLATE WHITEGLOSS ENAMEL.
4. PROVIDE NEW INTERCOM HORN AT CANOPY LOCATION.
5. PROVIDE NEW INTERCOM CEILING MOUNTED SPEAKER, EXISTINGBACK BOX MAY BE REUSED.
6. ICTC-1 TO BE REUSED. PROVIDE NEW TERMINAL BLOCKS. PROVIDEIDENTIFICATION ON ALL CONDUCTORS.
7. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
8. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING/ CANOPY.
9. PROVIDE SURFACE MOUNTED IC SPEAKER.
#
BUILDING 1 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FACP1
PANEL2-101
A
FACP
IC IC IC IC IC
IC IC IC IC
FAAP
4
5
3
3
3
3
3
2
8 6TYP.
6
6
8TYP.
10
8
9
TYP.
7
A A
ICTC-2
13
C
WP
C
WP
C
WP
TYP
C
WP
FATC11
12
A
FABATTERY
CODE YELLOW
SEC, SEC,RADIO, PS
14
PNL2-101-39
IC
PLAN KEY NOTES:1. AIR HANDLER UNIT FIRE ALARM SHUT DOWN CONTROL MODULE.
LOCATE WITHIN 3' OF THE UNIT IT CONTROLS.
2. PROVIDE HAZMAT KEY CONTROL SWITCH AT REMOTEANNUNCIATOR IN MAIN OFFICE TO SHUT DOWN ALL AIRHANDLERS AND CLOSE ALL FIRE DOORS.
3. PROVIDE PULL STATION INSIDE SIGNAGE. REFER TO DETAIL 4 ONSHEET E-802
4. PROVIDE SURFACE MOUNT MANUAL PULL STATION BACKBOXSPACE AGE ELECTRONICS MODEL SSU03171
5. PROVIDE MONITORING OF KEY LOCK BOX.
6. PROVIDE METAL BLANK COVER PLATE AT ABANDONED DIGITALCLOCK LOCATION PAINTING TO MATCH WALL COLOR.
7. PATCH DRYWALL WHERE AHU SHUTDOWN AND DUKANE PANELWAS REMOVED. PAINT TO MATCH EXISTING WALL SURFACE.
8. PROVIDE NEW CEILING MOUNTED SPEAKER.
9. PROVIDE ADMINISTRATIVE INTERCOM PHONE.
10. ICTC-2 TO BE REUSED PROVIDE NEW TERMINAL BLOCKS.PROVIDE IDENTIFICATION ON ALL CONDUCTORS.
11. PROVIDE FIRE ALARM CONTROL PANEL (FACP). REFER TO FIREALARM RISER DIAGRAM.
12. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
13. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
14. PROVIDE NEW INTERCOM #2 GATEWAY ICER#2 REFER TO RISERDIAGRAM. PROVIDE DEDICATED 120VOLT CIRCUIT AND BREAKERLOCK AND RECEPTACLE.
15. PROVIDE ADMINISTRATIVE PHONE WITH KEYPAD.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 2 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
TVTC-D
1
IC
IC
IC
IC
IC
IC
IC
2
3
33
3
3
3
ICTC-3
FATC-3
4TYP.
4TYP.
6 TYP.
6 TYP.
4
4 TYP.
C
WP
C
WP
8TYP
7
C
WP
C
WP
5 PNL 3-101
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
PLAN KEY NOTES:1. AIR HANDLER UNIT FIRE ALARM SHUT DOWN CONTROL MODULE.
LOCATE WITHIN 3' OF THE UNIT IT CONTROLS
2. PROVIDE EXPLOSION PROOF RATED HEAT DETECTOR FORFLAMMABLE STORAGE.
3. PROVIDE PULL STATION INSIDE SIGNAGE. REFER TO DETAIL 4 ONSHEET E-802
4. PROVIDE WALL MOUNTED SURFACE INTERCOM SPEAKER ANDCALL BUTTON.
5. PROVIDE NEW ICTC-3 AND REQUIRED TERMINAL BLOCKS.PROVIDE GROUNDING ELECTRODE AND CONDUCTOR #4 CU.
.6 PROVIDE NEW CEILING MOUNTED INTERCOM SPEAKER.
.7 PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
.8 PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
#
BUILDING 3 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
WP
WP
WP
WP
333
2 2 2 2 2
1
MATCHLINE E204MATCHLINE E204
PANEL 4-102
EXISTINGPA
1 1 1 1 1
1 1
WG
IC
IC
IC
IC
IC
4
4 4
4
4
PANEL4-L1
PANEL4-101 PA1
9
IC
IC
5 TYP.
5 TYP.
8 TYP.
IC
8 TYP.
8 TYP.
5 TYP.
7 TYP.
FATC
FARP
CATV ICTC-4
FACP EVAC
TTB
2
10
11
TO FATC
12
13 13
PNL Z-1
6 TYP.
WPWP
WP WP
333
333
333
2
2
2
1
1
1
MATCHLINE E204MATCHLINE E204
WG
IC IC
44
14FAAP W/ FAMIC
7 TYP.
SPEAKER MOUNTED
5 TYP.
6
ABOVE GYM FLOOR
6TYP
7 TYP.
6 TYP.
PLAN KEY NOTES:1. REMOTE SMOKE DETECTOR/ALARM
INDICATING LIGHT AND TEST SWITCHSTATION.
2. FAN SHUT-DOWN RELAY.
3. CEILING MOUNTED NOTIFICATION APPLIANCESPEAKER.
4. PROVIDE PULL STATION INSIDE SIGNAGE.REFER TO DETAIL 4 ON SHEET E-802.
5. PROVIDE NEW CEILING MOUNTED INTERCOMSPEAKER.
6. PROVIDE NEW EXTERIOR LOUD SPEAKERHORN.
7. PROVIDE NEW LOUD SPEAKER HORN.
8. PROVIDE WALL SURFACE MOUNTED SPEAKERAND CALL BUTTON.
9. ICTC-4 TO BE REUSED PROVIDE NEWTERMINAL BLOCKS. PROVIDE IDENTIFICATIONON ALL CONDUCTORS.
10. PROVIDE FIRE ALARM CONTROL PANEL WITHVOICE EVACUATION (FACP). REFER TO FIREALARM RISER DIAGRAM.
11. FIRE ALARM TERMINAL CABINET (FATC).REFER TO FIRE ALARM RISER DIAGRAM.
12. NEW INTERCOM #5 GATEWAY REFER TORISER DIAGRAM ICER#5.
13. PROVIDE BLANK METAL COVER OVER OLDDUKANE CLOCK BACKBOX PAINT TO MATCHWALL COLOR.
14. PROVIDE FAAP WITH REMOTE MICROPHONEREFER TO FIRE ALARM RISER DIAGRAM.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK
SPECIFICATIONS, RISER DIAGRAMSHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATELOCATIONS. LOCATE DEVICES WITHOUTINTERFERENCE OF CHALKBOARDS,TACKBOARDS, PROJECTOR SCREENS,ETC... COORDINATE WITH ALL OTHERTRADES PRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWNIN THEIR APPROXIMATE LOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BEROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUMOF 6' AWAY FROM ANY A/C DIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OFEACH OTHER SHALL FLASH INSYNCHRONIZATION AS REQUIRED BYNFPA 72.
g. FIRE ALARM AND INTERCOM WORKSHALL BE PHASED SO THAT FIRE ALARMAND INTERCOM ARE FULLYOPERATIONAL FOR THE DURATION OFTHE PROJECT. THE ONLY EXCEPTIONWILL BE DURING THE CHANGE OVERAFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES ANDGATEWAYS AS SHOWN ON PLANS.
i. COORDINATE EXACT PLACEMENT OF ALLDEVICES, EQUIPMENT, FIXTURES,SWITCHES AND OUTLETS WITH EXISTINGSITE CONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CANNOT BE FLUSH MOUNTED PROVIDED 5000SERIES WIREMOLD BOXES ANDRACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLESAND FIRE ALARM RACEWAYS FROMBUILDING STRUCTURE WITH J HOOK ANDRACEWAY STRAPS AND ALL THREAD. DONOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 4 SECTION A RENO SYSTEMS PLAN
BUILDING 4 SECTION B RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FATC-5
1
22
2
IC
IC IC
ICIC
STAFF ICPHONE
3TYP.
4
C
WP
C
WP
C
WP
C
WP
6TYP
5
PNL5-101
PNL5-102
ICTC-5
TV
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. PROVIDEPULL STATION INSIDE SIGN. REFER TO DETAIL 4 ON SHEET E-802.PROVIDE METAL COVER PLATE, SCREWS AND CLIPS TO COVEREXISTING BACK BOX. PROVIDE GROMET HOLE FOR NEWINTERCOM CONDUCTORS TO CHASE INTO NEW SURFACEMOUNTED SPEAKER. PROVIDE NEW CALL BUTTON. PAINT METALCOVER PLATE WHITE GLOSS ENAMEL.
3. PROVIDE CEILING MOUNTED INTERCOM SPEAKER.
4. ICTC-5 TO BE REUSED. PROVIDE NEW TERMINAL BLOCKS.PROVIDE IDENTIFICATION ON ALL CONDUCTORS.
5. FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIRE ALARMRISER DIAGRAM.
6. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEALCONDUIT ABOVE CEILING.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 5 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
TV
FATC-7
1
1
2
2 2
2
2
ICTC-7
PANEL MAI
PANEL L3
PANEL PA2
PANEL7-101
FATC
TTB
IC
IC
IC
IC IC
IC
C
C
110 CD3TYP.
C
WP
C
WP
5
C
WP
C
WP6
7
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR
2. COMBINATION SPEAKER/DIGITAL LOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTEDSPEAKER. PROVIDE NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL.
3. PROVIDE NEW CEILING MOUNTED INTERCOM SPEAKER.
4. ICTC-7 TO BE REUSED. PROVIDE NEW TERMINAL BLOCKS.PROVIDE IDENTIFICATION ON ALL CONDUCTORS.
5. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
6. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
7. PROVIDE CALL BUTTON TO REPLACE OLD STAFF PHONE.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 7 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTEDSPEAKER. PROVIDE NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL. CONNECT EXISTING CIRCUIT.
3. PROVIDE BREAKER AND CIRCUIT TO FEED NEW FAPS.
4. PROVIDE NEW CEILING MOUNTED SPEAKER.
5. EXISTING ICTC-8 TO BE REUSED PROVIDE NEW TERMINALBLOCK AND IDENTIFICATION ON ALL CONDUCTORS
6. NEW INTERCOM RACK - GATEWAY #1
7. PROVIDE FIRE ALARM CONTROL PANEL (FACP). REFER TO FIREALARM RISER DIAGRAM.
8. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TOFIRE ALARM RISER DIAGRAM.
9. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEALALL CONDUIT ABOVE CEILING.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
11
2
2
2
ICTC-8
IC RACK
IC
IC
IC
IC
IC
ICIC
PANEL 8-101
C
C
C
C
C
C
110CD
110CD
110CD 110CD
110CD 110CD
C
C
C
C
EXISTING TVTC
FATC
FAPS
EXISTING
8-101-36
NEW
6
4 TYP.
3
EXISTING IDFRACK
4 TYP.
C
WP
C
WP
C
WP
C
WP
FACP7
8
9
BUILDING 8 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
FATC-9
TVTC-I
ICTC-92
2
2
22
22
2
IC
1
ICIC
IC IC
IC
IC IC IC
PANEL 9-101
4TYP.
3C
C
WP
C
C
WP
C
WP
C
WP
C
WP
C
WP
FACP
5
6
7
PANEL L-4
A
9
TOPORTABLES
PNL 9-101-110
8
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. COMBINATION SPEAKER/DIGITAL LOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTEDSPEAKER. PROVIDE NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL.
3. ICTC-9 TO BE REUSED PROVIDE NEW TERMINAL BLOCKS ANDIDENTIFICATION ON CONDUCTORS.
4. PROVIDE NEW CEILING MOUNTED INTERCOM SPEAKER.
5. PROVIDE FIRE ALARM CONTROL PANEL (FACP). REFER TO FIREALARM RISER DIAGRAM.
6. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TOFIRE ALARM RISER DIAGRAM.
7. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEALALL CONDUIT ABOVE CEILING.
8. PROVIDE NEW INTERCOM #3 GATEWAY ICER #3 REFER TO RISERDIAGRAM.
9. PROVIDE ADMINISTRATIVE PHONE WITH KEY PAD.
10. PROVIDE CIRCUIT AND RECEPTACLE FOR FIRE ALARM NODEAND GATEWAY. PROVIDE BREAKER LOCKS.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 9 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
FATC-10
TVTC-K
ICTC-10
2
22
IC
IC
2
IC
2
IC
2
IC
IC IC
IC
3
3
4
TYP.
5
C
WP
C
WP
C
WP
C
WP
C
WP
C
WP
TO FATC
7
TO FATC
8
8
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTED SPEAKER.PROVIDE NEW CALL BUTTON. PAINT METAL COVER PLATE WHITEGLOSS ENAMEL.
3. PROVIDE CEILING MOUNTED INTERCOM SPEAKER.
4. ICTC-10 TO BE REUSED PROVIDE NEW TERMINAL BLOCK PROVIDEIDENTIFICATION FOR ALL CONDUCTORS.
5. PROVIDE INTERCOM STAFF PHONE IN NEMA 3R LOCKABLE COVERBOX FOR BUS LOOP.
6. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
7. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
8. PROVIDE NEW EXTERIOR LOUD SPEAKER HORN.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 10 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
1
TVTC-M
FATC-11
MC-1
3
MC-2 ICTC-11
WPS
3
3IC
IC
IC
1 1
IC
IC
IC
IC
IC
IC
WPS
C
C
6
3 TYP.
4TYP.
4 TYP.
5
6
C
WP
C
WP
C
WP
C
WP
C
WP
C
WP
7
8TYP
6
8 TYP.
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. CEILING MOUNTED FIRE ALARM STROBE.
3. PROVIDE METAL COVER PLATE, SCREWS AND CLIPS TO COVEREXISTING BACK BOX. NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL.
4. PROVIDE CEILING MOUNTED INTERCOM SPEAKER.
5. ICTC-11 TO BE REUSED. PROVIDE NEW TERMINAL BLOCK PROVIDEIDENTIFICATION ON ALL CONDUCTORS.
6. PROVIDE NEW LOUDSPEAKER HORN.
7. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
8. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 11 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FATC-12
TVTC-N
1
WPS
2
ICTC-12
2
IC
IC
IC
IC
PANEL 12-101
3TYP.
4
5
6
C
WP
C
WP
C
WP
C
WP
7
WP
S
5
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTEDSPEAKER. PROVIDE NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL.
3. PROVIDE NEW CEILING MOUNTED INTERCOM SPEAKER.
4. ICTC-12 TO BE REUSED. PROVIDE NEW TERMINAL BLOCKSPROVIDE IDENTIFICATION ON ALL CONDUCTORS.
5. PROVIDE NEW LOUDSPEAKER HORN.
6. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
7. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS, AND THE INSTRUCTIONALSTATION DETAIL FOR ALL REQUIREMENTS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 12 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
MATCHLINE E212MATCHLINE E212
1
TVTC-L
FATC-13
ICTC-13
3
MC-3
4
1
IC
IC IC
IC IC
13-101
IC
6TYP.
LOCALSOUNDSYSTEM
5
6TYP.
C
WP
C
WP
C
WP
C
WP
FACP 8
9
10TYP
PNL 13-101-23
PNL 13-101-24
12
12
PNL
SS
11 11
11
/EVAC
IC
MATCHLINE E212MATCHLINE E212
2
1
3IC
IC
IC IC
1 1
IC
S
S
IC
7TYP.
6TYP.
7TYP.
C
WP
C
WP
C
WP
C
WP
PNL 13-103
PNL 13-102
PNL13-105
PNLL-104
PNLL-7
GASH.W.
16
15 15
13-105-27
14
SK13
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE
DETECTOR.
2. KITCHEN HOOD FIRE SUPPRESSION ACTIVATIONSWITCH.
3. COMBINATION SPEAKER/DIGITAL CLOCK,WALL-FLUSH. PROVIDE METAL COVER PLATE,SCREWS AND CLIPS TO COVER EXISTING BACKBOX. PROVIDE GROMET HOLE FOR NEWINTERCOM CONDUCTORS TO CHASE INTO NEWSURFACE MOUNTED SPEAKER. PROVIDE NEWCALL BUTTON. PAINT METAL COVER PLATE WHITEGLOSS ENAMEL.
4. AUDITORIUM SPEAKER.
5. ICTC-13 TO BE REUSED. PROVIDE NEW TERMINALBLOCKS. PROVIDE IDENTIFICATION ON ALLCONDUCTORS.
6. PROVIDE NEW CEILING MOUNTED INTERCOMSPEAKER.
7. PROVIDE NEW LOUD SPEAKER HORN.
8. PROVIDE FIRE ALARM CONTROL PANEL WITHVOICE EVACUATION (FACP). REFER TO FIREALARM RISER DIAGRAM.
9. PROVIDE FIRE ALARM TERMINAL CABINET (FATC).REFER TO FIRE ALARM RISER DIAGRAM.
10. PROVIDE FLUSH MOUNTED CEILINGHORN/STROBE. CONCEAL ALL CONDUIT ABOVECEILING.
11. LOCAL SOUND SYSTEM SPEAKERS AND RACK TOREMAIN PROVIDE OVERIDE RELAY.
12. PROVIDE DEDICATED CIRCUIT AND RECEPTACLEFOR FIRE ALARM NODE AND INTERCOM GATEWAYPROVIDE BREAKER LOCKS.
13. LOCATE KEY RESET FOR GAS VALVE IN KITCHENMANAGER OFFICE. COORDINATE EXACTLOCATION.
14. LOCATE GAS SHUTDOWN EQUIPMENT ANDBATTERY IN THIS ROOM REFER TO SHEET E-804DETAIL #2, PROVIDE CIRCUIT AND BREAKER ASSHOWN.
15. PROVIDE QUAD CEILING MOUNTED SPEAKERS TOREMAIN.
16. PROVIDE METAL COVER PLATE FOR OLD DUKANECLOCK. PAINT TO MATCH WALL.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS,
RISER DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS.LOCATE DEVICES WITHOUT INTERFERENCE OFCHALKBOARDS, TACKBOARDS, PROJECTOR SCREENS,ETC... COORDINATE WITH ALL OTHER TRADES PRIORTO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIRAPPROXIMATE LOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN ARACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAYFROM ANY A/C DIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHERSHALL FLASH IN SYNCHRONIZATION AS REQUIRED BYNFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASEDSO THAT FIRE ALARM AND INTERCOM ARE FULLYOPERATIONAL FOR THE DURATION OF THE PROJECT.THE ONLY EXCEPTION WILL BE DURING THE CHANGEOVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYSAS SHOWN ON PLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES,EQUIPMENT, FIXTURES, SWITCHES AND OUTLETSWITH EXISTING SITE CONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BEFLUSH MOUNTED PROVIDED 5000 SERIES WIREMOLDBOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIREALARM RACEWAYS FROM BUILDING STRUCTURE WITHJ HOOK AND RACEWAY STRAPS AND ALL THREAD. DONOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 13 SECTION A RENO SYSTEMS PLANBUILDING 13 SECTION B RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
IC
2
EXISTING POLE
WP
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
PLAN KEY NOTES:1. PROVIDE NEW WALL MOUNTED INTERCOM LOUD SPEAKER HORN.
2. PROVIDE NEW LOUD SPEAKER HORN POLE MOUNTED.
3. PROVIDE NEW FIRE ALARM HORN STROBE, SMOKE, HEAD ANDREMOTE INDICATORS.
BUILDING 14 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. FLASHING LIGHT ALARM.
3. COMBINATION SPEAKER/DIGITAL CLOCK, WALL-FLUSH. PROVIDEMETAL COVER PLATE, SCREWS AND CLIPS TO COVER EXISTINGBACK BOX. PROVIDE GROMET HOLE FOR NEW INTERCOMCONDUCTORS TO CHASE INTO NEW SURFACE MOUNTEDSPEAKER. PROVIDE NEW CALL BUTTON. PAINT METAL COVERPLATE WHITE GLOSS ENAMEL.
4. PROVIDE NEW CEILING MOUNTED INTERCOM SPEAKER.
5. PROVIDE NEW TERMINAL BLOCKS. PROVIDE IDENTIFICATION ONALL CONDUCTORS.
6. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM
7. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
j. WHERE INTERCOM CALL STATIONS CAN NOT BE FLUSH MOUNTEDPROVIDED 5000 SERIES WIREMOLD BOXES AND RACEWAY.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
1
TVTC-J
FATC-15
3
ICTC-15
3
IC
IC
IC
IC
IC
1
IC
3IC
3IC
3IC
IC
3
IC
3IC
3IC
3IC
TTB
C
C
4TYP.
4TYP.
6
C
WP
C
WP
C
WP
C
WP
7
IC
BUILDING 15 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
3
IC
IC
TVTC-J
IC
IC
FATC-16IC
IC
ICTC-16
TTC
IC
PNL LP2
PNL PP2
PNL PP3
3
IC
3
IC 3
IC
3
IC
3
IC
3
IC
3
IC
3
IC 3
IC
NEW INTERCOM GATEWAY
C
WP
C
WP
C
WP
C
WP
C
WP
C
WP
4
5
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. FLASHING LIGHT ALARM.
3. PROVIDE SURFACE MOUNTED INTERCOM SPEAKER. PROVIDENEW IC CALL STATION.
4. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TO FIREALARM RISER DIAGRAM.
5. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEAL ALLCONDUIT ABOVE CEILING/ CANOPY.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 16 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
3IC
BAS
IC
IC
IC
IC3
3IC
ICTC-17
TELEPHONE
TVTCFATC
-17
LP-1
PP-1
4
C
WP
C
WP
C
WP
C
WP
5TYP
PLAN KEY NOTES:1. REMOTE INDICATING LIGHT FOR DUCT SMOKE DETECTOR.
2. FLASHING LIGHT ALARM.
3. PROVIDE NEW SURFACE MOUNTED IC SPEAKER. PROVIDE NEWIC CALL STATION.
4. PROVIDE FIRE ALARM TERMINAL CABINET (FATC). REFER TOFIRE ALARM RISER DIAGRAM.
5. PROVIDE FLUSH MOUNTED CEILING HORN/STROBE. CONCEALALL CONDUIT ABOVE CEILING/ CANOPY.
#
GENERAL NOTES:a. REFER TO: SYMBOL LEGEND, BOOK SPECIFICATIONS, RISER
DIAGRAM SHEETS, DETAIL SHEETS.
b. DEVICES ARE SHOWN IN APPROXIMATE LOCATIONS. LOCATEDEVICES WITHOUT INTERFERENCE OF CHALKBOARDS, TACKBOARDS,PROJECTOR SCREENS, ETC... COORDINATE WITH ALL OTHER TRADESPRIOR TO ROUGH-IN.
c. CEILING MOUNTED DEVICES ARE SHOWN IN THEIR APPROXIMATELOCATIONS.
d. ALL FIRE ALARM WIRING SHALL BE ROUTED WITHIN A RACEWAY.
e. LOCATE SMOKE DETECTORS A MINIMUM OF 6' AWAY FROM ANY A/CDIFFUSER.
f. FIRE ALARM STROBES WITHIN SIGHT OF EACH OTHER SHALL FLASHIN SYNCHRONIZATION AS REQUIRED BY NFPA 72.
g. FIRE ALARM AND INTERCOM WORK SHALL BE PHASED SO THAT FIREALARM AND INTERCOM ARE FULLY OPERATIONAL FOR THE DURATIONOF THE PROJECT. THE ONLY EXCEPTION WILL BE DURING THECHANGE OVER AFTER HOURS AND WEEKEND WORK.
h. PROVIDE FIBER BACKBONE NODES AND GATEWAYS AS SHOWN ONPLANS.
i. COORDINATE EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT,FIXTURES, SWITCHES AND OUTLETS WITH EXISTING SITECONDITIONS PRIOR TO ROUGH-IN.
k. SUPPORT ALL NEW INTERCOM CABLES AND FIRE ALARM RACEWAYSFROM BUILDING STRUCTURE WITH J HOOK AND RACEWAY STRAPSAND ALL THREAD. DO NOT SUPPORT FROM CEILING GRID WIRE.
BUILDING 17 RENO SYSTEMS PLAN
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
BLDG 17
BLDG 1BLDG 2BLDG 3
BLDG 4
BLDG 5
BLDG 7 BLDG 8 BLDG 9
BLDG 10
BLDG 11
BLDG 12
BLDG 13
BLDG 15
BLDG 14
BLDG 16
KEY PLAN
FIRE ALARM RISER NOTES:
FIRE ALARM RISER DIAGRAM
FLOOR
BLDG. 5
GENERAL NOTES:
FARP FATC
FARP
FARP
G
J
SK
120V
FARP FATC-3
FATC-2FARP
FARP
G
J
SK
120V
FARP FATC-1
FACU-8FARP
FARP
G
J
SK
120V
FARP FATC-7 FARP FATC-16 FARP FATC-17 FATC-14
FATC-9FARP
FARP
G
J
SK
120V
FARP FATC-10
FARP FATC-11
FLOOR
FARP FATC-12
FATC-13FARP
FARP
G
J
SK
120V
FARP FATC-15
BLDG. 4 BLDG. 3 BLDG. 2 BLDG. 1 BLDG. 8 BLDG. 7 BLDG. 16 BLDG. 17 BLDG. 14 BLDG. 9 BLDG. 10
BLDG. 11 BLDG. 12 BLDG. 13 BLDG. 15
FATC-4
FAAP
J
SK
120V
G G
FACP-5
J
SK
120V
KNOX
FACP-2
FAAP
J
SK
120V
G
FACP-1
J
SK
120V
J
SK
120V
J
SK
120V
G G G G
FACP-3
J
SK
120V
G
J
SK
120V
GG
J
SK
120V
G
J
SK
120V
FACP-4
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
INTERCOM SYSTEM RISER NOTES:1. MAIN INTERCOM SYSTEM EQUIPMENT RACK WITH VoIP CONTROLLER GATEWAY,
CD/RADIO PLAYER, MASTER CLOCK, PAGING AMPLIFIER AND ASSOCIATEDINTERCOM COMPONENTS. PROVIDE FIBER OPTIC ETHERNET SWITCH, RACKMOUNTED UPS WITH 120 VAC SURGE SUPPRESSION. PROVIDE DEDICATED 120VAC, 20 AMP CIRCUIT WITH BREAKER LOCKOUT.
2. INTERCOM CROSS-CONNECT CABLES BETWEEN ICER AND ICTC.
3. CABLING WITH FIBER OPTIC PATCH CORDS TO INTERCOM VoIP CONTROLLEREHTERNET GATEWAY.
4. INTERCOM CROSS-CONNECT CABLES BETWEEN ICER AND ICTC.
7. PROVIDE 10 FEET OF FIBER OPTIC CABLE SERVICE LOOP.
8. EXISTING ICTC FOR INTERCOM.
9. PROVIDE 4" DEEP EXTENSION RING TO EXISTING ICTC CABINETS. SIZE TO MATCHEXISTING CABINET HEIGHT AND WIDTH. PROVIDE EXTENSION AT ICTC-2, ICTC-4,ICTC-8, ICTC-9 AND ICTC-15 FOR NEW CONDUIT ENTRY.
10. REMOTE INTERCOM SYSTEM EQUIPMENT RACK WITH VoIP CONTROLLERGATEWAY, PAGING AMPLIFIER AND ASSOCIATED INTERCOM COMPONENTS.PROVIDE FIBER OPTIC ETHERNET SWITCH, RACK MOUNTED UPS WITH 120 VACSURGE SUPPRESSION. PROVIDE DEDICATED 120 VAC, 20 AMP CIRCUIT WITHBREAKER LOCKOUT.
11. EXISTING CIRCUITS FOR PORTABLE FIELD INTERCOM. RECONNECT TO ICTC ANDTEST.
12. PROVIDE #4 GROUND CONDUCTOR TO DRIVEN GROUND RODS. REFER TO DETAIL#2 ON SHEET E-802. WHERE GROUNDS ARE EXISTING ROUTE GROUND BUS BAR.
13. PROVIDE LOW VOLTAGE SURGE SUPPRESSION TO ALL CIRCUITS ENTERINGTERMINAL CABINET.
14. PROVIDE PUNCHBLOCK TERMINALS AS REQUIRED FOR ALL FIELD CIRCUITS.LABEL AND IDENTIFY ALL CABLES.
15. DEDICATED RECEPTACLE AND CIRCUIT. REFER TO ENLARGED PLANS FORCIRCUIT NUMBER. USE EXISTING CIRCUIT GATEWAY #1.
16. PROVIDE ENGRAVED LABELS FOR ALL EXISTING AND NEW ICTC CABINETS.
19. 2" CONDUIT WITH 6 STRAND MULTIMODE FIBER FOR INTERCOM. ROUTE FIBER INCANOPIES BETWEEN BUILDING.
20. THIS NOTE NOT USED.
22. PROVIDE ADDITIONAL GROUND ROD TO ACHIEVE 5 OHMS OR LESS.
23. PROVIDE FIBER WCH-02P AND CHAMELEON ST 6-PORT MM/SM ADAPTER PANELTA-06A AT EACH INTERCOM GATEWAY.
24. PROVIDE GROUND BUS BAR. REFER TO DETAIL #5 ON SHEET E-802. WHEREINTERCOM AND FIRE ALARM ARE ADJACENT TO EACH OTHER, (1) BUS BAR MAY BESHARED.
SOUND SYSTEMCENTRAL CONTROLCONSOLE(ROOM H-2) SOUND SYSTEM
AUXILIARY CONTROLCONSOLE(ROOM H-2)
CONDUITS STUBBED OUTFOR PORTABLES ANDFUTURE CONSTRUCTION(SEE PLANS)
ICM
STC-J STC-L STC-NSTC-GSTC-CSTC-A
STC-I STC-K STC-M
STC-E
PCUCM
115 VOLT 3/4" 3/4"
3/4"
3/4"3/4"
1"1"
2 1/2"
1"
2" 1 1/2" 1"
2" 1 1/2" 1"1" 1 1/2" 2"
1"
115 VOLT
115 VOLT
115 VOLT
STC-H
CUT 1 1/2" FROMBOTTOM OF DOOR
6 GANG MASONRY BOXCLOCK SYSTEMDUAL POWER SUPPLY DUKANE #17-302
CLOCK SYSTEMDUAL POWER SUPPLYDUKANE #17-302
6 GANG MASONRY BOX
6 GANG MASONRY BOX
CLOCK SYSTEMDUAL POWER SUPPLYDUKANE #17-302
MASTER CLOCKUNIT (ROOM E-16)
ROOM E-16A
CLOCK PROGRAMCONTROL UNIT(ROOM E-16)
DEMOLITION INTERCOM RISER DIAGRAM
RENOVATION INTERCOM RISER DIAGRAM
ICER-5
IC-GATEWAY #5
ICTC-5
GRADE LEVEL
ICTC-4 ICTC-7 ICTC-2
ICER-2
IC-GATEWAY #2
ICTC-17 ICTC-16 ICTC-8
ICTC-9 ICTC-10 ICTC-11 ICTC-15 ICTC-13 ICTC-12
ICER-1
IC-GATEWAY #1
ICER-3
IC-GATEWAY #3
ICER-4
IC-GATEWAY #4
NEW
TO PORTABLES
TO BLDG 1
BLDG 5 BLDG 4 BLDG 7 BLDG 8BLDG 15 BLDG 13
BLDG 12
STC-A
BLDG 16
STC-P
BLDG 17
BLDG 9BLDG 10 BLDG 11
BLDG 2
TO BLDG 3 TO BLDG 1
1" 1"
5. REMOVE EXISTING DUKANE CLOCK SYSTEM COMPLETELY.
6. EXISTING RACEWAYS WHERE NOT BEING REUSED PROVIDE PULL LINE ANDIDENTIFY OPPOSITE END.
17. PROVIDE GROUND BUS BARS IN ICTC.
18. PROVIDE NEW ICTC-3.
21. THIS NOTE NOT USED.
TYP
TYP
TYP
TYP TYP TYP TYP
TYP
TYP
TYP
TYPTYP TYP TYPTYP TYP
BLDG. 13BLDG. 9BLDG. 8BLDG. 2BLDG. 4
ICTC-3
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
Min Floor or Wall
Thkns In. (mm)
Nom Pipe Tube or
Conduit Diam in. (mm)
Max Annular
Space in. (mm)
Min Caulk
Thkns in. (mm)
F Rating
Hr
2-1/2 (64) 1/2-12 (13-305) 1-3/8 (35) 1/2 (13)
2
2-1/2 (64) 1/2-12 (13-305) 3-1/4 (83) 1 (25)
2
4-1/2 (114) 1/2-6 (13-152) 1-3/8 (35) 1/4 (6) (a)
2
4-1/2 (114) 1/2-12 (13-305) 1-1/4 (32) 1/2 (13)
3
4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25)
3
4-1/2 (114) 1/2-20 (13-508) 2 (51) 1 (25)
3
4-1/2 (114) 1/2-12 (13-305) 3-1/4 (83) 1 (25)
3
4-1/2 (114) 22-30 (558-762) 2 (51) 2 (51)
3
5-1/2 (140) 1/2-6 (13-152) 1-3/8 (35) 1 (25) (b)
4
SECTION A-A
142
3
4
A
A
2
EMT THRU CONCRETE PENETRATION DETAIL
SECTION A-A
3
2
31A
1BA
A
EMT THRU GYP BOARD PENETRATION DETAIL
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
EQUIPMENT PHENOLIC LABEL DETAIL
GROUND BUSBAR DETAILFIRE ALARM PULL STATION DETAILGROUND ROD INSPECTION WELL DETAIL
INTERCOM SURGE SUPRESSION SYSTEM TYPICAL INSTALLATION DETAIL
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
DETAIL NOTES:
ALL FIRE ALARM WIRING SHALL BERUN IN 3/4" CONDUIT MINIMUM
FIRE ALARMTERMINALCABINET/
NAC PANELTYPICAL
#6 COPPER TO LOCAL SYSTEMSGROUND BUSBAR IN IDF
120V POWER FOR NFPA-72(PROVIDE SURGE PROTECTIONAT EACH 120V INPUT) (TYPICAL)
NOTIFICATION DEVICE
SS-2
SS-1
SIGNALINGLINE
CIRCUIT
NOTIFICATION APPLIANCE CIRCUIT
SIGNALING LINE CIRCUIT
MUST USE TWO SEPARATE CABINETSFOR CLASS 'A' SYSTEMS
DETAIL NOTES:
MOTOR STARTER SERVING HVAC SYSTEM FAN.
CONTROL MODULE FOR FAN SHUT DOWN. LOCATED WITHIN 36" OFMOTOR STARTER OR VARIABLE FREQUENCY DRIVE.
VARIABLE FREQUENCY DRIVE SERVING HVAC SYSTEM FAN.
CONTROL MODULE SHALL RELEASE THE HOLD-OPEN DOORS UPONACTIVATION OF THE FIRE ALARM SYSTEM. CONTROL MODULE SHALLBE LOCATED ABOVE FINISHED ACCESSIBLE CEILING WITHIN 36" OFDOOR. WHERE CEILING SPACE IS NOT ACCESSIBLE THE CONTROLMODULE SHALL BE FLUSH MOUNTED ON CEILING WITHIN 36" OFDOOR.
120V DOOR HOLD OPEN DEVICE SUPPLIED WITH DOOR HARDWARE.
CONNECT TO ADDITIONAL DEVICES, SEE COMMUNICATIONS FLOORPLANS FOR QUANTITY.
LOCATE MONITOR MODULE WITHIN 36" OF THE FLOW SWITCH ORTAMPER SWITCH IT SERVES.
INITIATING LINE CIRCUIT CONNECTING MONITOR MODULE TOINITIATING DEVICE.
SIGNALING LINE CIRCUIT SURGE SUPPRESSOR AT PIV EXTERIOR TOFACILITY.
SIGNALING LINE CIRCUIT SURGE SUPPRESSOR WITHIN 36" OFENTRANCE INTO FACILITY.
END OF LINE
INITIATING DEVICE
#
EXPOSED RACEWAY AND HARDWARE SECURED TO THE WALL.
SURFACE MOUNTEDSINGLE-GANG DEVICE BOX ANDADDRESSABLE MANUAL PULL STATION
FINISH FLOOR
METALLIC SINGLE-GANG DEVICE BOXWIREMOLD #V5741 SURFACE MOUNTED
AND BLANK IVORY PLASTIC COVERPLATE. MOUNT OVER EXISTING BACK BOX.
FINISH FLOOR
SURFACE MOUNTEDSINGLE-GANG DEVICE BOX ANDAUDIO/VISUAL, AUDIO ONLY OR VISUAL ONLY SIGNALING DEVICE
WIREMOLD #V5741 SURFACE MOUNTED
PLATE. MOUNT OVER EXISTING BACK-BOX.AND BLANK IVORY COVERMETALLIC SINGLE-GANG DEVICE BOX
HARDWARE SHALL MATCH EXISTING WALL FINISHES AS CLOSELYAS POSSIBLE.
2
1 2
2
2
2
1 2WIREMOLD 5000 SERIESMETALLIC SURFACEMOUNTED RACEWAY
HORN/STROBE DEVICE INSTALLATION
FIRE ALARM FLUSH MOUNTED CEILINGRELOCATED FIRE ALARM
ROOFROOF STRUCTURE
LAY-IN CEILING
FINISHED FLOOR
48"
MEA
SURE
MEN
TS S
HOW
NAR
E TO
TOP
OF
BOX
80" A
.F.F
. OR
6" B
ELOW
CEI
LING
, WHI
CHEV
ER IS
LOW
ER, T
O CE
NTER
OF
STRO
BE
ROOFROOF STRUCTURE
FINISHED FLOOR
RELOCATED AUDIO/VISUAL, AUDIOOR VISUAL SIGNALING DEVICE
RELOCATED PULL STATION
LAY-IN CEILING
DEVICE MOUNTING HEIGHTS
FIRE
PULL DOWN
FIRE ALARM
A/C SUPPLYOR RETURNDIFFUSER
3' (MIN)CEILING
4"
4"
NOTE: MEASUREMENTS SHOWNARE TO THE CLOSEST EDGE OFTHE DETECTOR.
12" MAX
SIDE WALL
FINISHED WALL
WALLMOUNTEDSMOKE/HEATDETECTOR
SMOKE/HEATDETECTORSNEVER HERE
CEILING MOUNTEDSMOKE/HEATDETECTOR
5' (MAX.)TO EXIT DOOR
MANUAL PULLSTATION
MAGNETICDOORHOLDER
5"
LESS 3"
DOORWIDTH
48"
MEA
SURE
MEN
TS S
HOW
NAR
E TO
TOP
OF
BOX
FINISHED FLOOR
NFPA 72 AUDIBLE ONLY APPLIANCE 6"MIN BELOW FINISHED CEILING
90" MIN AB
OVE FIN
ISHED FL
OOR
AUDIBLE
ONLY D
EVICES
SYNCHRONIZE MORE THAN TWOAPPLIANCES IN ANY FIELD OF
VIEW.
AUDIBLE/VISUAL & VISUAL ONLYAPPLIANCES
FOR CEILING HEIGHTS LESS THAN 86"THE VISUAL LENS MOUNTING HEIGHTSHALL BE WITHIN 6" OF THE CEILING.
96" MAXABOVE FINISHEDFLOOR TO TOP OFLENS
80" MIN TO
BOTTO
M OF LE
NSFOR
VISUAL A
ND AUD
IBLE/VISU
AL DEVIC
ES
FIREFIRE
60" A
.F.F
. TO
CENT
ER O
F BO
X
ANNUNCIATOR PANEL
TYPICAL FIRE ALARM RISER DIAGRAM CLASS "B" FIRE ALARM DEVICE MOUNTING (PER NFPA 72)
FIRE ALARM DEVICE CONNECTION
TYPICAL PULL STATIONRELOCATION
TYPICAL WALL MOUNTEDNOTIFICATION DEVICE RELOCATION
ALL NOTES MAY NOT APPLY
WIREMOLD 5000 SERIESMETALLIC SURFACEMOUNTED RACEWAY
HORN/STROBEFIRE ALARM DEVICE
FLEXIBLECONDUIT
ELECTRICALBACKBOX
WITH HANGERT-BAR SUPPORT
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION
1/2 SSS1/2 S
36" 36"
4"
1/2 S
S S S S S
36" MAX.
ANYWHERE INTHIS AREA
NOT IN THIS AREA
S = SPACE BETWEEN DETECTORS = SMOKE OR HEAT DETECTOR
S = SPACE BETWEEN DETECTORS = SMOKE OR HEAT DETECTOR
SMOKE OR HEAT DETECTOR SPACINGLAYOUT, SLOPED CEILINGS (PEAKED TYPE)
SMOKE OR HEAT DETECTOR SPACINGLAYOUT, SLOPED CEILINGS (SHED TYPE)
TYPICAL SMOKE OR HEAT DETECTOR CEILING LOCATIONS
GAS SHUTDOWN DETAIL
FIRE ALARM MATRIX
FIRE ALARM SYSTEM SURGE SUPPRESSION SYSTEM TYPICAL INSTALLATION DETAIL
MEP CONSULTING ENGINEERSENGINEERING
CA-00006208935 Lake Baldwin Lane
Orlando, Fl. 32814Tel: 407-767-5188Fax: 407-767-5772
www.sgmengineering.comCopyright © 2017 SGM Engineering, Inc.
SGM
INC
.
SGM #: 2016-186
02-17-18 BID AND CONSTRUCTION