  • ABB GroupNovember 27, 2015 | Slide 1

    Current developments inHigh-voltage switchgearSome examples

    Dr. Walter Holaus, Global Product Manager, ABB Switzerland. 25.11.2015

    SF6 free high-voltage GIS installation in Zrich, CH.

  • ABB GroupNovember 27, 2015 | Slide 2

    Different types of high-voltage switchgearGIS Hybrid PASS DTB - LTB

    GIS Hybrid PASS DTB

    all voltage levels all components encapsulated most compact

    busbar in air include DS, ES, CT busbar in air

    focus on USA market complete shipment no FAES, DS, ES

    LTB all voltage levels no grounded enclosures

  • ABB GroupNovember 27, 2015 | Slide 3

    Current developments in high-voltage switchgear

    Lower environmental impact over lifetime

    PD sensor optimization using powerful simulations

    Pulsed X-ray Induced Partial Discharge Measurement forroutine testing

    Multi-functional modules: A substation on a trailer

    Motor drive to operate HV circuit breakers

    Products for new voltage levels

    SF6 replacement with alternative gases

    Examples by ABB

  • ABB GroupNovember 27, 2015 | Slide 4

    Design for lower environmental impact over lifecycleExample: 420 kV GIS

  • ABB GroupNovember 27, 2015 | Slide 5

    Optimization of PD sensors

    PD sensors are used to measure & monitorPD activity inside a GIS

    Shape and design of the sensor determinesthe output signal

    Optimization improves sensor voltageoutput over a wide frequency range

    Electromagnetic simulations

    0 1 2 3 4 5 6 7 8 9 10

    x 108

    -70

    -65

    -60

    -55

    -50

    -45

    -40

    -35

    -30Model 3Model 4Model 5Model 6Model 7

    Frequency (Hz)

    Sen

    sorv

    olta

    ge(d

    B)

    Model 7

    PD sensor Optimized model

    From: Smajic, Elektromagnetische Analyse und Optimierung des neuen TE-Sensors, Rapperswil, 19 Dezember 2013.

  • ABB GroupNovember 27, 2015 | Slide 6

    Pulsed X-ray Induced Partial Discharge (PXIPD)High voltage pre-testing of insulators

    Automated test facility for spacers

    Checks for invisible voids inside the insulationmaterial that may create failures during lifetimeof a GIS.

    Cycle time < 7 min / insulator.

    HV-transformer

    PXIPD insulationpretesting

    LifetimeD

    iele

    ctric

    stre

    ss

    IEC test voltage

    Fina

    lDie

    lect

    ricTe

    st Comparison of HVtest methods

  • ABB GroupNovember 27, 2015 | Slide 7

    Multi-functional modules245kV substation on a single trailer

    MV Transformer HV: Assembled and tested in factory.

    Designed for easy transportation and installation

    A solution for rapid or temporary electricity distribution

  • ABB GroupNovember 27, 2015 | Slide 8

    Motor drive for HV products

    Motor with digitally controlled motion to operate HV circuit breakers.

    Smart Human-Machine Interface (HMI) to visualize: Single Line Diagrams, System status, operation counter, temperature, ..

    Compact motor size. Scalable energy storage up to 4 kJ

    Simple configuration and data upload Configurable interlocking function

    Torque limitation

    Available for LTB and PASS products SPO and TPO: 72.5 kV - 245 kV

    Digital interfaces: IEC 61850-8-1 (MMS) IEC 61850-9-2 (GOOSE)

    A smart drive, IEC 6150 enabled

  • ABB GroupNovember 27, 2015 | Slide 9

    Products for new voltage levels

    Ultra-high voltage applications requested for super grids

    800 kV network is rapidly expanding in china, india

    1100 kV network is rapidly expanding in china

    1200 kV network is under site testing in india

    Rated voltage: 800 kV, 1100 kV, 1200 kV

    ABB GroupNovember 27, 2015 | Slide 91100kV substation Jingmen, China. Commercial operation since 2009

  • ABB GroupNovember 27, 2015 | Slide 10

    Modeling & simulation of very fast transients GISExample: Disconnector switching @1100 kV

    See: J. Smajic, W. Holaus, J. Kostovic, U. Riechert, 3D Full-Maxwell Simulations of Very FastTransients in GIS, IEEE Transactions on Magnetics, Vol. 47, No. 5, pp. 1514-1517, May 2011.

  • ABB GroupNovember 27, 2015 | Slide 11

    1200 kV DTB for Powergrid, IndiaBINA substation. Energized 2014. One phase DTB for test installation at

    BINA 1200 kV SS Assembly and routine tested in ABB India PD sensors to allow PD measurement

    and localization Installation done for CIGRE UHV

    conference 2013

  • ABB GroupNovember 27, 2015 | Slide 12

    Main characteristics

    Rated voltage 145 kV

    Rated frequency 50 Hz

    Rated short-circuit current 31.5 kA

    Capacitive switching factor 1.4

    Rated current 3150 A

    Ambient temperature -50 C

    Tested according to IEC 62271-100

    SF6 free circuit breaker 145 kV, 31.5 kA

    Product release for reduced ratings

    72.5/84 kV, 31.5kA, -50C, LTB+DCB, CO2

    Pilot installation with CO2 gas

    Ratings:

    Pilot installation since 2010