Seminar
-
Upload
aliyu-aliyu -
Category
Documents
-
view
78 -
download
0
Transcript of Seminar
Cyprus International University 1
CORONA PHENOMENON AND CORONA LOSS CALCULATION IN TRANSMISSION LINES
ALIYU ALIYU
Outline
Introduction
How corona discharge effect occur
Factors affectıng corona discharge effect
Advantages and disadvantages of corona
Methods of reducing corona discharge
Calculation on power loss due to corona discharge
Conclusion
Cyprus International University 2
Introduction What is corona?
Where do we find corona ?
At what voltage level do corona occur ?
Cyprus International University 3
Corona discharge effect
Ionization of air
Produces sound
Produces bluish glow on the conductor
Produces ozone gas
Reduces efficiency
Cyprus International University 4
How corona discharge occur
Cyprus International University 5
Factors affecting corona discharge effect
Conductor
Line Voltage
Atmosphere
Spacing between the Conductors
Cyprus International University 6
Advatages of corona
Corona reduces the effects of transientsproduced by surges.
Due to corona formation, the airsurrounding the conductor becomesconducting and hence virtual diameter ofthe conductor is increased. The increaseddiameter reduces the electro-static stressesbetween the conductors.
Removal of unwanted volatile organics,such as chemical pesticides, solvents, orchemical weapons agents, from theatmosphere.
Cyprus International University 7
Disadvanges of corona
Ozone is produced by corona and may cause corrosion of the conductor due to chemical action.
Corona is accompanied by a loss of energy. This affects the transmission efficiency of the line.
The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal Voltage drop occurs in the line. This may cause inductive interference with neighboring Communication lines.
Cyprus International University 8
Methods of reducing corona
By increasing the spacing between the conductors
By increasing the diameter of the conductor
By using Bundled Conductors
Cyprus International University 9
Power loss due to corona
P = 𝟐𝟒𝟐.𝟐
𝜹𝑭 + 𝟐𝟓
𝒓
𝒅𝑽 − 𝑽𝒄
𝟐 × 𝟏𝟎−𝟓 KW/Km/Phase
Where
P = corona loss
𝛿= air density factor
𝐹= frequency
r= conductor radius in cm
d= conductor spacing in cm
V= supply voltage per phase
𝑉𝑐= disruptive critical voltage
Cyprus International University 10
Power loss due to corona
Disruptive critical voltage is given as
𝑽𝒄= 𝒎𝟎×𝒈𝟎𝛿r𝐥𝐧𝒅
𝒓KV
Where
𝑚0= irregularity factor
𝑔0=dielectric strength of air
𝛿=air density
t= temperature
Where
𝛿=3.92×𝑏
273+𝑡
Cyprus International University 11
Question
A three phase 220KV transmission line consist of 1.5cm radius conductor spaced 2m apart in equilateral triangle formation. If the temperature is 40 degree Celsius and the atmospheric pressure is 76cm. Calculate the corona loss per KM of the line. Take 𝑚0= 0.85 and 𝑔0=21.2KV per cm.
Cyprus International University 12
Summary
In summary, to reduce corona loss in transmission lines the critical breakdown voltage should be increased by adding the diameter of the conductors, increasing the spacing between the conductors and using bundled conductors instead of the normal conductor.
Cyprus International University
13
References
Y. Nie, Y. Wen, C. Liu, X. Yin, M. Mao, Z. Tian, C. Peng, and J. Yin,“Thestudy of the corona current characteristics of transmission lineinsulators,” inProc. Int. Elect. Insulating Materials Conf., 2001.
Y. Cheng, C. Li & X. Huang, Study of corona discharge pattern on high voltage transmission line for inspecting faulty proceleın insuator.
Power System Analysis, By VK Mehata, AK Mehta.
Li Chengrong, S. Qian, C. Yangchun, H. Xingquan, and S. Wei, “Thesensitivity of identifying faulty insulator strings by detecting insulatorcorona current,” in Proc. Int. Electrical Insulating Materials Conf.,1998.
Cyprus International University 14
Thank You
Cyprus International University 15