Semi-Instantaneous Indirect Fired Water Heater n Co l d W ater n To Drain To Drain Dra n Dr n 6 n Bo...
Transcript of Semi-Instantaneous Indirect Fired Water Heater n Co l d W ater n To Drain To Drain Dra n Dr n 6 n Bo...
MODEL BWX
Semi-Instantaneous Indirect Fired Water HeaterUse Boiler Water Or HTHW To Heat Domestic Water
Model BWX Semi-Instantaneous Type
The Model BW is equipped with all operating controls and ready for immediate installation
ASME
UA Heavy Duty Indirect Fired Water HeaterTheModelBWXisafullypackagedindirectfiredwaterheaterwhichutilizesboilerwaterorhightemperaturehotwater(HTHW)astheenergysourceforheatingpotablewater.Theentirepackageisdesignedtobeareliableandlonglastingsourceforhotwater.Eachcomponentiscarefullyselectedtoensurehighperformanceineventhemostdemandingapplication.
Whetheryouareheatingpotablewaterinacommercialbuildingorprocesswaterinanindustrialapplication,youcanselectaHubbellBWXmodeltodothejob.WhenyouspecifyandinstallaHubbellwaterheater,youwillbeprovidedwithaqualityproductthatisalonglastingandtroublefreesourceforhotwater.
Features■ Reliable
� Onlyhighgradematerialsusedinconstructiontoensurelongoperatinglife
� Hydrastonecementliningprovidessuperiorprotectionandtanklongevity
� Heavydutyconstructionwithstandsdemandingcommercial/industrialuse
■ Packaged System� Factoryselectedandsizedboilerwater
controlvalvesimplifiesinstallationandensuresreliableoperation
■ Versatile� Fullrangeofstyles,sizes,andoptional
featurestomeetyourexactheatingneeds
� Compactdesignrequiresminimalfloorspace
Applications■ Schools■ OfficeBuildings■ SportsVenues■ Hotels
■ IndustrialFacilities■ NursingHomes■ Hospitals
A Packaged Water Heater Ready For Installation
2
Model BWX Semi Instantaneous Standard Equipment
Optional Equipment
Heating Coil4. Doublewalltubingwithaleakdetectionport
5. Alternatetubingmaterialpleasespecify:(StainlessSteel,90/10Copper-Nickel,Admiralty)
6. Fabricatedheadconstructedfrom:(StainlessSteel,CopperAlloy)
Vessel Construction1. Designed andbuiltinstrictaccordancewith
theASME CodeSectionVIIIandstamped,certified,and registeredwiththeNationalBoardofBoiler andPressureVesselInspectors
2. Designedfor150psiworkingpressureandhydrostaticallytested
Heating Coil1. Factorysizedandinstalledcopperheatingcoil
withagenerouslysizedheatingsurfacedesignedtoensurereliableoperation
2. U-Tubeheatingcoilconstructedfromsinglewallcoppertubingdesignedforamaximumworkingpressureof150psi
3. HeavydutyfabricatedsteelheadwiththreadedNPTinletandoutletconnections
4. Allwettedpartsarenon-ferrousformaximumlongevity
5. Non-Ferroustubesheet
Boiler Water Operating Controls1. Operatingcontrolsarefactoryselected,sized,
piped,andtestedtoensurereliableoperation
2. Allcomponentsarefactorypipedandreadyforboilerwaterinandoutconnections
3. Modulatingcontrolvalve(2-way,3-way)toregulatetheflowofheatingwaterthroughthecoil.Modulatingcontrolvalvetobe(electric,pneumatic)powered
4. Allbronzeintegralcirculatingpump
5. Directmountedboilerwateranddomesticwatertemperatureandpressuregauges
6. HighlimitSinglesolenoidsafetysystemclosestheboilerwatersupplytotheheatingcoilshouldthewatertemperatureinthetankreachthehi-limitsetpoint.Requires120volt5ampelectricalservice
General1. Heavydutyfiberglassinsulationformaximum
operatingefficiencyandminimalstand-byheatloss
2. Heavygaugepaintedgalvanizedsteelprotectiveouterjacket
3. Heavydutyintegrallyweldedsteelsupportsforfloormounting
4. Fullfive(5)yearNonPro-Ratedtankwarrantyandaone(1)yearcomponentwarranty
5. ASMEratedcombinationT&Preliefvalvesetatthetankworkingpressureand210oF
Vessel1. Alternatevesselconstruction:
StainlessSteelType304or316L,galvanizedsteel or 90/10 Copper-Nickel
2. Alternateworkingpressure:Pleasespecify
3. HorizontalConstruction
Operating Controls8. Boilerwatercontrolvalvecanbefactory
selectedandsized,butshippedlooseforinthefieldinstallationbyothers
9. Adoublesolenoidsafetysystemdumpsoverheatedwaterinthepressurevesseltodraininadditiontoclosingtheboilerwatersupplytotheheatingcoil.Requires120volt5ampelectricalservice.
NOTE:Otheroptionalfeaturesareavailable,pleaseconsultfactoryifrequired.
General7. Type304stainlesssteelprotectiveouter
jacket,pleasespecifyifpainted.
Heating Chamber:
3
Vertical Dimensions (inches)Model No. Based on 100˚FΔT Recovery Rate (40-140˚F)
Note:Alldimensionsareapproximateandsubjecttochange.Pleasereferencethesubmittaldrawingforactualdimensions.Pleaseconsultfactoryforrecoveryratingsforboilerwatertemperaturesnotshown.
Liters x 0.2641 = Gallons
Gallons x 3.79 = Liters
Gallons x 0.003785 = m3
m3 x 264.2 = GallonsOC∆T = 1.8OF∆T1
OF = (OC x 1.8) + 32OC = (OF - 32) x 0.556
psi x 0.06896 = Bar
Bar x 14.5 = psi
psi x 6.86 = kPa
kPa x 0.1456 = psi
Lbs x 0.4536 = Kg
Kg x 2.2 = Lbs
ft2 x 0.0929 = m2
m2 x 10.765 = ft2
Metric Conversion
Base ModelRecovery
Rating (GPH) 40-140°F
BTU/HrBoiler Water
Entering & Exiting Temperatures (°F)
Vertical Model BWX Overall Dimensions (inches)Weight (Lbs)
Single Wall Double Wall
A B C D E A B C D E
BWX-600 600 500,000180-160°F 88 41 28 15 21 101 47 34 17 23 810
200-180°F 88 40 29 13 19 100 47 34 15 21 655
BWX-900 900 750,000180-160°F 100 47 34 15 21 90 42 27 19 25 850
200-180°F 76 35 22 15 21 89 41 28 17 23 770
BWX-1200 1200 1,000,000180-160°F 100 47 34 15 21 102 48 33 19 25 850
200-180°F 88 41 28 15 21 89 41 28 17 23 810
BWX-1500 1500 1,250,000180-160°F 89 41 28 17 23 102 48 33 19 25 1035
200-180°F 88 41 28 15 21 101 47 34 17 23 810
BWX-1800 1800 1,500,000180-160°F 89 41 28 17 23 108 49 39 20 27 1035
200-180°F 77 35 22 17 23 101 47 34 17 23 985
BWX-2400 2400 2,000,000180-160°F 101 47 34 17 23 108 49 39 20 27 1090
200-180°F 77 35 22 17 23 90 42 27 19 25 985
BWX-3000 3000 2,500,000180-160°F 90 42 27 19 25 111 30 39 22 31 1195
200-180°F 78 36 21 19 25 102 48 33 19 25 1130
BWX-3600 3600 3,000,000180-160°F 90 42 27 19 25 111 50 39 22 31 1195
200-180°F 78 36 21 19 25 96 43 33 20 27 1130
BWX-4200 4200 3,500,000180-160°F 90 42 27 19 25
200-180°F 78 36 21 19 25 108 49 39 20 27 1130
BWX-4800 4800 4,000,000180-160°F 96 43 33 20 27
200-180°F 84 37 27 20 27 99 44 33 22 31 1480
BWX-6000 6000 5,000,000180-160°F 99 44 33 22 31
200-180°F 99 44 33 22 31
4
Outline Dimensions - Model BWXH (Horizontal)
Indirect-Fired Semi-Instantaneous
Outline Dimensions - Model BWX (Vertical)
Indirect-Fired Semi-Instantaneous
Hot Water Outlet
Protective JacketT&P Relief Valve
Thermometer
Hi-Limit ThermostatPump Switch
Pressure Gauge
Cold Water Inlet
Recirculation Pump
Temperature Controller
Hi-Limit Solenoid Valve
Control Valve
Drain
D
E
A
B
C
Insulation
Hot WaterOutlet
TOP VIEW
ProtectiveJacket
Thermometer
Pump Switch
Cold WaterInlet
Recirculation Pump
TemperatureController
Drain
Insulation
Withdrawal�Space
Hi-Limit Thermostate
END VIEW
T&P Relief Valve
Pressure Gauge
Control Valve
Hi-LimitSolenoid Valve
5
Boiler Wat
e
e
t
r
u
S
rn
upply
Boiler Water R
Bypass Line if 3-Way Valve
To Drain
Boiler Water R
eturn
Boiler Water S
upply
Hot Water O
ut
Recirculation
Cold Water In
Drain
Piping Layouts
SINGLEUNIT
DUALUNIT
Hot Water Out
RecirculationCold Water In
To Drain
To Drain
Drain
Drain
6
Boiler Water R
eturn
Boiler Water Supply
Hot Water Supply
Recirculation
Hot Water Out
Drain
Cold Water InSt T
oar na kg
e
Hot Water Return
To Drain
To Drain
SINGLEUNITWITHSTORAGETANK
Strainer
Stop Valve
Check Valve
Control Valve
Relief Valve
Thermal Element
Pressure Gauge
Temperature Gauge
Circulator
Expansion Tank
LEGEND
Piping Layouts
Access Panel Side View
−
7
Formulas
Note: A minimum 10 oF differential (∆T)between the exiting boiler water temperature and the exiting domestic hot water temperature is requiredto maintain efficient heat transfer rates. For detailed information regarding the heating coil, please reference the Hubbell brochure titled “Hubbell Heating Coils”.
DomesticWaterGPHHeated
DomesticWateroF∆T
x 0.01666 x= GPMBoilerWaterRequired
BoilerWaterDropoF∆T
ToDetermineTheBoilerWaterFlowRateRequired
ToDetermineMaximumDomesticWaterRecoveryRate
BoilerWaterGPM
BoilerWaterDropoF∆T
x 60 x= GPHDomesticWaterHeated
DomesticWaterRiseoF∆T
Ihave30GPMof200oFboilerwaterthatIcantakedownto160oF.HowmanyGPHofdomesticwatercanIheatfrom40-140oF?
Iwanttoheat950GPHfrom40-140oFwith180oFboilerwaterthatIcantakedownto160oF.HowmuchboilerwatermustIhaveavailable?
1582.7950 x .01666 x (140-40)180-160 20
Examples
A. B.
79GPMofBoilerWater
7200030 x 60 x (200-160)
140-40 100
= = =
Option NoteAny and all optional equipment for a water heater must be called out in the written specifications. A model number in and of itself does not reflect any optional equipment selected.
Example:BWXCN-3600S A vertically installed semi-instantaneous indirect fired water heaterwith a 90/10 Copper-Nickel pressure vessel and single wall heating coil rated to heat 3600 GPH at a 100oF temperature rise.
■ Step 2 Vessel Type:CN =90/10 Copper-NickelSS =Stainless Steel (Specify Type)M =Galvanized Steel
■ Step 1 Model:BWX = Vertical BWXH = Horizontal
■ Step 3 Recovery Rating:In GPH at 100oF ∆T
BWX Model Number Designation
—
■ Step 4 Coil Type:S = Single Wall D = Double Wall
Model Number Designation
720GPHDomestic Water
=
GENERALProvideaquantityof_________semiinstantaneousindirectfiredwaterheater(s),ModelNo.___________________________asmanufacturedbyHUBBELLElectricHeaterCo.,Stratford,CT.Thepressurevesselshallbemountedonstructuralsupportsandbesuitablyinsulated,jacketedandpainted.Theentireunitistobepackagedreadyforserviceconnections.
PRESSURE VESSELThepressurevesselsectionshallbeconstructedfrom304 Stainless Steel material.( OptionalSpecification:90/10copper-nickel or316Lstainlesssteel,Hotdippedgalvanizedsteel).Vesselwillbestampedfor150PSIunderSectionVIIIoftheASMECode.Manufacturer’sdatareportandU-1formsshallbefurnishedtotheowner.Nooverheadclearanceshallberequiredforservicingorremovingtheheatingcoil.Eachheatershallbedesignedtoheat________GPH(______GPM)ofdomesticwaterfrom_______to_______oFwhensuppliedwith______GPMofboilerwaterenteringat_______oFandexitingat_______oF.
OptionalSpecification:Doublewall) Coppertubes,( OptionalSpecification:Stainlesssteel,90/10copper-nickel,admiralty)non-ferrousbafflesandacopper-linedtubesheet.Theheater shallhaveitstemperaturecontrolbulblocatedfordirectsensingofwater.
CONTROLSThewaterheatercontrolsshallbefactoryassembledandpiped.Amodulatingcontrolvalveshallbea(Specify:2-wayor3 way) type,(Specify:PneumaticorElectric)powervalve.Solenoidcontrolvalveswillnotbeaccepted.
• Allbronzeintegralcirculatingpumpwithcopperpipingandisolationvalves• Directmountedboilerwaterandthermometergauges• Highlimitsafetysystem• ASMEratedtemperatureandpressurereliefvalve• Fiberglassinsulationwithpaintedmetaljacket
OPTIONSInaddition,thewaterheatershallbesuppliedwiththefollowingoptionalfeatures:
Option
Option
Option
WARRANTYThewaterheatermanufacturershallwarrantyallcomponentsagainstdefectsinWorkmanshipandmaterialforaperiodofone(1)yearfromdateofstart-upandthepressurevesselforafullfive(5)yearsNonPro-Rated( OptionalSpecification:fullten(10)yearsNonPro-Rated)fromdateofstart-up,providedthattheunitisstartedwithinthree(3)monthsofdateofshipmentandinstalledandoperatedwithinthescopeoftheheater’sdesignandoperatingcapability.Eachwaterheatershallbeshippedwithacompletesetofinstallationandoperatinginstructionsincludingasparepartslistandapproveddrawing.
JOBNAME
REPRESENTATIVE
ENGINEER
CONTRACTOR
Master Specification: Model BWX
HEATING SECTIONThe heating coil shall be fabricated with single wall
The Electric Heater Company ■ P.O. Box 288 ■ Stratford, CT 06615-0288 ■ Phone: 203-378-2659 ■ Fax: [email protected] ■ www.hubbellheaters.com
Committed to continuous improvement...Continuing research results in product improvement; therefore specifications are subject to
change without notice. For the most updated information, consult the factory directly.
Each heater shall be factory packaged with the following components: