CE1N2265en20.08.2002
Siemens Building TechnologiesHVAC Products
2265
REV23RF REV-R.02/1
REV23RF/SET
Self-learning RoomTemperature Controller REV23RFReceiver REV-R.02/1Consisting of controller (with integrated radio transmitter) and receiver(switching unit with relay outputs)
• Mains-independent room temperature controller• Straightforward, self-explanatory menu selection via roller selector• Self-learning 2-position controller providing PID mode (patented)• Choice of operating modes:
Automatic with maximum 3 heating or cooling periods, continuously comfort,continuously economy, frost protection with one 24-hour operating mode in-cluding one heating or cooling period
• In automatic mode, one temperature setpoint can be entered for each heatingor cooling period
• Optional control of cooling equipment• Advantageous for retrofitting and upgrading projects
(wireless room unit)
Use
For control of the room temperature in:• Apartments, single-family or holiday houses• Offices, individual rooms, consulting rooms or commercially used spaces
For control of the following pieces of equipment:• Solenoid valves of instantaneous water heaters
2/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
• Solenoid valves of atmospheric gas burners• Forced draft gas or oil burners• Circulating pumps of heating systems, zone valves• Electric direct heating systems or fans of electric storage heaters• Thermal actuators• Cooling and refrigeration equipment
Functions
• Radio signal transmission• PID control with self-learning or selectable switching cycle• 2-position control• Automatic mode with 7-day switching program for 24-hour, working day, weekend or
7-day operation with up to 3 heating or cooling periods per day• Each heating or cooling period has its own temperature setpoint• One 24-hour operating mode with one heating or cooling period• Override button• Sensor calibration and reset function• Frost protection or overtemperature protection• Limitation of the minimum setpoint• Holiday mode• Heating or cooling mode• Periodic pump run• Optimum start control with the first heating period
Type summary
Radio signal equipment consisting of:Room temperature controller (transmitter), receiver (switching unit)and support REV23RF/SETRoom temperature controller (transmitter) and support REV23RFReceiver (switching unit) REV-R.02/1
Ordering
When ordering, please give the type references according to «Type summary».The controller / transmitter REV23RF is supplied complete with batteries.
Technical design
Display andoperating elements
3/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Operating elements
Selection of operating mode (see below)
«Warmer» button
«Colder» button
Override button (see below)
Roller selector for the menu, submenu and the settings
Confirm by pressing
Leaving the current menu level and returning to the menu levelpreviously active (settings currently displayed will be ac-cepted)
Displays
Time of day
° C Room temperature
Change batteries (display appears about 3 months before bat-teries are exhausted)
Holiday mode active
Selection of operating mode (only one operating mode active)
Automatic mode
Comfort mode
Economy mode
Frost protection or overtemperature protection24-hour mode with one heating or cooling period(heating or cooling period is automatically generated from thecurrent 24-hour program)
Temporary change of the current setpoint temperature(change only active until the next switching point is reached)
° CPress the + or – button once to display the adjusted tempera-ture setpoint. It can be readjusted in increments of 0.2 °C (max.+/- 4 °C)
Override buttonIn operating modes and , this button can be used to manually switchfrom comfort to economy temperature, or vice versa. The selection is automati-cally reset when the next switching point is reached or when the operatingmode is changed
4/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Menu-driven user settings: 4 main menus are available
Time of day and weekday Main menu Submenu Settings
h Current time
Current weekday
Temperature Main menu Submenu Default settings – heating / cooling
T Setpoint of comfort mode 19 °C 23 °C
Setpoint of economy mode 16 °C 29 °C
Setpoint frost orovertemperature protection 5 °C 35 °C
Setpoint remote operation isnot used with this unit (10 °C) (30 °C)
Time switch Main menu Submenu Settings
Selection of weekday, working day,weekend or weekSelection of the number of heatingor cooling periods (max. 3 periodsper day)
h
Selection of the heating / cooling period’s start and end time
° CT
Selection of the heating / cooling period’s temperature setpoint
Absence Main menu Submenu
Entry of holidays or periods of absence. Numberof days with economy mode setting / max. 99days
Temperature setpoint during absence.Default setting is 12 °C for heating and 30 °C forcooling
5/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Menu-driven heatingengineer settings Menu items Settings
CAL Sensor calibration
Setpoint limitation
Optimum start control for the first heating period(in unit of time per 1 °C)
2-position control
PID mode, self-learning
PID mode, switching cycle 6 or 12 minutes
/ Periodic pump run off / on
Heating / cooling mode
In automatic operating modes, the temperature setpoints can be individually adjustedfor every comfort period and for the continuous operating modes. The temperaturesetpoint of economy mode is the same in automatic and continuous operation.
In frost or overtemperature protection mode, the room temperature is constantly moni-tored. If it falls (rises) below (above) the adjusted setpoint, control to the adjusted frostor overtemperature protection setpoint will be ensured.
The controller generates the 24-hour operating mode from its current 24-hour program.It automatically selects the switch-on time of the first heating / cooling period and theswitch-off time of the last heating / cooling period to generate and display a completeheating / cooling period. The comfort setpoint used by the controller is the currentlystored standard setpoint of continuous operating mode . The self-generated 24-houroperating mode is maintained until another operating mode is selected.
2264
Z01
°C
18
20
22
08 10 18 22 h
T
T
Automatically generated 24-hour switching program when 24-hour 24-hour operating mode operating mode is activated
Temperaturesetpoints
Protective function
24-hour operatingmode
Example
6/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
The switching program can be used as a 7-day or 24-hour program, depending onprogramming. It is also possible to select one of the continuous operating modes
with which the switching program is not used.
With the 7-day program, all individual days, working days (1-5), weekend (6-7), or theentire week (1-7) can be programmed.For each heating / cooling period, 3 different switching patterns are available.There is a choice of 1, 2 or 3 heating / cooling periods. For each heating / cooling pe-riod, the start time, end time and comfort setpoint are to be entered.In between heating / cooling periods, it is always the same economy temperature set-point that is used. This economy temperature setpoint can be adjusted on the tem-perature menu.
2261
Z02
16
°C
18
20
22
08 10 18 22 h
Heizphase 1
Heizphase 2
The holiday function is to be selected on the user menu. Set the start of the holidayperiod (day of departure / / weekday), the duration of the holiday period andthe temperature setpoint ( ). This will enable the controller to maintain the adjustedtemperature for a period of up to 99 days. Every day at midnight, the counter subtractsone day.When the holiday period is over, the counter reads 00, and the controller will automati-cally resume the operating mode selected last.
To be flexible, the REV23RF has no connection facility for remote operation.
Switching times Temperatures in ° C
1stperiod
2ndperiod
3rdperiod
Oper-atingmode
Block /week-days 1st period 2nd period 3rd period
Auto1-5
Mo-Fr6-7
Sa-Su
06:00
07:00
08:00
23:00
11:00 13:00 17:00 22:00 19
19
23
23
20 23 21 23 16
16
29
29
1-7Mo-Su
00:00 24:00 19 23
1-7Mo-Su
00:00 24:00 16 29
1-7Mo-Su
00:00 24:00 5 35
Absence 12 30
Switching program
Example with 2 heatingperiods per day
Holiday function
Remote operation
Factory settings
7/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Setpoint limitation
PID mode, self-learning
Optimum start control
Periodic pump run off
Heating active
Heating engineer level
To access the heating engineer level, keep the «Warmer» and «Colder» buttons de-pressed and simultaneously roll the roller selector away from the display and then to-ward the display.
If the displayed temperature does not agree with the room temperature effectivelymeasured, the temperature sensor can be recalibrated (recalibration to be made on theheating engineer level.)The displayed temperature can be matched to the effective room temperature in incre-ments of 0.2 °C (max. ± 2 °C).Minimum setpoint limitation to 16 °C prevents undesired heat transfer to neighboringapartments in buildings with several heating zones. The setting is to be made on theheating engineer menu.
Optimization brings forward the switch-on point of the first heating period such that theadjusted setpoint will be reached at the required time.The setting depends on the type of controlled system, that is, on heat transmission(type of piping system, radiators), building dynamics (building mass, insulation), andheat output (boiler capacity, flow temperature).
Optimum start control is switched off at
t
T
17
18
19
- 4 - 2
2264
D03
16
- 3
1/4h/°C1/2h/°C
1h/°CStart
- 2 - 1 - ½- 1½- 1 - ½ - ¼- ¾
Pon
20°C
- 1 h h h
TRx
hhh
hhh
hhh
1st heating period
(slow controlled system)
(medium controlled system)
(fast controlled system)
(no impact)Optimum start controll Off
T
T Temperature (°C) TRx Actual valve of room temperaturet Forward shift of switch-on point (h) Pon Starting point of optimum start control
REV23RF is a 2-position controller providing PID mode. The room temperature is con-trolled by the cyclic switching of an actuating device.
Factory settingsHeating engineer level
Access
Sensor calibration
CAL
Setpoint limitation
Optimum start control
Example using an actualroom temperature of 18 °Cand a setpoint of 20 °C
Control
8/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
The controller generates the positioning signals depending on the deviation of the set-point from the actual value acquired by the built-in temperature sensor.The rate of response to the deviation depends on the selected control algorithm:The controller is supplied with an active self-learning mode, enabling it to automaticallyadapt to the type of controlled system (building construction, type of radiators, size ofthe rooms, etc.). After a certain learning period, the controller optimizes its parametersand then operates with the parameters it has learned.In exceptional cases, where the self-learning mode may not be ideal, it is possible toselect PID 12, PID 6 or 2-Pt mode:
PID 12 mode Switching cycle of 12 minutes for normal or slow controlled systems(massive building structures, large spaces, cast-iron radiators, oilburners).
PID 6 mode Switching cycle of 6 minutes for fast controlled systems (light buildingstructures, small spaces, plate radiators or convectors, gas burners).
2-Pt mode Pure 2-position control with a switching differential of 0.5 °C (±0.25 °C)for very difficult controlled systems with considerable outdoor tem-perature variations.
Protects the pump against seizing during longer off periods. Periodic pump run is acti-vated for one minute every 24 hours at midnight. This function can be selected on theheating engineer menu.
Periodic pump run active: / periodic pump run inactive:
The controller is suited for cooling applications.The function can be selected on the heating engineer menu.The controller comes set for heating operation (refer to section «Factory settings»).
User-defined data:Press the button behind the pin opening for at least one second: This resets the user-specific settings to their default values (heating engineer settings will not be changed).The clock starts at 12:00. During the reset time, all sections of the display are lit, ena-bling them to be checked.
All user-defined data plus the heating engineer settings:Press the button behind the pin opening together with the warmer and colder buttonsfor at least one second.After the reset, all factory settings will be reloaded (also refer to section «Factorysettings»).
Mechanical design
The REV23RF has a plastic housing with a large display and easily accessible operat-ing elements. The controller is removed from its base by sliding it upward. It is thuspossible to replace the two type AA 1.5 V alkaline batteries contained in the compart-ment at the rear of the controller.About 3 months before the batteries are exhausted, battery symbol appears onthe display, but all functions are fully maintained. When replacing the batteries, thecurrent data will be retained for a maximum of one minute.
Plastic housing with easily accessible operating elements and removable cover. Theunit can be fitted to all commercially available recessed conduit boxes or directly on thewall. A relay with a potentialfree changeover contact, the connection terminals and thereceiving antenna are integrated in the housing.
Self-learning mode
Exceptions
Periodic pump run
/
Operating modeHeating / cooling
/
Controller
Battery change
ReceiverREV-R.02/1
9/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
The base can be fitted to most types of commercially available recessed conduit boxesor directly on the wall.
The support supplied with the controller enables the unit to be put on a shelf. It can beeasily fitted to the controller with no need for tools.
Notes
• The room unit should be located in the main living room (on the wall or free-standingusing the support provided) while giving consideration to the following points:
• The distance to the receiver should not exceed 20 m or 2 floors• The unit should be located such that the sensor is able to capture the room tem-
perature as accurately as possible, without getting affected by direct solar radiation orother heat or refrigeration sources (in the case of wall mounting, about 1.5 m abovethe floor)
• The unit should be located such that it can transmit signals with as little interferenceas possible. For this reason, the following points should be observed:− Do not mount the unit on metal surfaces− Not in the vicinity of electrical cables and equipment such as PCs, TV sets, mi-
crowave appliances, etc.− Not in the vicinity of large metal structures or construction elements with fine
metal meshes like special glass or special concrete• In the case of wall mounting, ensure that there is sufficient clearance for removing the
controller from its base, and for replacing it
min. 10 cm
2261
Z03
• The receiver and switching unit should preferably be mounted near the controlleddevice
• The unit should be located such that it can receive signals with as little interferenceas possible. For this reason, the following points should be observed (same as withthe transmitter):− Not in control panels− Not on metal surfaces− Not in the vicinity of electrical cables and equipment such as PCs, TV sets, mi-
crowave appliances, etc.− Not in the vicinity of large metal structures or construction elements with fine
metal meshes like special glass or special concrete• The location where the unit is mounted should be dry and free from splash water• The unit can be fitted to most commercially available recessed conduit boxes or di-
rectly on the wall
• First, fit the base. Then, engage the controller from the top. The base can be fitted tomost commercially available recessed conduit boxes or directly on the wall
Base
Support
PlanningController /transmitter REV23RF
Wall mounting
PlanningReceiverREV-R.02/1
Wall mounting ofcontroller / transmitterREV23RF
10/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Refer to the Installation Instructions printed on the package.
The receiver must be wired with the power supply switched off.Mains voltage may be switched on again only after the unit is completelymounted.
• When mounting the unit, the base must first be fitted and wired (L/N = AC 230 Vmains supply, LX/L1 = consumers). Then, engage the unit at the top, swing it down-ward and secure it with a screw
• For more detailed information, refer to the Installation Instructions supplied with theunit
For the electrical installation, the local safety regulations must be complied with.
It is recommended to first commission and switch on the receiver, then the transmitter.
• Switch on mains supplya) Press the «Reset» button (= delete) for about 3 seconds, LED flashes for about 5
seconds (deleting the stored address)b) Press «Set» button (= setting / learning) for about 1 second until the LED lights
upc) The duration of the receiver’s learning readiness is a maximum of 25 minutes.
If no signal is received from the transmitter during that period of time, repeat steps b) and c)
d) Mount transmitter and put it into operatione) When the receiver receives a signal from the transmitter, the LED flashes brieflyf) When the LED is steady on, the relay is energized = controlled device ONg) When the LED is dark, the relay is deenergized = controlled device OFFh) In the event of a power failure at the receiver, the relay will automatically be de-
energized.The transmitter repeats the ON or OFF signal at 20-minute intervals, depending on the operating state. This means that the relay will be energized / deenergized
again after 20 minutes at the latest. This interval was selected to extend batterylife.
If the REV-R.02/1 receives no signal from the controller / transmitter for 60 minutes, therelay will drop out so that the controlled device will automatically be switched off.
It is recommended to first commission the receiver and then the transmitter.• If the reference room is equipped with thermostatic radiator valves, they must be fully
openeda) Remove the battery transit tab, which prevents inadvertent operation of the unit
during transport and storage. The unit switches onb) When – immediately after switching on – symbol or appears on the
display (controlled device ON), the first signal has already been sent to the re-ceiver and communication has been opened
c) Make the settings according to the Operating Instructionsd) If symbol or does not appear on the display (controlled device OFF), it
must first be activated for signal transmissione) Select operating mode (comfort mode)f) On menu T, select the setpoint for comfort mode g) Use the roller selector to adjust the setpoint to 29 °C and confirm by pressingh) Heating ON symbol or appears on the display after a maximum of one
minutei) The first signal transmission to the receiver has taken placej) After 10 seconds, the transmitter sends another signal
Support
Mounting and installa-tion of receiverREV-R.02/1
CommissioningReceiverREV-R.02/1
CommissioningController / transmit-ter REV23RF
11/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
k) The ON / OFF signal will then be repeated every 20 minutes (the 20-minute in-terval has been chosen to extend battery life)
l) Reset the setpoint according to f) and g)
m) Press to reset the operating mode to the required positionThe receiver’s readiness to learn is a maximum of 25 minutes. If no signal is receivedfrom the transmitter during that period of time, repeat steps d) through m) above.The control mode can be changed via the menu-driven heating engineer settings.If the room temperature displayed does not agree with the room temperature effectivelymeasured, the temperature sensor should be recalibrated (refer to «Calibration of sen-sors»).
Technical data controller / transmitter REV23RF
Operating voltage DC 3 VBatteries (alkaline AA)
Battery lifeBackup for battery change
2 x 1.5 Vapprox. 2 yearsmax. 1 min
Sensing element NTCMeasuring rangeTime constant
NTC 10 kΩ at 25 °C ±1 %0…50 °Cmax. 10 min
Setpoint setting rangesNormal temperatureEconomy temperature
5 … 29 °C5 … 29 °C
Frost protection setpointSetting rangeFactory setting
5...29 °C5 °C
Resolutions of settings and displaySetpointsSwitching timesMeasurement of actual valueDisplay of actual valueDisplay of time
0.2 °C10 min0.1 °C0.2 °C1 min
SRD bandTransmit frequency REV23RFMax. transmitter powerMax. data throughputModulationFrequency stabilityAddress range
(preset in the factory)
868.7 to 869.2 MHz868.95 MHz< 10 mW / typically 4 mW19200 symbol/s = 38400 Bit/sbinary frequency changeover BFSK< ±20 ppm (±17 kHz)16 Bit (0...65535)
OperationClimatic conditionsTemperatureHumidity
to IEC 60 721-3class 3K35...+40 °C<85 % r. h.
TransportClimatic conditionsTemperatureHumidityMechanical conditions
to IEC 60 721-3class 2K3−25...+70 °C<93 % r. h.class 2M2
conformityEMC directiveR&TTE directive
89/336/EECEN 301 489-3
Product safetyRadio equipment EN 301 489-3
Important:
General datacontroller / transmitter
General data controller
General data transmitter
Environmentalconditions
Norms and standards
12/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Automatic electrical controls for household and similar use EN 60 730-1
Electromagnetic compatibilityImmunityEmissionsRadio equipment
EN 50 082-1EN 50 081-1EN 300 220-3
ApprovalsIn the following countries
0359 !
all ECC countries,Norway, Iceland and Switzerland
Devices of safety classDegree of pollution
II to EN 60 730-1normal
Weight (incl. package)REV23RFREV23RF/SET
0.37 kg0.68 kg
ColorHousing signal-white RAL 9003Base grey RAL 7038Dimensions 140x103x30 mm
Technical data receiver REV-R.02/1
Operating voltagePower
AC 230 V +10/−15 %< 10 VA
Frequency 45...65 HzSwitching capacity of relays
VoltageCurrent
AC 24...250 V6 (2.5) A
OperationClimatic conditionsTemperatureHumidity
to IEC 60 721-3class 3K30...+45 °C<85 % r. h.
Storage and transportClimatic conditionsTemperatureHumidityMechanical conditions
to IEC 60 721-3class 2K3−25...+70 °C<93 % r. h.class 2M2
conformityEMC directivesLow-voltage directivesR&TTE directives
89/336/EEC73/23/EECEN 301 489-3
Product safetyRadio equipmentAutomatic electrical controlsfor household and similar useSpecial requirements placed onenergy controllers
EN 301 489-3EN 60 730-1
EN 60 730-2-11
Electromagnetic compatibilityImmunityEmissionsRadio equipment
EN 50 082-1EN 50 081-1EN 300 220-3
ApprovalIn the following countries
0359 !
all ECC countries,Norway, Iceland and Switzerland
General unit data
Environmental conditions
Norms andstandards
13/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Devices of safety classDegree of pollution
II to EN 60 730-1normal
Weight (incl. package)REV-R.02/1REV23RF/SET
0.24 kg0.68 kg
ColorUnit frontBase
Signal-white RAL 9003grey RAL 7038
Dimensions 83x104x32 mm
Connection diagram receiver REV-R.02/1
L Live conductor, AC 230 VN Neutral conductor, AC 230 VLx Live, AC 24...250 VL1 N.O. contact,
AC 24...250 V / 6 (2.5) AL2 N.C. contact,
AC 24...250 V / 6 (2.5) AM1 Circulating pumpN2 Receiver REV-R.02/1
Lx
L1
Y1M1
N2
Nx
L
N L2
2255
A01
AC 2
30 V
AC 2
4...2
50 V
Lx
NxN
L
Y1 Actuating device
Application examples
T
T
F1F2
N2
M1Y2
2255
S01
N1T
F1F2
N2
M1Y2
2255
S02
T T
TN1
Instantaneous hot water heater Atmospheric gas burner
N1
Y4
2255
S03
Y3
N2
T
N4
TN3
T N1
2255
S05E1
N2
Zone valve Cooling equipment
14/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Y1
2252
S04
M1
N2TN1
Circulating pump with precontrol by manual mixing valve
E1 Cooling unitF1 Thermal reset limit thermostatF2 Safety limit thermostatM1 Circulating pumpN1 Room temperature controller (transmitter) REV23RFN2 Receiver REV-R.02/1N3 Room temperature controller (transmitter) REV23RFN4 Receiver REV-R.02/1Y1 3-port valve with manual adjustmentY2 Solenoiod valveY3 Motorized 3-port valveY4 Motorized 2-port valve
15/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
Dimensions
127140
78.8
104.
5
83.50
5612
11.75
2265
M03
30
Ø60
84
104
32
2265
M01
60
60
2265
M02
Controller / transmitter REV23RF
Receiver REV-R.02/1
16/16
Siemens Building Technologies Raumtemperaturregler REV23RF CE1N2265enHVAC Products 20.08.2002
2002 Siemens Building Technologies AG Änderungen vorbehalten