Self Healing @CEZ RomaniaMirel Velea, Sales Manager EM DG Romania

September 20-21, 2017VAR Partner Day

Self Healing @CEZ Romania, Sales Manager EM DG Romania

21, 2017 I Berlin

21

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 2

Self Healing @CEZ ROBasic Functionality

NOP

Regional controller

Mirel Velea / Sales Manager EM DG

Semi-Distributed

Time zero

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 3

Self Healing @CEZ ROBasic Functionality

NOP

Regional controller IEC 60870IEC 60870DNP3

Mirel Velea / Sales Manager EM DG

Semi-Distributed

IEC 60870-5-101IEC 60870-5-104

Less than1 minute

Fault locationFault isolationPower restoration

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 4

Self Healing @CEZ ROThe Project Phase 1

Challenge• Following the periodic analysis of the incidents and equipment damaged in the 20 kV network, there was an increase of the SAI

the non-selective identification of the faults network area.

• ČEZ DISTRIBUŢIE intention was to install a self healing feeder automation system as a pilot project installation. This pilotavailability of the grid and in case of problems and outages in the grid, the concerning zone (ZONA) shall be isolated; the oautomatically if this is possible.

Solution• 1 Self Healing Controller in the dispatch center.• 1 compact RTU SICAM CMIC in the substation Breasta.

• 8 Siemens Recloser 3AD including a Siemens recloser controller SIPROTEC 7SC80

Benefits• Reduction of outage times.• Improvement of voltage stability, including voltage optimization.• Reducing the duration and frequency of incidents.• increasing the availability of the network, and in case of occurrences of network problems and interruptions, the area will b

will be automatically powered.

Mirel Velea / Sales Manager EM DG

Following the periodic analysis of the incidents and equipment damaged in the 20 kV network, there was an increase of the SAIDI-SAIFI indicators due to

ČEZ DISTRIBUŢIE intention was to install a self healing feeder automation system as a pilot project installation. This pilot installation shall increase theavailability of the grid and in case of problems and outages in the grid, the concerning zone (ZONA) shall be isolated; the other zones shall be empowered

controller SIPROTEC 7SC80.

increasing the availability of the network, and in case of occurrences of network problems and interruptions, the area will be isolated and the other areas

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 5

Self Healing @CEZ ROThe Project Phase 1

SIPROTEC 7SC80

SICAM CMIC

Recloser (3AD)

ControllerSIPROTEC 7SC80

Mirel Velea / Sales Manager EM DG

SIPROTEC 7SC80

SICAM PAS & FASE

SICAM CMIC

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 6

Self Healing @CEZ ROThe Project Phase 1 – First Experience

1. The Self Healing Controller in the dispatching center is responsible for all the logic and automaticrestoration therefore it needs:GPRS communication to the newIEC 104 communication via an existing Network to the substation

IEC 104 communication to the SCADA system in the dispatching center2. Thesettings of theAutomation Sequence Editor (FASE) and with that tool, the basic logics for the Self Healing Controlleras well as the basic parameters including the protection settings for thecreated3. For all defined failures/trigger events an automatic self restoration will be initiated in case ofautomatic mode. The sequences will run automatically, controlled and monitored by the Self HealingController. The mode can be changed by a command (from the SCADA center) to the maintenancemode, where the automatic restoration will be deactivated.

Normal operation and topologyFigure

Outage

Recloser (3AD)

ControllerSIPROTEC 7SC80

Mirel Velea / Sales Manager EM DG

1. The Self Healing Controller in the dispatching center is responsible for all the logic and automaticrestoration therefore it needs:GPRS communication to the new recloser controllerIEC 104 communication via an existing Network to the substation Breasta

IEC 104 communication to the SCADA system in the dispatching center.2. The sequences for the isolation and restoration in case of trigger events, as well as the protectionsettings of the recloser controller will be created with the Engineering tool Siemens FeederAutomation Sequence Editor (FASE) and with that tool, the basic logics for the Self Healing Controlleras well as the basic parameters including the protection settings for the recloser controller will becreated.3. For all defined failures/trigger events an automatic self restoration will be initiated in case ofautomatic mode. The sequences will run automatically, controlled and monitored by the Self HealingController. The mode can be changed by a command (from the SCADA center) to the maintenancemode, where the automatic restoration will be deactivated.

Normal operation and topologyFigure – Normal operation within the pilot area, red=closed, green = open

Outage times can be minimized to < 1min.

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 7

Self Healing @CEZ ROThe Project Phase 2

CEZDispatchingCenter

R

Siemens Recloserexisting pilot project

R R R R R R R

SS Breasta

RSchneider/ Tavrida Recloserexisting installation

R R R R R R R

SIEMENS SelfHealing Controller

CEZControl Center

SS Barsesti

SS Godinesti

GPRS - IEC 104

Mirel Velea / Sales Manager EM DG

• Integration of further existing recloser into thisconcept.

• Communication also with GPRS and IEC60970-5-104

• Interoperability of Tavrida and Schneiderrecloser with Siemens Self HealingController without any compatibilityproblems.

SS Barsesti

SS Godinesti

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 8

Self Healing @CEZ ROThe Project Phase 2

Mirel Velea / Sales Manager EM DG

Outage times can be minimized to a few seconds,in case of GPRS problems even to >1 min

Siemens provides several different solutions:• For recloser or switches• different isolating scenarios• cable or OHL• control or only monitoring• decentralized or central solution..

Siemens can also integrate different types andvendors of recloser, also existing installation

Unrestricted © Siemens AG Österreich 2017. All rights reservedSeptember 2017Page 9

Self Healing @CEZ Romania

Mirel VeleaSales ManagerEnergy Management DivisionDigital Grid

Preciziei, 24Bucharest, Romania

Telephone:Fax: +40 21 62 96 606Mobile: +40 72 36 00 949

E-Mail:[email protected]

siemens.com

Mirel Velea / Sales Manager EM DG

Mirel VeleaSales ManagerEnergy Management Division

, 24, Romania

: +40 21 62 96 562+40 21 62 96 606

+40 72 36 00 949

[email protected]

siemens.com