Security Enhancement of Differential Protection of Power ... · PDF filenew algorithm is...
Transcript of Security Enhancement of Differential Protection of Power ... · PDF filenew algorithm is...
J. Energy Power Sources Vol. 4, No. 1, 2017, pp. 9-15 Received: February 15, 2017, Published: March 25, 2017
Journal of Energy and Power Sources
www.ethanpublishing.com
Security Enhancement of Differential Protection of
Power Transformers Based on Second Order Harmonics
Usama Khaled1, 2, Mohamed Qais1, Saad Alghuwainem1 and Abderrahmane Beroual3
1. Department of Electrical Engineering, King Saud University, Riyadh 11421, Saudi Arabia
2. Department of Electrical Engineering, Aswan University, Aswan 81528, Egypt
3. Ampere CNRS UMR, Ecole Centrale de Lyon, Ecully 69134, France
Corresponding author: Usama Khaled ([email protected])
Abstract: Differential relays are designed to protect the PTs (power transformers) from total damage when faults occur inside the PTs. Differential protection security of PTs is affected by external disturbances such as inrush currents, external faults, and over-excitation which cause undesired PT outage. In this work, a reliable algorithm is presented to improve the speed and security of PT protection. FFT (fast Fourier transform) method is used for taking out the second order harmonic of measured currents by CTs (current transformers) of the primary side and secondary side of PTs. The algorithm produces two signals: operating signal to disconnect PT during internal faults; and restraint signal to block the undesired action of the differential relay through external disturbances. The algorithm is inspected using PSCAD/EMTDC, where various abnormal conditions internal faults and external disturbances are simulated. The achieved results reveal that the proposed algorithm enhanced the speed and security of differential relay with simplest signal processing method compared to other techniques. Keywords: Power transformers, differential protection, harmonics, PSCAD/EMTDC, current transformer.
Nomenclature
Idiff Differential current (A)
Ips Primary current seen by relay (A)
Iss Secondary current seen by relay (A)
I2nddiff Second order harmonic of differential current (A)
I2ndps Second order harmonic of primary current seen by
relay (A)
I2ndss Second order harmonic of secondary current seen
by relay (A)
Ipickup Pickup current (A)
i(n) Discrete signal of current (A)
n Number of samples
N Periodic number of samples
Idiff1 The RMS fundamental component of differential
current (A)
Idiff2 The RMS second harmonic of differential current
(A)
I2nd The sum of RMS second harmonic of primary and
secondary currents (A)
1. Introduction
PTs (power transformers) are an essential and vital
link between two levels of voltages in the electrical
systems. The faulted transformers should be
de-energized as soon as possible to avoid permanent
damage. Protection of power transformers is the most
challenging problem in the power system relaying,
due to its importance and high cost. However, the
energization of transformer not only impacts the
differential protection of the incoming transformer but
also imposes a threat to the other electrical equipment
which has already been operating in the system. The
existence of inrush current due to the energization of
power transformers and over-excitation due to
overvoltage affect the security of differential relay.
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
10
The protective relays should avoid the undesired
operation due to external faults, over-excitation and
inrush currents.
Many researchers concerned with the security
enhancements of differential relays to prevent
permanent outage of power transformers. Kennedy [1]
used the harmonic components as a restraint for
electromechanical relays to prevent the false operation
of differential relays on the unbalanced currents due to
any reasons. Some authors have proposed new
numerical algorithms and techniques, excluding the
principle of harmonics restraint to satisfy most of the
design criteria of differential relays such as speed,
security, selectivity, etc. Discrete wavelet transform
method [2-6] is used to extract the features of
differential current to discriminate between internal
short circuits and inrush currents or external short
circuits. Fuzzy logic algorithms [7, 8] are employed in
differential relays to distinguish between inrush
currents and internal faults. ANNs (artificial neural
networks) based methods [9, 10] are used to detect the
inrush currents, CT (current transformer) saturation,
and over excitation to avoid undesired operation of
differential relays. The statistical calculations such as
calculating the differential current gradient [11, 12]
are used to identify the inrush currents.
Other researchers proposed different schemes to
determine the inrush currents, such as phase angle
difference method [13]. The relationship of the PS
(power spectrum) of second harmonic to the PS of
fundamental based on the autoregressive process is
used for inrush identification [14]. Based on the
magnetic characteristics, Lin et al. [15] proposed filter
algorithm to distinguish the external faults from
internal faults. Khalkhali et al. [16] proposed a new
method based on the developed polynomial model for
magnetic characteristics where the average fault
detection delay is 16 ms (in the 50 Hz base) with
accuracy above 97%. Time-time transform is applied
to fault diagnosis of power transformers as revealed in
Ref. [17]. Ramachandraiah et al. [18] used active
band-pass filters to detect the second order harmonic
ratio to avoid tripping during inrush current.
In this paper, FFT (fast Fourier transform)
technique is used to extract the second order
harmonics of secondary currents of CTs located in the
primary and secondary sides of PTs. FFTs technique
is straightforward and reliable method compared to
other methods used for signal processing.
2. The Principle Operation of Differential Power Transformer Protection
Schematic diagram of differential protection of Y-Δ
power transformer is shown in Fig. 1. Current
transformers CTs are connected in opposite manners
(Δ-Y) to eliminate the 30° phase shift between
primary and secondary currents. Electromechanical
relays that are shown in Fig. 1, consist of operating
coil which is responsible for sending a trip signal to
CBs (circuit breakers) during internal faults; and bias
windings which produce electromagnetic force
opposes those generated by operating coil then no trip
signal will be sent during external disturbances.
3. The Concept of Proposed Algorithm
In new numerical relays, many algorithms with
different signal processing techniques are proposed
according to the principle operation of differential
protection of power transformer. In this research, a
new algorithm is proposed for the differential
protection of power transformer as shown in Fig. 2.
Firstly, differential relays receive primary and
secondary current signals that are measured by CTs
Fig. 1 Schematic diagram of differential protection of power transformer.
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
11
Fig. 2 Proposed algorithm for differential protection of power transformer.
then the differential current is calculated as in Eq. (1).
diff ps ssI I I (1)
Secondly, FFT is used to extract the second order
harmonic from discrete current waveforms as in Eq.
(2).
2 4 /ndn
I i n e j n N
(2)
The decision of differential relay to send trip signal
to the circuit breaker depends on Eqs. (3) and (4).
diff pickupI I (3)
2 2 21
1.2nd nd nd
diff ps ssI I I (4)
During the internal fault, the differential current Idiff
will be greater than the pickup current Ipickup and the
second order harmonic of Idiff is equal the sum of
second order harmonic of Ips and Iss as in Eq. (5) then
the trip signal will be sent to CBs as shown in Fig. 2.
2 2 2 = nd nd nddiff ps ssI I I (5)
During external disturbances such as external fault,
inrush current or over-excitation, the differential
current Idiff could be greater than the pickup current.
But the second order harmonic of Idiff will be smaller
than the sum of second order harmonic of Ips and Iss as
in Eq. (6), and then the relay is restrained from the
undesired operation: 2 2 2nd nd nddiff ps ssI I I (6)
4. Methodology Simulation
The proposed algorithm is applied to protect three
winding (tertiary) power transformer in a national
electrical grid of Republic of Yemen. Tertiary
transformer 400 kV-Y/132 kV-Y/33 kV-Δ, 600 MVA
is simulated using PSCAD as shown in Fig. 3, where
this tertiary transformer is the largest transformer in
the Yemeni grid and considered the most important
part. The 400 kV and 132 kV transmission system of
Yemeni network are modeled by PSCAD/EMTDC,
where the number of 132 kV transmission lines is 19
and one 400 kV transmission line. Also, five major
power plants are modeled with their step-up power
transformers. CTs ratios are assumed to be 1000:5 at
400 kV side, 3000:5 at 132 kV side, and 12000:5 A at
33 kV side. The proposed algorithm is simulated using
PSCAD as shown in Fig. 4. Idiff1 is the RMS
fundamental component of differential current, Idiff2 is
the RMS second harmonic of differential current, I2nd
is the sum of RMS second harmonic of primary and
secondary currents of power transformer seen by the
relay, and Ipick is the pickup current and assumed as a
constant (0.5 A).
5. Results and Discussion
5.1 Inrush Current
The complex inrush current, including the
magnetizing inrush current and the sympathetic inrush
current, is considered to be relevant with transformer
switching-on of mal-operation. It is disclosed that the
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
12
Fig. 3 Differential protection layout of tertiary transformer.
Fig. 4 PSCAD modeling of proposed scheme.
CT transient saturation or CT local transient saturation,
caused by the long-lasting aperiodic component from
the magnetizing inrush current, leads to the
mal-operation [18]. In this section, the burden of CTs
is set to significant value 5 Ω to make CTs operate
under stressed conditions. The inrush current occurs
during the energization process of transformers; then
the conventional differential relay sends a trip signal
to the circuit breakers CBs because differential current
Idiff1 will be greater than the pickup current (0.5 A) as
shown in Fig. 5. The proposed scheme did not send a
trip signal because the sum of RMS second harmonic
for both primary and secondary currents I2nd is greater
than 1.2 times the RMS second harmonic of
differential current Idiff2. Hence, the proposed scheme
is secure during the starting conditions of power
transformers.
5.2 Internal Fault
In this part, the proper operation of transformer
differential protection is reproduced by
PSCAD/EMTDC based simulation tests for deeper
and more useful analysis. Either symmetrical or
Fig. 5 Tripping during inrush current.
asymmetrical faults could be applied to the tertiary
power transformer as an internal fault having different
values of ground resistance. Fig. 6 indicates that once
the internal fault is initiated at time 1 s, the proposed
scheme send a trip signal at 1.005 s. That means the
protective relay starts operating only after 5 ms,
equivalent to a quarter of 50 Hz cycle, of elapsed time.
5.3 Turn-to-Turn Fault
In this section, turn-to-turn fault of single phase
transformer is simulated in PSCAD by Juan Carlos
Garcia [19]. The leakage impedances between
windings of studied transformer are calculated using
finite element type program. Turn to turn fault is
incepted in High voltage side turns of windings where
10% of turns are short-circuited. According to IEEE
standard C37.91-2000, fewer turn to turn fault harder
to be detectable. Fig. 7 shows that the proposed
scheme sends trip signal during the turn-to-turn fault.
5.4 External-Fault
In this section, an external fault is applied to the
closest location to the tertiary power transformer. Fig.
8 shows that the conventional differential relay will
send trip signal during the external fault case. On the
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
13
Fig. 6 Tripping during internal fault.
Fig. 7 Tripping during turn to turn fault.
contrast, the proposed scheme will not send trip signal
during external fault because the sum of RMS second
order harmonic of primary and secondary currents of
tertiary transformer I2nd seen by relay will be greater
than 1.2 times the RMS second order of differential
current Idiff2. According to the results, the proposed
method distinguishes between the internal fault and
other abnormal fault conditions.
Fig. 8 Tripping during external fault.
5.5 Overexcitation
The differential current of the transformer, which is
obtained from the secondary current of CTs, consists
of two parts, the error current due to CT overexcitation
and the magnetizing current of the transformer.
Transformer overexcitation is mainly caused by
overvoltage in the power system. In this section, the
lightning stroke, with 1.2/50 μs and peak current 100
kA, hits the substation (close to the transformer), it
induces overvoltage in the system. Fig. 9 shows that a
lightning stroke hits the line conductor (phase
conductor) directly at 1 s. The induced overvoltage
causes overexcitation to the tertiary transformer as
illustrated in Fig. 10. The conventional differential
relay will detect the overexcitation as an internal fault,
and then send a trip signal. On the other hand, the
proposed scheme will not send a signal which means
that the proposed scheme is immune to the
overexcitation.
6. Conclusions
A new and straightforward algorithm to enhance the
security and speed of differential protection of power
transformers is proposed in this research. The proposed
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
14
Fig. 9 Lightning surge and transient overvoltage.
Fig. 10 Tripping during over-excitation.
algorithm uses FFT technique to extract the second
order harmonic of primary, secondary and calculated
differential currents. The new algorithm has two
conditional terms to make a trip decision: Firstly,
calculates the differential current and compare it with
pre-set or pickup value; secondly, compares the
second order harmonic of differential current with the
sum of second order harmonic of measured primary
and secondary currents of the power transformer.
400/132 kV, 50 Hz Yemeni grid is simulated using
PSCAD then the proposed algorithm is investigated
and applied to the tertiary transformer. The obtained
results reveal that the proposed algorithm operates in
the presence of internal faults and secure to the
external disturbances such as inrush current, external
fault, and over-excitation. The main impact of this
algorithm is its simplicity and reliability because it
uses only FFT technique and the response to the
internal fault is faster which functions within a quarter
of cycle only.
Acknowledgment
The authors extend their appreciation to the ISPP
(International Scientific Partnership Program) at King
Saud University for funding this research work
through ISPP#0047.
References
[1] L.F. Kennedy, C. Hayward, Harmonic-current-restrained
relays for differential protection, Transactions of the
American Institute of Electrical Engineers 57 (5) (1938)
262-271.
[2] R.A. Ghunem, R. El-Shatshat, O. Ozgonenel, A novel
selection algorithm of a wavelet-based transformer
differential current features, IEEE Transactions on Power
Delivery 29 (3) (2014) 1120-1126.
[3] B. Noshad, M. Razaz, S.G. Seifossadat, A new algorithm
based on Clarke’s transform and discrete wavelet
transform for the differential protection of three-phase
power transformers considering the ultra-saturation
phenomenon, Electr. Power Syst. Res. 110 (2014) 9-24.
[4] M. Rasoulpoor, M. Banejad, A correlation based method
for discrimination between inrush and short circuit
currents in differential protection of power transformer
using discrete wavelet transform: Theory, simulation and
experimental validation, Int. J. Electr. Power Energy Syst.
51 (2013) 168-177.
[5] S.A. Saleh, B. Scaplen, M.A. Rahman, A new
implementation method of wavelet-packet-transform
differential protection for power transformers, IEEE
Transactions on Industry Applications 47 (2) (2011)
1003-1012.
[6] M.O. Oliveira, A.S. Bretas, G.D. Ferreira, Adaptive
differential protection of three-phase power transformers
based on transient signal analysis, Int. J. Electr. Power
Energy Syst. 57 (2014) 366-374.
[7] A. Rahmati, M. Sanaye-Pasand, Protection of power
transformer using multi criteria decision-making, Int. J.
Electr. Power Energy Syst. 68 (2015) 294-303.
Security Enhancement of Differential Protection of Power Transformers Based on Second Order Harmonics
15
[8] D. Bejmert, W. Rebizant, L. Schiel, Transformer differential protection with fuzzy logic based inrush stabilization, Int. J. Electr. Power Energy Syst. 63 (2014) 51-63.
[9] M. Yazdani-Asrami, M. Taghipour-Gorjikolaie, S.M. Razavi, S.A. Gholamian, A novel intelligent protection system for power transformers considering possible electrical faults, inrush current, CT saturation and over-excitation, Int. J. Electr. Power Energy Syst. 64 (2015) 1129-1140.
[10] H. Balaga, N. Gupta, D.N. Vishwakarma, GA trained parallel hidden layered ANN based differential protection of three phase power transformer, Int. J. Electr. Power Energy Syst. 67 (2015) 286-297.
[11] M. Panteli, P.A. Crossley, J. Fitch, Design of dependable and secure system integrity protection schemes, Int. J. Electr. Power Energy Syst. 68 (2015) 15-25.
[12] R.J.N. Alencar, U.H. Bezerra, A.M.D. Ferreira, A method to identify inrush currents in power transformers protection based on the differential current gradient, Electr. Power Syst. Res. 111 (2014) 78-84.
[13] A. Hosny, V.K. Sood, Transformer differential protection with phase angle difference based inrush restraint, Electr. Power Syst. Res. 115 (2014) 57-64.
[14] H. Zhang, P. Liu, O.P. Malik, A new scheme for inrush identification in transformer protection, Electr. Power Syst. Res. 63 (2) (2002) 81-86.
[15] X. Lin, J. Lu, R. Zhang, N. Tong, O.S. Adio, Z. Li, Internal fault fast identification criterion based on superimposed component comparison for power transformer, Int. J. Electr. Power Energy Syst. 73 (2015) 491-497.
[16] B. Khalkhali, J. Sadeh, Transformer differential protection by online core modeling and orthogonal polynomials, IEEE Transactions on Power Delivery 30 (5) (2015) 2146-2153.
[17] A. Ashrafian, B. Vahidi, M. Mirsalim, Time-time-transform application to fault diagnosis of power transformers, IET Generation, Transmission & Distribution 8 (6) (2014) 1156-1167.
[18] S.H.J.H.B. Ramachandraiah, J. Balakrishnan, Design, fabrication and testing of transformer static differential relay circuit with harmonic blocking, in: Proceedings of the 4th IASTED Asian Conference on Power and Energy Systems (AsiaPES 2010), 2010, pp. 203-209.
[19] Internal Fault Transformer Example, 2014, http://forum.hvdc.ca/1008297/Internal-Fault-transformer-example.