Sectos SF Load Break Switch - ABB Group...Gas-low locking device or manual locking device as options...
Transcript of Sectos SF Load Break Switch - ABB Group...Gas-low locking device or manual locking device as options...
© ABB GroupOctober 30, 2014 | Slide 1
Sectos SF6 Load Break Switch
One ABB Surabaya, 30th October 2014Total Solution for Energy Efficiency and Improved Industrial Productivity
© ABB GroupOctober 30, 2014 | Slide 2
Sectos Load Breaking SwitchOverview
§ Sectos load breaking switch offers the following features:
§ Completely sealed stainless steel tank
§ 2-position(ON - OFF) or 3-position(ON - OFF - EARTH)§ Reliable spiral spring operation mechanism with light
reflecting and clear position indicator
§ Stable gas density switch with a temperaturecompensated gauge
§ Mechanical manual locking device or low gas lockingdevice
§ Multiple mounting modes
§ Complete feeder automation solutions§ Easily upgraded from manual to motor operation
© ABB GroupOctober 30, 2014 | Slide 4
UnitedKingdom
NorwayFinland
SwedenLithuaniaPoland
HungarySlovenia
FranceSpain Croatia
Algeria
MoroccoIsrael
SaudiArabia
IranJordan
Tunisia
Egypt
India
China
ThailandVietnam
PhilippinesMalaysia
Indonesia
Australia
New Zealand
South Africa
Tanzania
Senegal
USA
Honduras
Ecuador
PeruBolivia
Chile
Argentina
Brazil
Greece
Sectos Load Breaking SwitchInstalled in more than 40 countries
© ABB GroupOctober 30, 2014 | Slide 5
Sectos Load Breaking SwitchNXB and NXBD
NXB
Two-way load break switch
Three-position: ON / OFF /EARTH
NXBD
Three-way load break switch
Three-position: ON / OFF /EARTH
© ABB GroupOctober 30, 2014 | Slide 6
Sectos Load Breaking Switch_NXBDStructure
NXBD
Three-way load break switch
2 position C/O
or 3-position: C/O/E© ABB GroupOctober 30, 2014 | Slide 6
Hook stick lever
Clear, reflectibleindicator
3 mm stainless steel tank
Silicone rubberinsulator
Operation housingIP67
Gas fillingvalve
© ABB GroupOctober 30, 2014 | Slide 7
Sectos Load Breaking Switch_NXBDStructure
© ABB GroupOctober 30, 2014 | Slide 7
1 2
3
© ABB GroupOctober 30, 2014 | Slide 8
Sectos Load Breaking Switch_NXBDFeature of NXBD
§ IEC 12-24 kV
§ 2- or 3-position load break switch
§ Silicone rubber insulator
§ Creepage distance 620mm
§ Low weight, appr. 141kg
§ Manual or motor operated
§ Protection degree of operate box IP67
§ Complete sealed 3mm stainless steel tank
§ Two separate Independent spiral springoperation mechanism with light reflecting andclear position indicator
© ABB GroupOctober 30, 2014 | Slide 9
Sectos Load Breaking SwitchNXB and NXBD parameter
NXB NXBD
Rated voltage 12-24 kV 12-24 kV
Rated current 630 A 630 A
Number of breaking operation C – O ( undernormal load current) 400 400
Short time withstand current (4 sec) 20 kA 20 kA
Peak withstand current 50 kA 50 kA
Short circuit making operation(kA / operations)50kA / 5
31.5kA / 1050kA / 5
31.5kA / 10
Mechanical endurance C-O (No load operation)
Main switch 5000 5000
Earthing switch 2000 2000
Creepage distance 620/960 mm 620/960 mm
Two-way load break switch Yes -
Three-way load break switch - Yes
© ABB GroupOctober 30, 2014 | Slide 10
Sectos Load Breaking SwitchNXBD
§ NXBD: double NXB
§ 3-way switch disconnector
§ Two independent operating mechanisms,one in each end numbered 1 and 2
§ Has all the features and functions of NXB
§ Especially useful for loop power supply
§ 1 input + 2 outputs or 2 inputs + 1 output
1 2
3
1 2
3
Two-position 3-wayswitch types NXBD__A_
Three-position 3-wayswitch types NXBD__C_
switchedway no.1
switchedway no.1
switchedway no.2
switchedway no.2
tapped way tapped way
© ABB GroupOctober 30, 2014 | Slide 11
Sectos Load Breaking SwitchNXBD
§ NXBD application cases: Tölby station outside Vaasa,Finland
§ All 4 motors of the two NXBD are all controlled from thesame RTU (REC523 in the control box).
Before After
© ABB GroupOctober 30, 2014 | Slide 12
Main Components of SectosContact system
§ Contact material: copperwith silver-plating.
§ Short time withstandcurrent: 20kA / 4 seconds.
§ Making current: 50kA / 5times
§ Effective arc extinction bycooling plate
§ Large clearance betweenopen contact gaps
§ Internal arc fault current16kA/1S
© ABB GroupOctober 30, 2014 | Slide 13
Main Components of SectosEarthing Switch
§ Integrated earthing switchfor NXB & NXBD type
§ Earthing Switch for safetymaintenance
§ Close-open-earthingoperations sequence, onlyearthing the switch whenSectos is opened
§ Mechanical endurance2000 CO
§ Earthing switch can only beoperated by manualoperation for safety reason
© ABB GroupOctober 30, 2014 | Slide 14
Main Components of SectosOperation Mechanism
§ Reliable manual and motor operation mechanism.
§ Independent spiral spring operation mechanism (no need
to charge the spring first)
§ Easy to be upgraded from manual operation to motoroperation at site
§ Operation mechanism box made from aluminum alloy
§ Spray painting of RAL7035, anti-corrosion, IP67
© ABB GroupOctober 30, 2014 | Slide 15
Main Components of SectosPosition Indicator
§ Large position indicatorsymbols
§ Reflective colours
§ Visible even at night
§ The reliable indication ofthe device meets thedesign and testing of IEC129 A2
© ABB GroupOctober 30, 2014 | Slide 16
Main Components of SectosGas Pressure Indicators
§ Temperature compensated gas density switch and gauge
§ Gas density switch: gas-low contact (NC) will open whenthe gas pressure is below 1.2bar, the alarm is then sent tothe relay
§ Gas gauge: under the tank, with large indication symbols.
© ABB GroupOctober 30, 2014 | Slide 17
Main Components of SectosGas Pressure Locking Devices
§ Optional gas-low locking device and manual locking device.
§ Gas-low locking device will lock the switch when gaspressure is below 1.1bar, the alarm contact (NC) will openand providing the signal to the relay
§ The switch will be completely locked when manual lockingdevice is active, and the motor control circuit is alsoautomatically disabled in the locked position
© ABB GroupOctober 30, 2014 | Slide 18
Main Components of SectosMeasurement Input Signals
Ring type current transformer for current measurement
§ Installed around the bushings for protection and monitoring
§ Easily to be installed and replaced.
§ Internal solution is also available
§ Service conditions: -40...+40 ℃.
§ Ith/Idyn: 20/50 kA.
§ Type: KOKU 072 G4
§ Ratio: 400/1A,600/1A
§ Burden/Class 3VA/5P10(0.5) 0.5VA/5P20
© ABB GroupOctober 30, 2014 | Slide 19
Main Components of SectosMeasurement Input Signals
§ With 3 ABB voltage sensors (KEVCY 24 SA 2) and 3Combi sensors (KEVCY 24 SB 3)
§ Or 6 local capacitive voltage dividers and 3 currenttransformers
§ Providing 6 voltage inputs and 3 current inputs.
© ABB GroupOctober 30, 2014 | Slide 21
Summary
§ Completely sealed stainless steel tank (Leakage<0.15% per year)
§ ABB patent spiral spring operation mechanism with clear indicator
§ Reliable, stable gas density switch and gauge with temperaturecompensation
§ Gas-low locking device or manual locking device as options
§ Easily upgrading from manual to motor operation
§ Safe, compact design and wide dynamic range of the sensorsolution
§ Powerful relay solution with strongly logic function
§ Full options for Sectionalizer: Current-count and Voltage-time
© ABB GroupOctober 30, 2014 | Slide 22
Contact
Ganjar NugrahaPower Product Medium VoltageTlp. : 021-2551 5555 / 0811-9998004E-mail : [email protected] : www.abb.com