CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572 Leviton Manufacturing Co., Inc. 201 N Service Rd Melville, NY 11747-3138 Phone: 1.800.323.8290 Fax: 1.800.832.9538 SECTION 16572 MODULAR DIMMING CONTROLS Leviton Dimensions D4000 System This specification is dated May 1, 2011 . It replaces any and all previous Dimensions D4000 specifications. This document can and should be edited to suit project requirements. Editing notes are included as HIDDEN TEXT . They can be revealed or hidden by one of the following methods: To display hidden text in Word 2010 documents: Click the File tab. The Backstage view appears. Under Help , click Options . The Options dialog appears. Click Display and select Hidden Text . To disable printing of hidden text in Word 2010 documents: Click the Microsoft Word button. Then click the Word tab. Then click the Options button. The Word Options dialog opens. Click the Display tab in the left pane. Uncheck the Print hidden text checkbox under Printing Options in the right pane of the Word Options dialog. In older versions of Microsoft Word: From the pull-down menus select TOOLS, then OPTIONS. Under the tab labeled VIEW, select or deselect the HIDDEN TEXT option. To print a copy of the specification that includes the HIDDEN TEXT , (1) Select “Print” (2) Select “Options” (3a) Check the box to print HIDDEN TEXT (3b) Uncheck the box to not print HIDDEN TEXT . PART 1 – GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 specification Sections. Leviton 05/01/11 MODULAR DIMMING CONTROLS Dimensions D4000 System 26 09 36-1

Transcript of Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types...

Page 1: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

Leviton Manufacturing Co., Inc.201 N Service RdMelville, NY 11747-3138Phone: 1.800.323.8290Fax: 1.800.832.9538

SECTION 16572MODULAR DIMMING CONTROLS

Leviton Dimensions D4000 SystemThis specification is dated May 1, 2011. It replaces any and all previous Dimensions D4000 specifications.

This document can and should be edited to suit project requirements. Editing notes are included as HIDDEN TEXT. They can be revealed or hidden by one of the following methods:

To display hidden text in Word 2010 documents: Click the File tab. The Backstage view appears. Under Help, click Options. The Options dialog appears. Click Display and select Hidden Text.

To disable printing of hidden text in Word 2010 documents: Click the Microsoft Word button. Then click the Word tab. Then click the Options button. The Word Options dialog opens. Click the Display tab in the left pane. Uncheck the Print hidden text checkbox under Printing Options in the right pane of the Word Options dialog.

In older versions of Microsoft Word: From the pull-down menus select TOOLS, then OPTIONS. Under the tab labeled VIEW, select or deselect the HIDDEN TEXT option.

To print a copy of the specification that includes the HIDDEN TEXT, (1) Select “Print” (2) Select “Options” (3a) Check the box to print HIDDEN TEXT (3b) Uncheck the box to not print HIDDEN TEXT.

PART 1 – GENERAL1.1RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 specification Sections.

B. All contract documents and addenda.1.2SUMMARY

A. Section Includes:1. Modular dimming control system.

B. Related Sections:1. Section [13845 – Relay Lighting Controls:] Switching panels controlled by Modular

Dimming Control System.2. Section [13846 – Network Lighting Controls:] Switching panels controlled by Modular

Dimming Control System.3. Section [16140 - Wiring Devices/Lighting Controls.]

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-1

Page 2: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

4. Section [16580 - Ballasts:] Fluorescent lighting ballasts controlled by Modular Dimming Control System.

5. Section [16950 - Occupancy Sensors:] Occupancy sensors used in conjunction with Modular Dimming Control System.

C. Contractor responsibilities:1. Coordinate, receive, mount, connect, and place into operation all equipment. Furnish

all conduit, wire, connectors, hardware, and other incidental items necessary for the complete and properly functioning relay lighting control system as described herein and shown on the plans.

1.3REFERENCESA. American National Standards Institute/Institute of Electrical and Electronic Engineers

(ANSI/IEEE) 1. C62.41-1991 — Recommended Practice for Surge Voltages in Low-Voltage AC

Power Circuits.B. ASTM International (ASTM) ()

1. D4674 -02a Standard Test Method for Accelerated Testing for Color Stability of Plastics Exposed to Indoor Fluorescent Lighting and Window-Filtered Daylight.

C. Canadian Standards Association (CSA) ().1. CSA C22.2 # 14 Industrial Control Equipment2. CSA C22.2 # 184 Solid-State Lighting Controls3. CSA C22.2 # 156 Solid-State Speed Controls

D. International Electrotechnical Commission ().1. (IEC) 801-2 Electrostatic Discharge Testing Standard.2. IEC/EN 60669-2-1 Switches for household and similar fixed electrical installations -

electronic switches.E. International Organization for Standardization (ISO)

1. 9001:2000 — Quality Management Systems.F. National Electrical Manufacturers Association (NEMA)

1. WD1 (R2005) - General Color Requirements for Wiring Devices.G. National Fire Protection Association (NFPA) (www.nfpa.org)

1. NFPA 70: National Electrical Code (NEC), Article 100H. Norma Official Mexicana (NOM).

1. NOM-003-SCFI Productos eléctricos - Especificaciones de seguridad (Electrical products - Safety Specifications)

2. 489 (2002) - Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures.

3. 508 (1999) - Standard for Industrial Control Equipment.4. 1472 (1996) - Solid-State Dimming Controls.5. 924 (2003) - Emergency Lighting and Power Equipment

I. American Society of Heating, Refrigerating and Air-Conditioning (ASHRAE)

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-2

Page 3: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1. ASHRAE 90.1J. California Energy Commission (CEC)

1. Title 241.4SUBMITTALS

A. General1. Submit under provisions of Section [01330] and in accordance with Conditions of the

Contract.B. Bill of Materials: Complete list of all parts needed to fully install selected system

components.C. Specification Conformance Document: Indicate whether the submitted equipment:

1. Meets specification exactly as stated.2. Meets specification via an alternate means and indicate the specific methodology

used.D. Product Certificates: Signed by manufacturers of equipment certifying that products

furnished comply with specified requirements.E. Shop Drawings

1. To be prepared by competent draftspersons specifically for this projecta. Generic drawings are not acceptable.

2. Submit for approval within 30 days following receipt of contracta. Approval is required prior to equipment fabrication

3. Detail all mechanical and electrical equipment, including:a. Load schedule indicating:

1) For each circuit:a) actual connected loadb) load typec) voltaged) capacitye) phase

2) Circuit numbers and their respective control zones3) Circuits having emergency priority.

b. Separate system wiring riser diagrams for each and every system showing each major item of equipment and connections.

c. Separate 1/8” = 1’ scale floor plans keyed to the system riser diagrams for each and every system to be provided showing all equipment locations, conduit routing and sizes, quantity and types of cables.

d. Device termination diagramse. System programming information including zones and schedules.

F. Product Data: Product data sheets with performance specifications demonstrating compliance with specified requirements.

G. Installation Instructions: Manufacturer’s installation instructions.

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-3

Page 4: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

H. Field Test Reports: Indicate and interpret test results for tests specified in Part 3.I. Maintenance Data

1. Include record of Owner’s equipment-programming option decisions.1.5CLOSEOUT SUBMITTALS

A. To be provided within two weeks following system turn-on.1. Warranty documents specified herein.2. Three sets of operation and maintenance manuals.3. Two complete sets of as-built drawings

1.6QUALITY ASSURANCEA. Manufacturer Requirements

1. Continuously engaged in the manufacture of architectural lighting controls and relays for no less than ten years.

2. Provide telephone and field support by qualified applications engineers.3. Maintain a quality system that is registered to the ISO 9001:2000 Quality Standard.

B. Modular dimming control system components:1. Listed by [CE] [CSA] [NOM] [UL] specifically for the required loads, or certified by

recognized independent testing organizations that test to [CE] [CSA] [NOM] [UL] standards.

2. Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction.

3. Comply with ASHRAE 90.1a. Designed and tested to withstand voltage surges up to 6000V and current surges

up to 3000A per ANSI/IEEE standard 62.41-19804. Comply with CEC Title 245. Designed and tested to withstand electrostatic discharges up to 15,000 V without

damage or memory loss per IEC 801-2.C. Installer Qualifications

1. Experienced in performing the work of this section2. Has specialized in installation of work similar to that required for this project.

D. Source Limitations1. To assure compatibility, obtain all system components from a single source with

complete responsibility for all lighting controls and accessories specified in this Section, in Division 13 Section “Lighting Controls,” and in Division 16 Section “Relay Lighting Controls.” The use of subcontracted component assemblers is not acceptable.

1.7PRODUCTS INSTALLED BUT NOT FURNISHED UNDER THIS SECTIONA. Dimming [panels] [and] [racks] [and switching panels] controlled by the Dimensions

D4000 System (see Sections 13845 & 13846 as referenced above).B. Ballasts

1. Any fluorescent ballasts supplied to be compatible with the equipment being furnished on this project.

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-4

Page 5: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

C. All conduit, wire, connectors, hardware, and other incidental items necessary for the complete and properly functioning central dimming control systems described herein and shown on the plans.

1.8DELIVERY, STORAGE & HANDLINGA. General: Comply with Division 1 Product Requirements Sections.B. Ordering: Comply with manufacturer’s ordering instructions and lead-time requirements

to avoid construction delays.C. Delivery

1. Deliver materials in manufacturer’s original, unopened, undamaged packages with intact identification labels.

2. Deliver to other trades in a timely manner.D. Storage and Protection: Store materials away from exposure to harmful weather

conditions and at temperature and humidity conditions recommended by manufacturer.1.9PROJECT CONDITIONS

A. Do not install equipment until the following conditions can be maintained in spaces to receive equipment:1. Ambient temperature: 0° to 40° C (32° to 104° F).2. Relative humidity: Maximum 95 percent, non-condensing.3. Lighting control system must be protected from dust during installation.

1.10 WARRANTYA. Manufacturer’s Warranty

1. Warrant all equipment free of defects in materials and workmanship.2. Warranty Period

a. Warrant all system components for 25 months from date of shipment, or two years from date of turn-on, whichever occurs first.

b. Make extended warranties available.3. Owner’s Rights: Manufacturer’s warranty is in addition to, not a limitation of, other

rights the Owner may have under contract documents.1.11 COMMISSIONING

A. Provide factory-certified field service engineer to ensure proper system installation and operation under following parameters:1. Certified by the equipment manufacturer on the system installed.2. Site visit activities:

a. Verify connection of power feeds and load circuits.b. Verify connection of controls.c. Verify system operation control by control, circuit by circuit.d. Obtain sign-off on system functions.e. Demonstrate system capabilities, operation and maintenance and educate

Owner’s representative on the foregoing.3. At least three site visits to accomplish the following tasks:

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-5

Page 6: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

a. Prior to wiring1) Review and provide installer with instructions to correct any errors in the

following areas:a) Low voltage wiring requirementsb) Separation of high and low voltage wiring runsc) Wire labelingd) Load schedule informatione) Switching panel locations and installationf) Physical locations and network addresses of controlsg) Analog phone line requirementsh) Computer-to-network connectionsi) Load circuit wiringj) Connections to other systems and equipment

b. After system installation1) Check and approve or provide correction instructions on the following:

a) Connections of power feeds and load circuitsb) Connections and locations of controlsc) Connections of low voltage inputsd) Connections of the data network

2) Turn on system control processor and download any pre-programmed system configuration

3) Verify panel address(es)4) Download pre-programmed system configuration and information to switching

and/or dimming panels5) Check load currents and remove bypass jumpers6) Verify that each system control is operating to specification7) Verify that each system circuit is operational according to specification8) Verify that manufacturers’ interfacing equipment is operating to specification9) Verify that any computers and software supplied by the manufacturer are

performing to specifications10)Verify that any remote WAN (Wide Area Network) connections such as dial-up

or broadband access points are operating properly11)Have an owner’s representative sign off on the above-listed system functions

c. Before project completion and hand-off1) Demonstrate system capabilities and functions to owner’s representative2) Train owner’s representative on the proper operation and maintenance of the

system.

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-6

Page 7: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

B. Notification: Upon completion of the installation, the contractor shall notify the manufacturer that the system is ready for formal checkout. Notification shall be given in writing a minimum of 21 days prior to the time factory-trained personnel are required on site. Manufacturer shall have the option to waive formal turn-on.

C. Turn-On: Upon completion of all line, load and interconnection wiring, and after all fixtures are installed and lamped, Manufacturer’s Rep or, if waived, Contractor shall completely check the installation prior to energizing the system. Each installed relay system shall be tested for proper ON/OFF operations, and proper LED illumination. Each installed control panel shall be tested verifying that each controlled load adjusts to the selected setting and that all switch LED’s illuminate properly.

D. At the time of checkout and testing, the owner’s representative shall be thoroughly instructed in the proper operation of the system.

1.12 MAINTENANCEA. Enable the end user to order new equipment for system expansion, replacements, and

spare parts.B. Make new replacement parts available for a minimum of ten years from the date of

manufacture. C. Provide factory-direct technical support hotline 24 hours per day, 7 days per week.D. Offer renewable annual service contracts, to include parts, factory labor, and annual

training visits. Make service contracts available up to ten years after date of system commissioning.

PART 2 – PRODUCTS2.1MANUFACTURERS

A. Acceptable Manufacturer: Leviton Manufacturing Co. Inc. — System: Leviton Dimensions D4000

A. [Basis of design product: Leviton Manufacturing Co. Inc. Dimensions D4000 System or subject to compliance and prior approval with specified requirements of this section, one of the following:]1. Leviton Manufacturing Co. Inc. Dimensions D4000 System2. <<To specify an alternate manufacturer and product, insert the names here.

Otherwise, delete this entire line.>>B. Substitutions: [Not permitted.] [Permitted.]

1. Show all substitutions as an add or deduct from the base bid pricea. All substitutions subject to provisions of [Section 01 25 00] [Division 1]

2. Clearly delineate all proposed substitutions as such and submit in writing for approval by the design professional a minimum of 10 working days prior to the bid date.a. Proposed substitutions must be made available to all bidders.b. Proposed substitutes must be accompanied by a review of the specification

noting compliance on a line-by-line basis.3. Prior to rough-in, provide complete engineered shop drawings, including power

wiring, with deviations from the original design highlighted in an alternate color, to the engineer for review and approval.

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-7

Page 8: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

4. By using pre-approved substitutions, the contractor accepts responsibility and associated costs for all required modifications to circuitry, devices, and wiring.

2.2GENERALA. DIMMING PERFORMANCE REQUIREMENTS

1. Designed for continuous operation at any temperature in an ambient temperature range of 0° C (32°F) to 40° C (104°F) and 90 percent non-condensing relative humidity.

2. Designed and tested to withstand line-side surges without performance degradation.a. Other power handling devices to withstand surges of 6,000 volts, 200 amps per

ANSI/IEEE C62.41, without degradation of performance.3. Include a means to disconnect the load from line supply voltage for servicing.4. Power failure memory and dimmer/relay recovery:

When power is restored following an interruption, lights shall automatically return to the previously set levels.a. Each dimmer to smoothly raise illumination levels to programmed settings within a

programmed fade time interval after initial turn-on.b. Control all light sources in a smooth and continuous fashion without visible steps.c. Each dimmer to have the following assignable load types with corresponding

dimming curves and ranges:1) Incandescent2) Magnetic Low Voltage3) Forward-Phase-Compatible Electronic Low Voltage4) Two-Wire Fluorescent Ballasts5) Neon6) Cold Cathode7) [Leviton Power Extenders]

d. Load types to be assignable per circuit.e. Load types to be field-configurable.f. Minimum and maximum light levels to be adjustable on circuit-by-circuit basis.g. Cutoff light levels to be adjustable on circuit-by-circuit basis.h. Electrical input

1) 120V Models: 120V +/- 10%, 50 or 60Hz, 1,920W continuous Max2) 230V Models: 230V +/- 10%, 50 or 60Hz, 2,400W continuous Max3) Peripheral network power: +24 VDC, 150 mA

i. Electrical output1) 120V, 1000W/VA per dimmers

a) Maximum of 1,200W per sideb) Maximum of 1,920W continuous

2) 230V, 800W/VA dimmersa) Maximum of 1,200W per side

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-8

Page 9: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

b) Maximum of 2,400W continuousj. Minimum load for flicker-free operation to be 15Wk. [Assignable to any network channel]l. [Assignable to maximum of 4 network groups]m. Provide real-time cycle-by-cycle compensation for incoming line voltage

variations.1) change in RMS voltage per cycle to be less than ±2 percent2) filter dynamic harmonics3) filter RFI (radio and television interference) and line noise

B. Network1. Luma-Net Network

a. Up to 127 devicesb. 2000’ max run lengthc. Daisy chain topology with zero drop length

1) Hub shall be available for star base topologies2. Network cable

a. RS-485 cabling provided in accordance with all applicable standards including but not limited to EIA-485 standard1) Belden 1502R (Non-Plenum)2) Belden 9829 (Non-Plenum)3) Belden 1502P (Plenum)

b. Accompanied by a stranded copper wire power pair not less than #18 AWG 1) Gauge to be determined by run length, power supply and total device load2) COM of power pair must be connected to all devices

2.3ARCHITECTURAL LIGHTING CONTROL STATIONSA. [Network] Master Station: Leviton [D4200] [D4206] [D4104] [D4106] Multi-Zone

[Network] Lighting Control1. [Control remote and auxiliary dimming and switching loads]2. [Control six (6) internal (local) dimmers and remote dimming and switching loads on

up to thirty two (32) channels]3. [Control [four (4)] [six (6)] internal (local) dimmers and remote dimming and switching

loads on up to thirty two (32) channels] in [four] [six] zones]4. Addressable5. Electrical Input

a. [+9-24VDC, 75 mA]b. [Power: 120V +/- 10%, 50 or 60Hz, [1,920W] [Power: 230V +/- 10%, 50 or 60Hz,

[2,400W]c. [Peripheral Network Power: +24VDC, 150 mA]d. Separate Class I (high voltage) and Class II PELV wiringe. Suitable for use with Advance Transformer Mark X ballasts

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-9

Page 10: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

6. Internal Time clocka. Continue to keep time for at least two weeks without external power

7. Store scenes in non-volatile memory8. Programmable password security

a. Provide multi-level electronic password locks1) User Preset Scene information2) Setup and configuration3) Station User Lockout

9. Provide a terminal strip for connection to an external keyswitch1) Keyswitch to have configurable functionality

10.Connect directly to [Leviton] low voltage occupancy sensors1) Occupancy sensors configurable to activate and/or de-activate user-

programmed scenes11.External Trigger

a. Provide auxiliary input to trigger any sceneb. Optionally, lock Master station

12.Controlsa. Backlit LCD display

1) Provide a visible menu-driven user interface for programming and operation2) Two (2) lines of sixteen (16) characters3) LED backlit

a) Electro-luminescent backlighting not acceptable4) Display relevant information including preset status, illumination levels in

percent, time of dayb. Eight (8) Scene Buttons

1) Automatically illuminate to indicate currently selected Sceneb. LED bar-graphs

1) Display illumination level for eight (8) Scenesc. Raise and Lower pushbuttons next to each LED bar-graph

1) Allow manual over-ride without modifying programmed scenesa) Allow operator to bring any Zone to 100% illumination instantly by

pressing the Raise pushbutton twiceb) Allow operator to turn any Zone Off instantly by pressing the Lower

pushbutton twicec. Numerical indicators above each bar-graph

1) Indicate zone being controlled for Groups 1 and 2 onlyd. INFO button above each bar-graph

1) Display alphanumeric Zone label and illumination level on LCDe. Buttons

1) Page: Select among four (4) groups of eight (8) zones

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-10

Page 11: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

2) MAX: 100% illumination, all Zones3) OFF: All Zones Off

13.Air-gap Off switch to eliminate shock hazards when servicinga. Accessible on the face

14. Infrared Receiver - Compatible with Leviton remote controls 15.Physical

a. Fit within a 4-gang back box, 2.5 inches deep with a ¾-inch 4-gang device coverb. Fit within a 5-gang box, 2.5 inches deep with a ¾-inch 4-gang device coverc. Faceplate

1) Seamless, showing no visible means of wall connection2) Available in white, ivory, almond, gray, and black3) Available with translucent cover available so that LEDs remain visible when

cover is down4) Blank stainless steel

16.Environmental1) Operating Temperature Range: 0ºC to +40ºC.2) Relative Humidity: 20% to 90% non-condensing.

17.Non-Volatile Memorya. Provide a 20-year warrantyb. Store all system settingsc. Ensure that all lights return automatically to currently set levels following a power

interruption2.4SOFTWARE

A. PC interface for installation, setup and programming1. Windows GUI (Graphical User Interface)2. Functionality: program the following

a. Namesb. Scheduled scene changesc. Zone parameters

1) Minimum light level2) Lock / Unlock: prevent / allow changing Zone’s illumination level

d. Date and time3. Store system settings in non-volatile memory for uploading to same-system

controllers on the networkB. Patch any zone to any channel or groupC. Configure any D4000 system dimmer from front panelD. Remote to any other Master stationE. Control any LumaNet receiving devices from the 32 control zones (channels)F. Scenes

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-11

Page 12: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1. Select scenes 1-8, Max and Off from Master station2. Select any scene from an Entrance station3. Record Max & Off scenes4. Set individual fade time for each Zone

1) 0-59 seconds in 1 second increments2) 1-99 minutes

5. Exclude any zone from a scene6. Minimum fade-up time from Off: two seconds

G. Sequencer1. 64 steps2. Programmable fade time for each step3. Can run once or continuously in a loop4. Supports multiple sequences5. Can be activated manually from any master or entrance station, at a scheduled time,

or from any sceneH. Scheduler

1. Weekly scheduler2. Astronomical time clock3. Recall scenes or start/stop sequencer4. Program up to 64 scheduled events

I. Daylight Harvesting1. Support Closed-Loop systems2. Requires Leviton Network Protocol Converter (NPC) [or a-2000 dimmer panel]

J. Room Partitioning1. Combine and separate dimming and switching loads throughout four (4) partition-

able spaces2.5REMOTE STATIONS

A. Physical:1. Mount in a standard 1 gang, 2-1/4 inch deep back box

a. Capable of being gang mounted with other remote stations to access up to thirty-two (32) scenes

2. Color: WhiteB. Controls:

1. Buttons: Backlit to indicate current preset or control selection2. Labels

a. Applied [at the factory] [in the field] as [standard: Scene 1, Scene 2, Scene 3, etc.] [as shown on the drawings]

C. Configurations1. Provide the following as shown on the drawings:

a. One (1) button stations

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-12

Page 13: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1) Sequencer [Leviton p/n D42SQ-00W]: start or stop a sequence.2) Event Timer [Leviton p/n D42ET-00W]: start or stop an event.3) Link Station [Leviton p/n D42LI-NKW]: join or separate the controls for two

adjacent rooms respective of the position of a movable partition.4) Lock Station [Leviton p/n D42LO-CKW]: lock or unlock a control station at a

remote location.b. Two (2) button stations with infrared receivers

1) Master Raise/Lower Station [Leviton p/n D42RL-00W]: master dimming and brightening of a selected scene

2) One Scene Station [Leviton p/n D42P1-00W]: select Scene 1 and OFF3) MAX/OFF Station [Leviton p/n D42MO-00W]: select MAX and OFF

c. Three (3) button station with infrared receiver1) MAX/One Scene/OFF Station [Leviton p/n D42P1-M0W]: select MAX, Scene 1

and OFFd. Four (4) button station with infrared receiver

1) MAX/RL/OFF Station [Leviton p/n D42MO-RLW]: select MAX and OFF; master dimming and brightening of a selected scene

e. Five (5) button stations with infrared receivers1) Four Scene Station [Leviton p/n D42P4-00W]: select Scenes 1 through 4 and

OFF2) MAX/RL/One Scene/OFF Station [Leviton p/n D42P1-RLW]: select MAX,

Scene 1 and OFF; dimming and brightening of a selected scenef. Eight (8) button stations with infrared receivers

1) MAX/RL/Four Scene/OFF Station [Leviton p/n D42P4-RLW]: select MAX, Scenes 1 through 4 and OFF; dimming and brightening of a selected scene

2) Eight (9/16) Scene Station [Leviton p/n D42P9-16W]: select Scenes 9 through 16

g. Ten (10) button stations with infrared receivers1) MAX/Eight Scene/OFF Station [Leviton p/n D42P8-00W]: select MAX, Scenes

1 through 8 and OFF2) Eight (9/16) Scene/RL Station [Leviton p/n D42P9-RLW]: select Scenes 9

through 16; dimming and brightening of a selected scene2. Furnish each station complete with a faceplate:

1) [Leviton] [“Decora Plus”] [screw-less polycarbonate] [803XX Series] [“Decora”] [commercial grade nylon] [standard size 804XX-N Series] [midway size PJ26X Series] [residential grade plastic] [standard size 804XX Series] [midway size 806XX Series] [white] [as shown on drawings] [metal] [standard size] [oversize] [Type 302 stainless steel finish] [finished as shown on drawings]

D. Electrical: 12 VDC2.6ROOM COMBINE STATIONS

A. Physical:

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-13

Page 14: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1. Mount in a standard 1 gang, 2-1/4 inch deep back box2. Color: Manufacturer’s standard “white”3. Faceplate

a. Display graphic of the room layoutb. Color selected by Architect/Engineerc. No visible attachment

B. Controls1. Buttons backlit to indicate current wall position2. Labels

a. Applied [at the factory] [in the field] as [standard: Partition A+B, Partition C+D, etc.] [as shown on the drawings or as directed by Architect/Engineer]

C. Electrical: 12 VDCD. Configurations

1. Provide the following as shown on the drawings:a. One (1) button control station

1) Two Room/One Wall Combine Station [Leviton p/n D42CS-01W]: combine/separate lighting controls for two (2) rooms with one (1) partition

b. Two (2) button control station1) Three Room/Two Wall Combine Station [Leviton p/n D42CS-02W]:

combine/separate lighting controls for three (3) rooms with two (2) partitionsc. Three (3) button control stations

1) Three Room/Three Wall Combine Station [Leviton p/n D42CS-3AW]: combine/separate lighting controls for three (3) rooms with three (3) partitions

2) Four Room/Three Wall Combine Station [Leviton p/n D42CS-03W]: combine/separate lighting controls for four (4) rooms with three (3) partitions

d. Four (4) button control station1) Four Room/Four Wall Combine Station [Leviton p/n D42CS-04W]:

combine/separate lighting controls for four (4) rooms with four (4) movable partitions.

2.7 INFRARED REMOTE CONTROLA. General

1. Range: 40 feet2. Angle: 100 degrees

B. Functions:1. All IR Controllers

1) Bright/raise button2) Dim/lower button3) one-touch maximum illumination button4) all devices off button

2. Four Scene IR Controller [Leviton p/n D42IR-04L]

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-14

Page 15: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1) four (4) scene buttons3. Eight Scene IR Controller [Leviton p/n D42IR-08L]

1) eight (8) scene buttons4. Sixteen Scene IR Controller [Leviton p/n D42IR-16L]

5) sixteen (16) scene buttonsC. Finish:

1. [Leviton] standard blackD. Electrical: 6 VDC; four (4) AAA batteries

2.8POWER EXTENDERSA. Incandescent Power Extender: [Leviton p/n PE100-1]

1. Suitable Loads: Incandescent, magnetic low voltage, halogen and neon/cold cathode.

2. Input Voltage: 120 VAC, 60 Hz.3. Load Rating: 1920 W/VA.

B. Fluorescent Power Extender: [Leviton p/n PE200-1 or PE200-7 as required]1. Suitable Loads: Fluorescent dimming ballasts.

a. Compatible Ballast Manufacturers:1) Advance Mark X™ Series.2) Lutron Hi-Lume™ Series.

b. Input Voltages: 120 or 277 VAC, 60 Hz as required. See drawings for all circuit voltage requirements.

c. Load Ratings: 1) 1920 W/VA at 120 VAC, 60 Hz.2) 3000 W/VA at 277 VAC, 60 Hz.

2. Analog (0-10 VDC) Dimming Fluorescent Power Extender: [Leviton p/n PE300]3. Suitable Loads: Fluorescent dimming ballasts.

a. Compatible Ballast Manufacturers:1) Advance Mark VII™ Series.2) OSRAM/Sylvania Quicktronic Helios™ Series.

4. Input Voltage Range: 105 to 305 VAC, 60 Hz.5. Load Ratings:

a. 2400 W/VA at 120 VAC, 60 Hz.b. 5500 W/VA at 277 VAC, 60 Hz.

6. Output Ballast Control: 0-10 VDC.C. Electronic Low Voltage Power Extender: Leviton p/n PE400-1]

1. Suitable Loads: Incandescent and electronic low voltage.2. Input Voltage: 120 VAC, 60 Hz.3. Load Rating: 1000 W/VA.

D. Two Zone Power Extender: [Leviton p/n PEAUX-12]

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-15

Page 16: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

1. Suitable Loads: Incandescent, magnetic low voltage, halogen and neon/cold cathode.

2. Input Voltage: 120 VAC, 60 Hz.3. Load Rating: 1920 W/VA total or 1000W/VA per zone.

2.9COMPONENTSA. Architectural Lighting Control Stations

1. Network Master Stationa. Multi-Zone Network Lighting Control [Leviton p/n D4200–0LW]

2. Network Master Stations With Dimmersa. 120V Multi-Zone Network Lighting Control with six (6) 1000W/VA dimmers

[Leviton p/n/ D4206–1LW]b. 230V Multi-Zone Network Lighting Control with six (6) 800W/VA dimmers [Leviton

p/n/ D4206–2LW]3. Master Stations With Dimmers

a. 120V Four-Zone Lighting Control with four (4) 1000W/VA dimmers [Leviton p/n D4104-1LW]

b. 230V Four-Zone Lighting Control with four (4) 800W/VA dimmers [Leviton p/n D4104-2LW]

c. 120V Six-Zone Lighting Control with six (6) 1000W/VA dimmers [Leviton p/n D4106-1LW]

d. 230V Six-Zone Lighting Control with six (6) 800W/VA dimmers [Leviton p/n D4106-2LW]

4. Master Station Accessoriesa. Standard Doors

1) White Door & White Frame [Leviton p/n D32CK-0WW]2) Ivory Door & Ivory Frame [Leviton p/n D32CK-0II]3) Almond Door & Almond Frame [Leviton p/n D32CK-0AA]4) Grey Door & Grey Frame [Leviton p/n D32CK-0GG]5) Black Door & Black Frame [Leviton p/n D32CK-0EE]6) Smoke Door & White Frame [Leviton p/n D32CK-0SW]7) Light Almond Door & Light Almond Frame [Leviton p/n D32CK-0AT]8) Smoke Door & Black Frame [Leviton p/n D32CK-0SE]

b. Doors With LCD Status Window9) White Door & White Frame [Leviton p/n D32CK-HWW]10) Ivory Door & Ivory Frame [Leviton p/n D32CK-HII]11) Almond Door & Almond Frame [Leviton p/n D32CK-HAA]12) Grey Door & Grey Frame [Leviton p/n D32CK-HGG]13) Black Door & Black Frame [Leviton p/n D32CK-HEE]14) Smoke Door & White Frame [Leviton p/n D32CK-HSW]15) Light Almond Door & Light Almond Frame [Leviton p/n D32CK-HAT]

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-16

Page 17: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

16) Smoke Door & Black Frame [Leviton p/n D32CK-HSE]c. Infrared Remote Controls

17) Scenes 1-4, Raise, Lower, Max, & Off [Leviton p/n D42IR-04L]18) Scenes 1-8, Raise, Lower, Max, & Off [Leviton p/n D42IR-08L]19) Scenes 1-16, Raise, Lower, Max, & Off [Leviton p/n D42IR-16L]

5. Remote Stationsa. D4200 Room Combine Stations

1) Two rooms with one movable partition [Leviton p/n/ D42CS-01W]2) Three rooms with two movable partitions [Leviton p/n/ D42CS-02W]3) Three rooms with three movable partitions [Leviton p/n/ D42CS-3AW]4) Four rooms with three movable partitions [Leviton p/n/ D42CS-03W]5) Four rooms with four movable partitions [Leviton p/n/ D42CS-04W]

b. D4200 Remote Wall Stations1) Sequencer [Leviton p/n 000-D42SQ-00W]2) Event Timer [Leviton p/n 000-D42ET-00W]3) Link [Leviton p/n 000-D42LI-NKW]4) Lock [Leviton p/n 000-D42LO-CKW]5) Master Raise/Lower [Leviton p/n 000-D42RL-00W]6) One Scene [Leviton p/n 000-D42P1-00W]7) MAX/OFF [Leviton p/n 000-D42MO-00W]8) MAX/One Scene/OFF [Leviton p/n 000-D42P1-M0W]9) MAX/RL/OFF [Leviton p/n 000-D42MO-RLW]10)Four Scene [Leviton p/n 000-D42P4-00W]11)MAX/RL/One Scene/OFF [Leviton p/n 000-D42P1-RLW]12)MAX/RL/Four Scene/OFF [Leviton p/n 000-D42P4-RLW]13)Eight (9/16) Scene [Leviton p/n 000-D42P9-16W]14)MAX/Eight Scene/OFF [Leviton p/n 000-D42P8-00W]15)Eight (9/16) Scene/RL [Leviton p/n 000-D42P9-RLW]

B. Remote Dimmers1. 120V network dimmer for incandescent, MLV, forward-phase-compatible electronic

low voltage, two-wire fluorescent lamps and ballast, Leviton Power Extenders [Leviton p/n D4006–1LW]

2. 230V network dimmer for incandescent, MLV, forward-phase-compatible electronic low voltage, two-wire fluorescent lamps and ballast, Leviton Power Extenders [Leviton p/n D4006–2LW]

C. Power Extenders1. [Leviton p/n PE100-1]2. [Leviton p/n PE200-1]3. [Leviton p/n PE200-7]4. [Leviton p/n PE300]

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-17

Page 18: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

5. [Leviton p/n PE400-1]D. Low Voltage Control Interfaces

1. Contact Closure Interface2. Ethernet Interface[s]

a. Network Protocol Converter [Leviton p/n NPC XP]b. Network Protocol Converter [Leviton p/n NPC DLR]

E. Sensors1. Ceiling-Mounted Infrared Receivers

a. [Leviton p/n D42IR-RSW]b. [Leviton p/n D42IR-RFW]

2. Outdoor Photocell, 0-10V [Leviton p/n PCOUT-000]3. Indoor Photocell, 0-10V [Leviton p/n PCIND-000]4. Atrium Photocell, 0-10V [Leviton p/n PCATR-000]5. Skylight Photocell, 0-10V [Leviton p/n PCSKY-000]6. Occupancy Sensors

PART 3 – EXECUTION3.1INSTALLATION

A. Coordinate, receive, mount, connect, and [place into operation] all equipment.B. Install equipment in accordance with manufacturer’s installation instructions.

1. Install relay panels in locations where audible noise is acceptable.2. Use only with 75° C (167° F) copper wire at 75% ampacity.

C. Provide complete installation of system in accordance with Contract Documents.D. Maintain performance criteria stated by the manufacturer without defects, damage, or

failure.E. Provide equipment at locations and in quantities indicated on Drawings

1. Provide any additional equipment required to provide control intent.F. Ensure that daylight sensor placement minimizes sensors view of electric light sources;

ceiling mounted and fixture-mounted daylight sensors shall not have direct view of luminaries.

G. Furnish all conduit, wire, connectors, hardware, and other incidental items necessary for a properly functioning lighting control and relay system as described herein and shown on the plans. The Electrical Contractor shall maintain performance criteria stated by the manufacturer without defects, damage, or failure.

H. Comply with manufacturer’s product data, including shop drawings, technical bulletins, product catalog installation instructions, and product carton instructions for installation.

I. Test that all branch load circuits are operational before connecting loads to system load terminals, and then de-energize all circuits before installation.

J. DO NOT apply power to the relay system during construction and prior to turn-on unless specifically authorized by written instructions from the manufacturer.

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-18

Page 19: Sector CSI 04 Spec [260943] 09-09-2009 - Leviton · Web viewFor best results, lamp brands and types should not be intermixed on a circuit All conduit, wire, connectors, hardware,

CSI/AIA Specifications MODULAR DIMMING CONTROLS SECTION 16572

K. [Programming: Program [low-voltage] [and] [digital switch] functionality at the control panel.]

L. Furnish information as to the exact brand, type, and model number of the fluorescent dimming ballasts being used in the fixtures on this project to the dimming manufacturer.1. Failure to inform dimmer manufacturer terminates all responsibility for system

compatibility with the ballasts on job site.M. Wire networks with 2000 feet (600 meters) total run length: verify run lengths prior to

installation.1. No splices. No exceptions.2. Provide field installation reports verifying that cable installations are operational and

compliant with standard.N. Notify the Lighting Control System Supplier that the system is ready for testing.

1. Provide notification a minimum of thirty (30) days prior to the date for testing.3.2SITE VERIFICATION

A. Verify that wiring conditions, which have been previously installed under other sections or at a previous time, are acceptable for product installation in accordance with manufacturer’s instructions.

3.3FIELD MEASUREMENTSA. Take field measurementsB. Coordinate the physical size of all equipment with the architectural requirements of the

spaces into which they are to be installed.3.4 INSPECTION

A. Inspect all material included in this contract prior to installation.B. Notify Manufacturer of unacceptable material prior to installation.

3.5SITE PROTECTIONA. Contractor shall protect installed product and finished surfaces from damage during all

phases of installation including storage, preparation, testing, and cleanup.

END OF SECTION

Leviton 05/01/11MODULAR DIMMING CONTROLSDimensions D4000 System 26 09 36-19