Secret Fix SF500 - Building ProductsThe range of products available, ... establish local and general...
Transcript of Secret Fix SF500 - Building ProductsThe range of products available, ... establish local and general...
CI/SfB (47) Nh2
July 2004
Secret Fix SF500
Technical
Specifications
1
Contents
System Benefits 2
Services 2
Applications, Aesthetics
Weatherability and Standard Details 3
Durability/Warranties, Quality
and On-site Manufacture 4
SF500 Profile and Load/Span Considerations 5
Curving, Lateral Restraint,
Thermal Expansion and Steelwork 6
Fire 7
Typical Constructions 8
Vapour Control, Breather Membranes,
Air Permeability and Insulation 9
Unloading and Handling,
Site Storage and Lifting 10
Use of Tools 11
Standard Components 12
Fixings 13
Setting Out 14
Fixing Verge Section
(Starter and End Details) 15
Ridge Detail 16
Eaves Gutter Detail 17
Valley Gutter Detail 18
Hip Detail 19
Hip Valley Gutter Detail 20
Rooflights 21
Roof Access, Fall Arrest Systems
and Latchways 22
Roof Penetrations 23
Roof Step 24
Replacing Damaged Sheet 25
On-Site Production 26
Secret Fix SF500
Introduction
Euroclad Ltd is one of the UK’s foremost
producers of metal cladding systems.
Continuous development is specifically
geared towards offering Architects and
Specifiers the ultimate choice in design
flexibility. The range of products available,
developed over 20 years, allows
multi-performance specification covering
the whole building envelope in a wide
range of materials.
Secret Fix SF500 is a case in point,
giving the Specifier and Contractor a
proven and simple system to use for low
pitch roof applications, where speed of
fixing and guaranteed performance are
required and continuity of finish, colour
and material choice are paramount.
SF500 has been specifically designed to
function at design pitches down to 2.5°
(minimum actual pitch 1°), with no
external penetration of the sheet, no end
laps and low maintenance performance.
Manufactured predominantly in HPS200
coated steel, the system offers many of
the advantages of a true standing seam
system, but is simpler to install and may
be more simply integrated into projects
where the material of choice is steel
rather than aluminium.
3
Applications
SF500 has been used in educational, commercial,
retail, industrial and leisure applications amongst
others. The system is suitable for new build,
refurbishment, over-roofing and flat to pitch
conversion and can be considered as a viable
alternative to sealed membrane, felt or asphalt
systems.
The ability to produce the sheets on site, in
single lengths and the simple ‘snap fix’ overlap
gives SF500 its greatest advantages over other
systems designed for low pitch application.
Aesthetics
SF500 has low visual impact allowing clean,
uncluttered roof lines.
Standard stock materials in a wide range of
colours in HPS200, PVDF, Leathergrain Plastisol
along with Aluzinc can be used. Standard colour
charts are available from Euroclad and are
included in the Roofing and Cladding Manual.
Weatherability
SF500 provides superb weathering performance
through a precision engineered snap fit 55mm
overlap. The underlap is designed to take a
3mm bead mastic seal, whilst the low profile
pan allows excellent drainage at low pitch.
2
System Benefits
• BBA assessed performance
• No external fixings
• Long sheet length allowing end-lap free construction
• Sheet fixed directly to structure with no separate clips or brackets
• Drive-on-drive-off manufacture if required,reducing transport and crane costs
• Fast installation
• Short lead times
• Range of cost effective standardaccessories
• Confidex Guarantees on HPS200 material
• Extensive Stocks of materials
• Robust profile
• Full integration with Euroclad Liner Paneland associated products
• Comprehensive range of related services
Services
Euroclad offers specifiers a broad spectrum
of support from initial enquiry and bespoke
technical consultation to project realisation.
NBS draft specifications are provided for all
standard constructions and can be tailored to
suit project performance requirements through
consultation.
This service draws on Euroclad experience and
the flexibility of built-up systems, to respond to
individual requirements for specific thermal,
acoustic, structural and other performance
considerations.
Euroclad can provide specific advice to help
design a wide range of features that enhance
basic concepts. This allows full integration of
the roof construction with flashings and bespoke
fabrications as well as composite or twin-skin
wall cladding.
Euroclad products are supported through RIBA
Information Services with full coverage in NBS
Plus, On-line Services and Product Selectors.
Euroclad has RIBA CPD Providers Network and
RIAI approval.
Secret Fix SF500
Single eaves-to-eaves or ridge-to-eaves sheet
lengths with no end laps and no external fixings
penetrating the sheet, along with on-site
manufacture, means that sheet lengths are
effectively limited only by handling requirements.
Carefully designed accessories and details
ensure no compromise of performance.
The structurally tested system and longevity
of materials provide long-term security.
Standard Details
A CD-ROM of Standard Construction Details
modelled for performance under the Building
Regulations is available on request.
Euroclad provides systems which can be
modelled in house on state-of-the-art
3 dimensional software to be compliant with
Part L2 of the Building Regulations.
This facility can be used as easily for details
as it is for plane elements.
There are inevitably cases where a one-off,
bespoke detail is required for a particular
situation. In these circumstances, Euroclad
will provide relevant advice.
Standard component drawings and construction
details are shown in this brochure along with a
basic component list and other useful information.
Further assistance may be obtained from the
Euroclad Technical Department.
5Load/Span Considerations
The responsibility for defining and specifying wind
loads and purlin centres lies with the structural
engineer for the project. Wherever possible the
loads should be determined while the adjustment
of purlin centres is still possible, allowing the
chosen roof profiles performance to be taken
into account. BS 6399 pt 2 should be used to
establish local and general wind pressures.
The new Eurocode EN 1991- 1-4: Wind Actions
is currently in the process of being introduced.
It is anticipated that the final results derived from
this standard will be essentially the same as
those reached using BS 6399. CP3 chapter
5 pt 2: 1972 and its amendments was declared
obsolete in 1998 and was due for full withdrawal
June 2001.
View of SF500 Profile
4
Durability and Warranties
The Confidex Guarantee is available for all SF500
supplied in Corus HPS200 material. Full details
are available in the Roofing and Cladding Manual.
The majority of colours used for roof applications
can achieve CD1 status under the Guarantee.
BBA Certification covering standard
constructions is due for issue in the near future.
Latent Defects Insurance is available for
all Euroclad products covering design,
workmanship and materials and is the most
comprehensive cover, available.
Elite Warranty System
Euroclad offers a 25-year warranty on all
components of the fully warranted roofing and
cladding systems manufactured or approved by
Euroclad. The building designer and owner can
therefore be confident the system specified will
be installed by Euroclad’s ‘Elite
Contractor Network’ to the highest
standard. Please consult the
Euroclad Technical Department for specification
of the systems and their installation procedures.
Quality Assured
Euroclad’s commitment to quality and service
is reflected in it’s ISO 9001:2000 Quality
Management System which ensures that
systems are in place from manufacture to after
sales service. The company is
also accredited with ISO14001,
demonstrating its commitment
to the environment.
Euroclad interfaces with the industry in a way
which has earned a reputation for service and
flexibility that is second to none.
Euroclad works closely with the industry to
ensure that high standards are achieved and
regularly contributes to industry development
on issues such as amendments to the Building
Regulations, fire in construction and fragility
testing of steel liners and all pertinent subjects.
On-site Manufacture
Normal delivery by road can be achieved for
sheet lengths up to 14 metres. Road haulage
can be arranged for lengths up to 28 metres,
however, it is usually preferable to have the
sheets rollformed on site.
Transporting very long sheets can be a costly
and time consuming business involving
requests for movement documentation, police
escorts etc but Euroclad’s mobile rollforming
capability can obviate these problems.
By rollforming from a trailer which is self
contained and drives on and off the site,
problems such as limited access, high transport
costs, extended lead time due to transport
permits and potential damage during transit
are removed.
Euroclad will carry out pre-manufacture
assessment visits to ensure that everything runs
to plan and can provide method statements,
lifting beam certificates and advice for each
project on request.
Straight sheets can be rolled at an impressive
rate of 3000 linear metres per day and may
either be rolled up a ramp directly onto the roof
structure or lifted by crane, which can be
co-ordinated with the manufacture to
minimise costs.
Secret Fix SF500
500mm cover width
Colour side
52 54
500500
colour side
The tables below have been set out to allow the designer to look up Span against Load.
Load Span Table
SF500 Load Spans
Loads in kn/m2 double/multispan for 0.7mm thickness
Note: Imposed Deflection Limit = L/250 Weight per linear metre = 3.870 KGS (0.7mm)Suction Deflection Limit = L/150 Weight per square metre = 7.741 KGS (0.7mm)
Span (M) 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
New Imposed (Factor 1.6) 4.75 4.48 4.15 3.92 3.65 3.38 3.11 2.91 2.70 2.43 2.22
New Suction (Factor 1.4) 4.27 4.00 3.62 3.11 2.70 2.25 2.11 1.98 1.84 1.75 1.63
New Imposed (Factor 2.0) 3.80 3.58 3.32 3.13 2.92 2.71 2.49 2.33 2.16 1.95 1.78
New Suction (Factor 2.0) 2.99 2.80 2.53 2.18 1.89 1.58 1.47 1.38 1.29 1.23 1.14
The maximum permissible cantilever for SF500 sheet is 300mm.
7
BS 476 Part 3: External fire exposure roof test
Roofs are graded according to the length of time
they resist fire from the outside (e.g. fire in an
adjacent building) and the distance of superficial
spread of flame on the outside surface.
The ‘Part 3’ test procedure has to be performed
on a section of roof structure and it is not just
a test of material. There is no reason why a
properly built pitched roof constructed of Corus
organic and metallic coated steels should not
achieve the top classification, AA. The Building
Regulations designate profiled sheets of
galvanised steel and PVC and PVF2 organic
coated steels as grade AA. Other shapes and
other Corus coatings on steel are entirely within
the spirit of the Regulations and may be
regarded as satisfactory.
BS 476 Part 4: Combustibility
Either a material burns or it does not, there are
no intermediate degrees. All Corus metallic
coated sheets, such as Galvatite hot-dip
galvanised steel or Zalutite, are deemed ‘non-
combustible’. Organic coated steels such as
Colorcoat have to be further assessed.
BS 476 Part 6: Propagation
This is a test which assesses the rate of heat
release of a material in burning, by means of a
standard procedure. This measures the total
heat given off by a material over a period of
twenty minutes expressed as an index of
performance, I, calculated from an empirical
formula contained in the standard. In addition,
the initial heat given off over shorter periods –
expressed as the sub-indices i1, i2, and i3 –
is also assessed. All Corus coated steels have
indices of performance, I, not exceeding 12
and i1 (first 3 mins) not exceeding 6, which have
particular significance in relation to Building
Regulation requirements.
BS 476 Part 7: Surface spread of flame
This test grades materials in Classes 1 down
to 4 in descending order of ranking. Test
certificates are available for the Colorcoat range
of products whichconfirm compliance with
Class 1.
BS 476 Parts 21 and 22:Fire resistance of elements ofconstruction
These tests are designed to assess the
performance of complete elements. These
should remain stable, resist penetration of flame
and hot gases and limit the transfer of heat from
one side to the other for the fire resistance
period required, usually 1/2, 1, 11/2 or 2 hours.
Steel sheet cladding alone is given a zero rating
in terms of fire resistance and would therefore
be classified as an ‘unprotected area’ in the
context of the Building Regulations. When used
in conjunction with suitable insulating materials,
the required degree of fire resistance can be
met. It should be noted that in most buildings,
a large percentage of the external wall may be
designated ‘unprotected areas’ so that profiled
steel cladding can be used without any fire
resistance requirement
The essential parts of the BS 476 relevant to Corus Products are listed below:
6
Curving
SF500 can be successfully self curved to a
minimum radius of 85M.
Lateral Restraint
With reference to British Standard 5427: 1996
‘Code of Practice for the use of Profiled Sheet
for Roof and Wall Cladding on Buildings’, Part 1
‘Design’ Euroclad trapezoidal external profiles
and Euroclad liner profiles in >.4mm gauge,
fixed according to the recommendations
contained the Euroclad literature (other than
perforated liners), will provide lateral restraint to
the top flange of the purlins. Euroclad liners
used in conjunction with SF500 will therefore
provide lateral restraint.
Thermal Expansion
The rate of expansion for steel is much lower
than that of aluminium and SF500 requires no
special detailing as such to accommodate it.
Steelwork
On very low pitches there may be a build up of
materials at the eaves line due to the inclusion
of closure flashings, gutter flanges etc which
should be allowed for to maintain the fall either
by adjustment of the purlin at the eaves or by
reduction of spacer height etc.
Tolerances acceptable for purlin levels are
as follows:
Secret Fix SF500
Structural movement joints present should be
echoed in the sheeting.
The maximum allowable step at purlin laps or
sleeved joints is +/- 10mm for double skin
situations and +/- 5mm for single skin roofing.
Element Tolerances (in the level of thepurlin relative to the purlinseither side)
Purlin Levels Purlin spacing above designlevel/180 or 10mm (chooselower of these values)
Purlin spacing below designlevel/360 0r 5mm (chooselower of these values)
Purlin Slope +/- 1° (purlins should alwaysbe at 90° to the roof slope)
9
Vapour Control
Following research commissioned by the
MCRMA, the BRE report of Feb 2000 concluded
that “metal liners provide an effective vapour
control layer in twin skinned metal roof
construction. So long as the cladding is installed
to a reasonable standard with a well sealed liner,
it is not necessary to use a separate plastic VCL
or breather membrane in most applications.”
With more complex build-ups in very high
temperature/ humidity buildings extra
precautions are still needed in both built-up and
composite systems. For SF500 double skin
constructions using sealed liner panels the
current recommendations are as follows:
Air Permeability
Correctly installed built-up systems,
incorporating sealed profiled metal liners,
to form an effective vapour control layer in twin
skinned metal roof constructions, can be
expected to achieve an air permeability of
5m3/hr/m3 (at 50 Pascals).
Project specific advice should be sought from
the supplier where separate VCL’s are required
or if there is any doubt as to requirements.
Insulation
There are several materials available, the most
commonly used being mineral fibre and glass
wool quilts. The key factors to look out for in the
insulation are:
Lambda 90/90 thermal conductivity – ensures
that the thermal conductivity complies with CE
regulations, non-combustibility, water
repellent/non-hygroscopic, chemically inert,
rot proof, ease of handling, recyclability, CFC
and HCFC free.
8
Typical View of Built-up System
Rail and Bracket SpacerSystem and Quilt
The Secret Fix sheet may be used in a number
of constructions. In many cases of refurbishment
the substructure is already defined and a system
must be devised which best suits the particular
circumstances of the existing building.
However, in a new construction there are several
systems which are commonly used. The one
illustrated on this page uses the Euroclad liner
panel on the inner skin. The built up system is
an adaption of the standard system, simply
replacing the normal trapezoidal sheet with the
Secret Fix. Perhaps the most commonly used
system for new buildings is the double skin
insulated construction which comprises sealed
inner liner, optional additional VCL, bar & bracket
spacer, insulation and SF500 outer sheet.
Insulation thickness and composition can
be varied to suit design requirements.
Euroclad Liners in 19/1000 and 32/1000 profile
are the most commonly used and are available
in .4mm and .7mm coated steel with Bright
White Liner Enamel finish. Perforated liner
in .7mm can be supplied if required for acoustic
projects. Information on Non Fragility of Euroclad
liners is available in the Liner Profiles Booklet.
Euroclad should be consulted for draft NBS
specifications and details which are tailored to
performance requirements for insulation, vapour
control, acoustics etc and can be further
adapted for project specific requirements.
Secret Fix SF500
Breather Membranes
Work has been carried out by BRE East Kilbride,
in collaboration with the MCRMA, to examine
in detail the factors that determine the risk of
condensation within twin skin metal roofs.
This work has demonstrated that, if a well sealed
liner is used in conjunction with vented fillers for
the outer sheet, only small amounts of
condensation may occur on the external sheet
over the winter and there will not be sufficient
accumulation to cause dripping or running.
Therefore, so long as the cladding is installed
with a high standard of workmanship with
appropriate detailing, especially a well sealed
liner, it is not necessary to install a breather
membrane except in cases where there is likely
to be an unusually high internal moisture load.
HumidityClass
BuildingType
1 Storage areas
2 Offices, shops
3 Dwellings with low occupancy
4 Dwellings with high occupancyie: Sports halls, kitchens, canteens,buildings heated with un-flued gasheaters etc
5 Special buildings ie Swimmingpools, brewerys, laundrys etc
11
Use of Tools
Fixing tools are supplied with every
contract and are refundable upon return.
To ensure that the product is fixed correctly the
following tools are supplied with every contract
for SF500. It is essential that they are used,
and used in the correct manner.
Profile Template
Made of plastic the template is positioned
adjacent to the fixing point whilst the sheet is
being fixed and ensures that no spread of cover
width can occur.10
This section is intended to be a general guide
to principles for fixing the system but is not
exhaustive. The information provided in the
Technical Reference section should be read
in conjunction with the following and further
information and assistance is available from
Euroclad on request.
Unloading and Handling
SF500 sheets are typically of considerable
length and therefore careful arrangements
must be made to avoid damage whilst
handling. Sheets up to 8M long may be
unloaded with forklifts taking care not to
damage the pan of the sheet. It is preferable
to use a lifting beam attachment with slings
if unloading with a forklift where sheets are
over 8M long.
Site Storage
Where sheets are to be stored on the ground
they should be be on a dry, firm base, sloped
to allow drainage and should be protected
from accidental damage and theft.
Lifting
The structures load bearing capacity should
be considered where packs and sheets are
laid on the roof and they must be restrained
from sliding down the slope or being moved
by wind forces.
The sheet underlap should be oriented towards
the direction of lay ready to set out.
A Spreader Beam to assist unloading will be
supplied automatically with all SF500 orders
where sheet lengths are in excess of 8M unless
we are notified otherwise. Spreader beams are
available for sheets up to 60m long.
SF500 sheets up to 8 metres can usually be
successfully loaded to the roof without a lifting
beam. However, longer sheets must be lifted
with a beam and the correct slings.
Sheets over 60m are normally rolled directly
from the rollformer up a ramp to the roof
(as illustrated on page 28). A telescopic ramp
can be hired from Euroclad.
SF500 packs of sheets will be packed in
bundles of 18 sheets, however each pack will
weigh no more than one tonne in total for
shipping by road.
Packs can be produced on-site to 2.5 tonnes
when utilising the Spreader Beam.
Proof Load Test up to 5 tonnes using the 52.5m Spreader Bream.
Turn-up/down-Tool
Carefully designed to turn up the pan of the
profile at the ridge/hip detail.
To turn down the pan of the profile at the
eaves detail.
Secret Fix SF500
The tool is handed and it must be used the
right way around.
Turndown must be a minimum of 10°.
Standard Components
The SF500 system has been designed to
incorporate Standard Accessory components
which should be used to ensure the integrity
of the system.
13
Fixings
The fixings listed are suitable for use with the
system. All those listed are carbon steel.
Stainless steel fixings are also available if required.
Primary Fixings are listed in red,
Secondary fixings are listed in blue.
Details of fixing locations are given below the table.
Primary Fix
Fixes the underlap of the profile to the main
purlin/spacer. Also fixes the bottom flange of the
verge section and the Spacer brackets to the
purlin in the same manner. Illustrated on the
following pages.
Secondary Fix
Application and frequency as follows:
A. Verge detail to sheet. Through the flange of
the verge section, through the mastic sealant
into the crest of the profile, as shown in the
illustrations on the following pages.
B. Ridge/Hip Support Section to sheet.
Through the flange of the profile to the crest
of the sheet, as shown in the illustrations
on the following pages.
C. Flashings to Verge Section through the
2mm x 19mm mastic on the upper flange
of the Verge.
D. Flashings to Ridge/Hip Support Section
positioned between the sheet profile
crests.
E. Drip Angle to sheet pan. Preferably prior
to turning the sheet down. One number
in the sheet pan either side of each side
lap detail.
It is the responsibility of the building designer
to ensure the correct specification of all fixings.
Specific advice regarding the application of
fixings can be sought from Euroclad or
fixing suppliers.
12
65
30
30
*Requirements for these items should be notified as early as
possible to establish availability and lead time. Ridge Support
Sections and Hip Support Section Blanks to be notched out on
site are held in stock in 10A05 Goosewing Grey HPS200 but
other colours availability is subject to stock and lead time. Hip
Support sections precut to suit pitch and angle are available but
subject to lead time and stock.
Fixing details are given on the following page.
Component name Unit Length
*Ridge Support Section 2.020m
*Hip Support Section Blank 3.658m
Verge Section 3.658m
3mm dia Mastic Bead 12m roll
2mm x 19mm Mastic strip 22.5m roll
Ridge Filler 500mm
Eave Filler 500mm
*Raked Hip Ridge Filler Dependent on roof pitchand hip plan angle
*Raked Eaves Filler Dependent on roof pitchand hip plan angle
Secret Fix SF500
Application SFS Reference Frequency
Sheet to Spacer (+ secure bottom of verge)
*SD3-5,5x25 Non-washered 2 fixings at each spacer
Spacer to purlin fixings *SD3-5.5x25 2 fixings per bracket
Verge Section to sheet crown *SL2-T- A14-4.8x20 At 450mm centres
Ridge/Hip Support to sheet *SL2-T- A14-4.8x20 2 fixings at each sheet crest
Drip angle to sheet (Anchor fixing) *6604/6/3W 2 per sheet
Flashing to Ridge Support *SL2-T- A14-4.8x20 At 500mm centres
Flashing to Verge Section *SL2-T- A14-4.8x20 At 600mm centres
Flashing to Hip Support *SL2-T- A14-4.8x20 1 at the centre of each sheetprofile (varies dependent on hip)
Single Skin Application
Sheet to Cold rolled purlin *SD3-5,5x25 2 fixings at each purlin
Sheet to Hot rolled purlin SD14-5.5x32 2 fixings at each purlin
Ridge Support Section
0.7mm Gauge Colorcoat
20mm Diameter holes
Available in 2.020m length
Effective cover width 2.00m
Ridge Filler
Available in 500mm length
The ridge filler should be clipped into the ridge
support section prior to fixing.
Fixed at every crest with two secondary fixings.
The 2mm x 19mm mastic sealant is fixed to the
top face of the section to seal the joint between
the ridge support section and the ridge flashing.
The ridge flashing is fixed to the ridge support at
500mm centres between the crests of the profile.
The end detail allows the overlap over the
adjacent section.
We recommend that these are fixed as the
roof sheets are laid, not left until later.
A
D
G
FE
B
cB & C Viewed From
15
Verge Section
The section shown as ‘Verge Section B’ is in
fact the starter sheet when sheeting the roof
from right to left. The verge section is the first
item fixed to the purlins. Since all subsequently
laid panels are laid parallel to this verge section
it is imperative that it is laid correctly and at right
angles to the purlin. The distance from the edge
of the roof should also be calculated with care
as this will predetermine the position of the last
sheet relative to the other end of the roof. It will
obviously be ideal if the size of the barge board
flashings were the same at each side of the roof
and this can only be achieved by careful setting
out in the initial stages.
The procedure for fixing is as follows. The first
sheet has a strip of mastic laid on the crest as
shown and then is placed into the verge section.
The location of which is best illustrated in the
section drawing.
A fixing is then placed through the verge section
and sealant into the crest of the profile. These
are fixed at 450mm centres. The Fixing Template
is used to secure the sheet while the two Primary
fixings are fixed in to the underlap at each purlin.
A bead of 3mm matic is laid into the sheet
underlap in the grove provided and the next
sheet overlap is snapped over to continue fixing.
The bargeboard flashing is then fixed as
illustrated, again using a strip of mastic sealant.
The procedure for fixing the left hand verge detail
is very similar. It is, of course, the same verge
section reversed. The last sheet is, in this case,
already laid, but not fixed. The bottom flange of
the verge section fits inside the underlap of the
profiled sheet. The mastic and fixing requirements
are as above, or the bead mastic can be used.
14
Setting Out
This operation provides a good opportunity to
check steelwork for tolerances and to ensure
that the design roof pitch has been achieved,
particularly at the ridge and eaves. To ensure
that the system is set out correctly the fixing
template must be employed and used correctly.
Typical SF500 Roof
Secret Fix SF500
View of Verge Section B
Section of Verge B
View of Verge Section C
Section of Verge C
The SF500 sheets install to a nominal cover
width of 500mm. Care should be taken when
setting out to avoid variation between SF500
and liner panel cover width particularly where
rooflights are to be incorporated.
Sheet pan onlyturned up
150mm minimumclearancerecommended forturn up operation
17
Eaves
The eaves detail incorporates a filler which
is usually positioned above the drip angle.
The eaves flashing shown here is used in
conjunction with a built up system using
Euroclad liner panel. The detail shown is fairly
typical but there are many variations on the
same theme.
The last 25mm of the trough is turned down
using the tool provided, which stiffens the profile
in the critical area and reduces the incidence
where water is held on the reverse of the sheet.
Anchor fixings together with their flashing,
in addition to securing the end of the sheet,
also provide an opportunity to place the small
flute filler securely.
16
Ridge Detail
The ridge support detail, together with its filler,
is designed to be fitted at 90° to the length of the
sheet in a convenient position close to the apex.
The filler clips into the ridge support and they
are fixed to the crest of the profile in the manner
shown in the illustration. It is important to
exercise great care when installing the mastic to
ensure a continuous bead in the position shown.
The illustration also reveals the pan of the profile
turned up at the very top of the sheet. Thus, a
secondary barrier is created. All sheets have the
pan turned up in the same manner under the
ridge flashing. A tool is available from Euroclad
to facilitate the up turn.
The normal ridge flashing may then be fitted
and fixed to the top flange of the ridge support
detail, as illustrated. Care must be taken not to
penetrate the crest of the profile when fixing
the ridge to the ridge support.
The ridge support detail must be fixed in
conjunction with the profile as any spread or
shrinkage of the sheet will then be immediately
evident and corrective action should be taken.
Secret Fix SF500
Not shown turned up
View of Ridge Detail A
Section of Ridge Detail A
View of Eaves Gutter G
19
Hip Detail
The hip is perhaps the most difficult section
to detail for the secret fix systems. They usually
involve very costly sections which add
significantly to the overall budget. Euroclad’s
system is straightforward and cost effective.
Essentially a modification of the ridge support
detail, the pitch of the notches and their shape
vary with the pitch of the roof and the angle of
the hip.
A ‘blank’ is supplied which is notched out by
the contractor on site to fit the profile.
The procedure for fixing is identical to that of
the ridge support.
The pan of the profile is turned up by the
Sheeting Contractor on-site.
18
View of Valley Gutter F
Secret Fix SF500
Section of Valley Gutter F
Allowance should be made to turn down the
trough of the profile and incorporate the flashing
to which the anchor fixings are attached.
The location of the anchor fixings allows the
opportunity to place the small flute filler nearer
the end of the sheets, if required. An alternative
flashing detail is shown here to that shown on
the Eaves gutter. In all cases the anchor fixing
must be applied.
Fixing the drip angle prior to turning
the sheet pan down is recommended.
The Valley Gutter detail, as illustrated, includes
the use of the Euroclad liner panel although the
principals of the construction could be amended
to exclude it if required.
Individual circumstances will predetermine which
details are applicable, but the arrangement
illustrated includes the basis of the construction.
The small flute filler will be fixed in the position
above the last spacer or the drip angle where
the anchor fixings are located.
Section of Hip Detail D
View of Hip Detail D
Sheet turned down
21
Rooflights
Curving
When self curved to minimum 85M radius,
an additional stitcher screw should be
used to secure the sheet overlap to
underlap. This fixing should be fitted on the
crown of every overlap over the gutter (ie: as
near to the end of the sheet as practical and
below the drip angle outside the insulated area).
Rooflights
A common form of roof penetration requiring
careful attention is the rooflight. Attention should
be paid to cover widths during installation of
both liners and SF500 sheet to avoid
misalignment in rooflight details.
There are a wide range of rooflights available to
suit SF500 in both GRP and Polycarbonate from
a number of manufacturers. There are two types
of standard rooflight available for SF500,barrel
vault and in-plane throughfixed.
A. Rooflights with no Primary Fixings
Where the use of primary fixings penetrating the
outer skin is prohibited the Barrel Vault rooflight
is the only satisfactory answer. One such system
is illustrated below. The extra cost of such an
item is compensated by the units integrity. The
item illustrated is manufactured in sections to fit
any size of roof opening. They must start at or
very near to the ridge but can be terminated
whenever required down slope. The system
drawing illustrates one particular type.
B. Rooflights with visible fixings
There is only one type of rooflight which can be
incorporated into the SF500 system if primary
fixings penetrating the weather sheet are
acceptable.
1000mm Cover Width
The sheet is suitable if a site assembled light
is required. The liner translucent is fixed by the
normal method. The outer sheet is a trapezoidal
shape with two side overlaps. Again primary
fixings penetrate the sheet (as illustrated) at
every purlin. End laps are possible but not
recommended below 5°. The appropriate
washers must be used with the primary fixings.
The sheet must run from ridge to eave.
A secondary translucent may be required to
form a “triple skin” system for compliance with
the building regulations.
20
Section of Hip Gutter
Rake cutting of the sheet must be carried out
with the utmost care since the profile is difficult
to cut neatly. The angle of the hip will determine
the distance between the main profiles and this
could increase the effective pitch of the profile
considerably.
The support/drip flashings can be manufactured
in plain galvanised steel up to 1.6mm thick to
give the support necessary.
View of Hip Gutter E
Section of Hip Gutter E
Secret Fix SF500
23
Other Penetrations
There are an infinite number of reasons for roof
penetrations, but where possible, on a Secret Fix
roof of low (below 5°) pitch, they should be
avoided. Inevitably it will be necessary to
accommodate such details and, with care,
satisfactory solutions can be achieved.
Two examples of the type of penetrations which
are most common are illustrated. The detail of
the flashing must be such that the troughs
should not be blocked.
If the penetration is of a diameter and position
that a trough would be completely filled then
this must be detailed back to the ridge capping,
as illustrated.
Where large penetrations are necessary it
is possible to use ridge support sections
to support the flat areas of flashing.
Note: As with any large penetration, structural
trimmers may be required to support the
built-up system.
Roof Penetrations
Section through large roof Penetration
General view of large roof Penetration
22
Roof Access
F500 is designed as a low maintenance system
but generally the sheets can be walked upon
without imposing damage. However, care should
be taken on precoated material not to damage
the coating.
Fall Arrest Systems
Design Considerations – General.
Take the following into consideration when
choosing, designing and specifying a
Fall Arrest/Restraint system for SF500:
• Always use non-penetrative systems
• Identify the areas of the roof which
require access for cleaning, maintenance
or inspection
• Give consideration to safe access points
and ground clearance, whilst keeping the
system more than 2 metres from the
nearest hazard where possible
• Review anticipated or actual work patterns
to determine the number of workers
required to use the system simultaneously.
Latchways
Euroclad’s approach to the market requires
a commitment to quality and innovation which
is reflected in Latchways ManSafe® system
utilising the Constant Force™ post.
The system has been tested for use with
Euroclad Secret Fix SF500.
Latchways plc is the world leader in the design
and manufacture of cable based fall arrest
systems offering continuous protection to
individuals working at height. Their products
are made using the highest quality components
and meet or exceed all appropriate national,
European and international standards and
legislation.
All Latchways systems are CE marked and
hold EC Declarations of Conformity. Latchways
is also a BS EN ISO 9002 certified company.
Ongoing advice and support is available from
your local installer or from Latchways on:
+44 (0)1380 732700.
Secret Fix SF500
General view of small roof Penetration
2524
It is the very nature of the Secret Fix system
that makes the successful achievement of
an end lap virtually impossible. It is in certain
circumstances however, sometimes impossible
to fix one sheet from ridge to eave.
One can think of examples such as excessive
roof slopes or problems with access which
demonstrate this point.
Euroclad have designed a step detail which
allows the specifier the advantage of using the
Secret Fix system where previously the length
of sheet required would have been prohibitive.
Using standard components the detail illustrated
reveals a strong, easily fixed effective step.
Should you require any advice on incorporating
this feature, please contact the sales office.
Traditionally a problem with Secret Fix systems is
the replacement of a damaged sheet, particularly
if it is in the middle of a long run of sheets.
This problem was addressed at the design stage
of SF500 and as a result, replacement is
straightforward and relatively painless.
The most important factor in replacement is
ensuring that the adjoining sheets are not
damaged in the process, necessitating another
replacement. There are several methods but the
one that Euroclad recommended is as follows:
Cut along the whole length of the damaged
sheet approximately in the positions shown in
the below diagram as ‘A’ and ‘B’. Once
completed, carefully remove the pan of the profile
with particular regard to the sharp cut edges.
Gripping the remainder of the sheet at ‘A’ it will be
straightforward to ‘unclip’ the overlapping edge.
With great care to avoid damage to the adjoining
sheet’s overlap, gently prise away the remaining
section left by the cut at ‘B’. This will then allow
access to the primary fixings in the underlap.
The old underlap section can then be removed.
During replacement it is important to ensure
that all the old mastic is removed and a new
bead laid. Laying of the new sheet will be then
straightforward.
Secret Fix SF500
500mm cover width
colour side AB
Roof Step Replacing Damaged Sheet
27
Secret Fix SF500
26
On-Site Production
All Euroclad site produces SF500 Secret Fix
projects have pre-production site visit to discuss
Euroclads’ and the Contractors requirements and
responsibilities on site. A Site Specific Method
Statement will be provided for The Roofing
Contractor and Main Contractor.
Coil Delivery
A delivery of coils will be sent to site on projects
larger than 500m2 (based on 0.7mm material).
The Contractor must supply a counterbalance or
telescopic truck to unload the coil into a prepared
safe area on arrival to site. Coils weigh a maximum
of 2.5 tonnes.
Mobile Rollforming Trailer
Trailer Details:
Length: 15.30 metres
Height: 4.04 metres
Width: 2.60 metres
Weight: 33 tonnes (approx)
Producing Sheet Lengths up to 44 metres
Manpower
Euroclad will supply manpower to produce
sheets lengths up to 18 metres without labour
assistance from the Contractor. For sheet
lengths over 18 metres up to 30 metres 3
labourers are required to assist the rollforming
team. For lengths over 30 metres up to 44
metres 5 labourers will be required.
Work procedure
The rollformer will arrive on site and set up in
the required location as determined in the
pre-production site visit for rollforming sheets.
The rollforming team after attending any
required Site Induction will then produce the
sheets and pack at ground level onto
Loading SF500 packed into crates – available for sheetlengths upto 6 metres by request. Pallet charges apply.
polystyrene bearers and then secure the sheets
for ready for lifting with a nylon banding system.
All cut lengths are required 10 working days
before site commencement.
The process can then be completed at different
locations around sites (where required) to keep
crane size requirements down – and in-turn
cranage costs.
Producing Sheet Lengths over 44 metres
Manpower
Euroclad will supply manpower to produce
sheets to the ramp and up to the roof height.
The roof area is the responsibility of the
Contractor. The roof area must be prepared
before production commences.
Careful planning will ensure trouble free
site operation.
NB. All loading of the roof area will be the
Contractors responsibility.
Work procedure
The rollformer will arrive on site and set up
in the required location ready for ramp set-up.
Before the ramp is erected it is possible to
relocate it into position using lifting slings along
with a Telescopic Fork Truck. The ramp is then
erected using the on board motorised controls.
Assistance may be required.
For further details please contact the On-site
Production Department at Euroclad.
The Euroclad Mobile Ramp
The Mobile telescopic ramp enables Euroclad to
produce sheets in excess of lifting restrictions
with ease to the roof. SF500 sheets have been
produced in single lengths up to 87 metres long.
The loading equipment ramp is available for hire
on a weekly basis for loading Euroclad
products only.
28
Euroclad Limited
Wentloog Corporate Park
Cardiff
CF3 2ER
Telephone +44 (0)29 2079 0722
Facsimile +44 (0)29 2079 3149
E-mail [email protected]
Internet www.euroclad.com
Euroclad (Ireland) Limited
Unit 4
Newhall Industrial Estate
Naas
Co. Kildare
Telephone 00 353 (0) 45 435 470
Facsimile 00 353 (0) 45 435 472
Internet www.euroclad.com
The details and information contained in this publication are correct at time of going to press. Euroclad reserves the right to change details andspecifications without prior notice. No responsibility is assumed for errors or misinterpretations resulting from the information contained in this publication.Typical construction details are illustrative only and no liability is accepted.