Second Revision No. 75-NFPA 1983-2016 [ Detail ] 8.7.10 (title) Specific Requirements for Auxiliary Equipment Systems, System Components, Escape Systems, Fire Escape Systems, and Manufactured Systems Submitter Information Verification Submitter Full Name: Chris Farrell Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Mon Jan 11 14:38:52 EST 2016 Committee Statement Committee Statement: Correction of terms. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 96 4/5/2016 1:11 PM

Transcript of Second Revision No. 75-NFPA 1983-2016 [ Detail ] · PDF fileSecond Revision No. 75-NFPA...

Second Revision No. 75-NFPA 1983-2016 [ Detail ]

8.7.10 (title)

Specific Requirements for Auxiliary Equipment Systems, System Components, EscapeSystems, Fire Escape Systems, and Manufactured Systems

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:38:52 EST 2016

Committee Statement

Committee Statement: Correction of terms.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 96 4/5/2016 1:11 PM

Second Revision No. 77-NFPA 1983-2016 [ Detail ]

8.16.8 (title)

Specific Requirements for Testing Fire Escape Webbing Used in Flame Resistant Life SafetyHarnesses and Belts

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:00:12 EST 2016

Committee Statement

CommitteeStatement:

Correcting term. “Fire Escape Webbing” is separate product category and not applicablehere.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 96 4/5/2016 1:11 PM

Second Revision No. 93-NFPA 1983-2016 [ Detail ]

Make the following changes in Chapter 3:

3.3.47  Load Straps.

3.3.47.1  3.3.21 End-to-End Load Straps.  **move as 3.3.21**

Straps with end connection points meant to be loaded in end-to-end fashion, including, but notlimited to, pick-off straps, load-releasing straps, or vertical lifting straps.

3.3.47.2*  3.3.56* Multiple Configuration Load Straps.  **move as 3.3.56*

Straps with end connection points that can be configured in multiple loading, including, but notlimited to, end-to-end, basket, and choker configurations.

Submitter Information Verification

Submitter Full Name: Sonia Barbosa

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 16 11:36:49 EST 2016

Committee Statement

Committee Statement: Make definition reflect current usage.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 96 4/5/2016 1:11 PM

Second Revision No. 48-NFPA 1983-2016 [ Chapter 2 ]

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard and shall beconsidered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 1500, Standard on Fire Department Occupational Safety and Health Program, 2013 edition.

2.3 Other Publications.

2.3.1 AATCC Publications.

American Association of Textile Chemists and Colorists, P.O. Box 12215, Research Triangle Park, NC27709.

AATCC 135, Dimensional Changes in Automatic Home Laundering of Woven and Knit Fabrics, 2010.

2.3.2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P. O. Box C700, West Conshohocken, PA 19428-2959.

ASTM B117, Standard Practice for Operating Salt Spray (Fog) Apparatus, 2011.

ASTM D4966, Standard Test Method for Abrasion Resistance of Textile Fabrics, (Martindale AbrasionTester Method), 2012 e1.

ASTM D6413/D6413M, Standard Test Method for Flame Resistance of Textiles (Vertical Test),2013b 2015 .

ASTM D7138, Standard Test Method to Determine Melting Temperature of Synthetic Fibers , 2016.

ASTM E794, Standard Test Method for Melting and Crystallization Temperatures by Thermal Analysis,2006, reaffirmed 2012.

ASTM F1772, Standard Specification for Climbing Harnesses, 2012.

ASTM F1956, Standard Specification for Rescue Carabiners, 2013.

ASTM F2436, Standard Test Method for Measuring the Performance of Synthetic Rope Rescue BelaySystems Using a Drop Test, reaffirmed 2011 2014 .

ASTM F2821, Standard Test Methods for Basket Type Rescue Litters, 2010 2015 .

ASTM F2894, Standard Test Method for Evaluation of Materials, Protective Clothing and Equipment forHeat Resistance Using a Hot Air Circulating Oven , 2014.

2.3.3 Cordage Institute Publications.

The Cordage Institute, 994 Old Eagle School Road, Suite 1019, Wayne, PA 19087.

CI 1801, Low Stretch and Static Kernmantle Life Safety Rope, 2007.

CI 1805, 3-Strand Life Safety Rope, Moderate Stretch, 2008.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 96 4/5/2016 1:11 PM

2.3.4 ISO Publications.

International Standards Organization International Organization for Standardization , 1 rue de Varembé,Case Postal 56, CH-1211 Geneve 20 ISO Central Secretariat, BIBC II, Chemin de Blandonnet 8, CP 401,1214 Vernier, Geneva , Switzerland.

ISO Guide 27, Guidelines for corrective action to be taken by a certification body in the event of misuse ofits mark of conformity, 1983.

ISO/DIS 9001, Quality management systems — requirements, 2014 2008 .

ISO 17011, General requirements for accreditation bodies accrediting conformity assessment bodies,2004.

ISO/IEC 17021, Conformity assessment — Requirements for bodies providing audit and certification ofmanagement systems, 2011.

ISO/IEC 17025, General requirements for the competence of testing and calibration laboratories, 2005.

ISO/IEC 17065, Conformity assessment — Requirements for bodies certifying products, processes, andservices, 2012.

ISO 17493, Clothing and equipment for protection against heat — Test method for convective heatresistance using a hot air circulating oven , 2000.

ISO 22159, Personal equipment for protection against falls — Descending devices, 2007.

2.3.5 SAE International Publications.

SAE International Society of Automotive Engineers , 400 Commonwealth Dr. Drive , Warrendale, PA15096-0001.

SAE AMS-2175A, Castings, Classification and Inspection of, 2010.

2.3.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 913, Standard for Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II,and III, Division 1, Hazardous (Classified) Locations, 2006, Revised revised 2013.

2.3.7 U.S. Government Publications.

U.S. Government Printing Publishing Office, 732 North Capitol Street, NW, Washington, DC20402 20401-0001 .

MIL-83420M, Military Specification: General Specification for Flexible Wire Rope for Aircraft Control, ( 1April 2005) .

2.3.8 Other Publications.

Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

2.4 References for Extracts in Mandatory Sections. (Reserved)

Supplemental Information

File Name Description

staff_use_only_SR-48_Chapter_2.docx

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 23:51:28 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 96 4/5/2016 1:11 PM

Committee Statement

Committee Statement: Updating references.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 96 4/5/2016 1:11 PM

Second Revision No. 50-NFPA 1983-2016 [ Section No. 3.3.69 ]

3.3.68 Software.

A type of auxiliary equipment that includes, but is Flexible textile components of protective clothing orequipment, including, but not limited to, anchor straps, pick-off straps, and rigging slings end-to-endstraps and multiple configuration straps .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 09:49:45 EST 2016

Committee Statement

Committee Statement: Providing clear definition for software elements.

Response Message:

Public Comment No. 6-NFPA 1983-2015 [Section No. 3.3.69]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 96 4/5/2016 1:11 PM

Second Revision No. 51-NFPA 1983-2016 [ Section No. 4.1.6 ]

4.1.6

All compliant products shall also have a product label that meets the requirements specified in Section5.1 Chapter 5 , Product Label Requirements Labeling and Information .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 09:51:46 EST 2016

Committee Statement

Committee Statement: Correcting reference

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 96 4/5/2016 1:11 PM

Second Revision No. 52-NFPA 1983-2016 [ Section No. 4.3.6 ]

4.3.6

Inspection by the certification organization shall include an evaluation of any symbols and pictorial graphicrepresentations used on product labels or in user information, as permitted in 5.1.1.6 , 5.2.1.6 , 5.9.1.8 ,5.10.1.8 , 5.22.1.7 , 5.6.1.6 , 5.11.1.6 , 5.18.1.7 , 5.23.1.7 , 5.4.1.6 , 5.8.1.5 and 5.7.1.5 Chapter5 , to ensure that the symbols are clearly explained in the product's user information package.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 09:54:06 EST 2016

Committee Statement

Committee Statement: Correcting references.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 96 4/5/2016 1:11 PM

Second Revision No. 53-NFPA 1983-2016 [ Section No. 4.3.7 ]

4.3.7

Inspection by the certification organization shall include a review of the user information required bySection Chapter 5.2 , User Information, 5 to ensure that the information has been developed and isavailable.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 09:55:25 EST 2016

Committee Statement

Committee Statement: Correcting reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 96 4/5/2016 1:11 PM

Second Revision No. 1-NFPA 1983-2016 [ Section No. 5.2.1.4 ]

5.2.1.4

All letters shall be at least 1.6 2.0 mm (5⁄64 in.) high.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 10:03:30 EST 2016

Committee Statement

CommitteeStatement:

Revising letter height makes it consistent with height requirements in rest of document, perFR-12 and P1-60. These changes were submitted and accepted by committee during FirstRevision meeting but were inadvertently omitted.

ResponseMessage:

Public Comment No. 9-NFPA 1983-2015 [Section No. 5.2.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 96 4/5/2016 1:11 PM

Second Revision No. 54-NFPA 1983-2016 [ Section No. 5.2.1.13 ]

5.2.1.13

In addition to the compliance and information statements in 5.2.1.8 and 5.2.1.9 and 5.2.1.10 at leastthe following information shall also be printed on the product label(s)where all letters shall be at least 2mm (5⁄64 in.) high.

(1) Manufacturer’s name, identification, or designation

(2) Manufacturer’s address

(3) Country of manufacture

(4) Manufacturer’s product identification

(5) Model, style, lot, or serial number

(6) Elongation at 1.35 kN (300 lb)

(7) Elongation at 2.7 kN (600 lb)

(8) Elongation at 4.4 kN (1000 lb)

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 09:57:05 EST 2016

Committee Statement

Committee Statement: Correcting references.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 96 4/5/2016 1:11 PM

Second Revision No. 14-NFPA 1983-2016 [ Section No. 5.4.1.4 ]

5.4.1.4

All letters shall be at least 1.6 2.0 mm (5⁄64 in.) high.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 06:59:41 EST 2016

Committee Statement

Committee Statement: Changing letter height to be 2.0mm to be consistent with rest of document.

Response Message:

Public Comment No. 10-NFPA 1983-2015 [Section No. 5.4.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 96 4/5/2016 1:11 PM

Second Revision No. 55-NFPA 1983-2016 [ Section No. 5.6.1.10 ]

5.6.1.10

The MBS value of the throwline, which is required in 5.6.1.9 to be stated on the product label, shall bepermitted to be any value greater than the actual “pass” requirement value determined by the certificationtesting in accordance with 7.3.1 7.6.1 , but shall not be greater than the calculated MBS.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 10:39:05 EST 2016

Committee Statement

Committee Statement: Correcting reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 96 4/5/2016 1:11 PM

Second Revision No. 56-NFPA 1983-2016 [ Section No. 5.6.1.11 ]

5.6.1.11

The diameter of the throwline, which is required in 5.6.1.8 to be stated on the product label, shall be asdetermined by the certification organization in accordance with 7.3.2 7.6.2 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 10:42:14 EST 2016

Committee Statement

Committee Statement: Correcting reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 96 4/5/2016 1:11 PM

Second Revision No. 57-NFPA 1983-2016 [ Section No. 5.6.2 ]

5.6.2 Water Rescue Throwline User Information.

The manufacturer of a throwline that is certified as being compliant with this standard shall furnish thepurchaser with at least use criteria, inspection procedures, maintenance procedures, and retirementcriteria for the product.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 10:45:06 EST 2016

Committee Statement

CommitteeStatement:

Deleted “Water Rescue” to make consistent with terminology used throughout the rest ofthe document.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 96 4/5/2016 1:11 PM

Second Revision No. 58-NFPA 1983-2016 [ Section No. 5.9.1.11 ]

5.9.1.11

Where the life safety harness is certified as compliant with nonoptional requirements of this standard andalso certified as compliant with the optional flame resistance requirements specified in 6.9.2, and 7.9.6 ,the following statement shall be printed on the product label:

“ MEETS THE LIFE SAFETY HARNESS REQUIREMENTS OF NFPA 1983, STANDARD ON LIFE SAFETY

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 11:15:20 EST 2016

Committee Statement

Committee Statement: Added missing reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 96 4/5/2016 1:11 PM

Second Revision No. 59-NFPA 1983-2016 [ Section No. 5.10.1.11 ]

5.10.1.11

Where the belt is certified as compliant with nonoptional requirements of this standard and also certifiedas compliant with the optional flame resistance requirements specified in 6.10.2 and 7.10.7 , thefollowing statement shall be printed on the product label:

“ MEETS THE REQUIREMENTS OF NFPA 1983, STANDARD ON LIFE SAFETY ROPE AND EQUIPMENT

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 11:16:43 EST 2016

Committee Statement

Committee Statement: Added missing reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 96 4/5/2016 1:11 PM

Second Revision No. 11-NFPA 1983-2016 [ Section No. 5.14.1.2.4 ]

5.14.1.2.4

Each belay device shall also display the range of rope diameters with which the device is intended to beused.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 17:11:52 EST 2016

Committee Statement

Committee Statement: Delete redundant wording.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 96 4/5/2016 1:11 PM

Second Revision No. 60-NFPA 1983-2016 [ Section No. 5.14.1.3 ]

5.14.1.3

The product label for the portions of the product label information not specified in 5.14.1.2.1 through5.14.1.2.4 shall be permitted to be a hang tag affixed to each individual auxiliary equipment item belaydevice or shall be permitted to be printed on a sheet that is inserted and sealed in the packaging thatimmediately contains the auxiliary equipment item belay device .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 11:53:14 EST 2016

Committee Statement

Committee Statement: Correcting description to correct item.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 96 4/5/2016 1:11 PM

Second Revision No. 61-NFPA 1983-2016 [ Section No. 5.15.1.3 ]

5.15.1.3

The product label for the portions of the product label information not specified in 5.15.1.2.1 through5.15.1.2.4 shall be permitted to be a hang tag affixed to each individual auxiliary equipmentitem carabiner and snap link or shall be permitted to be printed on a sheet that is inserted and sealed inthe packaging that immediately contains the auxiliary equipment item carabiner and snap link .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 11:54:49 EST 2016

Committee Statement

Committee Statement: Correcting description to correct item.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 96 4/5/2016 1:11 PM

Second Revision No. 9-NFPA 1983-2016 [ Section No. 5.16.1.2.3 ]

5.16.1.2.3

Each descent control device shall display at least the minimum rated breaking strength prefaced by theletters “MBS.” The MBS value stated on the product label shall be permitted to be any value greaterthan the actual “pass” requirement value determined by the certification testing, but shall not be greaterthan the calculated MBS.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 16:34:32 EST 2016

Committee Statement

Committee Statement: MBS is not evaluated in the document, therefore any reference to it is inappropriate.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 96 4/5/2016 1:11 PM

Second Revision No. 12-NFPA 1983-2016 [ Section No. 5.16.1.2.5 ]

5.16.1.2.4

Each descent control device shall also display the range of rope diameters with which the device isintended to be used.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 17:16:53 EST 2016

Committee Statement

Committee Statement: Delete redundant wording.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 96 4/5/2016 1:11 PM

Second Revision No. 62-NFPA 1983-2016 [ Section No. 5.16.1.3 ]

5.16.1.3

The product label for the portions of the product label information not specified in 5.16.1.2.1 through5.16.1.2.45.16.1.2.5 shall be permitted to be a hang tag affixed to each individual auxiliary equipmentitem descent control device or shall be permitted to be printed on a sheet that is inserted and sealed inthe packaging that immediately contains the auxiliary equipment item descent control device .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 11:56:44 EST 2016

Committee Statement

Committee Statement: Correcting description to correct item.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 96 4/5/2016 1:11 PM

Second Revision No. 10-NFPA 1983-2016 [ Section No. 5.16.2.5 ]

5.16.2.5

Because the descent control device is tested with a rope or escape webbing, one of the followingstatements shall be provided in the user instructions:

For rope: “ THIS DESCENT CONTROL DEVICE HAS PASSED THE MINIMUM BREAKING STRENGTH MA

[insert rope manufacturer name, designation, part number, and diameter here].

For escape webbing: “ THIS DESCENT CONTROL DEVICE HAS PASSED THE MINIMUM BREAKING STR

[insert webbing manufacturer name, designation, part number, and perimeter here].

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 16:38:38 EST 2016

Committee Statement

Committee Statement: Replaced MBS, which is not evaluated, with manner of function test.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 96 4/5/2016 1:11 PM

Second Revision No. 13-NFPA 1983-2016 [ Section No. 5.21.1.2.4 ]

5.21.1.2.4

Each rope grab and ascending device shall also display the range of rope diameters with which thedevice is intended to be used.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 17:20:09 EST 2016

Committee Statement

Committee Statement: Delete redundant wording.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 96 4/5/2016 1:11 PM

Second Revision No. 63-NFPA 1983-2016 [ Section No. 5.23.1.2.2 ]

5.23.1.2.2

Each load-bearing hardware escape system component shall display the mark or logo of the certificationorganization and the manufacturer’s name or identifying mark.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:17:23 EST 2016

Committee Statement

CommitteeStatement:

The mark of the certification organization is required on the product label (see 5.23.1.8). The listingmark on each load bearing component can be misleading in that it can appear that each componenthas met the individual component requirements of NFPA 1983. This is not the case as systems aretested as systems and not as individual components.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 96 4/5/2016 1:11 PM

Second Revision No. 64-NFPA 1983-2016 [ Sections 5.23.1.2.3, 5.23.1.2.4, 5.23.1.2.5 ]

5.23.1.2.3

Each load-bearing hardware escape system component shall display at least the minimum ratedbreaking strength prefaced by the letters “MBS.” The MBS value stated on the product label shall bepermitted to be any value greater than the actual “pass” requirement value determined by thecertification testing, but shall not be greater than the calculated MBS.

5.23.1.2.4

Each load-bearing escape system component shall display an “E” for escape-use items. Thedesignation “E” shall be designated in accordance with 6.23.1.2 .

5.23.1.2.5

Each system device, rope grab device, and descent control device shall also display the range of ropediameters with which the device is intended to be used.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:18:22 EST 2016

Committee Statement

CommitteeStatement:

Device will have this information if device is certified on its own (ex. Descent control device) butotherwise should not be there because can be misleading. MBS on label for system and only onediameter used in a system (each different diameter would be separate system)

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 96 4/5/2016 1:11 PM

Second Revision No. 31-NFPA 1983-2016 [ Section No. 5.23.1.9 ]

5.23.1.9

Each escape system shall have the following compliance statement on the product label:

MEETS THE ESCAPE SYSTEM REQUIREMENTS OF NFPA 1983, STANDARD ON LIFE SAFETY ROPE A

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 10:48:37 EST 2016

Committee Statement

Committee Statement: Added language to inform user of precautions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 96 4/5/2016 1:11 PM

Second Revision No. 66-NFPA 1983-2016 [ Section No. 5.24.1.2.2 ]

5.24.1.2.2

Each load-bearing hardware fire escape system component shall display the mark or logo of thecertification organization and the manufacturer’s name or identifying mark.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:20:35 EST 2016

Committee Statement

CommitteeStatement:

The mark of the certification organization is required on the product label (see 5.24.1.8). The listingmark on each load bearing component can be misleading in that it can appear that each componenthas met the individual component requirements of NFPA 1983. This is not the case as systems aretested as systems and not as individual components.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 96 4/5/2016 1:11 PM

Second Revision No. 65-NFPA 1983-2016 [ Sections 5.24.1.2.3, 5.24.1.2.4, 5.24.1.2.5 ]

5.24.1.2.3

Each load-bearing hardware fire escape system component shall display at least the minimum ratedbreaking strength prefaced by the letters “MBS.” The MBS value stated on the product label shall bepermitted to be any value greater than the actual “pass” requirement value determined by thecertification testing, but shall not be greater than the calculated MBS.

5.24.1.2.4

Each load-bearing fire escape system component shall display an “E” for escape-use items. Thedesignation “E” shall be designated in accordance with 6.24.1.2 .

5.24.1.2.5

Each fire escape system device, rope grab device, and descent control device shall also display therange of rope diameters with which the device is intended to be used.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:19:42 EST 2016

Committee Statement

CommitteeStatement:

Device will have this information if device is certified on its own (ex. Descent control device) butotherwise should not be there because can be misleading. MBS on label for system and only onediameter used in a system (each different diameter would be separate system)

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 96 4/5/2016 1:11 PM

Second Revision No. 33-NFPA 1983-2016 [ Section No. 5.24.1.9 ]

5.24.1.9

Each fire escape system shall have the following compliance statement on the product label:

“ MEETS THE FIRE ESCAPE SYSTEM REQUIREMENTS OF NFPA 1983, STANDARD ON LIFE SAFETY R

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 10:52:13 EST 2016

Committee Statement

Committee Statement: Added language to inform user of precautions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 96 4/5/2016 1:11 PM

Second Revision No. 40-NFPA 1983-2016 [ Section No. 5.25.1.2.1 ]

5.25.1.2.1

Each manufactured system load-bearing component shall have the following compliance statement:

“MEETS NFPA 1983 (2017 ED).”

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 12:20:16 EST 2016

Committee Statement

Committee Statement: Deleted requirement so there's no confusion to end user over certified product.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 96 4/5/2016 1:11 PM

Second Revision No. 67-NFPA 1983-2016 [ Section No. 5.25.1.2.2 ]

5.25.1.2.1

Each load-bearing hardware manufactured system component shall display the mark or logo of thecertification organization and the manufacturer's name or identifying mark.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:22:07 EST 2016

Committee Statement

CommitteeStatement:

The mark of the certification organization is required on the product label (see 5.25.1.8). The listingmark on each load bearing component can be misleading in that it can appear that each componenthas met the individual component requirements of NFPA 1983. This is not the case as systems aretested as systems and not as individual components.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 96 4/5/2016 1:11 PM

Second Revision No. 68-NFPA 1983-2016 [ Sections 5.25.1.2.3, 5.25.1.2.4, 5.25.1.2.5 ]

5.25.1.2.3

Each load-bearing hardware manufactured system component shall display at least the minimum ratedbreaking strength prefaced by the letters “MBS.” The MBS value stated on the product label shall bepermitted to be any value greater than the actual “pass” requirement value determined by thecertification testing, but shall not be greater than the calculated MBS.

5.25.1.2.4

Each load-bearing hardware manufactured system component shall display a “G” for general-use items,a “T” for technical-use items, or an “E” for escape-use items. The designation “G,” “T,” or “E” shall bedesignated in accordance with 6.25.1.2 .

5.25.1.2.5

Each manufactured system ascending device, rope grab device, and descent control device shall alsodisplay the range of rope diameters with which the device is intended to be used.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 12:23:21 EST 2016

Committee Statement

CommitteeStatement:

Device will have this information if device is certified on its own (ex. Descent control device) butotherwise should not be there because can be misleading. MBS on label for system and only onediameter used in a system (each different diameter would be separate system)

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 96 4/5/2016 1:11 PM

Second Revision No. 32-NFPA 1983-2016 [ Section No. 5.25.1.9 ]

5.25.1.9

Each manufactured system shall have the following compliance statement on the product label:

“ MEETS THE MANUFACTURED SYSTEM REQUIREMENTS OF NFPA 1983, STANDARD ON LIFE SAFET

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 10:51:05 EST 2016

Committee Statement

Committee Statement: Added language to inform user of precautions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 96 4/5/2016 1:11 PM

Second Revision No. 88-NFPA 1983-2016 [ Section No. 6.4 ]

6.4 Fire Escape Rope.

6.4.1 Fire Escape Rope Design Requirements.

6.4.1.1*

Fire escape rope shall be constructed of virgin fiber.

6.4.1.2

Fire escape rope shall be of block creel construction.

6.4.1.3

Primary load-bearing elements of fire escape rope shall be constructed of continuous filament fiber.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 16:12:51 EST 2016

Committee Statement

Committee Statement: Annex material should be associated with 6.4.1.1, not 6.4.1

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 96 4/5/2016 1:11 PM

Second Revision No. 69-NFPA 1983-2016 [ Section No. 6.23.1.2 ]

6.23.1.2

The escape system shall comprise a flexible lifeline (e.g., rope/webbing/cable); a descent control deviceand a connector from the system to the user not to include the harness; and a means of attaching thesystem to an anchoring point (e.g., an escape anchor) that is capable of supporting human loads. Thedesign and construction requirements individual components of the escape system shall meet therespective design requirements of the individual components as specified in this standard .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:26:01 EST 2016

Committee Statement

CommitteeStatement:

Wording as written is confusing. There are no “construction” requirements in this document.Individual component testing is missing from the system requirements.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 96 4/5/2016 1:11 PM

Second Revision No. 70-NFPA 1983-2016 [ Section No. 6.24.1.2 ]

6.24.1.2

The fire escape system shall comprise a flexible lifeline; a descent control device and a connector fromthe system to the user not to include the harness; and a means of attaching the system to an anchoringpoint (e.g., an escape anchor) that is capable of supporting human loads. The design and constructionrequirements individual components of the fire escape system shall meet the respective designrequirements of the individual components as specified in this standard .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:28:26 EST 2016

Committee Statement

CommitteeStatement:

Wording as written is confusing. There are no “construction” requirements in this document.Individual component testing is missing from the system requirements.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 96 4/5/2016 1:11 PM

Second Revision No. 71-NFPA 1983-2016 [ New Section after 6.25.1.7 ]

6.25.1.8

The individual components of the manufactured system shall meet the respective design requirementsof the individual components as specified in this standard.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:30:07 EST 2016

Committee Statement

Committee Statement: Individual component requirements are missing from the system requirements.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 96 4/5/2016 1:11 PM

Second Revision No. 34-NFPA 1983-2016 [ Section No. 7.5.5 ]

7.5.5

Fire escape webbing product labels and identification tape shall be tested for high temperatureexposure durability as specified in Section 8.15 8.10 . This test shall be conducted at two independentconditions and shall have a minimum time to failure of 45 seconds at 600°C while holding 300 lb and of 5minutes at 400°C while holding 300 lb and shall be legible, shall remain in place, and shall not be torn orotherwise damaged .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:09:33 EST 2016

Committee Statement

Committee Statement: Section was duplicated and was intended to be for label durability.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 96 4/5/2016 1:11 PM

Second Revision No. 15-NFPA 1983-2016 [ Section No. 7.8.1 ]

7.8.1

Manufacturer-supplied eye termination shall be tested for breaking strength as specified in Section 8.2and shall meet one of the following criteria:

(1) It shall have a minimum breaking strength of not less than 85 percent of the certified rope’scalculated minimum breaking strength, as determined by the certifying organization.

(2) It shall have a minimum breaking strength of not less than 20 kN (4496 lbf) for technical use lifesafety rope.

(3) It shall have a minimum breaking strength of not less than 40 kN (8992 lbf) for general use life safetyrope.

(4) It shall have a minimum breaking strength of not less than 13.5 kN (3034 lbf) for escape rope andfire escape rope .

(5) It shall have a minimum breaking strength of not less than 13.5 kN (3034 lbf) for throwline escapewebbing and fire escape webbing .

(6) It shall have a minimum breaking strength of not less than 13.5 kN (3034 2923 lbf) for fire escaperope throwline .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:04:04 EST 2016

Committee Statement

CommitteeStatement:

Revising (4), (5), and (6) per PI-62 and FR-38, to add the webbings and group MBS requirement offire escape rope with escape rope. These changes were submitted and accepted by committee inFirst Draft meeting but were inadvertently omitted. Correction to (6) because requirement forthrowline is actually 13.0 kN, not 13.5 kN. The text now covers all of the different type of linesaddressed in the standard, plus includes the correct minimum MBS requirements.

ResponseMessage:

Public Comment No. 11-NFPA 1983-2015 [Section No. 7.8.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 96 4/5/2016 1:11 PM

Second Revision No. 44-NFPA 1983-2016 [ Section No. 7.8.2.1 ]

7.8.2.1

All thread used in the construction of fire escape rope manufacturer-supplied eye terminationin terminations for fire escape rope or fire escape webbing shall be tested for melting as specified inASTM E794, Standard Test Method for Melting and Crystallization Temperatures by Thermal Analysis,and shall have a melting point of not less than 260°C (500°F).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 22:12:16 EST 2016

Committee Statement

Committee Statement: Provide clarity for the thread for manufacturer-supplied eye terminations to be tested.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 96 4/5/2016 1:11 PM

Second Revision No. 5-NFPA 1983-2016 [ Section No. 7.9.6.3 ]

7.9.6.3

Where harnesses are represented as being flame-resistant, sewing thread utilized in the construction ofharnesses shall be tested for heat resistance melting as specified in Section 8.18 and shall notmelt ASTM D7138, Standard Test Method to Determine Melting Temperature of Synthetic Fibers ,Method 1, and shall have a melting point of not less than 260°C (500°F) .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 15:46:21 EST 2016

Committee Statement

CommitteeStatement:

This change will eliminate the test method for threads in the document and referencecurrent ASTM standard.

Response Message:

Public Comment No. 29-NFPA 1983-2015 [Section No. 7.9.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 96 4/5/2016 1:11 PM

Second Revision No. 6-NFPA 1983-2016 [ Section No. 7.10.7.3 ]

7.10.7.3

Where belts are represented as being flame resistant, sewing thread utilized in the construction ofharnesses belts shall be tested for heat resistance melting as specified in Section 8.18 ASTM D7138,Standard Test Method to Determine Melting Temperature of Synthetic Fibers , Method 1, and shall havea melting point of not melt less than 260°C (500°F) .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 15:53:20 EST 2016

Committee Statement

CommitteeStatement:

This change will eliminate the test method for threads in the document and referencecurrent ASTM standard.

Response Message:

Public Comment No. 30-NFPA 1983-2015 [Section No. 7.10.7.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 96 4/5/2016 1:11 PM

Second Revision No. 35-NFPA 1983-2016 [ Section No. 7.12.1 ]

7.12.1

Technical use end-to-end straps shall be tested for breaking strength as specified in Section 8.7 and shallhave a minimum breaking strength of at least 11 kN (4500 2473 lbf) without failure.

7.12.1.1

Where the strap includes an adjustment device, the adjustment device shall not slip more than 50 mm (2in.).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:19:31 EST 2016

Committee Statement

Committee Statement: Correcting a conversion.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 96 4/5/2016 1:11 PM

Second Revision No. 2-NFPA 1983-2016 [ Section No. 7.13.2 [Excluding any

Sub-Sections] ]

General use multiple configuration straps shall be tested for breaking strength as specified in Section 8.7and shall have a minimum breaking strength of at least 22 45 kN (4946 10,120 lbf) without failure.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 11:55:39 EST 2016

Committee Statement

CommitteeStatement:

22kN was incorrectly changed with the reorganization and 45 kN is the correct force as it isin the previous edition.

ResponseMessage:

Public Comment No. 12-NFPA 1983-2015 [Section No. 7.13.2 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 96 4/5/2016 1:11 PM

Second Revision No. 16-NFPA 1983-2016 [ Section No. 7.16.2 ]

7.16.2

Escape descent control devices shall be tested for maximum impact force as specified in Section 8.14and shall have the maximum impact force not exceed 8 kN (1798.5 lbf), shall not damage the device orrope, and shall remain functional.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:06:37 EST 2016

Committee Statement

CommitteeStatement:

This is to round the conversion to be consistent with other conversions in the document thatare in whole numbers.

ResponseMessage:

Public Comment No. 13-NFPA 1983-2015 [Section No. 7.16.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 96 4/5/2016 1:11 PM

Second Revision No. 19-NFPA 1983-2016 [ Section No. 7.19.3 ]

7.19.3

Technical use portable anchor devices shall be tested for strength as specified in Section 8.7 and shallwithstand a minimum load of at least 18 kN (4946 4046 lbf) without failure.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:09:19 EST 2016

Committee Statement

Committee Statement: This is to correct the conversion. The correct conversion value for 18 kN is 4,046 lbf.

Response Message:

Public Comment No. 14-NFPA 1983-2015 [Section No. 7.19.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 96 4/5/2016 1:11 PM

Second Revision No. 20-NFPA 1983-2016 [ Section No. 7.20.2 ]

7.20.2

Technical use pulleys shall be tested for strength as specified in Section 8.7 and shall have a minimumtensile strength of at least 18 kN (4946 4046 lbf) without failure.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:10:39 EST 2016

Committee Statement

Committee Statement: This is to correct the conversion. The correct conversion value for 18 kN is 4,046 lbf.

Response Message:

Public Comment No. 3-NFPA 1983-2015 [Section No. 7.20.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 96 4/5/2016 1:11 PM

Second Revision No. 21-NFPA 1983-2016 [ Section No. 7.20.5 ]

7.20.5

The becket on technical use pulleys shall be tested for strength as specified in Section 8.7 and shall havea minimum tensile strength of at least 11 kN (2698 2473 lbf) without failure.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:11:43 EST 2016

Committee Statement

Committee Statement: This is to correct the conversion. The correct conversion value for 11 kN is 2,473 lbf.

Response Message:

Public Comment No. 4-NFPA 1983-2015 [Section No. 7.20.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 96 4/5/2016 1:11 PM

Second Revision No. 72-NFPA 1983-2016 [ Section No. 7.23.5 ]

7.23.5

Where the escape descent control device used in the escape system incorporates a passive or activebreaking feature that creates friction between the device and the rope, the system shall be tested foraverage payout force as specified in Section 8.13 and shall not release the test torso and shall notexceed 90 N (20 lb lbf ).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:33:48 EST 2016

Committee Statement

Committee Statement: Correcting conversion.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 96 4/5/2016 1:11 PM

Second Revision No. 17-NFPA 1983-2016 [ Section No. 7.23.6 ]

7.23.6

Escape systems shall be tested for maximum impact force as specified in Section 8.14 and shall have themaximum impact force not exceed 8.0 kN (1798.5 lbf), shall not damage the rope or device, and shallremain functional.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:07:29 EST 2016

Committee Statement

CommitteeStatement:

This is to round the conversion to be consistent with other conversions in the document thatare in whole numbers.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 96 4/5/2016 1:11 PM

Second Revision No. 73-NFPA 1983-2016 [ Section No. 7.24.4 ]

7.24.4

Where the escape descent control device used in the fire escape system incorporates a passive or activebreaking feature that creates friction between the device and the rope, the system shall be tested foraverage payout force as specified in Section 8.13 and shall not release the test torso and shall notexceed 90 N (20 lb lbf ).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:34:50 EST 2016

Committee Statement

Committee Statement: Correcting conversion.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 96 4/5/2016 1:11 PM

Second Revision No. 7-NFPA 1983-2016 [ Section No. 7.24.7 ]

7.24.7

Sewing thread utilized in the construction of fire escape systems shall be tested for heatresistance melting as specific in Section 8.18 and shall not melt at or below a temperature of 260°C(500°F) specified in ASTM D7138, Standard Test Method to Determine Melting Temperature of SyntheticFibers , Method 1, and shall have a melting point of not less than 260°C (500°F) .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 15:56:20 EST 2016

Committee Statement

CommitteeStatement:

This change will eliminate the test method for threads in the document and referencecurrent ASTM standard.

Response Message:

Public Comment No. 31-NFPA 1983-2015 [Section No. 7.24.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 96 4/5/2016 1:11 PM

Second Revision No. 18-NFPA 1983-2016 [ Section No. 7.24.8 ]

7.24.8

Escape systems shall be tested for maximum impact force as specified in Section 8.14 and shall have themaximum impact force not exceed 8.0 kN (1798.5 lbf), shall not damage the rope or device, and shallremain functional.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:08:12 EST 2016

Committee Statement

CommitteeStatement:

This is to round the conversion to be consistent with other conversions in the document thatare in whole numbers.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 96 4/5/2016 1:11 PM

Second Revision No. 22-NFPA 1983-2016 [ Section No. 7.25.2 ]

7.25.2

Technical use manufactured systems shall be tested for strength as specified in Section 8.7 and shallhave a minimum tensile strength of at least 18 kN (4946 4046 lbf) without failure.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:13:00 EST 2016

Committee Statement

Committee Statement: This is to correct the conversion. The correct conversion value for 18 kN is 4,046 lbf.

Response Message:

Public Comment No. 5-NFPA 1983-2015 [Section No. 7.25.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 96 4/5/2016 1:11 PM

Second Revision No. 28-NFPA 1983-2016 [ Section No. 8.3.1.1 ]

8.3.1.1

This test shall apply to ladder belts, escape belts, and Class II and Class III life safetyharness harnesses, and Class II and Class III victim extrication devices .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:30:02 EST 2016

Committee Statement

CommitteeStatement:

Class II and Class III victim extrication devices were omitted from the application statement forthis test but should be included. The revised language adds them into the text. Revisions originallysubmitted per PI-63 and accepted by committee but then were inadvertently omitted.

ResponseMessage:

Public Comment No. 25-NFPA 1983-2015 [Section No. 8.3.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 96 4/5/2016 1:11 PM

Second Revision No. 29-NFPA 1983-2016 [ Section No. 8.3.1.2 ]

8.3.1.2

Each model of a belt, or a life safety harness, or a victim extrication device shall be tested in accordancewith Table 8.3.1.2, as appropriate for the product.

Table 8.3.1.2 Static Test Matrix

TestClass

IIClass

IIILadder

BeltVictim Escape

BeltClass II Extrication

DeviceClass III Extrication

Device

Upright YES YES YES YES YES YES

Headdown

NO YES NO NO NO YES

Horizontal NO NO YES NO NO YES

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:41:04 EST 2016

Committee Statement

Committee Statement: editorial; need to add in victim extrication device which was excluded in first revision

Response Message:

Public Comment No. 15-NFPA 1983-2015 [Section No. 8.3.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 96 4/5/2016 1:11 PM

Second Revision No. 30-NFPA 1983-2016 [ Section No. 8.6.4.5.6 ]

8.6.4.5.6

The test mass for a general-use belay device shall be 200 280 kg (617 lb).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:53:53 EST 2016

Committee Statement

CommitteeStatement:

Consistency with the design load between general use and technical use within this document andto provide consistency with ASTM F2436, Standard Test Method for Measuring the Performance ofSynthetic Rope Rescue Belay Systems Using a Drop Test and ASTM F2266, StandardSpecifications for Masses Used in Testing Rescue Systems and Components. 280kg is a threeperson rescue load or two fully encumbered firefighters.

ResponseMessage:

Public Comment No. 2-NFPA 1983-2015 [Section No. 8.6.4.5.6]

Public Comment No. 16-NFPA 1983-2015 [Section No. 8.6.4.5.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 96 4/5/2016 1:11 PM

Second Revision No. 36-NFPA 1983-2016 [ Section No. 8.6.7 ]

8.6.7 Specific Requirements for Testing Ascent Devices and Rope Grab Devices.

8.6.7.1*

Technical-use ascent devices and rope grab devices shall be tested at a load of 5 kN (1124 lbf) forProcedure A.

8.6.7.2

General-use ascent devices and rope grab devices shall be tested at a load of 11 kN (2500 lbf) forProcedure A.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:24:34 EST 2016

Committee Statement

Committee Statement: Editorial only

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 96 4/5/2016 1:11 PM

Second Revision No. 41-NFPA 1983-2016 [ Section No. 8.7.1.1 ]

8.7.1.1

This test shall apply to portable anchor devices, escape systems, manufactured systems, end-to-endstraps, multiple-configuration straps , escape anchors, pulleys, and other auxiliary equipment.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 21:55:50 EST 2016

Committee Statement

CommitteeStatement:

This editorial revision corrects the name of the product. The language was included in the 2012edition and remained in PC-63, but then was inadvertently removed in FR-32. This addition givesthe correct and full name for multiple configuration straps.

ResponseMessage:

Public Comment No. 17-NFPA 1983-2015 [Section No. 8.7.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 96 4/5/2016 1:11 PM

Second Revision No. 74-NFPA 1983-2016 [ Section No. 8.7.1.4 ]

8.7.1.4

Specific requirements for testing auxiliary equipment fire escape systems, system components, escapesystems, and manufactured systems shall be as specified in 8.7.10.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:36:41 EST 2016

Committee Statement

Committee Statement: Correcting to proper term used in standard.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 96 4/5/2016 1:11 PM

Second Revision No. 76-NFPA 1983-2016 [ Section No. 8.7.10.1 ]

8.7.10.1

Only Procedure B shall be conducted on auxiliary equipment fire escape systems, systemcomponents escape systems , and manufactured systems.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 14:40:35 EST 2016

Committee Statement

Committee Statement: Correction of terms.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 96 4/5/2016 1:11 PM

Second Revision No. 37-NFPA 1983-2016 [ Section No. 8.7.10.2 ]

8.7.10.2

Auxiliary equipment and manufactured systems shall be tested using a rope with a diameter of thesmallest and largest size specified by the auxiliary equipment manufacturer.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:29:04 EST 2016

Committee Statement

CommitteeStatement:

Not applicable for systems. A system will only have one diameter, not a range ofdiameters.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 96 4/5/2016 1:11 PM

Second Revision No. 42-NFPA 1983-2016 [ Section No. 8.7.12 ]

8.7.12 Specific Requirements for Testing Multiple-Configuration Straps .

8.7.12.1

Only Procedure B shall be conducted on multiple-configuration straps .

8.7.12.2*

Testing shall be conducted using 13 mm ± 1 mm (1⁄2 in. ± 1⁄8 in.) pins, bolts, or shackles.

8.7.12.3

Test pin cross section shall be permitted to be other than round. Any , and any cross section necessary toprevent test pin failure or any design to prevent test pin rotation shall be permitted as long as the contactpoint between the test pin and strap attachment point has the specified radius, material type, hardness,and surface roughness as per Section 6.2.1 of ASTM F1956, Standard Specification for RescueCarabiners.

8.7.12.4

The test fixture shall be designed to prevent the test pins from rotating such that the strap is free to locateitself on the test pins when force is applied.

8.7.12.5

Where the strap is adjustable in length, the strap shall be tested in the shortest length that places theadjustment device free of any interference of the test fixture.

8.7.12.6

Technical-use and general-use multiple-configuration straps shall be individually tested in the basket (U)configuration, the end-to-end configuration, and the choker configuration.

8.7.12.7

For technical-use and general-use multiple-configuration straps , all configuration values shall be reportedon the product label. Only , and only the basket (U) configuration value shall be utilized to determinepass/fail.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 22:02:53 EST 2016

Committee Statement

CommitteeStatement:

This editorial revision corrects the name of the product by adding the word, “strap.” The languagewas included in the 2012 edition and remained in PC-63, but then was inadvertently removed inFR-32.-This addition gives the correct and full name for multiple configuration straps. PC-18 onlyincluded the addition of the word in 8.7.12 and 8.7.12.1. However, during preparation of thesesubstantiations, it was discovered that the word was also missing in 8.7.12.6 and 8.7.12.7, and,therefore are added here as well.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 96 4/5/2016 1:11 PM

ResponseMessage:

Public Comment No. 18-NFPA 1983-2015 [Section No. 8.7.12]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 96 4/5/2016 1:11 PM

Second Revision No. 43-NFPA 1983-2016 [ Section No. 8.7.13.1 ]

8.7.13.1

Only Procedure B shall be conducted on escape anchor devices.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 22:06:08 EST 2016

Committee Statement

Committee Statement: This is given in bold text, but should not be in bold.

Response Message:

Public Comment No. 19-NFPA 1983-2015 [Section No. 8.7.13.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 96 4/5/2016 1:11 PM

Second Revision No. 23-NFPA 1983-2016 [ Sections 8.10.1, 8.10.2, 8.10.3 ]

8.10.1 Application.

8.10.1.1

This test method shall apply to permanently attached product labels and identification tapes, excludingmetal stamped or engraved labels.

8.10.1.2

Specific requirements for testing rope, webbing, and throwline identification tapes shall be specified in8.10.7.

8.10.1.3

Specific requirements for testing all other labels shall be specified in 8.10.8.

8.10.2 Samples.

8.10.2.1

Samples for conditioning shall be individual labels or, in the case of rope, webbing, or throwline, at least 1m (1 yd) in length.

8.10.2.2

Samples shall be conditioned as specified in 8.1.2.

8.10.3 Specimens.

8.10.3.1

Specimens shall be individual labels or, in the case of rope, webbing, or throwline, 1 m (1 yd) in length.

8.10.3.2

A minimum of four of each type of label shall be tested.

8.10.3.3

Where labels have “write-in” information, two additional specimens shall be tested that include thoseareas with sample information written in.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:16:26 EST 2016

Committee Statement

CommitteeStatement:

Webbing inadvertently omitted from First Draft. Sections should address webbing as well asrope and throwline.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 96 4/5/2016 1:11 PM

Second Revision No. 24-NFPA 1983-2016 [ Section No. 8.10.5.2 ]

8.10.5.2

For rope, webbing, and throwline, the ability of the label to remain in place shall be reported.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:20:22 EST 2016

Committee Statement

CommitteeStatement:

The label attachment should be evaluated on webbing as well as rope and throwline. It wasinadvertently omitted in the first revision.

ResponseMessage:

Public Comment No. 26-NFPA 1983-2015 [Section No. 8.10.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 96 4/5/2016 1:11 PM

Second Revision No. 25-NFPA 1983-2016 [ Section No. 8.10.7 ]

8.10.7 Specific Requirements for Testing Rope, Webbing, and Throwline Labels.

All rope, webbing, and throwline inserted identification tapes shall be tested only for laundering durabilityas specified in 8.10.4.2.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:21:34 EST 2016

Committee Statement

CommitteeStatement:

The inserted identification tapes for webbing should be evaluated as well as for rope andthrowline. It was inadvertently omitted in the first revision.

ResponseMessage:

Public Comment No. 27-NFPA 1983-2015 [Section No. 8.10.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 96 4/5/2016 1:11 PM

Second Revision No. 4-NFPA 1983-2016 [ Section No. 8.11.1 ]

8.11.3.1

Descent The holding test shall apply to descent control devices shall be tested in accordance withSection 5.5 of ISO 22159 , Personal equipment for protection against falls — Descending devices. .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 12:20:34 EST 2016

Committee Statement

CommitteeStatement:

Reformatted to remain consistent with rest of test methods in chapter 8. Moved current8.11.1 to become new 8.11.4.1.

ResponseMessage:

Public Comment No. 28-NFPA 1983-2015 [Section No. 8.11.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 96 4/5/2016 1:11 PM

Second Revision No. 92-NFPA 1983-2016 [ Section No. 8.11.6 ]

8.11.5 Interpretation.

One or more specimens failing this test shall constitute failing performance for the item being tested.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 10:15:07 EST 2016

Committee Statement

Committee Statement: 8.11 is for holding test and statement given is incorrect.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 96 4/5/2016 1:11 PM

Second Revision No. 38-NFPA 1983-2016 [ Section No. 8.13.1.1 ]

8.13.1.1

This test shall apply to escape systems and fire escape systems .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:32:01 EST 2016

Committee Statement

Committee Statement: Clarifying that fire escape systems are part of the payout test.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 96 4/5/2016 1:11 PM

Second Revision No. 46-NFPA 1983-2016 [ Section No. 8.13.2.3 ]

8.13.2.3

The descent control system shall be tested with each type of rope for its intended use.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 23:47:46 EST 2016

Committee Statement

Committee Statement: Redundant information that’s found in performance requirement.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 96 4/5/2016 1:11 PM

Second Revision No. 47-NFPA 1983-2016 [ Section No. 8.13.4.1 ]

8.13.4.1

Specimens shall be tested in a servohydraulic or screw-driven load frame with a controlled displacementrate of 100 mm/sec (±5 mm/sec) .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 23:49:03 EST 2016

Committee Statement

CommitteeStatement:

This is to add in tolerance of plus/minus 5mm/sec. The plus symbol was unintentionally leftout of the PC.

Response Message:

Public Comment No. 21-NFPA 1983-2015 [Section No. 8.13.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 96 4/5/2016 1:11 PM

Second Revision No. 3-NFPA 1983-2016 [ Section No. 8.13.5 ]

8.13.5 Report.

The average force encountered over the 100 mm (4 in.) payout shall be recorded from each test and theaverage and standard deviation calculated.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 12:15:44 EST 2016

Committee Statement

Committee Statement: The requirement is the average force and the standard deviation is not required.

Response Message:

Public Comment No. 22-NFPA 1983-2015 [Section No. 8.13.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 96 4/5/2016 1:11 PM

Second Revision No. 39-NFPA 1983-2016 [ Section No. 8.14.1 ]

8.14.1 Application.

This test shall apply to escape descent control devices, escape systems, and fire escape manufacturedsystems.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 11:34:08 EST 2016

Committee Statement

Committee Statement: Clarifying application and correcting terminology.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 96 4/5/2016 1:11 PM

Second Revision No. 26-NFPA 1983-2016 [ Section No. 8.14.5.1 ]

8.14.5.1

The maximum impact force shall be reported to the nearest 0.1 kN (23 lbf) .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:24:30 EST 2016

Committee Statement

CommitteeStatement:

This is editorial. Conversion is being added for consistency; other values throughoutdocument have conversion from metric.

ResponseMessage:

Public Comment No. 23-NFPA 1983-2015 [Section No. 8.14.5.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 96 4/5/2016 1:11 PM

Second Revision No. 27-NFPA 1983-2016 [ Section No. 8.14.6.1 ]

8.14.6.1

A recorded impact force in excess of 8.0 kN (1798 lbf) shall constitute failing performance.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 07:25:46 EST 2016

Committee Statement

CommitteeStatement:

This is editorial. Conversion is being added for consistency; other values throughoutdocument have conversion from metric.

ResponseMessage:

Public Comment No. 24-NFPA 1983-2015 [Section No. 8.14.6.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 96 4/5/2016 1:11 PM

Second Revision No. 78-NFPA 1983-2016 [ New Section after 8.17.1.2 ]

8.17.1.3

Modifications to this test method for testing hardware shall be as specified in 8.17.9 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:08:50 EST 2016

Committee Statement

Committee Statement: Adding in modification statements to be consistent throughout test method.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 96 4/5/2016 1:11 PM

Second Revision No. 79-NFPA 1983-2016 [ New Section after 8.17.1.2 ]

8.17.1.4

Modifications to this test method for testing hardware shall be as specified in 8.17.10 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:12:48 EST 2016

Committee Statement

Committee Statement: Adding in modification statements to be consistent throughout test method.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 96 4/5/2016 1:11 PM

Second Revision No. 80-NFPA 1983-2016 [ New Section after 8.17.1.2 ]

8.17.1.5

Modifications to this test method for testing other materials not covered in 8.17.1.2 , 8.17.1.3 , or8.17.1.4 shall be as specified in 8.17.11 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:14:28 EST 2016

Committee Statement

Committee Statement: Adding in modification statements to be consistent throughout test method.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 96 4/5/2016 1:11 PM

Second Revision No. 45-NFPA 1983-2016 [ Section No. 8.17.4 ]

8.17.4 Apparatus.

The test oven shall be as specified in ISO 17493, Clothing and equipment for protection against heat —Test method for convective heat resistance using a hot air circulating oven ASTM F2894, Standard TestMethod for Evaluation of Materials, Protective Clothing and Equipment for Heat Resistance Using a HotAir Circulating Oven . Testing , and testing shall be carried out at a temperature of 260°C +6/−0°C (500°F+10/−0°F).

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 22:26:08 EST 2016

Committee Statement

Committee Statement: Correcting to proper test method

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 96 4/5/2016 1:11 PM

Second Revision No. 8-NFPA 1983-2016 [ Section No. 8.18 ]

8.18 Thread Heat Resistance Test.

8.18.1 Application.

This test method shall apply to each type of sewing thread used in the construction of flame-resistant lifesafety harnesses and belts.

8.18.2 Samples.

Samples for conditioning shall be lengths of thread 150 mm (6 in.) or greater.

8.18.3 Specimens.

8.18.3.1

A total of three different specimens of each thread type shall be tested.

8.18.3.2

All specimens shall be conditioned as specified in 8.1.2 prior to testing.

8.18.4 Apparatus.

8.18.4.1

An electrically heated stage having a circular depression large enough to insert a micro-cover glassshall be used. The stage shall have a variable transformer controlling the rate of heat input into thestage.

8.18.4.2

The following equipment shall also be used:

Armored stem thermometer with a range of 150°C to 300°C accurate to 1°C

Low-powered magnifying glass

Two micro-cover glasses

Spatula, pick needle, or other instrument for applying pressure to the micro-cover glasses

Soxhlet extraction apparatus

8.18.4.3

The following reagents shall be used:

Chloroform, USP

U.S. Pharmacopoeia reference standards for melting point or other pure materials for calibratingthe apparatus

8.18.5 Procedure.

8.18.5.1

The specimen shall be extracted with chloroform for a minimum of 20 extractions in a Soxhlet extractorand dried. The specimen shall then be cut into lengths of 2 mm ( 1 ⁄16 in.) or less.

8.18.5.2

The apparatus shall be calibrated by determining the melting point of a pure material of known meltingpoint. The melting point of the pure material shall be in the range of the melting point of the fiber beingtested. The value obtained shall agree within +1°C of the known value.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 96 4/5/2016 1:11 PM

8.18.5.3

If the approximate melting point of the specimen is not known before testing, it shall be determined by atrial run.

8.18.5.4

In subsequent determinations immediately following the trial run or initial determination, the stage ineach case shall be cooled to approximately 50°C below the expected melting point before the specimenis placed for testing.

8.18.5.5

The specimen shall be placed in a small mound on a cover glass and covered with another cover glass.The two cover glasses shall be pressed together gently but firmly, and placed in the circular depressionon the stage. The temperature of the stage shall be raised with some rapidity to within 15°C of theexpected melting point, and thereafter at a rate of 3°C to 4°C per minute. At this rate of temperaturerise, a slight pressure shall be applied on the upper glass cover by pressing with a spatula, pick needle,or other instrument so that the complete fiber is in contact with the cover glass.

8.18.5.6

The specimen shall be observed with the aid of a magnifying glass, and the melting point taken as thetemperature at which flow of the specimen is observed. At the observed melting point, the temperatureshall be read to the nearest °C (°F).

8.18.6 Report.

8.18.6.1

The melting point of the sample unit shall be the average of the results obtained from the specimenstested and shall be recorded and reported to the nearest °C (°F).

8.18.6.2

The pass/fail results for each specimen tested shall be recorded and reported.

8.18.7 Interpretation.

One or more thread specimens failing this test shall constitute failing performance for the thread type.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jan 05 15:59:29 EST 2016

Committee Statement

CommitteeStatement:

This change will eliminate the test method for threads in the document and referencecurrent ASTM standard.

Response Message:

Public Comment No. 32-NFPA 1983-2015 [Section No. 8.18]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 96 4/5/2016 1:11 PM

Second Revision No. 81-NFPA 1983-2016 [ Section No. A.5.1.1.8 ]

A.5.1.1.8

When life safety rope is purchased, the AHJ should ensure that the product label(s) with the informationas specified in 5.15.1.1 and 5.1.2 is attached and remains with the rope until placed in service. Whenthe product label is removed from the rope, the label should be retained in the AHJ’s permanent roperecords.

It is very important that the information on the product label(s) and the information required in 5.15.1.2 tobe supplied by the manufacturer reach the persons who will actually be using the rope. It is useless for thesupply personnel or equipment officer to remove the product label and other pertinent information andsimply retain them in the rope record file. The persons who potentially will be using the rope need to beprovided with all the information available. Copies of the product label(s) and other pertinent informationshould be maintained with the rope wherever the rope is in service awaiting use so that the potential userscan consult the information.

Where life safety or escape line is purchased in long lengths and then cut by the end user agency to makeseveral life safety ropes or escape lines, the product label(s) should be photocopied or otherwisereproduced and attached to each life safety rope when it is sent into service. The end user(s) (in a firedepartment it probably would be a fire company) should keep the copy of the product label(s) and anyother pertinent information for reference and have the product label and other information readily availableso that they can be reviewed by all potential users whenever necessary.

Ropes can be damaged in use by high stresses, impact loading situations, abrasion, kinking, heat, andexposure to chemicals and other products.

Ropes should be inspected by a qualified person before and after every operation and carefully storedbetween each use. Records should provide a history of each rope and should call for regular inspectionand replacement as necessary. Any rope that fails to pass inspection or has been impact-loaded shouldbe destroyed immediately.

It is recommended that departments establish an inspection program and shelf-life criteria for their ropesbased on the conditions and environments encountered in their respective operations.

The destruction of rope means that it should be removed from service and altered in such a manner that itcould not mistakenly be used as a life safety rope. This could include disposal or removal of the label andcutting the rope into short lengths to be used for utility purposes.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:18:34 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 96 4/5/2016 1:11 PM

Second Revision No. 82-NFPA 1983-2016 [ Section No. A.5.2.1.1 ]

A.5.2.1.1

When escape line is purchased, the purchaser or the AHJ should ensure that a product label with theinformation as specified in 5.25.2.1 and 5.2.2 is attached and remains with the rope until placed inservice. This label should be retained either in the AHJ’s rope records or with the user of the rope forreference.

Escape line is intended only for emergency self-rescue situations and cannot be used for other roperescue situations. Escape rope is designed for one emergency use only and should be destroyed afteruse. This does not include use for training where ropes are not subjected to excessive conditions such asstress, impact-loading situations, abrasion, kinking, heat, and exposure to chemicals and other products.

Escape line is intended to be carried by a fire fighter or other emergency services personnel so that it willbe available in unanticipated situations from which self-rescue using the rope is the only option. Therefore,the escape line should be carefully stored and periodically inspected by a qualified person to ensurestatus and condition of the rope. During inspection, if there is any doubt as to the suitability of the escapeline for use, it should be destroyed immediately and replaced.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:26:06 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 96 4/5/2016 1:11 PM

Second Revision No. 83-NFPA 1983-2016 [ Section No. A.5.2.1.2 ]

A.5.2.1.2

Information useful to the purchaser that applies to a particular rope line could be added to the tape.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:43:15 EST 2016

Committee Statement

Committee Statement: For consistency. Could also be webbing and term “line” is used in previous section.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 96 4/5/2016 1:11 PM

Second Revision No. 84-NFPA 1983-2016 [ Section No. A.5.2.1.9 ]

A.5.2.1.9

See A.5.2.1.1A.5.1.1.8 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 15:44:23 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 96 4/5/2016 1:11 PM

Second Revision No. 85-NFPA 1983-2016 [ Section No. A.5.3.1.3 ]

A.5.3.1.3

See A.5.2.1.1A.5.1.1.8 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 16:06:43 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 96 4/5/2016 1:11 PM

Second Revision No. 86-NFPA 1983-2016 [ Section No. A.5.4.1.9 ]

A.5.4.1.9

See A.5.2.1.1A.5.1.1.8 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 16:07:23 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 96 4/5/2016 1:11 PM

Second Revision No. 87-NFPA 1983-2016 [ Section No. A.5.5.1.3 ]

A.5.5.1.3

See A.5.2.1.1A.5.1.1.8 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 16:08:41 EST 2016

Committee Statement

Committee Statement: To correct reference with reorganization

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 96 4/5/2016 1:11 PM

Second Revision No. 89-NFPA 1983-2016 [ Section No. A.6.22.1.6 ]

A.6.22.1.6

Alternative methods for finishing and securing webbing ends can be hardware capping, tucking andsewing, and coating the webbing ends with an air-drying solvent base sealant See A.6.9.1.4 .

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jan 11 16:19:11 EST 2016

Committee Statement

Committee Statement: For consistency with rest of document.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 96 4/5/2016 1:11 PM

Second Revision No. 90-NFPA 1983-2016 [ Section No. A.8.3.10.2 ]

A.8.3.10.2

A lesser force is used in this test than in the rescue harness test due to the personal protective applicationof belts. The indicated test force of 13 kN (2923 lbf) is compliant is consistent with the requirements forescape rope.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 10:08:15 EST 2016

Committee Statement

Committee Statement: Provide clarity on the testing for escape belts.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 96 4/5/2016 1:11 PM

Second Revision No. 91-NFPA 1983-2016 [ Section No. A.8.7.4.1 ]

A.8.7.4.1

In most cases, the portable anchor device will be weakest at its greatest (or highest) extension. However,many devices have multiple ways they can be used. Different rigging configurations could be stronger orweaker than others. It is intended that the testing be done in the configuration specified in themanufacturer's instructions to the user that would yield the lowest strength results. For example, anchorslings multiple configuration straps can be rigged in a basket, end-to-end, or choker configuration. Eachconfiguration will likely yield different results. The minimum breaking strength reported is for the weakestconfiguration allowed by the manufacturer’s instructions.

Submitter Information Verification

Submitter Full Name: Chris Farrell

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 13 10:13:34 EST 2016

Committee Statement

Committee Statement: Correcting term.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 96 4/5/2016 1:11 PM