SCI - SHORT CIRCUIT ISOLATOR
PRODUCT LISTINGS
Underwriters Laboratories: S5694Underwriters Laboratories of Canada: CS943CSFM #: 7300-0410:150MEA Report # 284-91-E Vol. IV
STANDARD FEATURES
• Can be placed at any location on SLC loop.• Checks the line for short circuit at power up. If the line is normal, the relay will be returned on. If a line short is detected, the relay remains open.• Indication of short circuit by a yellow LED
* Class A Configuration Wiring:The DCP-SCI short circuit isolator should be locatedbetween any devices on the SLC loop. In the event ofa short on the SLC loop, the two adjacent isolators(closest isolators to the left and right of the shortedsection) will activate and their respective LED indica-tors will be turned on. All devices between the activeshort circuit isolators will be dead. This will prevententire loop failure. Upon removal of the short condi-tion, the DCP-SCIs will automatically restore, theentire loop to the normal operating state.
* Class B Configuration Wiring:The DCP-SCI short circuit isolator should be locatedbetween any devices on the SLC loop. In the event ofa short on SLC loop, an isolator closest to the shortedsection will activate and the LED will be turned on. Allthe devices beyond the shorted section will bedisabled. Upon removal of the short condition, theDCP-SCI will automatically restore the entire loop tothe normal operating state.
For the best performance of DCP-SCI short circuit,use class A configuration.
WIRING:Note: All wiring must conform to local codes, ordi-nances and regulations.1. Install module wiring in accordance with job draw-ings and appropriate wiring diagram.2. Secure the module to an approved electrical box(supplied by installer).
MOUNTING REQUIREMENTS: 4" SQ Electrical box.
OPERATION
Specifications subject to change without notice.
SPECIFICATIONS
Absolute Maximum Applied Voltage: S, SC: 41 VDCSupply Voltage Norminal: S, SC: 33 VDCNormal Current Consumption: 270 µA (Typical)Active Current Consumption: 10 mA (Typical)(Short Circuit Condition)Dimensions: 4.2"W x 4.7"H x 1.4"DWeight: 1.4 ozVisual Indicator (Yellow Status LED): - No indication in normal condition. - On steady in active (short) condition.Maximum Quantity Per Loop: 127Operation Temperature Range: 0ºC (32ºF)~ 49ºC (120ºF) Non-condensingAllowable Ambient Humidity: 90% Non-condensing
Continued on back.
Representante Exclusivo Brasil
Hochiki America CorporationRepresentante Exclusivo Brasil Proline Equipamentos Eletrônicos LTDA. - Rua Santa Cristina,54 - CEP20241-250 Santa Teresa - Rio de Janeiro Tell : (21) 2 5 0 7-5 9 2 5 - Fa x : (21) 2 2 8 3 -1 7 7 8 - w w w. p r o l i n e e q u i p a m e n t o s . c o m . b r
Specifications subject to change without notice.Hochiki America Corporation DCP-SCI
BETWEEN ISOLATORS
ANY COMBINATION OF MODULESAND/OR SENSORS MAY BE PLACED
AND INHERENTLY POWER LIMITED.ALL WIRING SHOWN IS SUPERVISED
SHORT CIRCUIT ISOLATOR
GROUP OF VARIOUS DCP SENSORS
GROUP OF VARIOUS DCP MODULES
TO A COMPATIBLE LISTED CONTROL PANEL TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED
ISS
UE
NO
. AH
-977
4
S56
94LI
STE
DS
IGN
ALI
NG
DE
VIC
E
(IN) SC(OUT) S
(IN) S
SE
R. N
O. X
XX
XX
XX
XX
DC
P-S
CI
(OUT) SC
TB1
(NOT REQUIRED)
SHORT CIRCUIT ISOLATOR
(OU
T) S
C
DCP-SCISER. NO. XXXXXXXXX
(IN
) S
(OU
T) S
(IN
) SC
SIGNALING DEVICE
S5694
ISSUE NO. AH-9774
LISTED
TB1
OPTIONAL RETURN LINE
SHORT CIRCUIT ISOLATOR
TB1
(OUT) SC
DC
P-S
CI
SIG
NA
LIN
G D
EV
ICE
S56
94
SE
R. N
O. X
XX
XX
XX
XX
ISS
UE
NO
. AH
-977
4
(IN) S
(OUT) S
(IN) SC
++
+
CONTROLCOMPATIBLEUL LISTED
---
PANEL
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-SCI short circuit isolator. Themodules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting control panelloops. The isolator module must be suitable for mounting in a standard 4" square electrical box. The isolatormodule must provide a yellow LED for indication of status.
WIRING DIAGRAM
Back side of a DCP-SCI