Sanitary Water TankINSTALLATION & SVC MANUALMODEL : PHS Series
CAUTIONBefore Servicing the unit, read the safety precautions in this manual.Only for authorized service personnel.
http://biz.lgservice.com
- 2 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Sanitary Water Tank Installation/Serivce
TABLE OF CONTENTS
Safety precaution
1. Model Information1.1 Single coil
1.2 Double coil
1.3 Drawing
2. Installation
3. Replacement
4. Trouble Shooting4.1 No water flow from hot taps
4.2 Intermittent water discharge
4.3 Hot water from taps is cold
4.4 Excessive hot water from taps
5. Wiring Diagrams
6. Exploded View6.1 PHS02060310 PHS03060310
6.2 PHS02060320 PHS03060320
- 3 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Safety PrecautionTo prevent injury to the user or other people and property damage, the following instructions must be followed.� Be sure to read before installing the product.� Be sure to observe the cautions specified here as they include important items related to safety.� Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the fol-
lowing indications.
� Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
WARNING� Installation
Do not use a defective orunderrated circuit breaker. Usethis appliance on a dedicatedcircuit.
• There is risk of fire or electricshock.
For electrical work, contact thedealer, seller, a qualified elec-trician, or an AuthorizedService Center.
• There is risk of fire or electricshock.
Always ground the product.
• There is risk of fire or electricshock.
Always install a dedicated cir-cuit and breaker.
• Improper wiring or installationmay cause fire or electric shock
Be cautious when unpackingand installing the product.
• Sharp edges could cause injury.
For installation, always contactthe dealer or an AuthorizedService Center.
• There is risk of fire, electricshock, explosion, or injury.
Do not install the product on adefective installation stand.
• It may cause injury, accident, ordamage to the product.
Be sure the installation areadoes not deteriorate with age.
• If the base collapses, the prod-uct could fall with it, causingproperty damage, product fail-ure, and personal injury.
- 4 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Take care to ensure that Wires(between and sanitarywater tank could not be pulled out ordamaged during operation.
• There is risk of fire or electricshock.
Do not plug or unplug Wiresduring operation.
• There is risk of fire or electricshock.
Do not touch (operate) theproduct with wet hands.
• There is risk of fire or electricshock.
Do not place a heater or otherappliances near Wiresv.
• There is risk of fire or electricshock.
Do not allow water to run intoelectric parts.
• There is risk of fire, failure of theproduct, or electric shock.
Do not store or use flammablegas or combustibles near theproduct.
• There is risk of fire or failure ofproduct.
When flammable gas leaks,turn off the gas and open awindow for ventilation beforeTurn on the product.
• There is risk of explosion or fire.
When the product is soaked(flooded or submerged), con-tact an Authorized ServiceCenter.
• There is risk of fire or electricshock.
Be cautious that water couldnot be poured to the Outside ofthe product directly.
• There is risk of fire, electricshock, or product damage.
Turn the main power off whencleaning or maintaining theproduct.
• There is risk of electric shock.
Take care to ensure thatnobody could step on or fallonto the product.
• This could result in personalinjury and product damage.
� Operation
- 5 -Copyright ©2008 LG Electronics. Inc. All right reserved.
� Installation
Do not install the product whereit will be exposed to sea wind(salt spray) directly.
• It may cause corrosion on the product.
Keep level even when installingthe product.
• To avoid vibration or water leakage.
Use two or more people to liftand transport the product.
• Avoid personal injury.
Use a firm stool or ladder when cleaning or maintaining the product.
• Be careful and avoid personal injury.
Use a soft cloth to clean. Do notuse harsh detergents, solvents,etc.
• There is risk of fire, electric shock, ordamage to the plastic parts of the prod-uct.
Do not step on or put anythingon the product.
• There is risk of personal injury and fail-ure of product.
Do not insert hands or otherobjects into the product while itis operating.
• There are sharp and moving parts thatcould cause personal injury.
� Operation
- 6 -Copyright ©2008 LG Electronics. Inc. All right reserved.
1. Model Information
P H S 0 2 0 6 0 3 1 0
Sanitary Water Tank
1 2 3 4 5 6 7 8 9 10 11
Part
Product Name• Heating AWHP
Water Volume20 : 20030 : 300
Sanitary Tank
Electric Heater Capacity : 3kw
Serial Number
Power Source
Number of Heating coil
P H L T A
Installation Kit
1 2 3 4 5
Part
Product Name• Heating AWHP
Product Category- T :Sanitary Water Tank- L :Solar Thermal System
Accessary Instalation kit
Serial Alphabet
1 : 115/60/1 2 : 220/60/1 3 : 208-230/60/15 : 200~220/50/1 6 : 220~240/50/1 7 : 100/50(60)/18 : 380~415/50/3 9 : 380/60/3 A : 220/50/3B : 208~230/60/3 C : 575/60/3 D : 440~460/60/3E : 265/ 60/ 1 F : 200/50~60/1 G : 220~240/50,60/1H : 220,380/50/3 J : 220,380/60/3
Power Standards
- 7 -Copyright ©2008 LG Electronics. Inc. All right reserved.
1. Single coil
Function and construction
The Single coil is available in two capacities: 200and 300 litres. It is a floor standing water heaterwhich is delivered with three adjustable feet.The cold water supply is on top of the heater. Themixing valve and pressure relief valve are factory fit-ted. The mixing valve also functions as a stop valvetowards the cold water supply. Easy draining of theheater with a drain valve on the pressure relief valvewhich is placed below the electric central.The Single coil has a built-in coil in stainless steelwhich is designed for circulation from f.ex. a solarpanel. The electric element boosts the temperaturewhenever it is necessary.The Single coil is equipped with operation and maxi-mum thermostat. At delivery the thermostat is set at75°C, but it can easily be adjusted with a screwdriver.The safety temperature release is at 98°C.
For electrical heating of tap water.
Pressure: Max operating pressure 9 barTemperature: Max operating temp. 85°C
Balancing temp. 100°C
Product descriptionRecommended for Apartments, flats, cottages etc. Floor mounted or with a wall bracket – max 200 l. Indirect and/or electric heating.
Serial conn. – max 6x300 l.Pressure vessel Stainless SMS steel, design pressure 10 bar, For all water qualities with chloride content less than 250 ppm.Insulation ECO Foam, water based polyurethane. ISO 3285 certification. Flame retardant and recyclable.Insulation cover White epoxy coated steel. Good protection against rough transport and corrosive environment.Electric element RG 1/4" 3 kW 1x230 Volt. For all water qualities with chloride content <250 ppm. Electric thermostat TS2 adjustable 60-90°C, preset at 75°C. Safety cut-off at 98°C with reset. 30A 230-400V. Thermostat for 3 phase
can be fitted.Electric central Plastic VO material in frame and cover. Splash proof IP21. Internally connected included electric cable and plug.
Mixing valve UXT thermostatic blending valve, adjustable 45-75°C, preset at 55°C. Integrated non-return and stop valve.Pressure relief valve SV2 preset and sealed at 9 bar. Factory mounted at drain connection. Easy draining prevents frost during winter.User manual Is supplied with unit, complete with spare parts list and equipment. Environment Zero emissions to ground, earth or water from production and regular use of product. All parts 100% recyclable.
F/R
Built-in stainless steel single heat exchanger.
Model Name Itrs. - kW Diam. x H mm Conn. Volume heat exch. cap. Weight m3
PHS02060310 200 - 3 kW ø580 x 1230 H 22 mm 198 L. 9 kW when dt 20°C 45 kg 0.42 PHS03060310 300 - 3 kW ø580 x 1680 H 22 mm 287 L. 9 kW when dt 20°C 59 kg 0.58
Technical data
1.1 Single coil
- 8 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Quality:All units are fully CE approved. Pressure relief valve approved by NBI 06870/387.Electrical equipment is in accordance with LVD 73-23 (directive for low voltage systems) and EMC 89-336 (electromagnetic compatibility).
List of details:Pawer wire Be connected to (Refer wiring diagram) 1. Mixing valve Adjustable temperature range (45-80°C)2. Electric central containing:
Electric element 3kW stainless steel Incoloy 825 Thermostat 60-90°C Safety temperature release 98°C
3. Indirect heating coil Stainless steel Duplex LDX 21014. Pressure relief valve 9 bar
Drain valve On the pressure relief valve
Installation – important!The heater must be filled with water before the electricity is connected. Otherwise the warranty does not apply. If the heater is installed but not in use, it must be flushed with water once a week.
Electrical connections – technical data:Electric element: RG 3 kW 230V 1 phase, 1 1/4” connection with O-ring seal Thermostat: Adjustable 60-90°C.Safety cut-off: 98°CElectric central: Internally connected from factory. Splash proof IP21.Electric cable: 2,3 mtrs cable. Output >3kW or when 230V 1 phase is
installed requires fixed connection
For installation in sanitary rooms special regulations apply.
Connection to the vvx flow/return PHS02060310 and PHS03060310 is 3/4”. Internal thread from pressure relief valve is 3/4”.
Technical data Single coil
PHS02060310 PHS03060310
WarningDo not remove the factory fitted pressure relief valve (9 bar). The valve must have a free flowing, non closeable 1/2” outlet to a visi-ble and frost free drain! All alterations or repair concerning the electrical equipment must be performed by authorized electriciansonly, and in accordance with the diagrams shown. All connections must be pulled tight. This must be repeated after approximately 3months’ operation.
- 9 -Copyright ©2008 LG Electronics. Inc. All right reserved.
1.2 Double coil
Function and construction
The Double coil is available in two capacities: 200and 300 litres. It is a floor standing water heaterwhich is delivered with three adjustable feet.The cold water supply is on top of the heater. Themixing valve and pressure relief valve are factory fit-ted. The mixing valve also functions as a stop valvetowards the cold water supply. Easy draining of theheater with a drain valve on the pressure relief valvewhich is placed below the electric central.The Double coil has built-in twin coils in stainlesssteel which are designed for circu-lation from a solarpanel in f.ex. one coil and another heating source inthe other coil. The electric element boosts the tem-perature whe-never it is necessary.The Double coil is equipped with operation and maxi-mum thermostat. At delivery the thermostat is set at75 °C, but it can easily be adjusted with a screwdriver.The safety temperature release is at 98°C.
For electrical heating of tap water.
Pressure: Max operating pressure 9 barTemperature: Max operating temp. 85°C
Balancing temp. 100°C
Product descriptionRecommended for Apartments, flats, cottages etc. Floor mounted or with a wall bracket – max 200 l. Indirect and/or electric heating.
Serial conn. – max 6x300 l.Pressure vessel Stainless SMS steel, design pressure 10 bar, For all water qualities with chloride content less than 250 ppm.Insulation ECO Foam, water based polyurethane. ISO 3285 certification. Flame retardant and recyclable.Insulation cover White epoxy coated steel. Good protection against rough transport and corrosive environment.Electric element RG 1 1/4” 3 kW 1x230 Volt. For all water qualities with chloride content <250 ppm. Electric thermostat TS2 adjustable 60-90°C, preset at 75°C. Safety cut-off at 98°C with reset. 30A 230-400V. Thermostat for 3 phase
can be fitted.Electric central Plastic VO material in frame and cover. Splash proof IP21. Internally connected included electric cable and plug.Mixing valve UXT thermostatic blending valve, adjustable 45-75°C, preset at 55°C. Integrated non-return and stop valve.Pressure relief valve SV2 preset and sealed at 9 bar. Factory mounted at drain connection. Easy draining prevents frost during winter.User manual Is supplied with unit, complete with spare parts list and equipment.Environment Zero emissions to ground, earth or water from production and regular use of product. All parts 100% recyclable.
F/R
Technical data
Built-in stainless steeldouble heat exchangers
Model Name Itrs. - kW Diam. x H mm Conn. Volume heat exch. cap. Weight m3
PHS02060320 200 - 3 kW ø580 x 1230 H 22 mm 198 L. 9 kW + 6kW 50 kg 0.42 PHS03060320 300 - 3 kW ø580 x 1680 H 22 mm 287 L. 9 kW + 6kW 64 kg 0.58
- 10 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Quality:All units are fully CE approved. Pressure relief valve approved by NBI 06870/387.Electrical equipment is in accordance with LVD 73-23 (directive for low voltage systems) and EMC 89-336 (electromagnetic compatibility).
List of details:1. Pawer wire Be connected to (Refer wiring diagram)2. Mixing valve Adjustable temperature range (45-80°C)3. Electric central containing:
Electric element 3kW stainless steel Incoloy 825 Thermostat 60-90°C Safety temperature release 98°C
4. Indirect heating coil Stainless steel Duplex LDX 21015. Pressure relief valve 9 bar
Drain valve On the pressure relief valve
Installation – important!The heater must be filled with water before the electricity is connected. Otherwise the warranty does not apply. If the heater is installed but not in use, it must be flushed with water once a week.
Electrical connections – technical data:Electric element: RG 3 kW 230V 1 phase, 1 1/4” connection with O-ring seal Thermostat: Adjustable 60-90°C.Safety cut-off: 98°CElectric central: Internally connected from factory. Splash proof IP21.Electric cable: 2,3 mtrs cable. Output >3kW or when 230V 1 phase is
installed requires fixed connection
For installation in sanitary rooms special regulations apply.
Connection to the vvx flow/return PHS02060320 and PHS03060320 is 3/4”. Internal thread from pressure relief valve is 3/4”.
Technical data Double coil
PHS02060320 PHS03060320
WarningDo not remove the factory fitted pressure relief valve (9 bar). The valve must have a free flowing, non closeable 1/2” outlet to a visi-ble and frost free drain! All alterations or repair concerning the electrical equipment must be performed by authorized electriciansonly, and in accordance with the diagrams shown. All connections must be pulled tight. This must be repeated after approximately 3months’ operation.
- 11 -Copyright ©2008 LG Electronics. Inc. All right reserved.
1.3 Drawing
PHS02060310 / PHS03060310
PH
S02060310
PH
S03060310
- 12 -Copyright ©2008 LG Electronics. Inc. All right reserved.
PHS02060320 / PHS03060320P
HS
02060320P
HS
03060320
- 13 -Copyright ©2008 LG Electronics. Inc. All right reserved.
2. INSTALLATION
To establish sanitary water circuit, 3way control valve and sanitary water tank kit is required. If solar thermal system is pre-installed at theinstallation field, solar thermal kit is required to interface solar thermal system – to – sanitary water tank – to –
General Informationsupports following 3way valve.
(1) : SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting Flow A), Live 2 (for selecting Flow B), and Neutral (for common).
(2) : “Flow A” means ‘water flow from the indoor unit to under floor water circuit.’
(3) : “Flow B” means ‘water flow from the indoor unit to sanitary water tank.’
Specific conditions are required for installation place such as service space, water pipe length and height, total volume of water and waterquality.
General Considerations• The installation location is frost-free.
• Make sure to make the piping in size 1" or more (and reduce to 3/4" at the inlet of the tank) as to have sufficient water volume in the pipingbetween indoor unit and sanitary water tank.
• Locate the sanitary water tank in a suitable position to facilitate ease of maintenance, remember access is required to the electrical box.
• Provide a connection for the relief valve blow-off and drain.
• To avoid back siphonage it is advised to install a non-return valve on the water inlet of the sanitary water tank in accordance with local andnational regulations.
• Take care that in the event of a leak, water can not cause any damage to the installation space and surroundings.
Installing Sanitary Water Tank1. Check if all sanitary water tank accessories are enclosed.
2. When floor mounting, place the sanitary water tank on a level surface.And make sure the sanitary water tank is mounted level.
3. Apply thermal paste to the thermistor and insert the thermistor as deep as possible in the thermistor socket. Fix using the nut provided.
YesSelecting “ Flow B” between“ Flow A” and “ Flow B” (3)
YesSelecting “ Flow A” between“ Flow A” and “ Flow B” (2)
230V ACSPDT3-wire
(1)
SupportedOperating ModePowerType
Sanitary Water Tank and Sanitary Water Tank Kit/Solar Thermal Kit
Conditions where Sanitary Water Tank is Installed
- 14 -Copyright ©2008 LG Electronics. Inc. All right reserved.
How to Install Sanitary Water Tank
PHS02060310 / PHS03060310
PHS02060320 / PHS03060320
- 15 -Copyright ©2008 LG Electronics. Inc. All right reserved.
A
A
B
C D
E
Relay contactorport no. assignment
ELB port no.assignment
0
1
2
4
3
5
1 3
2 4
How to Install Sanitary Water Tank KitFollow below procedures Step 1a ~ Step 6.
Step 1. Find a relay contactor and ELB in the kit. Bolt them into control box.(symbol at picture)
Step 2. Connect ‘CN_B/HEAT(A)’ (White Connector) of the indoor unit PCBwith relay contact using included cable (symbol at the picture).Connect relay contactor port no. 0 and 1.
Step 3. Connect relay contactor port no. 2 and 4 with ELB port no. 2 and 4.(symbol at the picture).
Check Polarity• Connect relay contact port no. 2 to ELB port no. 2• Connect relay contact port no. 4 to ELB port no. 4
Step 4. Connect relay contactor port no. 3 and 5 with terminal block 1 port 6and 7. (symbol at the picture).
Check Polarity• Connect relay contact port no. 3 to terminal block 1 port 6• Connect relay contact port no. 5 to terminal block 1 port 7
Step 5. Connect ELB port no. 1 and 3 with terminal block 3 port 3 and 4.(symbol at the picture).
Check Polarity• Connect ELB port no. 1 to terminal block 3 port 3• Connect ELB port no. 3 to terminal block 3 port 4
- 16 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Step 6. Find sanitary water tank sensor. Connect it to ‘CN_TH4’ (Red Connector) of the indoor unit PCB (symbol at the picture). Thesensor wire should be passed through holes for sensor (symbol and at the picture). The sensor should be mounted correctlyto the sensor hole of sanitary water tank.
Sensor mountingInsert sensor into sensor socket and bolt it tightly.
Sanitary WaterTank
D
A B
C
- 17 -Copyright ©2008 LG Electronics. Inc. All right reserved.
How to Wire Sanitary Water Tank HeaterStep 1. Uncover heater cover of the sanitary water tank. It is located side of the tank.
Step 2. Find terminal block and connect wires as below. Wires are field-supplied item.
(L) : Live signal from PCB to Heater
(N) : Neutral signal from PCB to Heater
Wire specification• Cross-sectional area of the wire should be 5mm2.
Adjusting thermostat temperature
• To guarantee proper operation, it is recommended to set tem-perature of thermostat to maximum temperature (symbol atthe picture).
(L) (N)
A
WATERTANK
HEATER
BR BL
6L
7N
IMPORTANT: Make sure that the element enters the thread ring freely and tighten.
CAUTION: After adjustments are completed, ensure the lid to the electrical box is replaced correctly and the retaining screw isfitted.
CAUTION: If electric element (5) or thermostat (4) is defective, contact authorized electrician.
3.Replacement
WARNINGIncorrect handling of safety valves, thermostat and other valves may lead to tank rupture. Follow instructions carefully:
Replacement of the heating element
CAUTION: Remember before resetting the safety cut-off or altering the thermostat setting, isolate electrical supply to the unitprior to removal of the electrical box lid.
1. Always turn off main power (8) when water supply is shut off.2. Test free operation of safety valves regularly by opening valves and ensuring that water runs out.3. Electrical connection and repair operations should only be carried out by an authorized electrician.4. Fitting and repair of plumbing fixtures should only be carried out by an authorized plumber.5. When replacing thermostats, safety valves and other valves supplied with this unit, use only approved parts of same specification.
1. Disconnect the power cable (8).2. Remove the electric lid (3) in front of the electric box.3. Shut valve (1) fully towards – clockwise until the valve is completely closed.4. Open safety relief valve (10) . (Close the valve by turning counter clockwise until it clicks.)5. Loosen screw X and disable the wires.6. Remove the heating element (5) with the element socket tool Y. A certain amount of water will now come out of the element hole.7. Quickly rinse the O-ring slot and get ready to install the new heating element (5).8. Enter the new heating element with a new O-ring seal.
9. Open valve (1) and check that the heating element is not leaking.10. Mount the wires X and Y and tighten properly.11. Reconnect the power cable (8). Adjust the mixing valve (see "Installation and directions for use").
- 18 -Copyright ©2008 LG Electronics. Inc. All right reserved.
- 19 -Copyright ©2008 LG Electronics. Inc. All right reserved.
Replacement of the thermostat
1. Remove the electric lid (3) in front of the electric box.2. Loosen the 4 screws X and Y and disable the wires X and Y.3. Remove the thermostat (4) and replace this with a new one.4. Mount the wires X and Y properly.
Reset button
Safety cut-out
Thermostat
Temperatureadjustment
Electricelement 5/4"
- 20 -Copyright ©2008 LG Electronics. Inc. All right reserved.
4. Trouble Shooting
FAULT POSSIBLE CAUSE REMEDYNo water flow from hot taps
Water from hot taps is cold.
Intermittent water discharge.
Continuous water discharge.
1. Mains supply off.2. Strainer blocked.
3. Cold water inlet Pressure ReducingValve incorrectly fited.
1. Immersion heaters not switched on.2. Immersion heater thermal cut-out has
operated.3. Programmer set to central heating or not
switched on.4. Boiler not working.5. Cylinder thermal cut-out has operated.
(Indirect units only).6. Motorised valve not operating correctly.
1. Reduced internal expansion.2. Thermal control failure.
(Note Water will be hot).
1. Cold water inlet Pressure ReducingValve not working.
2. Temperature and pressure relief valvefaulty.
3. Expansion relief valve not working cor-rectly.
1. Check and open stopcock.2. Turn off water supply. Remove strainer
and clean. (See Pressure ReducingValve page 6 Installation Manual)
3. Check and refit as required, (see item 3page 5of installation manual).
1. Check and switch on.2. Check and reset button. (See thermostat
diagram page 9 and safty cut-out onpage 4 of installation manual).
3. Check and set to hot water.4. Check boiler operation. If fault suspected
consult installer or boiler manufacturer.5. As at No. 2.6. Check wiring and /or plumbing connec-
tions to motorised valve. (See pages 8or 10 of the installation manual).
1. Recharge "air gap" (See cold water dis-charge on page 4 of installation manual).
2. Switch off power to immersion heater(s)and boiler supply to the unit. When dis-charge has stopped, check thermal con-trols, replace if faulty.Contact a competent person.
1. Check pressure from valve if greaterthan 2.1 bar replace. (See page 6 ofinstallation manual).
2. As No. 2 of above.3. Check and replace if faulty. (See page 6
of installation manual).
Note : Disconnect electrical supply before removing any electrical equipment covers
- 21 -Copyright ©2008 LG Electronics. Inc. All right reserved.
4.1 No water flow from hot taps
4.2 Intermittent water discharge
Start
Mains supply off NO
YES
NOLine strainer blocked Cold water PRV incorrectly fittted
Open supply valve
YES
Clear line strainer
If problem still persistscontact a competent engineer
YES
Check and refit as required
Start
NO
YES
Cold water PRV incorrectly fittted
Recharge "air gap". Follow correct procedure
If problem still persistscontact a competent engineer / plumber
YES
Switch off power to immersion heaters andboiler supply to the unit.When discharge has stopped check thermal controls and replace as necessary
Reduced Internal expansion volume
- 22 -Copyright ©2008 LG Electronics. Inc. All right reserved.
4.3 Hot water from taps is cold
4.4 Excessive Hot water from taps
Start DIRECT
NO YES
Are immersion heaters switched
on
Switch on immersion
heaters
Check and resetbutton
If problem still persists contact a competent engineer / plumber
Has immersion heater thermal
cut-out operated ?YES
Start INDIRECT
YES YES
YES
Is the programmer set to central heating
or not switched on
Check and set to hot water
programme.
Has cylinder thermal cut-out
operated ?
Check andresetbutton
YES
Check wiringor plumbingconnections
Is the motorisedvalve operating
connections
Is the boiler working?NO
NO
NO
Start
Cylinder Thermostatset to high
Is Thermostat wiredas per layouts for "S"
or "Y" plan installation
Is 2-port motorised valve closing when
cylinder reachestemperature?
Check wiring on cylinder thermostat
Wiring Fault Seek advice
from electrician
Check cylinderthermostat is
switching on & off withprogrammer & hot water
ReduceTemperature setting
Faulty thermostat
replaceConnect wiring as
per instructions
YES
NONO
YESNO
YES
NO
YES
- 23 -Copyright ©2008 LG Electronics. Inc. All right reserved.
5. Wiring Diagrams
- 24 -Copyright ©2008 LG Electronics. Inc. All right reserved.
6. Exploded view
6.1 PHS02060310 / PHS03060310
147000
269300
552208
753000
552207
249300
2693006
1470005
5522074
249303
5522082
7530001
RemarkNo
Thermostat
Anode bar
Safety valve
Thermistor pocket
Mixing valve
Electric Heater
Part Name Part Number
EBG54834502 (80060)
MAK61841001 (56200)
MJX50035702 (90420)
MEE48107204 (71259)
MEG61846101 (81020)
MJX61841401 (90040)
- 25 -Copyright ©2008 LG Electronics. Inc. All right reserved.
147000
552207
269300
552208
753000
249300
6.2 PHS02060320 / PHS03060320
2693006
1470005
5522074
249303
5522082
7530001
RemarkNo
Thermostat
Anode bar
Safety valve
Thermistor pocket
Mixing valve
Electric Heater
Part Name Part Number
EBG54834502 (80060)
MAK61841001 (56200)
MJX50035702 (90420)
MEE48107204 (71259)
MEG61846101 (81020)
MJX61841401 (90040)
- 26 -Copyright ©2008 LG Electronics. Inc. All right reserved.