SANITARY SEWER - Washington Township

1
Copyright © 2018 Giffels Webster. No reproduction shall be made without the prior written consent of Giffels Webster. Developed For: Engineers Surveyors Planners Landscape Architects Environmental Specialists Executive: Manager: Designer: Quality Control: Section: Project: Sheet: Scale: Date: M.K. M.K. J.P. D.N. CHARTER TOWNSHIP OF WASHINGTON 57900 VAN DYKE WASHINGTON, MI 48094-2883 PH: 586-786-0010 Fax: 586-786-0404 N.T.S. 17850.00 6303 26 Mile Road Suite 100 Washington, MI 48094 p (586) 781-8950 f (586) 781-8951 www.giffelswebster.com ISSUE: DATE: ( TOLL FREE ) 800-482-7171 CALL MISS DIG BEFORE YOU DIG ( 3 WORKING DAYS ) 72 HOURS OR 811 SANITARY SEWER STANDARD DETAILS S-1 06.11.18

Transcript of SANITARY SEWER - Washington Township

Page 1: SANITARY SEWER - Washington Township

Copyright © 2018 Giffels Webster.No reproduction shall be made without the prior

written consent of Giffels Webster.

Developed For:

EngineersSurveyorsPlanners

Landscape ArchitectsEnvironmental Specialists

Executive:Manager:Designer:Quality Control:Section:

Project:Sheet:Scale:Date:

M.K.M.K.J.P.D.N.

CHARTER TOWNSHIPOF WASHINGTON

57900 VAN DYKEWASHINGTON, MI

48094-2883PH: 586-786-0010Fax: 586-786-0404

N.T.S.

17850.00

6303 26 Mile RoadSuite 100

Washington, MI 48094p (586) 781-8950f (586) 781-8951

www.giffelswebster.com

ISSUE:DATE:

( TOLL FREE )

800-482-7171 CALL MISS DIG

BEFORE YOU DIG( 3 WORKING DAYS )

72 HOURS

OR 811

SANITARY SEWERSTANDARD

DETAILS

S-1

06.11.18

AutoCAD SHX Text
15"-36" I.D.
AutoCAD SHX Text
O.D.+24"
AutoCAD SHX Text
O.D.+12"
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
O.D.
AutoCAD SHX Text
TRENCH WIDTH
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
%%UCONCRETE PIPE BEDDING DETAIL
AutoCAD SHX Text
42" I.D. & LARGER
AutoCAD SHX Text
MAX. 30" 4" - 12" I.D.
AutoCAD SHX Text
4'-0" DIA.
AutoCAD SHX Text
CONCRETE FLOW CHANNEL UP TO
AutoCAD SHX Text
SPRINGLINE OF PIPE, WITH 3/4"-
AutoCAD SHX Text
1-1/4" GAP AT PIPE ENDS PROVIDED
AutoCAD SHX Text
TO MAINTAIN JOINT FLEXIBILITY.
AutoCAD SHX Text
STONE
AutoCAD SHX Text
STONE BEDDING TO SPRINGLINE
AutoCAD SHX Text
AT OVER EXCAVATED AREA.
AutoCAD SHX Text
3" TO 4"
AutoCAD SHX Text
3" TO 4"
AutoCAD SHX Text
30" MAXIMUM TRENCH WIDTH.
AutoCAD SHX Text
6" TO 16" DIAMETER PIPE.
AutoCAD SHX Text
Flow
AutoCAD SHX Text
1/2D.
AutoCAD SHX Text
12"
AutoCAD SHX Text
6"
AutoCAD SHX Text
3'
AutoCAD SHX Text
3'
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
PROPOSED PAVEMENT AND SIDEWALK
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
%%UHOUSE LEAD DETAIL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
%%UBACKFILL UNDER PAVED AREAS
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
%%USANITARY SEWER CONSTRUCTION NOTES:
AutoCAD SHX Text
24"
AutoCAD SHX Text
MAX.
AutoCAD SHX Text
PRIOR TO ANY CONSTRUCTION, THE CONTRACTOR SHALL TELEPHONE MISS DIG (1-800-482-7171) FOR THE LOCATION OF UNDERGROUND FACILITIES AND SHALL ALSO NOTIFY REPRESENTATIVES OF ANY OTHER FACILITY, LOCATED IN THE VICINITY OF THE WORK, WHICH MAY NOT BE HANDLED BY MISS DIG. CONTRACTOR SHALL NOTIFY THE WASHINGTON TOWNSHIP DEPARTMENT OF PUBLIC WORKS 48 HOURS PRIOR TO START OF CONSTRUCTION AND REQUEST AN INSPECTION OF THE PROJECT. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL ATTEND A PRE-CONSTRUCTION MEETING AT A TIME AND PLACE AS ARRANGED BY THE TOWNSHIP, IN WHICH VARIOUS UTILITY COMPANIES AND GOVERNMENTAL AGENCY REPRESENTATIVES WILL BE PRESENT. PRIOR TO CONSTRUCTION, THE CONTRACTOR MUST HAVE IN HIS POSSESSION A COPY OF A PERMIT TO CONSTRUCT A CONNECTION TO, OR AN EXTENSION OF, THE SANITARY SEWER SYSTEM, FROM THE WASHINGTON TOWNSHIP DEPARTMENT OF PUBLIC WORKS. ALL CONSTRUCTION PROCEDURES AND MATERIALS USED ON THIS PROJECT SHALL CONFORM TO WASHINGTON TOWNSHIP CURRENT STANDARDS AND SPECIFICATIONS. ALL SEWERS OVER 24" DIAMETER SHALL BE SUBJECTED TO INFILTRATION OR EXFILTRATION TESTS. UNLESS WAIVED BY THE TOWNSHIP, ALL SEWERS OF 24" DIAMETER OR SMALLER WHERE THE GROUND WATER LEVEL ABOVE THE TOP OF THE SEWER IS OVER 2 FEET SHALL BE SUBJECTED TO AN INFILTRATION TEST INSTEAD OF AIR TEST. MANHOLE MANUFACTURER SHALL INSTALL 1/2" DIA. GALVANIZED STEEL PIPE AND CAP AT PIPE CROWN, FLUSH WITH OUTSIDE WALL AND EXTENDING 3" INSIDE. CONTRACTOR TO SEAL AFTER COMPLETION OF TESTS. CLEAN STONE TO BE PLACED ON OUTSIDE OF MANHOLE AT SITE CLEAN STONE TO BE PLACED ON OUTSIDE OF MANHOLE AT SITE TUBE TO PREVENT SITE TUBE FROM BECOMING PLUGGED. PRIOR TO AIR TEST, GROUNDWATER ELEVATION MUST BE DETERMINED BY BLOWING AIR THROUGH SITE TUBE TO CLEAR IT, THEN CONNECTING A CLEAR PLASTIC TUBE TO THE PIPE NIPPLE. SUSPEND CLEAR PLASTIC TUBE VERTICALLY INSIDE MANHOLE AND OBSERVE GROUNDWATER ELEVATION AFTER EQUALIZATION. NO SEWER INSTALLATION SHALL HAVE AN INFILTRATION RATE EXCEEDING 100 GALLONS PER INCH DIAMETER OF PIPE PER MILE OF PIPE PER 24 HOUR PERIOD, FOR ANY PART OF THIS PROJECT INCLUDING MANHOLES. ONLY MODIFIED GROOVE TONGUE, ASTM C-425, ASTM C-443, O-RING, UNILOC, AMVIT, NOBEL, RING-TITE, FLUID-TITE OR EQUIVALENT AS APPROVED BY WASHINGTON TOWNSHIP MAY BE USED FOR SEWER JOINTS IN REINFORCED CONCRETE PIPE. ALL JOINTS SHALL MEET REQUIREMENTS OF ASTM C-425 OR C-443. AT ALL CONNECTIONS TO AN EXISTING SEWER OR TO EXTENSIONS THERETO, A WATERTIGHT PLUG SHALL BE PROVIDED TO PREVENT ANY FLOW FROM ENTERING EXISTING SYSTEM UNTIL ALL TESTING HAS BEEN COMPLETED AND THE SYSTEM HAS BEEN APPROVED BY THE TOWNSHIP, UNLESS WAIVED BY THE TOWNSHIP. A TEMPORARY 12 INCH DEEP SUMP SHALL ALSO BE PROVIDED IN THE FIRST MANHOLE ABOVE THE CONNECTION WHICH WILL BE FILLED IN AFTER SUCCESSFUL COMPLETION OF ANY INFILTRATION TEST UP TO THE STANDARD FILLET PROVIDED FOR THE FLOW CHANNEL. ALL SANITARY SEWER UNDER 18" DIAMETER SHALL BE SDR 26 PVC PIPE PER ASTM D-3034 WITH GASKETED OR GLUED SPECIAL JOINTS PER ASTM D-3212 OR D-2564, RESPECTIVELY. WHERE PVC MAIN LINE IS USED, BUILDING LEADS, FITTINGS AND RISERS SHALL BE 6" PVC SOLID WALL SDR 23.5 PER ASTM D-3034 WITH GLUED JOINTS. SEWER WYE OPENINGS SHALL CONTAIN FACTORY INSTALLED PREMIUM JOINT MATERIAL OF THE TYPE IDENTICAL TO THAT OF THE BUILDING LEAD PIPE USED. BUILDING LEADS TO BE FURNISHED WITH REMOVABLE AIRTIGHT AND WATERTIGHT STOPPERS. GASKETED JOINTS MAY BE USED UNDER SPECIAL CIRCUMSTANCES WITH APPROVAL OBTAINED FROM THE DIRECTOR OF PUBLIC WORKS. IF BUILDING LEADS LARGER THAN 6" ARE REQUIRED, THEY SHALL BE PER TOWNSHIP ENGINEERING STANDARDS UNLESS SHOWN OTHERWISE ON THE PLANS. INSTALLATION OF PVC PIPE SHALL CONFORM TO ASTM SPECIFICATION D-2321. NO GROUND WATER, STORM WATER, CONSTRUCTION WATER, DOWNSPOUT DRAINAGE OR WEEP TILE DRAINAGE SHALL BE ALLOWED TO ENTER ANY SANITARY SEWER INSTALLATION. ALL SEWER PIPE SHALL BE INSTALLED IN BEDDING MATERIAL TO 12-INCHES ABOVE THE PIPE, ACCORDING TO THE DETAIL ON THIS SHEET. ALL NEW MANHOLES SHALL HAVE APPROVED FLEXIBLE, WATERTIGHT SEALS WHERE PIPES PASS THROUGH WALLS. MANHOLES SHALL BE OF PRECAST SECTIONS WITH MODIFIED GROOVE TONGUE AND RUBBER GASKET TYPE JOINTS. PRECAST MANHOLE CONE SECTIONS SHALL BE APPROVED MODIFIED ECCENTRIC CONE TYPE. ALL MANHOLES SHALL BE PROVIDED WITH EJ "CAM LOCK" SECURITY OPTION. INTERNAL DROP CONNECTIONS ARE REQUIRED AT NEW MANHOLES WHERE THE OUTLET PIPE IS 18 INCHES OR MORE BELOW THE INLET PIPE. A CONCRETE SLIDE WILL BE REQUIRED ON THE INLET PIPE WHEN THE INLET PIPE IS BETWEEN 3" AND 18" ABOVE THE OUTLET PIPE. ALL MANHOLES WITH AN INTERNAL DROP CONNECTION SHALL BE A MINIMUM OF 5' IN DIAMETER. WHEREVER EXISTING MANHOLES ARE TO BE TAPPED, THE WALL WILL BE CORED AND KOR-N-SEAL FLEXIBLE RUBBER JOINT INSTALLED. EXISTING PIPES TO BE CORED AND A WYE SADDLE USED OF SAME PIPE MATERIAL AS BUILDING LEAD. NEW MANHOLES CONSTRUCTED DIRECTLY ON WASHINGTON TOWNSHIP SEWERS SHALL BE PROVIDED WITH COVERS READING "WASHINGTON TWP SANITARY SEWER." NEW MANHOLES BUILT OVER ANY EXISTING SANITARY SEWERS SHALL HAVE MONOLITHIC POURED BOTTOMS. BRANCH PIPES SHALL HAVE INVERT ABOVE EIGHT-TENTH POINT OF MAIN LINE PIPE. WATERTIGHT CONNECTIONS BETWEEN THE EXISTING PIPE AND NEW MANHOLE SHALL BE REQUIRED. 18" MINIMUM VERTICAL SEPARATION MUST BE MAINTAINED BETWEEN SANITARY SEWER AND ALL OTHER UNDERGROUND UTILITIES. AIR TESTS OR INFILTRATION/EXFILTRATION AND TELEVISION VIEWING SHALL BE MADE ON ALL NEW SEWER LINES NOT SOONER THAN 3 WEEKS FOLLOWING COMPLETION OF BACKFILL. A DVD OF ALL TELEVISED SEWER LINES SHALL BE SUBMITTED TO THE TOWNSHIP DEPARTMENT OF PUBLIC WORKS FOR THEIR RECORDS WITHIN ONE WEEK OF INSPECTION. THE TOWNSHIP REQUIRES THE FOLLOWING STANDARDS FOR DVDS: 1.) STOP AND TURN TO ALL WYES/TEES; 2.) SLOW OR STOP AT ALL JOINTS, AND ROTATE CAMERA IN PIPES WITH DIAMETERS OF 15 INCHES OR GREATER; 3.) PIPES MUST BE CLEAN BEFORE DVD IS MADE; 4.) NO DVD SHALL BE MADE FOR RECORD UNLESS A TOWNSHIP INSPECTOR IS PRESENT AND OBSERVING. ALL AIR TESTS SHALL CONFORM TO ASTM F-1417 FOR PLASTIC PIPE UNLESS ALTERNATE REQUIREMENTS ARE APPROVED BY THE TOWNSHIP. UNLESS WAIVED BY THE TOWNSHIP, DEFLECTION TESTS SHALL BE PERFORMED ON ALL FLEXIBLE PIPE. THE TESTS SHALL BE CONDUCTED AFTER THE FINAL BACKFILL HAS BEEN IN PLACE AT LEAST 30 DAYS TO PERMIT STABILIZATION OF THE SOIL-PIPE SYSTEM. NO PIPE SHALL EXCEED A DEFLECTION OF 5 PERCENT OF THE INSIDE DIAMETER. IF DEFLECTION EXCEEDS 5 PERCENT, THE PIPE SHALL BE EXCAVATED. REPLACEMENT OR CORRECTION SHALL BE ACCOMPLISHED IN ACCORDANCE WITH THE REQUIREMENTS IN THE APPROVED SPECIFICATIONS. THE RIGID BALL OR MANDREL USED FOR THE DEFLECTION TEST SHALL HAVE A DIAMETER NOT LESS THAN 95 PERCENT OF THE BASE INSIDE DIAMETER OR AVERAGE INSIDE DIAMETER OF THE PIPE DEPENDING ON WHICH IS SPECIFIED IN THE ASTM SPECIFICATION D-3034, INCLUDING THE APPENDIX, TO WHICH THE PIPE IS MANUFACTURED. THE TESTS SHALL BE PERFORMED WITHOUT MECHANICAL PULLING DEVICES. ALL SHAFTS, PITS, TRENCHES AND HOLES TO BE LEFT OPEN OVERNIGHT SHALL BE COMPLETELY ENCLOSED WITH SUITABLE FENCING AND ACCEPTABLE LIGHTING SHALL BE PROVIDED. THE CONTRACTOR SHALL PROVIDE A 2" X 4" LOCATION STAKE AT THE END OF ALL HOUSE LEADS 48" BELOW GRADE. IF A MANHOLE IS INSTALLED IN, OR IN BACK OF, A ROAD DITCH THE CONTRACTOR SHALL INSTALL A 16 FT. LONG, 16 GAUGE C.M.P. CULVERT WITH END SECTIONS OF A DIAMETER AS DIRECTED BY THE MACOMB COUNTY DEPARTMENT OF ROADS, WASHINGTON TOWNSHIP DEPARTMENT OF PUBLIC WORKS, OR WHOEVER HAS JURISDICTION, IN THE DITCH IN FRONT OF THE MANHOLE AND SHALL BACKFILL WITH 22A AGGREGATE.
AutoCAD SHX Text
SEE STANDARD MANHOLE DRAWING FOR OTHER MANHOLE DETAILS.
AutoCAD SHX Text
2"X 4" LOCATION STAKE PLACED IN BACKFILL.
AutoCAD SHX Text
MINIMUM 1/8" FALL PER FOOT.
AutoCAD SHX Text
ALL HOUSE LEAD PIPE AND JOINTS TO BE TOWNSHIP APPROVED MATERIAL.
AutoCAD SHX Text
REMOVABLE WATERTIGHT AND AIRTIGHT STOPPER AS RECOMMENDED OR SUPPLIED BY PIPE AND JOINT MANUFACTURER.
AutoCAD SHX Text
PLACE RISER AGAINST UNDISTURBED GROUND WHERE POSSIBLE. BACKFILL WITH CARE TO AVOID SETTLEMENT.
AutoCAD SHX Text
1/4" TO 1 1/2" ANGULAR GRADED STONE PLACED AGAINST UNDISTURBED GROUND FOR SUPPORT OF WYE PIPE AND RISER.
AutoCAD SHX Text
6" RISER
AutoCAD SHX Text
45° BEND
AutoCAD SHX Text
6" GLUED JOINT WYE (PLACE WYE SO LEAD ENTERS SEWER MAIN IN SAME DIRECTION AS MAIN LINE FLOW)
AutoCAD SHX Text
30° MIN.60° MAX
AutoCAD SHX Text
3/4"-1 1/4" GAP TO BE PROVIDED TO MAINTAIN JOINT FLEXIBILITY.
AutoCAD SHX Text
FORM SMOOTH AND UNIFORM CHANNELS IN CONCRETE FILL
AutoCAD SHX Text
CONCRETE FILL IN SUMP AFTER COMPLETION OF ACCEPTANCE TESTS.
AutoCAD SHX Text
FLEXIBLE MANHOLE JOINTS
AutoCAD SHX Text
SLOPE 1:12
AutoCAD SHX Text
MANHOLE STEPS ARE TO BE M.A. INDUSTRIES PS-1 OR PS-1-PF " STEEL 12" STEEL ENCAPSULATED IN POLYPROPYLENE, OR APPROVED EQUAL. STEPS TO BE INSTALLED DURING MANHOLE MANUFACTURE. PLACE AT 16" C. TO C. 45° FROM C.L. OF SEWER.
AutoCAD SHX Text
ADJUSTING SUPPORT NUT FOR SETTING FRAME TO CORRECT GRADE.
AutoCAD SHX Text
TAR AND WRAP WITH PLASTIC (6 MIL MINIMUM) OR ALTERNATE AS APPROVED BY TOWNSHIP DEPARTMENT OF PUBLIC WORKS DIRECTOR.
AutoCAD SHX Text
FORM INSIDE MANHOLE AND COMPLETELY FILL SPACE WITH STIFF 6 BAG MIX CONCRETE, USING AIR-ENTRAINED CEMENT.
AutoCAD SHX Text
PROPOSED GRADE
AutoCAD SHX Text
COAT INTERIOR AND EXTERIOR BRICKWORK WITH CONCRETE ENCASEMENT AS APPROVED BY TOWNSHIP DEPARTMENT OF PUBLIC WORKS DIRECTOR.
AutoCAD SHX Text
FOUR CADMIUM COATED 5/8" DIA. THREADED STUDS WITH 3/4"x2"x1/8" THICK METAL WASHER, 3/4"x2"x1/16" THICK NEOPRENE SEALING WASHER AND NUTS.
AutoCAD SHX Text
EJ ERGO HINGED WATERPROOF CAST IRON MANHOLE COVER AND FRAME ASSEMBLY.
AutoCAD SHX Text
6" MINIMUM ADJUSTMENT 15" MAXIMUM ADJUSTMENT
AutoCAD SHX Text
%%UINTERIOR DROP CONNECTION TO EXISTING MANHOLE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
RELINER INSIDE DROP BOWL SECURED WITH STAINLESS STEEL FASTENERS
AutoCAD SHX Text
FILL EXCAVATED SPACE OUTSIDE OF MANHOLE & UNDER PIPE WITH CONCRETE FOR A WIDTH OF 6-INCHES EACH SIDE OF PIPE.
AutoCAD SHX Text
DROP PIPE SIZE TO BE ONE SIZE LESS THAN MAIN WITH 8" MIN. PLASTIC PIPE & 90° BEND.
AutoCAD SHX Text
LAY PIPE BEDDING ON UNDISTURBED SOIL.
AutoCAD SHX Text
NOTE: SEE STANDARD MANHOLE DRAWING FOR OTHER MANHOLE DETAILS.
AutoCAD SHX Text
PVC DROP PIPE LOCATION SHALL BE FLUSH WITH MANHOLE WALL AND NOT INTERFERE WITH MANHOLE STEPS.
AutoCAD SHX Text
38-INCH DIAMETER ALUMINUM STRAP ALLOY 6061-T6 EPOXIED IN PLACE (TYP.)
AutoCAD SHX Text
EXISTING MANHOLE BACKFILL MATERIAL
AutoCAD SHX Text
COMPACTED GRANULAR MATERIAL MDOT CLASS I OR CLASS II SAND, GRAVEL OR CRUSHED STONE 1 " MAXIMUM 12" MAXIMUM PARTICLE.
AutoCAD SHX Text
MDOT CLASS I OR CLASS II GRAVEL OR CRUSHED STONE TO SPRINGLINE AND SAND ABOVE, IF DESIRED. (NO PEA STONE)
AutoCAD SHX Text
MDOT CLASS I OR CLASS II GRAVEL OR CRUSHED STONE TO SPRINGLINE AND SAND ABOVE, IF DESIRED.
AutoCAD SHX Text
PVC PIPE BEDDING DETAIL
AutoCAD SHX Text
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23.
AutoCAD SHX Text
38-INCH DIAMETER ALUMINUM STRAP ALLOY 6061-T6 EPOXIED IN PLACE
AutoCAD SHX Text
STANDARD WATERTIGHT FLEXIBLE MANHOLE JOINT (TYP.)
AutoCAD SHX Text
10' MINIMUM AT PROPERTY LINE OR DEEPER IF REQUIRED FOR BASEMENT SERVICE.
AutoCAD SHX Text
WEIR DETAIL
AutoCAD SHX Text
COMPACTED GRANULAR MATERIAL MDOT CLASS I OR CLASS II SAND, GRAVEL OR CRUSHED STONE 1 " MAXIMUM PARTICLE. 12" MAXIMUM PARTICLE.
AutoCAD SHX Text
{
AutoCAD SHX Text
BRICK ADJUSTMENT
AutoCAD SHX Text
NOTE: MANHOLE RIM SHALL BE SET FLUSH WITH PROPOSED GRADE IN PAVEMENT AREAS OR 0.2 FT. ABOVE PROPOSED GRADE IN NON-PAVEMENT AREAS.
AutoCAD SHX Text
A.S.T.M. C478 RISER SECTIONS WITH MODIFIED GROOVE TONGUE JOINTS.
AutoCAD SHX Text
PRESS WEDGE II , RES-SEAL, LINK-SEAL, OR KOR-N-SEAL (WITH STAINLESS STEEL KORBAND) FLEXIBLE MANHOLE JOINTS.
AutoCAD SHX Text
ON 8" THROUGH 24" DIAMETER SEWERS STANDARD MANHOLE NOT TO SCALE NOTE: 5' DIAMETER STRUCTURES SHALL BE USED FOR 27" THRU 36" PIPE
AutoCAD SHX Text
NOTE: SAND BACKFILL IN TRENCHES CROSSING PAVED AREAS TO EXTEND 3' BEYOND EDGE OF SLAB THEN TAPER AT A 1 ON 1 SLOPE TO ORIGINAL GROUND.
AutoCAD SHX Text
MDOT CLASS II COMPACTED SAND BACKFILL
AutoCAD SHX Text
NOTE: APPROVAL MAY BE GIVEN TO ALTERNATE MATERIALS TO ACHIEVE CLASS B BEDDING.
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
SUMP MANHOLE NOT TO SCALE NOTE: CONSTRUCTED FOR TESTING, CLEANING, AND DEWATERING
AutoCAD SHX Text
STANDARD WATERTIGHT FLEXIBLE MANHOLE JOINTS.
AutoCAD SHX Text
NOTES: 1. ALL JOINTS TO BE GLUED. ALL JOINTS TO BE GLUED. 2. CONTRACTOR SHALL INSTALL A GLUED CAP CONTRACTOR SHALL INSTALL A GLUED CAP AT THE TERMINUS OF THE LEAD ONCE EXTENDED INTO BASEMENT EXCAVATION. CAP SHALL REMAIN IN PLACE UNTIL WASHINGTON TOWNSHIP BUILDING DEPARTMENT APPROVAL.
AutoCAD SHX Text
COVER SECTION A-A
AutoCAD SHX Text
COVER SECTION B-B
AutoCAD SHX Text
26"
AutoCAD SHX Text
3 3/8"
AutoCAD SHX Text
CAST GASKET GROOVE FOR NEOPRENE GASKET
AutoCAD SHX Text
1 5/16"
AutoCAD SHX Text
HINGE POSITONS
AutoCAD SHX Text
90°
AutoCAD SHX Text
120°"
AutoCAD SHX Text
SAFETY CATCH AT 90°
AutoCAD SHX Text
REMOVAL AT 120°
AutoCAD SHX Text
EJ ERGO HINGED WATERPROOF CAST IRON MANHOLE COVER AND FRAME ASSEMBLY PART NO. 001040035L02 NOT TO SCALE
AutoCAD SHX Text
PLAN VIEW
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
1 1/2"
AutoCAD SHX Text
(1) SPECIAL CORED PICKHOLE FOR MPIC
AutoCAD SHX Text
(1) LOCKING CAM (SEE DETAIL)
AutoCAD SHX Text
S
AutoCAD SHX Text
2" SHARP FACE GOTHIC
AutoCAD SHX Text
1 1/4" SHARP FACE GOTHIC
AutoCAD SHX Text
(4) 1" X 1 1/2" SLOTTED HOLES ON A 33 3/4" B.C. TO 32 3/4" B.C
AutoCAD SHX Text
FRAME SECTION A-A
AutoCAD SHX Text
7"
AutoCAD SHX Text
1 9/16"
AutoCAD SHX Text
26 1/4"
AutoCAD SHX Text
36"
AutoCAD SHX Text
24"
AutoCAD SHX Text
28 5/16"
AutoCAD SHX Text
FRAME SECTION B-B
AutoCAD SHX Text
7"
AutoCAD SHX Text
1 9/16"
AutoCAD SHX Text
26 1/4"
AutoCAD SHX Text
36"
AutoCAD SHX Text
24"
AutoCAD SHX Text
28 5/16"
AutoCAD SHX Text
26 1/4"
AutoCAD SHX Text
SITE TUBE CONNECTION (SEE NOTE NO. 7)