  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 1/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Contents

    1 Creating a project with 3 resources (example) ................................................ 2

    2 Definition of bus and subscribers..................................................................... 3

    3 Properties of the Resource................................................................................ 9

    4 Assigning the variables for the communication............................................ 13

    4.1 Notes regarding variable definition: .............................................................. 13

    5 Compiling PES - Master ................................................................................... 19

    6 Communication monitoring............................................................................. 24

    6.1 Communication monitoring in master PES................................................... 24 6.2 Communication monitoring in slave and master PES................................... 25

    7 Hardware, hints, system limits ........................................................................ 27

    8 Changes ............................................................................................................ 28

  • HIMA Training

    RS485 HIBUS-Communication

    Page 2/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    1 Creating a project with 3 resources (example)

    Example: Configuration with 3 resources:

    PESxxx01 with Program-Instance Program_PES1 PESxxx02 with Program-Instance Program_PES2 PESxxx03 with Program-Instance Program_PES3

    The programs are assigned as program-instances to the resources or type instance.

    In example the defined bus (Type HIBUS) has two tasks:

    1. Safety related communication (HIPRO-S) over master module F8621A

    2. Programming bus for ELOP II communication.

    Remark for practice: Depending on load it is recommended to split the networks in two independent systems.

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 3/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    2 Definition of bus and subscribers

    Step 1: Open context menu of the configuration and select properties

    Step 2: Add a new bus. Select the tab "Buses", button "Add" and define a name for the bus e. g. "NETWORK". Confirm with OK.

  • HIMA Training

    RS485 HIBUS-Communication

    Page 4/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 3: Add the stations of the bus

    Click on the button: "Add"

    Step 4: Define the slaves Select a resource out of existing list. BSN (bus station number) must be the same as set with the dip switches on the Central unit. Repeat this step for each resource!

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 5/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 5: Add ELOP II PC Select the bus name, click on the button "Edit"

    In the window "Edit HIBUS bus name" : click on Add Type: select PADT (PC) Insert name for PC Define BSN, No. 31 for PC ! Confirm with OK.

  • HIMA Training

    RS485 HIBUS-Communication

    Page 6/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 6: Add PES-Master(s)

    Click on Add Select the type "PES-Master" Insert name e. g. "Master"

    BSN of Master is automatically taken over from BSN of according central module. There is no special address setting on master module possible.

    PES master parameters:

    CU: master module located beside left central module means CU 1 master module located beside right central module means CU 2

    CM: position (in case of H51q 3 slots are available beside the central modules) Time master: time of master CU is distributed to slaves periodically Redundant Bus: Activates the second interface of F8621A to drive a redundant HIBUS

    Normally only the first bus is active. Second bus is tested periodically and hot standby (switch over automatically) For diagnostic use function block HK-AGM-3, see chapter 6.1

    Additional time delay: Standard timeout for response of slave is 25ms + STO STO = short time out (2ms for 57600bit/sec, 5ms for 9600bit/sec) The time, set by this parameter, is used as an additional time, especially for very slow systems e.g. modem connections.

    Additional pause time Additional time between master requests to create big additional pause times. Used e.g. for satellite communication.

    For further information see Help

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 7/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Repeat step 6 to define a redundant master!

    Redundant master must have the same name as the first master but defined in a different position (normally in the same PES beside CU 2, but not required).

    (example with redundant master)

  • HIMA Training

    RS485 HIBUS-Communication

    Page 8/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 7: Check communication parameters Recommendation for exercise: keep standard settings.

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 9/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    3 Properties of the Resource

    Step 1: Select context menu of the resource, properties, PADT (PC): Select bus out of existing bus list. Select PADT (PC) out of existing PADT list. Note: Do not insert own new names here!

    Take entries with Apply and confirm with button "OK".

    Repeat Step 1 for each resource!

  • HIMA Training

    RS485 HIBUS-Communication

    Page 10/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 2: Edit cabinet layout, checking the interfaces of the central unit and/or F8621A.

    In master PES insert the F8621A modules. (left is F8621, right is F8621x)

    Double click to module: The properties of the central unit are shown

    It is recommended to "use bus settings". By this the parameters can be defined central for all resources belonging to a defined bus.

    HW-settings means, the baud rate set with the dip switches on the central unit is active. It is also possible to set the parameters manually (for special applications).

    The setting can be different for both interfaces (left/up SIO1, right/down SIO2)

    Repeat Step 2 for each resource!

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 11/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 3: Introduce the communication partner in the resource: Select context menu of the resource, > properties, > HIPRO-S

    Select the resources, with which data shall be exchanged: Example: If you opened the properties of PES___01, you can select PES___02 and/or PES___03 as partners.

    Select the Master(s) responsible for organisation of the communication.

    Define the monitoring time: If there is no data exchange with the resource within the monitoring time, the values of the variables are reset if the setting "Reset imported variables" is marked. (Required for safety related communication)

    Repeat Step 3 for each resource!

  • HIMA Training

    RS485 HIBUS-Communication

    Page 12/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Result for PES___01:

    Result for PES___02:

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 13/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    4 Assigning the variables for the communication

    4.1 Notes regarding variable definition:

    Each HIPRO-S variable is defined twice. In the sender as "Export to Resource" and in minimum one receiver as "Import from Resource". The variable name must be the same in all resources where the variable is defined. One variable can be transferred to several receivers.

    To ensure correct spelling it is recommended to define the variable one time at the sender and to copy it using "drag and drop" to the receiver (keep left mouse key pressed) Another possibility: using EXCEL to define the variables and import them afterwards.

    Example: AN02_PES01to PES02 will be created in PES01 and send to PES02 to read it there. So the variable must exist in both program instances. Open both program instances and copy it by "drag and drop":

    The definition of these variables must be done for all resources according to the steps 1-6 in this chapter.

  • HIMA Training

    RS485 HIBUS-Communication

    Page 14/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Example: Variable Var01_PES01toPES02 should be transmitted from PES___01 to PES___02.

    Step 1 Export Open program instance PES___01, > Variable declaration Right mouse button, > New

    Step 2 Export Enter variable name in PES___01 e.g. Var01_PES01toPES02, declaration "BOOL"

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 15/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 3 Export Open folder "HIPRO-N/_S" Mark other resource (PES___02)

    Step 4 Export Select with double-arrow Export to Resource

  • HIMA Training

    RS485 HIBUS-Communication

    Page 16/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 5 Import Open program instance in PES___02 to define the corresponding Import: Create a new Variable in PES___02 with the same Name like in PES___01 used for Export or copy the variable from program instance PES___01 to program instance PES___02, refer to 4.1 (e.g. Var01_PES01toPES02)

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 17/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 6 Import Open folder "HIPRO-N/_S" Mark other resource

    Step 7 Import Select with double-arrow Import from Resource

    Repeat steps 1 to 7 till all variables are defined.

  • HIMA Training

    RS485 HIBUS-Communication

    Page 18/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 8 Start code generator for all resources The code generator must be started for all modified resources! It is not possible to generate reloadable code!

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 19/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    5 Compiling PES - Master

    Step 1 Edit PES-Master Configuration, right mouse button > PES-Master

    Step 2 Compiling PES-Master Mark the PES-Master Button "Execute"

  • HIMA Training

    RS485 HIBUS-Communication

    Page 20/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 21/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 3 Cross-Reference

    Then press button "Cross-Reference"

    With the cross-reference the defined communication variables can be checked. (button Cross-Reference in the PES-Master window.

    Example without errors:

    You can see the variables which will be exchanged between the resources. If there is no error shown in the column Error, all variables are defined correctly. If there are any errors shown they must be eliminated before you can proceed to the next step! (example with only one master)

    Example with errors:

    The variables with indication "no source" or "no target" must be checked again in the program instances . The indication "different data blocks" will sometimes appear additional, can be ignored.

    In example the definition for Export in PES___01 is missing.

    (example with two masters)

  • HIMA Training

    RS485 HIBUS-Communication

    Page 22/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Please note: Window PES-Master CRF-Docu Configuration must be closed! Otherwise code generation in a resource is locked

    Reaction:

    Step 4 Download of the resources If there is no error in the Cross-Reference, each resource can be downloaded. Right mouse button on the resource, > Control panel > Download

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 23/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Step 5 Download PES master(s) Mark both masters and click Execute

    Result:

    If master is not loaded successfully check settings and wiring.

  • HIMA Training

    RS485 HIBUS-Communication

    Page 24/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    6 Communication monitoring

    6.1 Communication monitoring in master PES

    Insert function block HK-AGM-3 in program instance of master PES:

    For settings and diagnostic information see online help of HK-AGM-3.

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 25/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    6.2 Communication monitoring in slave and master PES

    Example: Logic for communication monitoring in PES___03:

    The system variables "HIBUS.Resoucename.Receive counter" and "HIBUS.Resourcename.Fault" are created automatically during installing a HIPRO-S communication. The system variables must be assigned to normal variables to use them in logic.

    Please take care: Communication monitoring is only possible, if there is an installed "Import" from the other resources, means e.g. there must be an active data transmission from PES___02 (Export) to PES___03 (Import) to see "HIBUS.PES___02.Fault" as "FALSE" and a running "HIBUS.PES___02.Receive counter".

  • HIMA Training

    RS485 HIBUS-Communication

    Page 26/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    Advice: In example both system variables are used, in practice it is ok to use only "HIBUS.Resourcename.Fault"

  • HIMA Training

    RS485 HIBUS-Communication

    03-SA-HIBUS_RS485_e_Rev05_(0837).doc ELOP II Page 27/28 by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.

    7 Hardware, hints, system limits

    Bus configuration, Hardware: Please refer to the H41q/H51q catalogue, especially data sheet of interface converter H7505. Here you will find all information about bus configuration, wiring, necessary components and cables.

    Especially take care about final resistors in H7506 modules!

    Battery buffering for master program in F8621A: There is a special battery for buffering the master program: H51q: Two batteries on F7131 H41q: Two batteries on backplane of basic rack.

    Enable batteries with small switches S1 and S2 (must be in position 2, means On)

    System limits:

    Number of variables for HIPRO-S: Max.505 Bytes from one resources to another one, means in one transmission. "Word" will be counted as two Bytes, 8 "Bool" will be counted as one Byte (round up).

    Data memory: Max.64KB can be used in a central module for safety related data exchange with HIPRO-S Note: "Word" will be counted as two Bytes, "Bool" will be counted as one Byte.

    Max.31 communication partners

    Estimation of bus cycle time:

    Basic values: Base time per master: 40ms Writing safety related data, per task: 50ms Writing safety related data, per byte: 0,2ms

    Example: Configuration with 2 redundant F8621A master modules and 3 slaves. In summary there are 6 write tasks and 10 Bytes for each. Bus cycle time = 2x40ms + 6x50ms + 6x10x0,2ms = 392ms

    Estimation of data transmission time (Input => PES => BUS => PES => Output):

    worst case: 2x cycle time of sending PES + 2x bus cycle time + 2x cycle time of receiving PES statistic value: 1,5x cycle time of sending PES + 1,5x bus cycle time + 1,5x cycle time of receiving PES

  • HIMA Training

    RS485 HIBUS-Communication

    Page 28/28 ELOP II 03-SA-HIBUS_RS485_e_Rev05_(0837).doc by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.