S8610U3009 Universal Electronic Ignition Modules Training Module (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006). What you will learn. Ignition Types S8610U3009 Features and Benefits Installation and Set Up Troubleshooting S8610U Advantage Y8610U Retrofit Ignition Kit Overview - PowerPoint PPT Presentation

Transcript of S8610U3009 Universal Electronic Ignition Modules Training Module (plus Universal Retrofit Kits...

Page 1: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

S8610U3009 Universal Electronic Ignition

Modules Training Module

(plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Page 2: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

2

What you will learn

• Ignition Types• S8610U3009

- Features and Benefits- Installation and Set Up - Troubleshooting- S8610U Advantage

• Y8610U Retrofit Ignition Kit Overview• Product Cross Reference Information

Page 3: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

3

Ignition Sources

• There are 3 different ways a burner can be ignited:

- 1) Standing Pilot Ignition

- 2) Intermittent Pilot Ignition Intermittent Pilot - S8610U

- 3) Direct Burner Ignition Hot Surface Ignition – S8910UDirect Spark Ignition – S87

Page 4: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

S8610U3009

Page 5: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

5

Universal Intermittent Pilot Module

• What is the S8610U3009?- Provides electronic control of

intermittent pilot ignition systems used on gas fired furnaces, boilers, and other heating appliances

- It’s the brain of the ignition system Receives call for heat signal from the

thermostat Starts the spark ignition Opens the pilot valve Senses to see if the pilot is lit Opens the main burner Shuts things down at the end of the

call for heat Monitors damper as opened or closed,

if damper is attachedOne Part Number:

S8610U3009

Page 6: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

6

Normal Operation of an Intermittent Ignition Module

On Off

Valve On

Pilot Lights

Prove

Pilot

Off

Off

Burner Lights

Valve On

End Call

for Heat

MainBurner

Pilot

Ignition

Call for HeatOn a call for heat, both the Pilot valve and the Ignition come on together.

Once the pilot is proved, the Ignition shuts off and the Main burner opens and remains open throughout the call for heat.

When the call for heat ends, both the Main burner and Pilot shut off together.

Page 7: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

7

S8610U Features

• Universal Compatibility- Replaces more than 400

Honeywell and competitive models

• Application Flexibility- Works in single-rod and dual-

rod applications- Works with both natural and

LP gas• Quality Honeywell Control

- Provides electronic control for nearly any intermittent pilot ignition systems used on gas-fired furnaces, boilers and more

- Suitable for use with vent dampers

- Provides the ignition sequence, flame monitoring and 100% safety shutoff

• Enhanced Features- Single LED indicates flame

strength and gives diagnostic information

- Direct flame signal readout form the board

- Simplified error codes on label

Page 8: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

8

The Benefits

• Feature• Field selectable operating

sequence can be customized

• Control locks to selected sequence on 20th “call for heat”

• LED communicates system status

• Integral damper connector

• Continuous retry ignition sequence

• Benefit• Allows for more options in the field:

- 0 or 30 second prepurge and- 15 or 90 second trial for ignition

• Assures selected sequence is retained permanently

• Green LED indicates status, error codes and pilot flame strength

• If senses use with a vent damper it locks the control, so damper must be used

• Provides 100% shutoff for both Natural and LP applications

Page 9: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

9

Additional benefits

• Feature• Single-rod or dual-rod flame

sensor

• Terminal-to-terminal wiring instructions

• Flame sense terminal 3/16” male QC (virtually all 2-rod systems sold have the sense terminal as 3/16” QC)

• Spark cable adapter

• 2.0 A main valve load rating

• Benefit• Works in more applications

• Reduces wiring errors

• Prevents possible mis-wire of spark sense and potential for abnormal appliance light-off

• Includes adapter for rajah and nail type cable on existing systems; Simplified use

• Broader application; Fits more jobs

Page 10: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

10

Ignition Sequences when a pilot fails to light

Call for Heat Lockout

ContinuousRetry

Non-Lockout

Valve & Ignition On

Valve & Ignition Off

or...

or...

5 Min Off

Call for Heat

Valve & Ignition On

90 Sec Trial

90 Sec Trial

Trial Period

5 Min Off

LockoutShuts off and does not retry

Does not shut off, could be a safety issue

S8610U - Continuous retry with 100% safety shutoff between trials

Page 11: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

11

SPARK

REMOTE SENSE

SENSE JUMPER WIRE

CUSTOMIZE OPERATING SEQUENCE

STATUS LED

P1 VENT DAMPER CONNECTOR

MV

MV/PV

PV

BRN/GND 24 GND

24V (OPT.)

TH-W (OPT.)

S8610U Control Layout

FLAME CURRENT MEASUREMENT PORTS

Page 12: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Installation

Page 13: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

13

Installation of the S8610U

• Mount new ignition module - Do not mount with terminals facing up- protect the module from exposure to water, moisture, corrosive

chemicals and excessive dust and grease.

• Wire the module- Wire the module per the installation instructions- Verify the thermostat anticipator setting

Page 14: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

14

Wiring continued

For systems with a vent damper connect the damper to P1

Once the vent damper connection is made, the control must be used with a vent damper.

Page 15: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

15

Use With 1-Electrode Pilot

Jumperremains onSENSE

S8610U C

ON

TINU

OU

S RE-TR

Y24V, 60 H

z; PV = 1A M

ax.; MV = 2A

Max.

! WA

RN

ING

MV

MV/PV

PV

GND

24V

24V

TH-W

If module has been used w

ithvent dam

per, it will only w

orkw

ith damper connected.

Honeyw

ell

STATU

S

S1

1 2

ON

SPAR

K

SENSE

DA

MPER

0 Sec. P

repurge90 S

ec. Trial for Ignition

To wire this up, one wire runs from the Igniter to the module SPARK terminal. The black jumper connected to the SENSE terminal remains connected

Page 16: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

16

OR Use With 2-Electrode Pilot

S8610U C

ON

TINU

OU

S RE-TR

Y24V, 60 H

z; PV = 1A M

ax.; MV = 2A

Max.

! WA

RN

ING

MV

MV/PV

PV

GND

24V

24V

TH-W

If module has been used w

ithvent dam

per, it will only w

orkw

ith damper connected.

Honeyw

ell

S1

1 2

ON

SPAR

K

SENSE

DA

MPER

0 Sec. P

repurge90 S

ec. Trial for Ignition

Sense WireSpark Wire

Unplug jumperand cut off wire

On a two rod application, there will be two wires running from the pilot to the module. The high voltage wire to SPARK and the flame sensor wire to SENSE

STATU

S

Page 17: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Set Up

Page 18: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

18

Set Up the S8610U

• Review the module installation and set up for use- Visually inspect, safety check, and review operating sequence

per installation instructions- Customize the operating sequence based on the specifications

of the originally installed control

Page 19: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

19

Customize Operating Sequence

Prepurge Trials for Ignition Sw 1 Sw 2

None90 Seconds OFF OFF30 Seconds 90 Seconds ON OFFNone15 Seconds Off ON30 Seconds 15 Seconds ON ON

Set the dip switches per the application.

Page 20: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Troubleshooting

Page 21: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

21

Troubleshooting of the S8610U

Flame signal is not getting back to the module•This is a common problem

•Probable causes•Bad wiring in the flame detection circuit•Pilot not burning properly•Flame sensor damaged/corroded•Cracked/contaminated ceramic

Page 22: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

22

LED status and flame strength

Green LED status codes Indicates status, error codes and flame strength

Page 23: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

23

Status LED

Green Status LED CodesOFF No “call for heat”Flash fast Power up – internal checkHeartbeat Normal startup – ignition started2 5 min. retry delay3 Recycle4 Flame out of sequence5 Damper error6 Control internal error7 Flame rod shorted to ground8 Low voltage

4-second solid on followed by “x” 1-second flashes indicates flame current

Page 24: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

24

Flame current measurement

Pilot flame current can be measured using a standard micro-ammeter

Page 25: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Universal IP Retrofit Ignition System Kits

Y8610U

Page 26: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

26

Universal IP Retrofit Ignition System Kit

• What is the Y8610U?- Complete kit converting conventional standing pilot systems to

intermittent pilot systems. - Use with 24 Vac gas-fired atmospheric furnaces, boilers and

heating appliances- Natural or LP gas (includes LP conversion kit)- Reintroduced in 2007 to include the new S8610U3009

Page 27: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

27

Y8610U6006 Features

• The Y8610U6006 (replaced Y8610U3003) Ignition System Kit includes:- S8610U3009 Intermittent Pilot Ignition Module- VR8304M3558 Gas Valve - ¾” x ¾” - Harness Assembly, Ignition Cable Assembly, Mounting Kit,

Ignitor, L.P. Conversion Kit, Pipe Bushing or Fitting and ¾” Straight Flange

- Y8610U6006 FEATURES :- Continuous Retry Ignition Sequence - LP or Natural Gas - Valve Capacity – 270K BTUH- ¾” to ½” Bushings- LP Kit

Page 28: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

28

Y8610U4001 Features

• Y8610U4001 (replaced Y8610F5003) includes:- S8610U3009 Intermittent Pilot Gas Burner Control- VR8204A2142 Gas Valve – ½” X ½”- Harness Assembly, Ignition Cable Assembly, Mounting Kit, Igniter

Kit, L.P. Conversion Kit, and ¾” Straight Flange

- Y8610U4001 FEATURES :- Continuous Retry Ignition Sequence - LP or Natural Gas - Valve Capacity – 150K BTUH- LP Kit

Page 29: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

Product Cross Reference

Page 30: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

30

Product Cross Reference

• Where do I find Honeywell electronic ignition cross reference and selection information?

- www.customer.honeywell.com- Honeywell Application Selection and Cross Reference Guide – Form 63-9575- Honeywell Laminated Truck Visor – Form 63-9581G- S8610U Technicians Quick Reference Guide – Form - Honeywell Residential Technical Support: 1-800-468-1502

63-9581G 63-9575

Page 31: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

31

Product Cross Reference Guide

Forms 63-9575 and 63-9581G – information also found in product installation sheets.

Page 32: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

32

www.customer.honeywell.com

• See Cross Reference Search box in right column.

Page 33: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

33

The S8610U Advantage

• When promoting the S8610U keep these advantages in mind:

- The S8610U replaces over 400 Honeywell and competitor’s ignition modules, reducing inventory and callbacks.

- Easy Installation saves the contractor valuable time and resources.

- Field-selectable pre-purge and ignition timings make the S8610U a Universal replacement

- The S8610 is application flexible and can be used with single rod or dual rod systems, and natural or LP gas.

- The diagnostic LED and flame signal indicator make troubleshooting simple, solving the problem quickly and satisfying the customer.

Page 34: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

S8610U Universal Electronic Ignition

Knowledge Test

Page 35: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

35 HONEYWELL - CONFIDENTIAL File Number

• Now that you completed this training module, take the short quiz to test your knowledge.

Universal Electronic Ignition Knowledge Test

Page 36: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

36 HONEYWELL - CONFIDENTIAL File Number

Test

1. The S8610U3009 is an intermittent pilot ignition module? T or F

2. The S8610U is application flexible and work with single or dual rod systems? T or F

3. On the S8610U once the controls senses a vent damper, the control can be used without a vent damper? T or F

4. The operating sequence on the S8610U is customized by setting dip switches on the device? T or F

5. A new feature on the S8610U includes a separate LED flame signal indicator? T or F

Page 37: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

37 HONEYWELL - CONFIDENTIAL File Number

Test

6. The S8610U has continuous retry and 100% safety shut off between cycles? T or F

7. The S8610U works with only natural gas? T or F8. Flame strength readings can be taken directly

from the board with a standard micro-ammeter? T or F

9. The Y8610U kits convert applications from standing pilot to hot surface ignition? T or F

10.The Honeywell S8610U replaces over four hundred Honeywell and competitive ignition modules? T or F

Page 38: S8610U3009  Universal Electronic Ignition Modules  Training Module  (plus Universal Retrofit Kits Y8610U4001 and Y8610U6006)

38 HONEYWELL - CONFIDENTIAL File Number

Answer Key

1. T2. T3. F4. T5. F6. T7. F8. T9. F10.T