S7 400 CPU TYPES
1) CPU 412-1 2) CPU 412-2 3) CPU 414-2, 4) CPU 414-3, 5) CPU 414-3 PN/DP 6) CPU 416-2, 7) CPU 416-3, 8) CPU 416-3 PN/DP 9) CPU 417-4 10) CPU 414-4H, 11) CPU 417-4H 12) CPU 416-2F
![Page 2: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/2.jpg)
1) CPU 412-1, CPU 412-2
• The low-cost starter solution for the medium performance Range • Can be used in small and medium-sized systems with requirements Of the medium performance range 2) CPU 414-2, CPU 414-3, CPU 414-3 PN/DP
• CPUs for high demands in the mid-level performance range • Applicable for plants with additional demands on Programming scope and processing speed
![Page 3: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/3.jpg)
• Integrated PROFINET functions in CPU 414-3 PN/DP CPU 416-2, CPU 416-3, CPU 416-3 PN/DP
• High-performance CPUs in the high-end performance range • Applicable for plants with high requirements in the high-end Performance range • Integrated PROFINET functions in CPU 416-3 PN/DP CPU 417-4
• The most powerful SIMATIC S7-400 CPU • Can be used in the most sophisticated installations in the
![Page 4: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/4.jpg)
Upper performance range • With two slots for IF modules CPU 414-4H
• CPU for SIMATIC S7-400H and S7-400F/FH. • Can be used in high availability S7-400H systems • Can be used with F-runtime license and F-compatible CPU in Failsafe S7-400F/FH systems • With integrated PROFIBUS DP master interface • With 2 slots for sync modules CPU 417-4H
• CPU for SIMATIC S7-400H and S7-400F/FH. • Can be used in high availability S7-400H systems
![Page 5: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/5.jpg)
• Can be used with F-runtime license and F-compatible CPU in Failsafe S7-400F/FH systems • With integrated PROFIBUS DP master interface • With 2 slots for sync modules CPU 416F-2
• For design of a fail-safe automation system for plants with Increased safety requirements • High-performance CPU in the high-end performance range • With 2 interfaces (1x DP/MPI, 1x DP) • Complies with safety requirements up to SIL 3 to IEC 61508 And Cat. 4 according to EN 954-1 • Standard as well as safety-relevant tasks can be solved with
![Page 6: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/6.jpg)
Just one CPU • Multi-processor mode is possible • Safety-related communication with distributed I/O stations Over PROFIBUS DP with the PROFIsafe profile • Distributed fail-safe I/O modules can be connected over the Integral PROFIBUS DP interfaces and/or over communications Modules (CP443-5 Ext. and CP443-1 Adv) • Central and distributed use of standard modules for no safety- Relevant applications SM 421 AL INPUT MODULE
• Digital inputs for the SIMATIC S7-400 • For connecting standard switches and two-wire proximity Switches (BERO) DIGITAL INPUT MODULE
![Page 7: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/7.jpg)
• Digital outputs for the SIMATIC S7-400 • For connecting solenoid valves, contactors, low-power Motors, lamps and motor starters ANALOG INPUT MODULE
• Analog inputs for the SIMATIC S7-400 • For connection of voltage and current sensors, thermocouples, Resistors and resistance thermometers • Resolution from 13 to 16 bit ANALOG OUTPUT MODULE
![Page 8: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/8.jpg)
TECHNICAL SPECIFICATIONS FOR S7 400 CPU’S
![Page 9: s7 400 Cpu Types](https://reader031.fdocuments.in/reader031/viewer/2022020803/55206cfa4979597f2f8b4a42/html5/thumbnails/9.jpg)
Multi computing with UR1 or UR2
First Interface Second Interface Third Interface
Forth Interface
Of which central
Max AI/AO
Of which central
Max DI/DO
Slot required for CPU on the rack
Timers/Counters (S7)
Floating point
Bit/ Word/ Fixed point operation
Work Memory (Data + Code)*
Features
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
Profibus DP** Profibus DP**
8192
8192
131072
131072
2 Slots
2048/2048
0.09µµµµsec
0.03µµµµsec
20MB
CPU 417-4
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
None
None
2048
2048
32768
32768
1Slot
2048/2048
0.3µµµµsec
0.1µµµµsec
256KB
CPU 412-2
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
None
None
4096
4096
65536
65536
1Slot
2048/2048
0.18µµµµsec
0.06µµµµsec
512KB
CPU 414-2
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
Profibus DP** None
4096
4096
65536
65536
2 Slots
2048/2048
0.18µµµµsec
0.06µµµµsec
1.4 MB
CPU 414-3
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
None
None
8192
8192
131072
131072
1 Slot
2048/2048
0.12µµµµsec
0.04µµµµsec
2.8 MB
CPU 416-2
Max. 4 CPUs
MPI, DP Master/ Slave
DP Master/ Slave
Profibus DP** None
8192
8192
131072
131072
2 Slots
2048/2048
0.12µµµµsec
0.04µµµµsec
5.6 MB
CPU 416-3
Max. 4 CPUs
MPI, DP Master/ Slave
None None
None
2048
2048
32768
32768
1 Slot
2048/2048
0.3µµµµsec
0.1µµµµsec
144 KB
CPU 412-1