Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Order number6ES7334-0CE01-0AA0
Properties
• 4 inputs in one group and 2 outputs in one group
• Resolution 8 bits
• Programmable measurement type at each channel group
― Voltage
― Current
• Not programmable, measurement and output type defined by hardwiring
• Connected to potential of the backplane bus interface
• Electrically isolated to load voltage
Terminal assignmentThe diagrams below show various wiring options.
Note
Note when wiring the SM 334:
• analog ground MANA(terminal 15 or 18) is interconnected with chassis ground M of the CPU orinterface module IM. Use a cable with a conductor cross-section of at least 1 mm2.
The module will shut down if the ground connection between MANA and M is missing. Inputs are readwith 7FFFH, and outputs return a value of 0. The module may be destroyed if operated without groundover a longer period of time.
• the supply voltage for the CPU and/or the interface module (IM) may not be connected with reversedpolarity. Reverse polarity will inevitably lead to the destruction of the module, because MANA developsan impermissible high potential (+24 V.)
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Wiring: Current measurement and current output
① Internal supply
② Analog-to-Digital Converter (ADC)
③ Inputs: Current measurement
④ Outputs: Current output
⑤ Digital-to-Analog Converter (DAC)
⑥ Backplane bus interface
⑦ Equipotential bonding
⑧ Functional earthFigure 1 Wiring and block diagrams
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Wiring: Voltage measurement and voltage output
① Internal supply
② Analog-to-Digital Converter (ADC)
③ Inputs: Voltage measurement
④ Outputs: Voltage output
⑤ Digital-to-Analog Converter (DAC)
⑥ Backplane bus interface
⑦ Equipotential bonding
⑧ Functional earthFigure 2 Wiring and block diagrams
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Wiring: 4-wire transducers for current measurement and voltage output
① Internal supply
② Analog-to-Digital Converter (ADC)
③ Inputs: Current measurement with 4-wire transducer
④ Outputs: Voltage output
⑤ Digital-to-Analog Converter (DAC)
⑥ Backplane bus interface
⑦ Equipotential bonding
⑧ Functional earthFigure 3 Wiring and block diagrams
Technical data
Technical data
Dimensions and weight
Dimensions W x H x D (mm) 40 x 125 x 117
Weight approx. 285 g
Module-specific data
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Technical data
Isochronous mode supported no
Number of inputs 4
Number of outputs 2
Cable length
• shieldedmax. 200 m
Voltages, currents, electrical potentials
Rated supply voltage of the rated electronics and load voltage L+ 24 VDC
Electrical isolation
• between channels and the backplane bus
• between channels and electronics power supply
noyes
between channels no
Maximum potential difference
• between inputs and MANA (CMV)
• between inputs (CMV)
1 VDC1 VDC
Isolation test voltage 500 VDC
Current consumption
• from the backplane bus
• from supply and load voltage L+ (no load)
max. 55 mAmax. 110 mA
Power loss of the module typ. 3 W
Generation of analog input values
Measuring principle
• Resolution (including overshoot range)Actual value conversion8 bits
Integration/conversion time (per channel)
• programmable
• Integration time in µs
no<500
Basic execution time of inputs max. 5 ms
Time constant of the input filter 0.8 ms
Generation of analog output values
• Resolution (including overshoot range) 8 bits
Conversion time (per channel)
• programmable
• Conversion time in µs
no<500
Basic execution time of outputs max. 5 ms
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Technical data
Settling time
• with resistive load
• with capacitive load
• with inductive load
0.3 ms3.0 ms0.3 ms
Noise suppression, error limits for inputs
Noise suppression at F = n (f1 ± 1 %) (f1 = interference frequency)
• Common-mode noise (Vpp < 1 V) > 60 dB
Crosstalk between outputs > 50 dB
Operational error limit (across temperature range, relative to input range)
• Voltage input
• Current input± 0.9 %± 0.8 %
Basic error limit (operational error limit at 25 °C, relative to input range)
• Voltage input
• Current input± 0.7 %± 0.6 %
Temperature error (relative to input range) ± 0.005 %/K
Linearity error (relative to input range) ± 0.05 %
Repetition accuracy (in transient state at 25 °C, relative to input range) ± 0.05 %
Output ripple; range 0 Hz to 50 kHz (relative to output range) ± 0.05 %
Noise suppression, error limits of outputs
Crosstalk between outputs > 40 dB
Operational limit (across the temperature range, relative to output range)
• Voltage output
• Current output± 0.6 %± 1.0 %
Basic error limit (operational error limit at 25 °C, relative to output range)
• Voltage output
• Current output± 0.5 %± 0.5 %
Temperature error (relative to output range) ± 0.02 %/K
Linearity error (relative to output range) ± 0.05 %
Repetition accuracy (in transient state at 25 °C, relative to outputrange)
± 0.05 %
Output ripple (bandwidth relative to output range) ± 0.05 %
Status, interrupts, diagnostics
Interrupts none
Diagnostics functions none
Sensor selection data
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014
Technical data
Input ranges (rated values) / input impedance
• Voltage
• Current
0 V to 10 V/100 k Ω0 mA to 20 mA/50 Ω
Maximum voltage at voltage input (destruction limit) max. 20 V continuous; 75 V for max. duration of 1 s(duty factor 1:20)
Maximum current at current input (destruction limit) 40 mA
Wiring of the signal sensors
• for voltage measurement
• for current measurement as 2-wire transducer as 4-wire transducer
using a 20-pin front connectorsupported
supported with external supply
Actuator selection data
Output ranges (rated values)
• Voltage
• Current
0 V to 10 V0 mA to 20 mA
Load impedance (in the rated output range)
• For voltage outputs― capacitive load
• For current outputs― inductive load
min. 5 kΩmax. 1 µFmax. 300 Ωmax. 1 mH
Voltage output
• Short-circuit protection
• Short-circuit current
yesmax. 11 mA
Current output
• noload voltagemax. 15 V
Destruction limit against external voltages/currents
• Voltage at outputs to MANA
• Current
max. 15 V, continuousmax. 50 mA d.c.
Wiring of the actuators
• for voltage output 2-wire connection 4-wire connection (measuring line)
using a 20-pin front connector
supported not supported
S7-300 Module dataAnalog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0)
Este documento es un extracto gratuito, compilado por el propio usuario, de la documentación ofrecida por Siemens para este producto. Se declina cualquierresponsabilidad sobre la integridad de este documento. Esta previsto exclusivamente para fines propios e internos del usuario. No se permite su entrega a terceros.La documentación completa está disponible enhttps://www.automation.siemens.com/mdm/default.aspx?DocVersionId=6541330315&Language=en-US&TopicId=4920075787 4/9/2014