S ubcooling Mini-Split Senior Capstone Design

31
Subcooling Mini- Split Senior Capstone Design Bangor Hydro Presentatio 12/17/13 Samuel Prentiss Matt Strong Bruce Tuttle

description

S ubcooling Mini-Split Senior Capstone Design. Samuel Prentiss Matt Strong Bruce Tuttle. Bangor Hydro Presentation. 12/17/13. Tonight’s Points. Subcooling Heat Pump Installation & Testing Return on Investment Marketable Product. The Heat Pump Cycle. R-410A Vapor Condenses. - PowerPoint PPT Presentation

Transcript of S ubcooling Mini-Split Senior Capstone Design

PowerPoint Presentation

Subcooling Mini-SplitSenior Capstone Design

Bangor Hydro Presentation12/17/13Samuel Prentiss Matt StrongBruce TuttleTonights PointsSubcooling Heat Pump

Installation & Testing

Return on Investment

Marketable ProductThe Heat Pump Cycle

Image Source: http://www.air-conditioning-and-refrigeration-guide.com/ R-410A Vapor CondensesR-410A Liquid EvaporatesR-410A Vapor CompressedR-410A Liquid ExpandsHeat Pump No Subcooling

Image Source: http://www.dc429.4shared.com/docSaturated Liquid LineSaturated Vapor LineHeat Pump With Subcooling

Image Source: http://www.dc429.4shared.com/docQsubcoolerQevaporator_additionalAll Saturated Liquid After Passing Through EEVLatent & Sensible HeatSubcooler Coil Output

What is Coefficient of Performance?`Without Subcooling`With SubcoolingCOP=3COP=4C.O.P. for the Visual LearnersC.O.P. Due to Subcooling

At Least 20F Subcooling Needed to be BeneficialCompressor EER

Air Outlet TemperatureCapstone PlanBuild Subcooler Unit (Jan-Feb 2014)

Install at University Garage (Feb 2014)1 ton Fujitsu Mini-Split Heat PumpGE GeoSpring Hybrid Water HeaterSubcooler Unit

Monitor & Improve!!

Key Components

Image Source: http://www.amazon.comImage Source: http://greenenergymaine.comFujitsu 12RLS2 (1 ton)GE GeoSpring

Important Features

Centrifugal Duct FanMicro-Channel CoilConnect Liquid Refrigerant Line

Saturated Liquid From Indoor UnitSubcooled Liquid to Outdoor UnitAirstream Flows Over Coil

GE GeoSpringActuated Louvers10 Square Duct8 Round DuctCentrifugal FanSolid Model

Combine TogetherDeliver Heated Airstream to GeoSpring Intake

Heated Airstream Will Diffuse Into Garage if GeoSpring is not RunningUniversity Facilities GarageImage Source: https://maps.google.com/maps

Estimated Cost (With Rebates)Subcooler UnitFujitsu 12RLS2GE GeoSpringInstallation

Total Capital Cost= $1000.00= $1600.00= $700.00= $1400.00

= $4700.00Payback PeriodHow will The Subcooler Save Money?By increasing the performance of the Heat Pump! COP With Subcooling > COP No Subcooling

Payback Period

Equation derived with help from Peter Talmage.

Payback PeriodPrice of Electricity=$0.16/kWh*

4817 Hours of Operation Per Year**

Sources: (* Bangor Hydro ** James LaBrecque)Payback Period

Payback Period* = 24.4 Years Motivation

Source: Google PatentsMotivationTHEIR TECHNOLOGY: ADDITIONAL CONDENSER, EXPANSION VALVE, EVAPORATOR, AND COMPRESSOR OUR TECHNOLOGY: ONE ADDITIONAL COIL. SummarySubcooler Unit Increases Heat Pumps COP & EERUniversity of Maine Facilities GarageMonitor Installation:Fujitsu Mini-Split Heat PumpGeospring Hybrid Water HeaterSubcooler UnitImprove Design!

Final Marketable Product $$$Mass Produce as an Accessory for Heat Pump

Minimal Installation Time for HVAC Technician

Customize Where Heated Airstream is Delivered

Free Heat Is Currently Being Wasted!!Thank You For Your Time!