RXB application library (KNX)
FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12
(See separate document CM110385 for the FNC description of functions).
Fr RXB...
Application Page 21.1 21.1 22.1
FNC02 Two-pipe fan coil with changeover 3 X FNC03 Two-pipe fan coil with changeover and electric reheater 9 X FNC04 Four-pipe fan coil 15 X FNC05 Four-pipe fan coil with electric reheater 21 X FNC08 Four-pipe fan coil with room supply air cascade 27 X FNC10 Two-pipe fan coil with changeover and outside air damper 31 X FNC12 Four-pipe fan coil with outside air damper 37 X FNC18 Two-pipe fan coil (changeover) and radiator 43 X FNC20 Four-pipe fan coil controlled by damper 49 X Application package
FC-1
0
FC-1
1
FC-1
2
Related documents
CM110385 FNC description of functions for FC-10, FC-11, FC-12 CM1Y9775 RXB integration, S-mode. CM1Y9776 RXB / RXL integration individual addressing. CM1Y9777 Third party integration. CM1Y9779 Working with ETS. CA1N3804 DESIGO RX hardware overview.
CM110672en_03 30.11.2007 Building Technologies
-
2/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies 30.11.2007
-
3/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
FNC02 Two-pipe fan coil with changeover
KNX R Heating only (with LTHW), cooling only (with CHW) or changeover. Changeover via KNX bus. Modulating control of heating/cooling valve. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. D1 Window switch. D2 Presence detector. D3 Changeover signal via KNX
bus. Q1 Fan (1 ... 3 speeds). YHC Heating/cooling valve.
TB1
Q1
N1
R1 D1 D2T
YHC
D3
KNX R10
385S
10
Operating diagrams
100
0TR [C]
Y [%]
SpH SpC
Change-over
YHCYHC
H C
10385D45
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YHC Heating/cooling valve. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
10385D34Change-over
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
-
4/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
The following functions are available with Application FNC02 (refer to the description of functions CM110385 for detailed information):
Function Brief description) Two-pipe fan coil.. PI control.
Proportional control sequence, selectable: Only heating sequence, only cooling sequence or changeover.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM or AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves. Valve exercising feature.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC02 is supplied with RXB21.1/FC-10.
Functions
-
5/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
Y1 G Y2
YHC.23)
M
KNX
D3
T
4)
1 2 3
Q1
N
L
AC 230 V
1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1 G Y2 CP
CP
+
B1
25 26 27 RXB21.1
Q13
Q14
Y3 G Y4Q
24
Q34
2819 21
N LN
21L
CE
CE+
19
N1
MB
B1
T
D1 2) D2 2)
2 1 4 3
QAX...
R1
1038
5A01
CE
CE+
YHC.13)
N.C
.
3
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor, room temperature sensor. D1 Window contact 2). D2 Presence detector 2). D3 Changeover signal via KNX bus. Q1 1- or 3-speed fan 4). YHC.1 Heating/cooling valve actuator, thermal, 2-point (PDM) control 3). YHC.2 Heating/cooling valve actuator, motorized, 3-position control 3).
2) Type of operation (N/O or N/C) can be selected. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
6/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
The following parameters are available with application FNC02. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Sequences Control sequence Heating only
Cooling only Changeover
Cooling only
Actuator type heat/cool valve STA71 SSA81 STA72E SSB81 STE71 SSP81 STE72 SQS81 STP71 STP72E Electromech. 3rd devices Motorized 3rd devices Thermal 3rd devices Motorized bus
STP72E
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Motorized and electromechanic Runtime 0 ... 360 s 150 s
Motorized Offset 0 ... 360 s 0 s Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
Configuration
-
7/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
8/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC02 Two-pipe fan coil with changeover 30.11.2007
-
9/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
FNC03 Two-pipe fan coil with changeover and electric reheater
KNX R Heating only (with LTHW), cooling only (with CHW) or changeover. Changeover signal via KNX bus. Modulating control of heating/cooling valve. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. D1 Window switch. D2 Presence detector. D3 Safety thermostat, electric
heating coil. D4 Changeover signal via KNX
bus. Q1 Fan (1 ... 3 speeds). YHC Heating/cooling valve. YR Electric reheater.
1038
5S11
TB1
Q1
N1
R1 D1 D2T
YHC
D4
YRD3
KNX R
Operating diagrams Changeover = Heating. In "Heating" mode, the electric heating coil operates as a reheater for LTHW heating, i.e. only when the valve is fully open.
Changeover = Cooling.
In "cooling" the electric heating coil acts as the only heating as soon as temperature falls below SpH.
1-stage
OFFTR [C]
Y
ON
YR
H10385D30
1 K
YHC
SpH
OFFTR [C]
ON
10385D31
SpH
YR
SpC
YHC
Y
C
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YHC Heating/cooling valve. YR Contactor or solid state
relay for electric heating coil.
Mod.
OFFTR [C]
ONH
10385D32
YHC
SpH
YR
Y
0%
TR [C]
100%H
10385D33
SpH
YR
Y
SpC
YHC
C
-
10/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
10385D34Change-over
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
Application FNC03 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Two-pipe fan coil.. PI control.
Proportional control sequence, selectable: Only heating sequence, only cooling sequence or changeover.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /or AC 24 V 2-position / AC 24 V 3-position).
Control of motorized KNX bus actuator valves. Valve exercising feature.
Electric reheater. 2-position or proportional control. Control: AC 24 V, 2-position or proportional.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC03 is supplied with RXB22.1/FC-12.
Functions
-
11/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
2 1 4 3
QAX...
R1
1038
5A02
T
17 18
M D1
GN
D
D2
Y1
G Y2
B1
19 21 25 26 27 RXB22.1
N L Q13
Q14
N Q24
Q34
28
KNX
MB
B1
T
D1 2) D2 2) YHC.13)
4)
1 2 3 Q1
N
L
AC 230 V
N1
D4
T
22 23 24
Q43
Q44
6)
F1 7)
YR
Y1 G Y2
YHC.2 3)
M
CP
CP
+
CE
CE
+
D3 2)
21L
19
CE
CE
+
2 3 4 5 6 7 8 9 13 14 15 161
N.C
.
N.C
.
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor, room temperature sensor. D1 Window contact 2). D2 Presence detector 2). D3 Safety thermostat, electric heating coil. D4 Changeover signal via KNX bus. Q1 1- ... 3-speed fan. YR Electric reheater 6). F1 External fuse, max. 10 A 7). YHC.1 Heating/cooling valve actuator, thermal, 2-point (PDM) control 3). YHC.2 Heating/cooling valve actuator, motorized, 3-position control 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected.
Identical devices must not be connected to both inputs. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). 6) The output of the electric heating coil at output Q44 must not exceed 1.8 kW. 7) External fuse, max. 10 A (protects pcb tracks). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
12/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
The parameters below are available with application FNC03. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Sequences Control sequence Heating only
Cooling only Changeover
Cooling only
Actuator type heat/cool valve STA71 SSA81 STA72E SSB81 STE71 SSP81 STE72 SQS81 STP71 STP72E Electromech. 3rd devices Motorized 3rd devices Thermal 3rd devices Motorized bus
STP72E
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Motorized and electromechanic Runtime 0 ... 360 s 150 s
Motorized Offset 0 ... 360 s 0 s Electric heater 1-stage
Mod. Mod.
Power consumption 0 ... 6500 W 0 W LTE mode Heating outp bus el heating Off/On Off
Fan control. Fan speeds External control 1-speed/2-speed/3-speed
3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Fan overrun time 1 ... 10 min 1 min Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Overtemp. = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Overtemp. = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min
Configuration
-
13/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
Menu Parameters. Values/Range Basic setting Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
14/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC03 Two-pipe fan coil with changeover and electric reheater 30.11.2007
-
15/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 Four-pipe fan coil 30.11.2007
FNC04 Four-pipe fan coil
KNX R Heating with LTHW and cooling with CHW. Modulating control of heating and cooling valve. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. D1 Window switch. D2 Presence detector. Q1 Fan (1 3-speed). YH Heating valve. YC Cooling valve.
1038
5S12
TB1
YC
YH
Q1
N1
R1 D1 D2T
KNX R
Operating diagrams
100
0TR [C]
Y [%]
SpH SpC
YCYH
H C
1038
5D35
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YH Heating valve. YC Cooling valve. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
1038
5D36
-
16/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 Four-pipe fan coil 30.11.2007
Application FNC04 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Four-pipe fan coil. PI control.
Two proportional control sequences, heating and cooling. Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /
AC 24 V, 2-position / AC 24 V, 3-position). Control of motorized KNX bus actuator valves. Valve exercising feature.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC04 is supplied with RXB21.1/FC-10.
Functions
-
17/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC04 Four-pipe fan coil 30.11.2007
2 1 4 3
QAX...
R1
1038
5A03
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1
G Y2
CP
CP+
B1
25 26 27 RXB21.1
Q13
Q14
Y3
G Y4
Q24
Q34
2819 21N LN
21
L
CE
CE
+
19
KNXY1 G Y2
YH.2 3)
M
MB
B1
T
Y1 G Y2
YC.2 3)
M
D1 2) D2 2) YC.1 3)YH.13)
1 2 3
Q1
N
L
AC 230 V
N1
4)
CE
CE
+
N.C
.
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor, room temperature sensor. D1 Window contact 2). D2 Presence detector 2). Q1 1- or 3-speed fan 4). YH.1 Heating valve actuator, thermal, 2-position (PDM) control 3). YH.2 Heating valve actuator, motorized, 3-position control 3). YC.1 Cooling valve actuator, thermal, 2-position (PDM) control 3). YC.2 Cooling valve actuator, motorized, 3-position control 3).
2) Type of operation (N/O or N/C) can be selected. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
18/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 Four-pipe fan coil 30.11.2007
The parameters below are available with application FNC04. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Sequences Actuator type heat/cool valve STA71 SSA81
STA72E SSB81 STE71 SSP81 STE72 SQS81 STP71 STP72E Electromech. 3rd devices Motorized 3rd devices Thermal 3rd devices Motorized bus
STP72E
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Motorized and electromechanic Runtime 0 ... 360 s 150 s
Motorized Offset 0 ... 360 s 0 s Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-stufig
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
Configuration
-
19/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 Four-pipe fan coil 30.11.2007
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
20/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 Four-pipe fan coil 30.11.2007
-
21/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
FNC05 Four-pipe fan coil with electric reheater
KNX R Heating with LTHW and cooling with CHW. Modulating control of heating and cooling valve. Heating with electric reheater Automatic or manual fan control.
Plant diagram
N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. D1 Window switch. D2 Presence detector. D3 Safety thermostat electric
reheater. Q1 Fan (1 3-speed). YH Heating valve. YC Cooling valve. YR Electric reheater.
1038
5S13
TB1
YC
YHQ1
N1
R1 D1 D2T
D3YR
KNX R
-
22/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
Operating diagrams
Application mode "Auto" (0).
Application mode " Heating" (1).
In "Heating" mode, the electric heating coil operates as a reheater for LTHW heating, i.e. only when the valve is fully open.
Application mode "Cooling" (3).
In Cooling mode, the electric heating coil is the only heating source once the temperature falls below SpH.
1-stage
OFFTR [C]
Y
ON
YR
H1 K
YH
SpH
YC
C
SpC10
385D
61
OFFTR [C]
Y
ON
YR
H
1038
5D37
1 K
YH
SpH
OFFTR [C]
ON
1038
5D38
SpH
YR
SpC
Y
C
YC
Mod.
OFFTR [C]
ONH
YH
SpH
YR
Y
YC
C
SpC
1038
5D62
OFF
TR [C]
ONH
1038
5D39
YH
SpH
YR
Y
0%
TR [C]
100%H
1038
5D40
SpH
YR
Y
SpC
YC
C
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YH Heating/cooling valve. YR Contactor or solid state relay for electric
heating coil. Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
1038
5D41
-
23/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
Application FNC05 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Four-pipe fan coil. PI control.
Two proportional control sequences, heating and cooling. Control of thermal / electromechanic valve actuators
(AC 24 V, PDM or AC 24 V, 2-position). Control of motorized KNX bus actuator valves. Valve exercising feature.
Electric air heater. 2-position or proportional control. Control: AC 24 V, 2-position or proportional.
Fan control. 1 ... 3-speed Automatic, or
Manual with room unit. Temperature measurement. Room temperature sensor or
Return air sensor. Room operating modes. Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via /Auto switch on room unit, presence detector, window contact or central command.
Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC05 is supplied with RXB22.1/FC-12.
Functions
-
24/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
2 1 4 3
QAX...
R1
1038
5A05
T
M D1
GN
D
D2
Y1
G Y2
B1
19 21 25 26 27 RXB22.1
N L Q13
Q14
N Q24
Q34
28
KNX
MB
B1
T
D12) D2 2) YH 3)
4)
1 2 3 Q1
N
L
AC 230 V
N1
22 23 24
Q43
Q44
6)
F17)
YR
CP
CP+
CE
CE
+
D3 2)
21L
19
YC3)
CE
CE
+
2 3 4 5 6 7 8 9 13 14 15 16 17 181
N.C
.
N.C
.
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor,
room temperature sensor. D1 Window contact 2). D2 Presence detector 2). D3 Safety thermostat, electric heating coil. Q1 1- ... 3-speed fan. YR Electric reheater 6). F1 External fuse, max. 10 A 7). YH, YC
Heating/cooling valve actuator, thermal, 2-point (PDM) control 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected.
Identical devices must not be connected to both inputs. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). 6) The output of the electric heating coil at output Q44 must not exceed 1.8 kW. 7) External fuse, max. 10 A (protects pcb tracks). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
25/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
The following parameters are available with application FNC05. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Sequences Actuator type heat/cool valve STA71
STA72E STE71 STE72 STP71 STP72E Electromech 3rd devices Thermal 3rd devices Motorized bus
STP72E
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Motorized and electromechanic Runtime 0 ... 360 s 150 s
Motorized Offset 0 ... 360 s 0 s Electric heater 1-stage
Mod. Mod.
Power consumption 0 ... 6500 W 0 W LTE mode Heating outp bus el heating Off/On Off
Fan control. Fan speeds External control 1-speed/2-speed/3-speed
3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min =Off) 360 min (Off) Fan overrun time 1 ... 10 min 1 min Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
Configuration
-
26/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 Four-pipe fan coil with electric reheater 30.11.2007
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
27/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 Four-pipe fan coil with room supply air cascade 30.11.2007
FNC08 Four-pipe fan coil with room supply air cascade
KNX R Heating with LTHW and cooling with CHW. Modulating control of heating and cooling valve. Room supply air cascade. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Supply air temperature
sensor. D1 Window switch. D2 Presence detector. Q1 Fan (1 3-speed). YH Heating valve. YC Cooling valve.
1038
5S14
B1
YC
YH
Q1
N1
R1 D1 D2T
KNX R
Operating diagrams
100
0TR [C]
Y [%]
SpH SpC
YCYH
H C
1038
5D42
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YH Heating valve. YC Cooling valve. Q14 Fan speed 1. F1 Fan speed 2. Q34 Fan speed 3. TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
1038
5D43
-
28/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC08 Four-pipe fan coil with room supply air cascade 30.11.2007
Application FNC08 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Four-pipe fan coil. PI control.
Two proportional control sequences, heating and cooling. Control of motorized valve actuators (AC 24 V, 3-position). Control of motorized KNX bus actuator valves. Room supply air cascade. Valve exercising feature.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor and Supply air temperature sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC08 is supplied with RXB21.1/FC-10.
Functions
-
29/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC08 Four-pipe fan coil with room supply air cascade 30.11.2007
4)
1 2 3
Q1
N
L
AC 230 V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1
G Y2
CP
CP
+
B1
25 26 27 RXB21.1
Q13
Q14
Y3 G Y4Q
24
Q34
28
N1
MB
B1
T
D12) D2 2)
2 1 4 3
QAX...
R1
KNX
1038
5A06
Y1 G Y2
YC3)
M
YH3)
19 21N LN
21
L
CE
CE+
19
CE
CE+
N.C
.
Y1 G Y2
M
Ref. Description N1 Room controller. R1 Room unit B1 Supply air temperature sensor. D1 Window contact 2). D2 Presence detector 2). Q1 1- or 3-speed fan 4). YH Heating valve actuator, motorized,
3-position control 3). YC Cooling valve actuator, motorized,
3-position control 3). 2) Type of operation (N/O or N/C) can be selected. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
30/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC08 Four-pipe fan coil with room supply air cascade 30.11.2007
The following parameters are available with application FNC08. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Other setpoints Maximum supply air temperature 10 ... 40 C 35 C Minimum supply air temperature 10 ... 40 C 16 C Sequences Actuator type heat/cool valve SSA81
SSB81 SSP81 SQS81 Third-party, motorized Bus, motorized
SSP81...
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Motorized and electromechanic Runtime 0 ... 360 s 150 s
Motorized Offset 0 ... 360 s 0 s Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Supply air (cascade) Supply air (cascade) Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 The controllers are delivered with the basic settings shown above.
Configuration
Ordering
Example
Note
-
31/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC10 Two-pipe fan coil with changeover and outside air damper 30.11.2007
Two-pipe fan coil with changeover and outside air damper
FNC10
KNX R Heating only (with LTHW), cooling only (with CHW) or changeover. Changeover signal via KNX bus. Modulating control of heating/cooling valve. Outside air damper for outside air supply. Outside air temperature sensor via KNX bus. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. B2 Outside air temperature
sensor via KNX bus. D1 Window switch. D2 Presence detector. D3 Changeover signal via KNX
bus. D4 Safety thermostat, outside
air. Q1 Fan (1 3-speed). YHC Heating/cooling valve. YM Outside air damper.
1038
5S19
M T
YM
B1
Q1 B2
N1
R1 D1 D2T
YHC
D3
D4
KNX R
Operating diagrams
100
0TR [C]
Y [%]
SpH SpC
Change-over
YHCYHC
H C
1038
5D45
TO [C]
Y [%]
SpC
100
0SpEcmSpFr
min 1038
5D44
YM
Y Output signal. TR Room temperature. TO Outside air temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. SpEcm Economizer setpoint. SpFr Risk of frost limit H Heating sequence. C Cooling sequence. YHC Heating/cooling valve. YM Outside air damper. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
1038
5D46
Change-over
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
-
32/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies Two-pipe fan coil with changeover and outside air damper 30.11.2007
Application FNC10 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Two-pipe fan coil.. PI control.
Proportional control sequence, selectable: Only heating sequence, only cooling sequence or changeover.
Control of thermal or motorized valve actuators (AC 24 V, PDM / AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves. Valve exercising feature.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling. Free inputs / outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC10 is supplied with RXB21.1/FC-11.
Functions
-
33/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies Two-pipe fan coil with changeover and outside air damper 30.11.2007
Y1 G Y2
YHC.2 3)
M
YHC.1 3)
KNX
D3
T
4)
1 2 3
Q1
N
L
AC 230 V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1 G Y2 CP
CP+
B1
25 26 27 RXB21.1
Q13
Q14
Y3 G Y4Q
24
Q34
28
N1
MB
B1
T
D1 2) D2 2)
Q23
Q24 2 1 3 4
QAX...
R1
1038
5A07
Y1 G Y2
YM 3)
M
B2
T
D4 2)
T
CE
CE+ CE
CE+
N.C
.19 21
N LN
21
L
19
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor,
room temperature sensor. B2 Outside air temperature sensor via KNX bus. D1 Window contact 2). D2 Presence detector 2). D3 Changeover signal via KNX bus. D4 Safety thermostat, outside air. Q1 1- ... 3-speed fan 4). YHC.1 Heating/cooling valve actuator, thermal, 2-point (PDM) control 3). YHC.2 Heating/cooling valve actuator, motorized, 3-position control 3). YM Damper actuator for outside air AC 24 V, 3-position 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
34/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies Two-pipe fan coil with changeover and outside air damper 30.11.2007
The following parameters are available with application FNC10.
They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Risk of frost limit 2 ... 10 C 5 C Other setpoints Outside air supply Outside temp min damper pos 10 C ... 40C 16 C Running time outside air damper 0 ... 360 s 150 s Minimum damper position 0 ... 100 % 0 % Sequences Control sequence Heating only
Cooling only Changeover
Cooling only
Actuator type heat/cool valve STA71 SSA81 STA72E SSB81 STE71 SSP81 STE72 SQS81 STP71 STP72E Motorized 3rd devices Thermal 3rd devices Motorized bus
STP72E
Motorized and electromechanic Runtime 0 ... 360 s 150 s Motorized Offset 0 ... 360 s 0 s LTE mode Heating outp bus valve Off/On Off
Cooling outp bus valve Off/On Off Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed OT < Frost = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed OT < Frost = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min
Configuration
-
35/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies Two-pipe fan coil with changeover and outside air damper 30.11.2007
Menu Parameters. Values/Range Basic setting Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Rapid ventilation Enabled / Disabled Enabled Night purge Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
36/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies Two-pipe fan coil with changeover and outside air damper 30.11.2007
-
37/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
FNC12 Four-pipe fan coil with outside air damper
KNX R Heating and cooling with LTHW and cooling with CHW. Modulating control of heating and cooling valve. Outside air damper for outside air supply. Outside air temperature sensor via KNX bus. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. B2 Outside air temperature
sensor via KNX bus. D1 Window switch. D2 Presence detector. D3 Safety thermostat, outside
air. Q1 Fan (1 3-speed). YH Heating valve. YC Cooling valve. YM Outside air damper.
1038
5S20
M T
YM
B1
YC
YH
Q1 B2
N1
R1 D1 D2T
D3
KNX R
100
0TR [C]
Y [%]
SpH SpC
YCYH
H C
1038
5D47
TO [C]
Y [%]
SpC
100
0SpEcmSpFr
min
1038
5D48
YM
Operating diagrams Y Output signal. TR Room temperature. TO Outside air temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. SpEcm Economizer setpoint. SpFr Risk of frost limit H Heating sequence. C Cooling sequence. YH Heating valve. YC Cooling valve. YM Outside air damper. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
1038
5D49
-
38/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
Application FNC12 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Four-pipe fan coil. PI control.
Two proportional control sequences, heating and cooling. Control of thermal valve actuators (AC 24 V, PDM). Control of motorized KNX bus actuator valves. Outside air damper. Valve exercising feature.
Fan control. 1 ... 3-speed automatic. Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling. Free inputs / outputs
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC12 is supplied with RXB21.1/FC-11.
-
39/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
KNX
4)
1 2 3
Q1
N
L
AC 230 V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1
G Y2
CP
CP
+
B1
25 26 27 RXB21.1
Q13
Q14
Y3 G Y4Q
24
Q34
28
N1
MB
B1
T
D1 2) D2 2)
2 1 3 4
QAX...
R1
1038
5A08
YH 3) YC3)
B2
T
Y1 G Y2
YM 3)
M
D3 2)
T
CE
CE
+
CE
CE
+
N.C
.19 21
N LN
21
L
19
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor,
room temperature sensor. B2 Outside air temperature sensor via KNX bus. D1 Window contact 2). D2 Presence detector 2). D3 Safety thermostat, outside air. Q1 1- ... 3-speed fan 4). YH.1 Heating valve, thermal, 2-position (PWM) control 3). YC.1 Cooling valve, thermal, 2-position (PWM) control 3). YM Damper actuator for outside air AC 24 V, 3-position 3).
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
Connection diagram
List of equipment
Note
-
40/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
The following parameters are available with application FNC12. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Risk of frost limit 2 ... 10 C 5 C Other setpoints Outside air supply Outside temp min damper pos 10 C ... 40C 16 C Running time outside air damper 0 ... 360 s 150 s Minimum damper position 0 ... 100 % 0 % Sequences Actuator type heat/cool valve STA71
STA72E STE71 STE72 STP71 STP72E Thermal 3rd party devices Motorized bus
STP72E
Motorized and electromechanic Runtime 0 ... 360 s 150 s Motorized Offset 0 ... 360 s 0 s LTE mode Heating outp bus valve Off/On Off
Cooling outp bus valve Off/On Off Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed OT < Frost = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed OT < Frost = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Rapid ventilation Enabled / Disabled Enabled Night purge Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
Configuration
-
41/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
42/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC12 Four-pipe fan coil with outside air damper 30.11.2007
-
43/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
FNC18 Two-pipe fan coil (changeover) and radiator
KNX R Heating/cooling coil: heating only (with LTHW), cooling only (with CHW) or
changeover. Changeover signal via KNX bus. Outside air temperature sensor via KNX bus. Heating with LTHW radiator. Downdraft compensation Modulating control of heating/cooling valve and radiator valve. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. B2 Outside temp. via KNX bus. D1 Window switch. D2 Presence detector. D3 Changeover signal via KNX
bus. Q1 Fan (1 3-speed). YH Heating valve (radiator). YHC Heating/cooling valve (fan
coil).
1038
5S21
B1
YHC
Q1
N1
R1 D1 D2T
YH
T
D3
B2
T
T
KNX R
Operating diagrams
100
0TR [C]
Y [%]
SpH SpC
YH
H C100
0TR [C]
Y [%]
SpH SpC
Change-over (Fan-Coil)
YHC
H C
1038
5D50YHC
Heating sequence: The heating coil in the fan coil system operates in sequence with the radiator, i.e. the heating/cooling valve is only operated after the radiator valve is fully open (thermal valves are operated in alternation, because fully open here means 1 second ON / 1 second OFF). Cooling sequence: Control of heating/cooling valve.
Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YH Heating valve (radiator). YHC Heating/cooling valve (fan
coil). Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
1038
5D51
Change-over
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
-
44/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
Application FNC18 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Two-pipe fan coil. PI control.
Proportional control sequence, selectable: Only heating sequence, only cooling sequence or changeover.
Heating/cooling coil: Control of thermal or motorized valve actuators (AC 24 V, PDM / AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves. Radiator: Control of thermal valve actuators
(AC 24 V, PDM). Downdraft compensation Valve exercising feature.
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling. Free inputs / outputs
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC18 is supplied with RXB21.1/FC-11.
Functions
-
45/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
KNX
4)
1 2 3
Q1
N
L
AC 230 V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1 G Y2 CP
CP+
B1
25 26 27 RXB21.1
Q13
Q14
Y3
G Y4
Q24
Q34
28
N1
MB
B1
T
D1 2) D2 2)
2 1 3 4
QAX...
R1
1038
5A09
YH.13)
Y1 G Y2
YH.2 3)
M
T
D3
CE
CE+
CE
CE+
N.C
.
YHC.13)
Y1 G Y2
YHC.2 3)
M
19 21
N LN
21L
19
M M
YH.3 YHC.3
T
B2
Heating surface (YH) / fan coil changeover (YHC) Y1 Y2 Y3 Y4 Thermal / thermal YH YHC X -- Motorized / motorized YH YH YHC YHC Thermal / motorized YH X YHC YHC Motorized / thermal YH YH YHC -- Motorized/bus YH YH -- -- Bus/motorized X X YHC YHC Thermal/bus YH X -- -- Bus/thermal X YHC X -- Bus/bus X X -- --
X = Not freely available 2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays).
Connection diagrams
Connection variants for valve actuators
-
46/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
Ref. Description N1 Room temperature controller. R1 Room unit B1 Return air temperature sensor, room temperature sensor. B2 Outside air temperature sensor via KNX bus. D1 Window contact 2). D2 Presence detector 2). D3 Changeover signal via KNX bus. Q1 1 ... 3-speed fan 4). YH.1, YHC.1 Radiator valve, heating/cooling valve, thermal, 2-point control (PDM)
3). YH.2, YHC.2 Radiator valve, heating/cooling valve, motorized, 3-point control
(PDM) 3). YH.3, YHC.3 Radiator valve, heating/cooling valve, bus.
2) Type of operation and allocation to inputs D1 and D2 can be selected. Identical devices must not be
connected to both inputs.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804).
List of equipment
Note
-
47/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
The following parameters are available with application FNC12. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Other setpoints Downdraft compensation Outside temp 0% valve pos
Outside temp max valve pos Maximum valve pos
30 ... 10C 30 ... 10C 0 ... 100%
0C 10C 100%
Sequences Control sequence Heating only Cooling only Changeover
Cooling only
Actuator type heating/cooling coil valve STA71 SSA81 STA72E SSB81 STE71 SSP81 STE72 SQS81 STP71 STP72E Motorized 3rd devices Thermal 3rd devices Motorized bus
STP72E
Actuator type heating surface valve STA71 SSA81 STA72E SSB81 STE71 SSP81 STP71 SQS81 STP72E Motorized 3rd devices Thermal 3rd devices Motorized bus
STA72E
Motorized and electromechanic Runtime 0 ... 360 s 150 s Motorized Offset 0 ... 360 s 0 s LTE mode Heating coil outp bus valve Off/On Off
Cooling coil outp bus valve Off/On Off Heating surface outp bus valve Off/On Off Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative
Configuration
-
48/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 Two-pipe fan coil (changeover) and radiator 30.11.2007
Menu Parameters. Values/Range Basic setting General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
-
49/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 Four-pipe fan coil, controlled by one damper 30.11.2007
FNC20 Four-pipe fan coil, controlled by one damper
KNX R Heating with LTHW and cooling with CHW. 3-position damper actuator. Automatic or manual fan control.
Plant diagram N1 Room controller. R1 Room unit with temp.
sensor. B1 Return air sensor. D1 Window switch. D2 Presence detector. Q1 Fan (1 3-speed). YM 3-position damper actuator.
1038
5S22
TB1
Q1
N1
R1 D1 D2T
YM
KNX R
Operating diagrams Y Output signal. TR Room temperature. SpH Effective heating setpoint. SpC Effective cooling setpoint. H Heating sequence. C Cooling sequence. YM Damper actuator. Q14 Fan speed 1. Q24 Fan speed 2. Q34 Fan speed 3.
1038
5D52
100
TR [C]
Y [%]
SpH SpC
YM
H C
0
N
TR [C]
Y
H C
Q14
Q24
Q34
SpH SpC
1038
5D53
-
50/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 Four-pipe fan coil, controlled by one damper 30.11.2007
Application FNC20 includes the following functions (refer to the description of functions CM110385 for detailed information):
Function Brief description) Four-pipe fan coil with damper control.
PI control. Two proportional control sequences, heating and cooling. Control of motorized damper actuators (AC 24 V, 3-position).
Fan control. 1 ... 3-speed, automatic, or Manual with room unit.
Temperature measurement. Room temperature sensor or Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.. Change of operating mode via /Auto switch on room unit, presence detector,
window contact or central command. Setpoint shift. Locally via room unit or centrally. General functions. Presence detector.
Window switch. Master/slave operation. Boost heating, night cooling etc. Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display.
Compatible controllers. FNC20 is supplied with RXB21.1/FC-10.
2 1 4 3
QAX...
R1
1038
5A10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
M D1
GN
D
D2
Y1
G Y2
CP
CP
+
B1
25 26 27 RXB21.1
Q13
Q14
Y3 G Y4Q
24
Q34
2819 21
N LN
21
L
CE
CE
+
19
KNX
Y1 G Y2
YM3)
M
MB
B1
T
D1 2) D2
1 2 3
Q1
N
L
AC 230 V
N1
CE
CE
+
N.C
.
2)
2) Type of operation (N/O or N/C) can be selected. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays).
Functions
Connection diagram
-
51/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC20 Four-pipe fan coil, controlled by one damper 30.11.2007
Ref. Description N1 Room controller. R1 Room unit B1 Return air temperature sensor, room temperature sensor. D1 Window contact 2). D2 Presence detector 2). Q1 1- or 3-speed fan 4). YM 3-position damper actuator, AC 24 V 3).
2) Type of operation (N/O or N/C) can be selected. 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). The following parameters are available with application FNC20. They are set via ETS, ACS, or HandyTool.
Menu Parameters. Values/Range Basic setting Communication Communication mode S-mode / LTE and S-mode S-mode. Receive timeout 0 ... 105 min. 60 min. Send heartbeat 0 ... 105 min. 45 min. Room temperature setpoints Protection cooling setpoint 10 ... 40 C 40 C Economy cooling setpoint 10 ... 40 C 35 C Precomfort cooling setpoint 10 ... 40 C 28 C Comfort cooling setpoint 10 ... 40 C 24 C Comfort heating setpoint 10 ... 40 C 21 C Precomfort heating setpoint 10 ... 40 C 19 C Economy heating setpoint 10 ... 40 C 15 C Protection heating setpoint 10 ... 40 C 12 C Sequences Damper setting Running time damper heating 0 300 sec 150 sec Running time damper cooling 0 300 sec 150 sec Switchover period H/C 0 300 sec 0 sec
LTE mode Heating outp bus valve Off/On Off Cooling outp bus valve Off/On Off Fan control. Fan speeds External control
1-speed/2-speed/3-speed 3-speed
Fan control. Manual / Auto Auto Minimum on time. 1 ... 10 min 6 min Temperature sensor B1 Room
Return air Measured value only No sensor
No sensor
Periodic fan kick Comfort 0 ... 90 min (90min = Off) 90 min (Off) Periodic fan kick Economy 0 ... 360 min (360min = Off) 360 min (Off) Room unit Measured value correction 3 ... 3 K 0 K Setpoint offset range 0 ... 10 K 3 K Local Comfort mode Enabled / Disabled Enabled Room unit Without LCD / with LCD Without LCD
With LCD Display heating/cooling symbols Enabled / Disabled Enabled Temperature unit C or F C Standard display No display / Room
temperature / Setpoint Room temperature.
Setpoint display Absolute / Relative Relative
List of equipment
Note
Configuration
-
52/52
Siemens RXB application library (KNX) FNC Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03Building Technologies FNC20 Four-pipe fan coil, controlled by one damper 30.11.2007
Menu Parameters. Values/Range Basic setting General functions. Digital input 1 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Digital input 2 Free (bus = 1) = Contact open/closed Free (bus = 1) Occupancy: Occupied = Contact open/closed = Contact closed. Window: Window open = Contact open/closed Temporary Comfort mode 0 ... 360 min 60 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 0 ... 90 min 5 min Central functions Heating demand signal Enabled / Disabled Enabled Cooling demand signal Enabled / Disabled Enabled Boost heating Enabled / Disabled Enabled Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master
The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 The controllers are delivered with the basic settings shown above.
Ordering
Example
Note
RXB application library (KNX)FNC Fancoil-Applikationen aus FC- 10, FC- 11, FC- 12FNC02 - Two-pipe fan coil with changeover FNC03 - Two-pipe fan coil with changeover and electric reheaterFNC04 - Four-pipe fan coil FNC05 - Four-pipe fan coil with electric reheater FNC08- Four-pipe fan coil with room supply air cascade FNC10 - Two-pipe fan coil with changeover and outside air damperFNC12 - Four-pipe fan coil with outside air damper FNC18 - Two-pipe fan coil (changeover) and radiator FNC20 - Four-pipe fan coil, controlled by one damper
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 150 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 150 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 600 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.00000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False