Run 2,4 Kw load With Only 4,9 Hrs /day Save 1350 liters...
Transcript of Run 2,4 Kw load With Only 4,9 Hrs /day Save 1350 liters...
-
site
client
THE GREEN SOLUTION
Energy Everywhere
Sudan ZAIN
Run 2,4 Kw load With Only 4,9 Hrs /day Save 1350 liters /month
Ascot DC-HPU Guarantees• 68% reduction in fuel consumption• 81% saving in runnings hours• 8 months free maintenance• Designed in different models to accommodate
the needs of telecom operators
-
CHOOSE Your Power, Get Your Results!
Average Load on site | 2,4 kW | 47Aresultsafterbefore
Parameter Ac genset Dc Hpu TOTAL SAVINGS
Average engine running hours per day [hours/day] 24 4,9 79% - 19,1 h/day
Average fuel consumption per day [liters/day] 66 21 68% - 30 l/day
Average fuel consumption per Month [liters/month] 1980 630 68% - 900 l/month
Average battery cycles per day N/A 1,2 N/A
The all in one package includes:
• Dc Diesel Generator - 48 VDC• Control Panel with Power Section & protection devices• Sound Proof Canopy 72 dB @ 1mt• Battery box with Deep Discharge Batteries• 750 lt Fuel Tank inside the battery box• Web Based Remote Management System
20
25
15
10
5
0
1
3,68 5,31
5,586,53
7,44
3,633,984,49
4,65
14,54
6,70
19,70
23,93
28,20
1,5 2 2,5 3 3,5 4
DC LOAD kWliters/day running hours/day battery life [years]
GREEN
OPEX
$100000
50000
150000
200000
2 4 6years
Comparison between current solution with Double AC Genset and Ascot DC-HPU
138.606 USD $
savings
Ascot DC-HPU 48/15-1250Double AC Gen Set
first service = 7 months Warranty exipiry
(CO)
180,0
120,0
60,0
0,0
(HC) (NOx) (PM)
AC Genset DC-HPU Genset
Emissions
[kg/year]
Physical Address - Ascot International S.r.l. - Zona industriale Terza strada - 93012 Gela (CL) ItalyContact Details - tel. +39 0933 901192 - fax +39 0933 915448 - www.ascotinternational.it - [email protected]
• Remote Non Grid Telecom Site
• Standard AC Gen-Set replaced by DC - HPU 48/15-1250 48 V, 15 kW, 1250 Amp/hrs