    RTD and Thermocouple Assemblies

    Reference Manual

  • 8/20/2019 RTD Thermouple BA

    2/26

  • 8/20/2019 RTD Thermouple BA

    3/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.rosemount.com

    Mounting and Installation Advicefor Resistance Thermometers

    and Thermocouple Assemblies

    NOTICE

    Read this manual before working with the product. For personal and system safety, and foroptimum product performance, make sure you thoroughly understand the contents beforeinstalling, using, or maintaining this product.

    For further details please contact your local Rosemount representative.

    The products described in this document are NOT designed for nuclear-qualifiedapplications. Using non-nuclear qualified products in applications that requirenuclear-qualified hardware or products may cause inaccurate readings.

    For information on Rosemount nuclear-qualified products, contact your local EmersonProcess Management Sales Representative.

  • 8/20/2019 RTD Thermouple BA

    4/26

  • 8/20/2019 RTD Thermouple BA

    5/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.emersonprocess.com/rosemount

    Table of Contents

    SECTION 1Introduction How to Use this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

    SECTION 2TemperatureMeasurement withResistanceThermometers

    Description and Measuring Principle . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1Methods of Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3

     Areas of Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4

    SECTION 3Temperature

    Measurement withThermocouples

    Description and Measurement Principle . . . . . . . . . . . . . . . . . . . . . . . 3-1Installation of Protective Tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3Leads and Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

     Areas of Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

    SECTION 4 Assembly of Housing

    Rules and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Stress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Housing Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Ceramic Housing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2Connection of Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2

     APPENDIX ALimit Tolerances of the

    Basic Values

     APPENDIX BLimit tolerances forThermocouples

  • 8/20/2019 RTD Thermouple BA

    6/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    TOC-2

  • 8/20/2019 RTD Thermouple BA

    7/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.emersonprocess.com/rosemount

    Section 1 Introduction

    How to Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1

    Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1

    HOW TO USETHIS MANUAL

    This manual provides installation, configuration, troubleshooting, and otherprocedures for the use of the Rosemount1075 Series. Specifications andother important information are also included.

    Section 2: Temperature Measurement wi th Resistance Thermometers

    Contains information on description and measuring principle, structure,methods of connection and areas of application.

    Section 3: Temperature Measurement with Thermocouples

    Contains information on description and measurement principle, installation ofprotective tubes, leads and connections, and areas of application.

    Section 4: Assembly of Housing

    Contains information on rules and regulations for the Rosemount 1075Series.

     Appendix A : L imit Tolerances of Basic Values

    Provides a chart with the limit tolerances of the basic values according to DINIEC 751 and DIN 43760.

     Appendix B : L imit Tolerances for Thermocouples

    Provides a chart for limit tolerances for thermocouples according to DIN IEC584-2.

    SAFETY MESSAGES Procedures and instructions in this manual may require special precautions toensure the safety of the personnel performing the operations. Refer to thesafety messages, listed at the beginning of each section, before performingany operations.

  • 8/20/2019 RTD Thermouple BA

    8/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    1-2

  • 8/20/2019 RTD Thermouple BA

    9/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.rosemount.com

    Section 2 Temperature Measurement withResistance Thermometers

    Descrip tion and Measuring Princ iple . . . . . . . . . . . . . . . . page 2-1

    Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1

    Methods of Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3

     Areas of Applicat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4

    DESCRIPTION ANDMEASURING PRINCIPLE

    Temperature measurement with resistance thermometers is based on theproperty possessed by all conductors and semiconductors, namely that theirresistance varies as a function of temperature. This property is more or lesspronounced, depending on the particular material. The relative change in theresistance as a function of temperature (dR/dt) is known as the temperaturecoefficient, the value of which is usually not constant over the range oftemperature of interest, but is itself a function of temperature. The result isthat the mathematical relationship between resistance and temperature takesthe form of a high-order polynomial.

    Figure 2-1 shows the change in resistance as a function of temperature for aPt 100 resistance thermometer.

    Figure 2-1. Pt 100 characteristiccurve

    STRUCTURE The resistance temperature detector is made up of a platinum coil wound on a

    suitable support. The wire coil is either fused into glass or embedded inceramic. To meet today’s requirements for more compact dimensions andhigher resistance values, extremely thin platinum layers are applied to aceramic substrate instead of wires (see Figure 2-2).

    0

    100

    -200

    200

    300

    400

    2000   400   600   800

    R

    t

  • 8/20/2019 RTD Thermouple BA

    10/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    2-2

    Figure 2-2. Glass wire-wound,ceramic wire-wound andthin-film resistancethermometers

    To protect them against mechanical damage (pressure of flowing liquid) thesemeasuring elements are usually installed into suitable protective tubes(measuring inserts). This also ensures easy replacement without the need toreplace the complete fitting. As resistance thermometers are contact-makingtemperature sensors (i.e. the sensor has to reach the temperature of themedium in which measurement is to be performed) the housing has to beadapted to the application (see Figure 2-3).

    Figure 2-3. Resistancethermometer modules

    Connection wires

    Measuring coil

    Ceramic substrate

    Strain relief 

    Connection wires

    Glass

    Measuring coil

    Ceramic tube

     Aluminum oxidepowder 

    Glass

    Connection wires

    Glass carrier 

    Measuring coil

    Glass sheath

    Connection wires

    Glass carrier 

    Measuring coil

    Glass sheath

    Measuring resistance

    Measuring insert

    Housing

  • 8/20/2019 RTD Thermouple BA

    11/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009

    2-3

    RTD and Thermocouple

    METHODS OFCONNECTION

    When using resistance thermometers for temperature measurement, the factthat the measurement result is influenced by the resistance of the selectedlead wire must be taken into account.

    Three circuit types are commonly used: 2-wire, 3-wire, and 4-wire circuits.

    The most accurate measurements are obtained with the 4-wire circuit, as inthis case the measurement is not affected by lead wire resistance orenvironment temperature of lead wires (see Figure 2-4).

    The 3-wire circuit is normally used for eliminating the lead wire resistance(Wheatstone bridge).

    In the case of the 2-wire circuit, the lead wire resistance is fully measured bythe measuring bridge. By the use of modern control equipment the influenceof the lead wire resistance at 2-wire circuit can be compensated by a linecompensation resistor, which is independent of temperature.

    Figure 2-4. Methods of

    connection

    To measuring unit

    To measuring unit

    To measuring unit

  • 8/20/2019 RTD Thermouple BA

    12/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    2-4

     AREAS OF APPLICATION

    Resistance thermometers can be used over a temperature range of -220 Cto +600 C.

    Their advantages are:

    • High temperature ranges• Resistance to vibration

    • High immunity to electrical interference

    • Long-term stability

    • Robust design

    • High accuracy

    Resistance thermometers are used in the following industries:

    • Chemical industries

    • Petrochemical industries

    • Pharmaceutical industries

    • Power generation• Mechanical engineering

    • Food & beverage

    • Mining

  • 8/20/2019 RTD Thermouple BA

    13/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.rosemount.com

    Section 3 Temperature Measurement withThermocouples

    Description and Measurement Princip le . . . . . . . . . . . . . page 3-1

    Installation of Pro tecti ve Tubes . . . . . . . . . . . . . . . . . . . . . page 3-3

    Leads and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3

     Areas of Applicat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-3

    DESCRIPTION ANDMEASUREMENTPRINCIPLE

     A thermocouple consists of two electrical conductors of different materialsconnected to one another at one end (measuring junction). The two free endsbuild a compensation point resp reference junction. The thermocouple can beextended by using an extension or a compensating cable. The extension orcompensating cables are connected to a measuring instrument, e.g. agalvanometer or electronic measuring unit (see Figure 3-1).

    Figure 3-1.

    The thermoelectric voltage appearing at the reference junction depends onthe thermocouple wire material and on the temperature difference betweenthe measuring junction and the reference junction. For temperaturemeasurement, the temperature of the reference junction must be keptconstant (e.g. 0 C) or must be well known, to make an appropriate correctionin mV (see Figure 3-2).

    Reference junction

    Extension/compensating cable

    Connection point

    Measuring junction

  • 8/20/2019 RTD Thermouple BA

    14/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    3-2

    Figure 3-2.

    Extension cables are manufactured of the same material as thecorresponding thermocouple, e.g. Cu-CuNi, Fe-CuNi. Compensating cablesare manufactured of special materials.

    Up to 200 C compensating cables supply the same thermoelectric voltage asthe thermocouples to which they are connected, The thermoelectric voltagesof the thermocouples are laid down in so-called basic value series.

    The compensating cable for a thermocouple must be make of a material tosuit the particular type of thermocouple, so compensating leads arecolor-coded. For standardized compensating cable the regulations containedin DIN EN 60584 apply.

    Maximum temperatures indicated by manufacturer have to be considered.

    Most thermocouples are supplied ready for operation, that is in a protectivemounting to prevent damage to the thermocouple by mechanical forces orchemical attack.

    e.g. PtRh30%-PtRh6% Type BFe-CuNi Type JNiCr-NiAl Type JPtRh87/13%-Pt Type RPtRh90/10%-Pt Type S

    and others in DIN IEC 584-1

    and Fe-CuNi Type LCu0CuNi Type UThese thermocouples are not more available for use in newplants (thermoelectric voltage according to DIN 43710) Basicvalue tables are available on request only at manufacturer site.

    Reference junction

    Extension/compensating cable

    Connection point

    Measuring junction

    Copper wire

  • 8/20/2019 RTD Thermouple BA

    15/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009

    3-3

    RTD and Thermocouple

    INSTALLATION OFPROTECTIVE TUBES

    The protective tubes of thermocouples must be adapted to the particularoperating conditions. Precious metal thermocouples are always protectedwith a ceramic tube, even if the unit has a metallic protective mounting.

     At high temperatures the protective tubes should be installed vertically, where

    possible, i.e. suspended, to avoid damage deflection to the protective tubeand thermocouple through bending. If specific conditions on site make ahorizontal installation unavoidable, long protective tubes have to be suitablysupported.

    LEADS ANDCONNECTIONS

    When laying and connecting extension resp. compensating cables, care mustbe taken to connect the positive pole of the thermocouple to the positiveterminal of the indicating instrument. If extension cables or compensatingcables are used, care must be taken not to interchange positive and negativeconductors. To prevent errors, the positive and negative leads bear acorresponding marking.

     All connections must be absolutely clean and firmly tightened. The

    corresponding positive and negative terminals should have the sametemperature potential.

    The compensating cables between the thermocouple and the indicatinginstrument should comply with the requirements for insulated leads in powersystems (VDE 0250). In exceptional cases, the regulations for insulated leadsin telecommunications systems (VDE 0810) may be applied.

     AREAS OF APPLICATION

    In the negative temperature range, thermocouples can be used down to -200C. For temperatures above 1000 C, thermocouples made of platinum and aplatinum/rhodium alloys are used.

     Advantages of thermocouples are:

    • Very high temperature ranges

    • Fast response

    • Compact design

    • Extremely high resistance to vibration

    • Long term stability

    • Robust design

    Thermocouples are used in the following, and other, industries:

    • Chemical industries

    • Pharmaceutical industries

    • Power generation

    • Mechanical engineering• Food & beverage

    • Mining

    • Iron and steel

    • Ceramics and glass

  • 8/20/2019 RTD Thermouple BA

    16/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    3-4

  • 8/20/2019 RTD Thermouple BA

    17/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.rosemount.com

    Section 4 Assembly of Housing

    Rules and Instruct ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

    Stress . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

    Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1

    Housing Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 4-1

    Ceramic Hous ing Installation . . . . . . . . . . . . . . . . . . . . . . page 4-2

    Connect ion of Transmitters . . . . . . . . . . . . . . . . . . . . . . . .page 4-2

    RULES ANDINSTRUCTIONS

    For housing assembly, please use the following instructions.

    VDE/VDI 3511Technical temperature measurement/instruction

    VDE/VDI 3512Set-up for temperature measurements

     AD - instruction leaflets(1)

    Working group pressure vessels

    TRB - technical directions for tank construction(1)

    Vd - TDV regulations(1)

    Stress The stresses indicated in the drawing apply to the supplied housing. The loaddata, included in the standards for every type, are valid for housing accordingto DIN 43763 and DIN 43772.

    Torque Starting torques for screw-in type threads

     Applicable to screw-in type threads according to DIN 43763 and DIN 43772as well as comparable housing according to customer’s specifications.

     Above starting torques are to be used as well for coupling rings with similarthreads.

    Housing Assembly  Assembly of housing with flange mounting

    The seal is to be selected according to the requirements. During insertion ofthe seal, a good support is necessary. Fastening screws are to be tightenedevenly and crosswise.

    (1) To be considered in case of weld-in type tubes. Material, weld and pressure test according

    to operating conditions

    G 3/8, G 1/2 50 Nm

    G 3/4 100 Nm

  • 8/20/2019 RTD Thermouple BA

    18/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    4-2

    Ceramic HousingInstallation

    Installation of ceramic housing in plants at operating temperature

    Temperature of the plant:

    • 1600 C insertion speed: 1-2 cm/min.

    • 1200 C insertion speed: 10-20 cm/min.

    Connection ofTransmitters

    When connecting transmitter, the installation-, connection, and testinstructions of the manufacturers are to be considered.

  • 8/20/2019 RTD Thermouple BA

    19/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009

     A-1

    RTD and Thermocouple

     Appendix A Limit Tolerances of the BasicValues

    Table A-1. Limit tolerances of the basic values according to DIN IEC 751 and DIN 43760

    Basic values Limit tolerances

     According to DIN IEC

    751 Platinum

    RTD-elements

     According to DIN 43760

    Nickel RTD-elements

     According to DIN IEC 751 Plati num

    RTD-elements

     According to DIN 43760

    Nickel RTD-elements

    Class A Class B

    C Ohm Ohm/K Ohm Ohm/K Ohm Corresp. C Ohm Corresp. C Ohm Corresp. C

    -200 18.49 0.44   0.24   0.55   0.56   1.3

    -100 60.25 0.41   0.14   0.35   0.32   0.8

    -60 69.5 0.47 -   1.0   2.1

    0 100.0 0.39 100.0 0.55   0.06   0.15   0.12   0.3   0.2   0.4

    100 138.5 0.38 161.8 0.69   0.13   0.35   0.30   0.8   0.8   1.1

    200 175.84 0.37 240.7 0.90   0.20   0.55   0.48   1.3   1.6   1.8

    250 289.2 1.04   2.3   2.1

    300 212.02 0.35   0.27   0.75   0.64   1.8

    400 247.04 0.34   0.33   0.95   0.79   2.3

    500 280.90 0.33   0.38   1.15   0.93   2.8

    600 313.59 0.33   0.43   1.35   1.06   3.3

    700 345.13 0.31   1.17   3.8

    800 375.71 0.30   1.28   4.3

    850 390.26 0.29   1.34   4.6

  • 8/20/2019 RTD Thermouple BA

    20/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

     A-2

  • 8/20/2019 RTD Thermouple BA

    21/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009

    B-1

    RTD and Thermocouple

     Appendix B Limit tolerances forThermocouples

    Table B-1. Limit tolerances for thermocouples according DIN IEC 584-2

    Class 1 2 3(1)

    (1) Thermocouples and thermocouple wires are usually supplied with limited tolerances according to the table above valid for temperature range above of -40   C. The thermocouple limit tolerances of same material at temperatures below -40    C may be exceeded as stated for tolerance class 3 according to DINIEC 584-2. Thermocouples requested by purchaser with limit tolerances according to classes 1, 2, or 3 may be obtained by special material selection.

    Limit tolerances(2)

    (2) Limit tolerances for thermocouples are indicated in degrees centigrade or as percentage of the measured temperature in degrees centigrade. Whichevervalue is greater applies.

    |t| = Temperature in degrees Centigrade

    0.5 C or 0.004 x |t| 1 C or 0.0075 x |t| 1 C or 0.015 x |t|

    (a) Limit tolerances apply to following temperature ranges

    Type T -40 C up to 350 C -40 C up to 350 C -200 C up to 40 C

    Limit tolerances(2) 1.5 C or 0.004 x |t| 2.5 C or 0.0075 x |t| 2.5 C or 0.015 x |t|

    () Limit tolerances apply to following temperature ranges

    Type E -40 C up to 800 C -40 C up to 900 C -200 C up to 40 C

    Type J -40 C up to 750 C -40 C up to 750 C --

    Type K -40 C up to 1000 C -40 C up to 1200 C -200 C up to 40 C

    Limit tolerances(2) 1 C or [1+9t-1100) x 003] C 1.5 C or 0.0025 x |t| 4 C or 0.005 x |t|

    () Limit tolerances apply to following temperature rangesType R and S 0 C up to 1600 C 0 C up to 1600 C --

    Type B -- 600 C up to 1700 C 600 C up to 1700 C

  • 8/20/2019 RTD Thermouple BA

    22/26

    Reference Manual00809-0301-2654, Rev BA

    September 2009RTD and Thermocouple

    B-2

  • 8/20/2019 RTD Thermouple BA

    23/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009 RTD and Thermocouple

    www.rosemountnuclear.com

    Numerics

    2-wire circuit  . . . . . . . . . . . . . 2-33-wire circuit  . . . . . . . . . . . . . 2-34-wire circuits  . . . . . . . . . . . . 2-3

     Aaccuracy  . . . . . . . . . . . . . . . . 2-4

     AD - instruction leaflets . . . . . . 4-1

    Bbasic values  . . . . . . . . . . . . . A-1

    C

    ceramic 

    . . . . . . . . . . . . . . . . . 2-1ceramic substrate  . . . . . . . . . 2-1ceramic tube  . . . . . . . . . . . . . 3-3chemical attack  . . . . . . . . . . . 3-2color-coded  . . . . . . . . . . . . . . 3-2compact dimensions . . . . . . . . 2-1compensating cable  . . . . . . . . 3-1Compensating cables  . . . . . . . 3-2compensating leads  . . . . . . . . 3-2conductors  . . . . . . . . . . 2-1, 3-1Considerations  . . . . . . . . . . . 2-2

    Environmental  . . . . . . . . . 2-4contact-making temperature sensors 2-2

    coupling rings 

    . . . . . . . . . . . . 4-1

    Ddesign  . . . . . . . . . . . . . 2-4, 3-3DIN 43763 . . . . . . . . . . . . . . . 4-1DIN 43772 . . . . . . . . . . . . . . . 4-1DIN EN 60584  . . . . . . . . . . . . 3-2DIN IEC 584-2  . . . . . . . . . . . . B-1

    Eelectrical interference  . . . . . . . 2-4electronic measuring unit  . . . . 3-1Environmental Considerations  . 2-4

    Extension cables 

    . . . . . . . . . . 3-2

    FFastening screws . . . . . . . . . . 4-1function of temperature . . . . . . 2-1

    G

    galvanometer   . . . . . . . . . . . . 3-1glass  . . . . . . . . . . . . . . . . . . 2-1

    Hhermoelectric voltage . . . . . . . 3-2higher resistance values  . . . . 2-1horizontal installation  . . . . . . . 3-3housing assembly  . . . . . . . . . 4-1

    Iimmunity  . . . . . . . . . . . . . . . 2-4independent of temperature  . . 2-3installed vertically  . . . . . . . . . 3-3

    LLimit tolerances . . . . . . . A-1, B-1load data  . . . . . . . . . . . . . . . 4-1

    MMaximum temperature  . . . . . . 3-2measurement result . . . . . . . . 2-3measuring bridge  . . . . . . . . . 2-3measuring elements  . . . . . . . 2-2measuring junction  . . . . . . . . 3-1Measuring Principle  . . . . . . . . 2-1mechanical damage  . . . . . . . 2-2

    mechanical forces  . . . . . . . . . 3-2metallic protective mounting  . . 3-3mV . . . . . . . . . . . . . . . . . . . . 3-1

    Nnegative conductor   . . . . . . . . 3-3negative lead  . . . . . . . . . . . . 3-3

    Pplatinum  . . . . . . . . . . . . . . . . 2-1platinum coil wound  . . . . . . . . 2-1platinum thermocouples  . . . . . 3-3platinum/rhodium alloys  . . . . . 3-3positive lead  . . . . . . . . . . . . . 3-3positive pole  . . . . . . . . . . . . . 3-3positive terminal  . . . . . . . . . . 3-3Precious metal thermocouples  3-3protective mounting  . . . . . . . . 3-2protective tubes . . . . . . . .2-2, 3-3Pt 100 resistance thermometer   2-1

    R

    reference junction  . . . . . . . . . .3-1replacement  . . . . . . . . . . . . . .2-2Resistance . . . . . . . . . . . . . . .2-4resistance  . . . . . . . . . . . . . . .2-3resistance temperature detector  2-1Resistance thermometer modules 2-2resistance thermometers  . 2-1, 2-2response  . . . . . . . . . . . . . . . .3-3

    Sscrew-in type threads  . . . . . . .4-1seal . . . . . . . . . . . . . . . . . . . .4-1semiconductors  . . . . . . . . . . .2-1

    SpecificationsHART and Foundation Fieldbus  A-1

    stability  . . . . . . . . . . . . . 2-4, 3-3standards . . . . . . . . . . . . . . . .4-1support  . . . . . . . . . . . . . . . . .3-3

    TTemperature  . . . . . . . . . . . . .2-1temperature coefficient  . . . . . .2-1Temperature Measurement  . . .3-1Temperature measurement  . . .2-1temperature potential  . . . . . . .3-3temperature range  . . . . . . . . .2-4thermocouple  . . . . . . . . . . . . .3-1thermocouple,  . . . . . . . . . . . .3-2Thermocouples  . . . . . . . . . . .3-1TRB - technical directions for tankconstruction  . . . . . . . . . . . . . .4-1

    VVd - TDV regulations . . . . . . . .4-1VDE/VDI 3511  . . . . . . . . . . . .4-1VDE/VDI 3512  . . . . . . . . . . . .4-1vibration . . . . . . . . . . . . . . . . .3-3voltage  . . . . . . . . . . . . . . . . .3-1

    Wwire material  . . . . . . . . . . . . .3-1

    Index

  • 8/20/2019 RTD Thermouple BA

    24/26

    Reference Manual00809-0301-2654, Rev BASeptember 2009

    Index-2

    RTD and Thermocouple

  • 8/20/2019 RTD Thermouple BA

    25/26

  • 8/20/2019 RTD Thermouple BA

    26/26

    Emerson Process Management

    Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale.The Emerson logo is a trademark and service mark of Emerson Electric Co.Rosemount, the Rosemount logotype, and Hot Backup are registered trademarks of Rosemount Inc.HART is a registered trademark of the HART Communication Foundation.FOUNDATION is a trademark of the Fieldbus Foundation.PlantWeb is a registered trademark of one of the Emerson Process Management companies.

    Teflon is a registered trademark of E.I. du Pont de Nemours & Co. All other marks are the property of their respective owners.

    Reference Manual00809-0301-2654, Rev BA

    September 2009

    Rosemount Temperature GmbHFrankenstrasse 2163791 KarlsteinGermanyT 49 (6188) 992 0F 49 (6188) 992 112

    Emerson Process Management AsiaPacific Private Limited1 Pandan CrescentSingapore 128461T (665) 777 8211F (665) 777 [email protected]

    Rosemount Inc.8200 Market BoulevardChanhassen, MN 55317 USAT (U.S.) 1-800-999-9307T (International) (952) 906-8888F (952) 949-7001

    www.rosemount.com