Product Data Sheet March 2014 00813-0100-5101, Rev AA Rosemount Tank Gauging Accessories for tank gauging systems Accessories for the Rosemount Tank Gauging system, including: Rosemount Segment Coupler Fieldbus Terminator Rosemount 2180 Field Bus Modem Rosemount 3180 Enraf Bus Mode Rosemount TankMaster I/O Terminals

Transcript of Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges...

Page 1: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Product Data SheetMarch 2014

00813-0100-5101, Rev AA

Rosemount Tank Gauging Accessoriesfor tank gauging systems

Accessories for the Rosemount Tank Gauging system, including:

Rosemount Segment Coupler

Fieldbus Terminator

Rosemount 2180 Field Bus Modem

Rosemount 3180 Enraf Bus Mode

Rosemount TankMaster I/O Terminals

Page 2: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Rosemount Segment Coupler

The 6-channel Tankbus Segment Coupler is designed for FOUNDATION™ fieldbus systems and is Entity and FISCO compliant. It includes adjustable spur short circuit protection and an integrated switchable bus termination. It is typically used as a junction box to distribute the Tankbus to multiple tanks and/or transmitters.

The spur circuit protection maximum current limitation is selected for all channels via a rotary switch. Different current values, 30, 35, 45 and 60 mA, can be selected, which allows all Rosemount tank gauging devices to be connected and protected.

Fieldbus Terminator

A Fieldbus terminator is required at the end of the Tankbus. The external Fieldbus terminator eliminates signal reflections at the end of the cable and converts the fieldbus signal transmitted as a current into a voltage, which is detectable by all devices.

There is no need for a separate bus terminator if a 2230, 2240S, or 5900S is the last device on the bus.

Contents

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Rosemount TankRadar

FBM 2180

Ext

. pw

r

RS-

232

US

B

Tx Rx

Lo - GAIN - Hi On - TERM - Off

Segment Coupler

Segment Coupler

Segment Coupler

Segment Coupler

2410 Tank Hub

Fieldbus Terminator

2410 Tank Hub

2 www.rosemount-tg.com

Page 3: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Rosemount 2180 Field Bus Modem

The Rosemount 2180 Field Bus Modem is used for connecting a TankMaster PC to the TRL2 fieldbus. The modem is connected to the PC using either the RS232 or the USB interface.

It has LEDs indicating power on and communication.

There are front panel switches to set gain and termination, if required.

The modem is fitted on a standard DIN rail with the mounting kit included in all deliveries.

The field bus modem is delivered with cables for RS232 and USB connection. The USB cable also supplies power to the modem. A separately power supply cable (included in delivery) is only necessary for the RS232 option.

Rosemount 3180 Enraf Bus Modem

When an Enraf gauge is replaced with a Rosemount Radar Gauge using emulation, it is necessary to configure the Rosemount gauge for emulation. Configuration is made with the WinSetup software and requires a 3180 Enraf Bus Modem. How the procedure is done depends on the system type.

The 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software.

Rosemount TankRadar

FBM 2180

Ext.

pwr

RS-

232

USB Tx Rx

Lo - GAIN - Hi On - TERM - Off

Network

PLC

3180 Enraf Bus Modem

Laptop with WinSetup

Entis /TankMaster

CIU

DCS / Host

TankMasterPC

2180Modem USB or

RS232Modbus

TRL2Modbus

2160 Field Communication Unit

3www.rosemount-tg.com

Page 4: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Rosemount TankMaster I/O Terminals

The I/O Terminals can be used for communication between the TankMaster Inventory Software and field equipment, for a more versatile system. The four versions are:

IOT 5110 for Analog Inputs

IOT 5120 for Analog Outputs

IOT 5130 for Digital Inputs

IOT 5140 for Digital Outputs

The analog inputs open up TankMaster for all 4-20 mA devices, such as pressure and temperature sensors.

The analog outputs enable mapping of values to analog indicators.

The digital inputs can for example be used to display alarms from external equipment in TankMaster.

The digital outputs can be used for alarm panels, horns, signal lamps etc.

The I/O terminals are complements to the TankMaster system, and are not designed to be used as stand-alone devices for critical operations.

IOT5110

IOT5130

IOT5120

IOT5140

TankMaster

4 www.rosemount-tg.com

Page 5: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Ordering information

Rosemount Tankbus Segment Coupler

Entity and FISCO compliant

Adjustable spur short-circuit protection

Robust die-cast aluminum housing

Protection degree IP 67

Integrated bus termination

Additional informationSpecifications: page 8Dimensional drawings: page 13

Fieldbus Terminator

Prevents reflections/distortions

Protection degree IP 67

Additional informationSpecifications: page 10Dimensional drawings: page 13

Table 1. Rosemount Tankbus Segment Coupler ordering information

Part Number Product Description

6853511-493Tankbus segment coupler with integrated user-selectable on/off termination and spur short-circuit protection (max 60 mA/spur). Connections; trunk input, trunk output, 6 spurs M20x1,5. Wall-mounted, IP 67. Delivered with junction box. Entity and FISCO compliant.

Table 2. Fieldbus Terminator ordering information

Part Number Product Description

6853511-494Tankbus termination, external, ½ NPT male thread. Termination for external installation, mounted on a junction box or a transmitter field housing, IP 67. Entity and FISCO compliant.

5www.rosemount-tg.com

Page 6: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Rosemount 2180 Field Bus Modem

Increases the maximum possible distance between a Rosemount 2160 Field Communication Unit and a TankMaster PC

Features diagnostic LEDs on front cover

Enables multidrop - one TankMaster can communicate with several 2160 units

Provides multiple mounting options

Additional informationSpecifications: page 11Dimensional drawings: page 14

Rosemount 3180 Enraf Bus Modem

Enables configuration of a Rosemount Radar gauge for Enraf emulation

Can connect Enraf gauges directly to the TankMaster Inventory software

Each 3180 can be connected to up to 10 Enraf gauges

Additional informationSpecifications: page 11Dimensional drawings: page 14

Table 3. Rosemount 2180 Field Bus Modem ordering information

Item No Product Description

FBM 2180 TRL2 Fieldbus Modem

Table 4. Rosemount 3180 Enraf Bus Modem ordering information

Item No Product Description

EBM 3180 Enraf Bus Modem

6 www.rosemount-tg.com

Page 7: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Rosemount TankMaster I/O terminals

Modules for communication between TankMaster and field equipment

Free mix of module types

Up to 64 modules per loop

8 or 16 channels per module

RS485 multi-drop bus connection

12-bit A/D- and D/A converter

Flexible mounting – DIN or a choice with enclosure for ESP protection

Additional informationSpecifications: page 12

Table 5. Rosemount TankMaster I/O ordering information

Item No Product Description

IOT 5110 AI(1) I/O Module Analog In, 16 channels

IOT 5120 AO(1) I/O Module Analog Out, 16 channels

IOT 5130 DI(1) I/O Module Digital In, 16 channels

IOT 5140 DO(1) I/O Module Digital Out, 8 channels

(1) Power supply (24 VDC) required, not included. TankMaster customized views option recommended for best functionality. Modules not designed for fail-safe usage.

7www.rosemount-tg.com

Page 8: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Specifications

Rosemount Tankbus Segment Coupler

Table 6. Rosemount Tankbus Segment Coupler specifications

General

Electrical connection cable glands TRUNK IN 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassTRUNK OUT 1 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassSpur 6 x M20 x 1.5 (Ø 6 to 13 mm), nickel-plated brassTerminal cross-section 2.5 mm²Earthing bolt M5 x 1

Fieldbus standard IEC 61158-2

Operating voltage range 12 to 32 VDCCurrent self-consumption 7 mAVoltage drop 0.3 V

Short-circuit protection 30, 35, 45, 60 mA

Ex approval according to conformity certificate PTB 03 ATEX 2236

Entity ParameterMax. output voltage Uo 24 VMax. output current Io 250 mAMax. output power Po 2560 mWMax. input voltage Ui 24 VMax. input current Ii 250 mAMax. input power Pi 2560 mWFISCO parameter acc. to IEC TS 60079-27Max. output voltage Uo 17.5 VMax. output current Io 380 mAMax. output power Po 5320 mWMax. input voltage Ui 17.5 VMax. input current Ii 380 mAMax. input power Pi 5320 mWExternal inductance / capacitance Li /Ci trunk (in/out):negligible / 5.00 nFper field current circuit:negligible / 0.47 nF field current circuits:negligible / 5.00 nFDevice designation:

II 2 G Ex ib IIC/IIB T4II 2(1) G Ex ia IIC/IIB T4II 2 G (2D) [Ex ibD] Ex ib IIB T4II 2 (1) G (1D)[Ex iaD] Ex ia IIB T4

FISCO / Entity field deviceProtection class IP 67

MTTF 117 years acc. to SN 29500 (Ed. 99) 40 °CAmbient temperature -25 to +70 °C (-13 to +158 °F)

Housing material Powder-coated die-cast aluminum

Housing color Black / blue RAL 5015

Connection mode Wall mounting with nickel plated brass cable glands

8 www.rosemount-tg.com

Page 9: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Figure 1. Segment Coupler, connections

Trunk OUTS0

Trunk INP1

2410 Tank Hub

5400 Level Transmitter

644 Temperature Transmitter

5400 Level Transmitter

5900S Radar Level Gauge

2240S Temperature Transmitter

2230 Display

Case ground

Tankbus (trunk)

Segment coupler

(Spur <60m)

(Spur <60m)

Tank

bus

(tru

nk)

SpurS1

SpurS3

SpurS5

SpurS2

SpurS4

SpurS6

9www.rosemount-tg.com

Page 10: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Fieldbus Terminator

Table 7. Fieldbus Terminator specifications

Fieldbus Interface

Connection 2-wire cable, red+, black-

Rated voltage 32 V DC

Ambient conditions

Ambient temperature -50 to + 85 °C (-58 to +185 °F)

Storage temperature -50 to + 85 °C (-58 to +185 °F)

Mechanical specifications

Core cross-section 0.75 mm²

Protection degree IP 67

Weight 100 g (0.2 lb)

Mounting ½ NPT thread

Directive conformity

Electromagnetic compatibility

Directive 2004/108/EC EN 61326-1:2006

Standard conformity

Electromagnetic compatibility NE 21:2006

Protection degree IEC/EN 60529

Fieldbus standard IEC 61158-2

Hazardous Location Certifications

EC-Type Examination Certificate DMT 01 ATEX 104 X

Group, category, type of protection, temperature class

II 1 G EEx ia IIC T6

Directive conformity

Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007, IEC 60079-27:2008

International approvals

IECEx approval IECEx BVS 10.0022X

Approved for Ex ia IIC T6 Ga

Hazardous Location Data

Temperature classT6 for ambient temperatures: 60 °C T5 for ambient temperatures: 75 °CT4 for ambient temperatures: 85 °C

Voltage Ui 30 V

Rated voltage 30 V

10 www.rosemount-tg.com

Page 11: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Rosemount 2180 Field Bus Modem

Table 8. Rosemount 2180 Field Bus Modem specifications

Rosemount 3180 Field Bus Modem (Enraf)

Table 9. Rosemount 3180 Field Bus Modem (Enraf) specifications

General

Protocol Modbus

Baudrate 4800

Explosion protection None

Power supply (only used for RS232)

AC/DC converter supplied (7-12 V, 50 mA)

Cable to PCRS232: 3 m (10 ft)USB: 3 m (10 ft)Included in delivery

Fieldbus over-voltage protection Galvanic insulation, and transient suppressors

Ambient temperature 0 to + 55 °C (0 to +130 °F)

General

Protocol Modbus/Enraf GPU

Baudrate 2400/1200

Compatible with Enraf devices with GPU protocol

Explosion protection None

Power supply 9 VDC (AC/DC converter included)

Cable to PC RS232

Signal gain control via internal jumpers

•10% (default)•35%•100%

Ambient temperature 0 to + 55 °C (0 to +130 °F)

11www.rosemount-tg.com

Page 12: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Rosemount TankMaster I/O Terminals

Table 10. Rosemount TankMaster I/O Terminals specifications

Technical data for TankMaster IOT 5110-5140

Communication type RS485

Communication speed 115 kbit/s

Isolation Opto-coupled (in I/O box)

Dimensions 160x100x80 mm (6.3x3.9x3.2 in.)

Mounting method DIN rail 35 mm (1.4 in.) clip

Supply voltage 24 VDC

Ambient temperature 0 to + 55 °C (0 to +130 °F)

IOT 5110 Analog In; 4-20 mA, 0-10 V

Channels 16 single ended

Input load 50 (current), 10 k (voltage)

Accuracy (current and voltage) Max ±0.5% of full range

Temperature drift (current and voltage)

Accuracy valid for 0 to +55 °C (0 to +130 °F)

IOT 5120 Analog Out; 4-20 mA, 0-10 V

Channels 16 single ended

Load impedance 50 / max 500

Load current < 5 mA for 0-10 VDC

Accuracy (current) Max ±0.5% of full range

Accuracy (voltage) Max ±0.2% of full range

Temperature drift (current and voltage)

Accuracy valid for 0 to +55 °C (0 to +130 °F)

IOT 5130 Digital In

Channels 16 negative common

Voltage range input 0 to +35 VDC

Source type Potential free contact

Input current Max 0.6 mA

IOT 5140 Digital Out

Channels 8 pot free SPDT

Capacity Max 250 VAC, 2 A

12 www.rosemount-tg.com

Page 13: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

Dimensional drawingsRosemount Segment Coupler

Figure 2. Rosemount Segment Coupler dimensions

Fieldbus Terminator

Figure 3. Fieldbus Terminator dimensions

122 (4.8)

64 (2.5)

36 (1.4)

173,

5 (6

.8)

185,

5 (7

.3)

207

(8.1

)

45 (1.8)

NoteDimensions are in millimeters (inches).

55 (2.2) 22 (0.9)

22 (0.9)

1

2

1. Cable cross sectional area 1.0 mm (0.04 in.)Cable length min. 290 mm (11.4 in.)

2. FN: ½” NPT thread

NoteDimensions are in millimeters (inches).

13www.rosemount-tg.com

Page 14: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories March 2014

Rosemount 2180 Field Bus Modem

Figure 4. Rosemount 2180 Field Bus Modem dimensions

Rosemount 3180 Enraf Bus Modem

Figure 5. Rosemount 3180 Enraf Bus Modem dimensions

Rosemount 2180 Field Bus Modem

Ext

. pw

r

RS

-232

US

B

Tx Rx

Lo - GAIN - Hi On - TERM - Off

RS-232DC IN±7-12V50mA

Only forRS-232

Operation

ROSEMOUNT 2180Field Bus Modem

Part No. 9240002-635 XMade inSweden

Shield|Bus|Bus|Gnd

FIELD BUSUSB

109 (4.3)

114 (4.5)

Connection to fieldbus (via Rosemount 2160/2165/2175 or Rosemount 2410)

Connection to PC

NoteDimensions are in millimeters (inches).

Field BusField Bus: Pin 4,6 Shield: Pin5

EBM 3180PC-modem

MADE IN SWEDEN

Rosemount Tank Radar ABGothenburg, Sweden

External DCPower Supply8-12V, 60mA

Pos+ Neg-

Normal (GPU)

Modbus(4800 baud)

1200 baud

2400 baud

ComputerRS 232

Tank Gauging

114(4.5)

109(4.3)

NoteDimensions are in millimeters (inches).

14 www.rosemount-tg.com

Page 15: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging AccessoriesMarch 2014

15www.rosemount-tg.com

Page 16: Rosemount Tank Gauging AccessoriesThe 3180 Enraf Bus Modem can also be used to connect Enraf gauges directly to the TankMaster Inventory Software. Ro mo un t Ta nkRadar FBM 2180 Ext.

Rosemount Tank Gauging Accessories00813-0100-5101, Rev AA

Product Data SheetMarch 2014

Emerson Process ManagementRosemount Tank Gauging

Box 130 45SE-402 51 GöteborgSWEDENTel: +46 31 337 00 00Fax: +46 31 25 30 22E-mail: [email protected]

Emerson Process ManagementRosemount Tank Gauging Middle East & Africa.

P. O Box 20048ManamaBahrainTel: +973 1722 6610Fax: +973 1722 7771E-mail: [email protected]

Emerson Process ManagementRosemount Tank Gauging North America Inc.

6005 Rogerdale RoadMail Stop NC 13677072 TX HoustonUnited StatesPrimary Phone: +1 281 988 4000Secondary Phone: +1 800 722 2865E-mail: [email protected]

Emerson Process ManagementAsia Pacific Pte Ltd

1 Pandan CrescentSINGAPORE 128461Tel: +65 6777 8211Fax: +65 6777 0947Email: [email protected]

Emerson Process ManagementLatin America

1300 Concord Terrace, Suite 400Sunrise Florida 33323United StatesTel: +1 954 846 5030

The Emerson logo is a trade mark and service mark of Emerson Electric Co.Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.HART and WirelessHART are registered trademarks of the HART Communication FoundationAll other marks are the property of their respective owners.© 2014 Rosemount Tank Radar AB. All rights reserved.