Room Data Sheets - Health Facility Briefing System 5 · Room Data Sheets HAAD Health Facility...

802
Room Data Sheets Health Facility Planner : HAAD 3 11 Apr 2014 Issue Date: Issue No: Project : HAAD Health Facility Guidelines Milestone: Version 3.3 Standard Components

Transcript of Room Data Sheets - Health Facility Briefing System 5 · Room Data Sheets HAAD Health Facility...

  • Room Data Sheets

    Health Facility Planner :

    HAAD

    3

    11 Apr 2014Issue Date:

    Issue No:

    Project :

    HAAD Health Facility GuidelinesMilestone: Version 3.3

    Standard Components

  • Room Data Sheets Instructions for Use

    Room Data Sheets are a briefing document providing information on the minimum requirements for each room in the

    facility incorporating Room Details, Room Fabric, Fittings and Furniture, Fixture, Equipment with associated services

    and Services.Room Details:This section includes Room Name, Hours of Operation and Occupancy as well as the following:

    Room Fabric

    Fittings and Furniture

    Group Description

    Fixtures, Equipment and Associated Service

    Service Code

    Services

    Service Description

    Room Tag:

    This is a room number allocated for briefing purposes only. The number is not re-used if the room is deleted and is

    moved with the room if an area is re-planned. It should not be confused with the Room Label/ Room Number

    which may be the final room identifier indicated in the Signage Package. Room Area:

    Room Area and circulation is the target for planning only. The builder should build rooms to sizes shown

    on the plans not Room Data Sheets.

    Also covers these rooms:

    Indicates all other room numbers (with the same room name) which have identical room requirements - this avoids

    repeating the same information for every similar room.

    Special Requirements:

    Includes any special provisions that the room requires which may include requirements for locking, special air

    conditioning, acoustic requirements and additional regulations or Australian Standards the room must comply with

    - such as Body Protected electrical requirements. These requirements are mandatory.

    Amendments:

    All reviews to the Room Data Sheets are dated and changes identified.

    This section includes the acceptable room fabric requirements for floors, skirtings, walls, celings , cornice and

    identifies wall protection, handrails and door protection where required. Door protection should be assumed to be

    applied to both sides of doors to the room nominated. Fabric types are identified in generic terms only - Brands are

    generally not nominated.

    This section lists all fittings (items which are attached to walls or floors) and loose furniture items required in each

    room. These items are identified with an ID number, a description and the quantity required. All items are identified

    with a group number which indicates who is responsible for providing the item according to a health industry wide

    accepted description as follows:

    12

    2T

    Provided and Installed by the builder

    Provided by the Client and installed by the builder

    Provided and installed by the Client

    This section lists all items which are fixtures (fixed equipment) and loose equipment which have a services

    requirement. As for Fittings/ Furniture these items are identified with an ID number, a description, the quantity required

    and Group number according to the above description. The services required for each equipment item are identified

    with 'yes' if required, ''___' if not required, and 'opt' if the service is optional. If a service is noted as optional, the

    'Selection' section of the table will note whether the service is required for that item. The following lists the description

    for the codes displayed:

    This section lists all services requirements for the room including communications outlets (telephone, data, etc) air

    conditioning, exhaust, special hydraulics such as floor wastes, lighting, medical gases, nurse call outlets and power.

    Quantities are indicated where appropriate; not every item requires a quantity to be identified such as air conditioning.

    Provision of Services items listed is mandatory.

    HAAD Health Facility Guidelines

    3

    3T

    Provided by the Client, an existing item to be transferred

    Provided by the Client, an existing item to be transferred

    Ele Power (special power requirements and quantities will be identified only in the Services section)DataCdWHtWWmWTapDns

    Data RequiredCold Water requiredHot water requiredWarm water requiredTaps requiredDrains required

    Gas Gas required (refers to Town/ Natural gas - medical gas requirements are listed in the Services sectStm Steam required

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1005

    Room Name 1 Bed Room - Standard Room Code: 1 BR-ST-U

    Net Room Area Briefed 18.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 18.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1-2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room will accommodate one patient for the delivery of nursing

    and medical care and treatment; natural light and outlook is essential;

    requires ability to view out of the window from either the chair or bed. The

    1 Bed Room may also be used as an Isolation Room - Class S (Standard

    Pressure). Door glazing and an internal window is recommended with

    this option.

    The 1 Bed Room may vary in configuration to suit different Ensuite options

    including:

    - 1 BR-ST-A1 Inboard Ensuite

    - 1 BR-ST-B1 Outboard Ensuite

    Acoustics: Acoustic privacy required

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1200mm (single door)/

    1400mm (1+1/2 door) clear

    opening, half leaf optional;

    obs panel for Isolation use

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    optional, to rooms with an

    outboard ensuite

    7010 Observation Glass Clear Through door/s for Isolation Room use

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    UAE Domain

    Provided by HAAD for :

    Page 3 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1005

    Room Name 1 Bed Room - Standard Room Code: 1 BR-ST-U

    Fabric RemarksSpecificationFinishMaterialID Selection

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards where required

    7001 Windows natural light & outlook

    essential.

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    1252 Blind: Venetian integral Furniture/ Fitting 1 if internal observation window

    provided, 2 way control

    1

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV2

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 12

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 optional1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ refer to BHWS-B (sim)___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    UAE Domain

    Provided by HAAD for :

    Page 4 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1005

    Room Name 1 Bed Room - Standard Room Code: 1 BR-ST-U

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 to desk

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 3 adjacent to patient chair; 2 on walls

    9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;

    1-refrigerator in cupboard

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 5 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1010

    Room Name 1 Bed Room - Large Room Code: 1 BR-LG-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1-2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room will accommodate one patient for the delivery of nursing

    and medical care and treatment; natural light and outlook is essential;

    requires ability to view out of the window from either the chair or bed. The

    1 Bed Room may also be used as an Isolation Room - Class S (Standard

    Pressure). Door glazing and an internal window is recommended with

    this option.

    The 1 Bed Room may vary in configuration to suit different Ensuite options

    including:

    - 1 BR-LG-A1 Inboard Ensuite

    - 1 BR-LG-B1 Outboard Ensuite

    Acoustics: Acoustic privacy required

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1200mm (single door)/

    1400mm (1+1/2 door) clear

    opening, half leaf optional;

    obs panel for Isolation use

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    optional, to rooms with an

    outboard ensuite

    7010 Observation Glass Clear Through door/s for Isolation Room use

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    UAE Domain

    Provided by HAAD for :

    Page 6 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1010

    Room Name 1 Bed Room - Large Room Code: 1 BR-LG-U

    Fabric RemarksSpecificationFinishMaterialID Selection

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards where required

    7001 Windows natural light & outlook

    essential.

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    480 Bassinet Furniture/ Fitting 1 optional3

    1252 Blind: Venetian integral Furniture/ Fitting 1 if internal observation window

    provided, 2 way control

    1

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV2

    2050 Chair: lounge, sofa bed Furniture/ Fitting 1 optional3

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 12

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 optional1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ refer to BHWS-B (sim)___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    UAE Domain

    Provided by HAAD for :

    Page 7 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1010

    Room Name 1 Bed Room - Large Room Code: 1 BR-LG-U

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 to desk

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 3 adjacent to patient chair; 2 on walls

    9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;

    1-refrigerator in cupboard

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 8 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1030

    Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1 - 2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    The 1 Bed Isolation Room - Postivie Pressure may be used to isolate

    patients to protect them from acquiring an infection. natural light and

    outlook is essential; Glazing to room front and doors is recommended for

    patient visibility. Each Isolation room is to have an internal handwash

    basin and direct access to ensuite toilet and shower facilities.

    Acoustics: Acoustic privacy is required.

    Body Protected electrical area

    Amendment 24.10.10, - First Draft

    13.04.11, - FE & Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1400 clear opening

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    to corridor side

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    UAE Domain

    Provided by HAAD for :

    Page 9 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1030

    Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    1252 Blind: Venetian integral Furniture/ Fitting 3 to external, internal windows & door

    glazing, 2 way controls to internal

    windows

    1

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV2

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 3 1 at desk3

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near entry2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 washable seat covering; with drawers

    under

    1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ elbow action levers___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    5040 Pressure: positive HVAC

    6001 General: colour corrected Lighting

    6065 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    UAE Domain

    Provided by HAAD for :

    Page 10 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1030

    Room Name 1 Bed Room - Isolation - Positive Pressure Room Code: 1 BR-IS-P-U

    ID Description Service Category Qty Selection / Remarks

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 to desk

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 3 1 adjacent to patient chair; 1 to cupboard; 1

    on wall near entry

    9000 GPO: Single Power 1 Bedhead low level, for electric bed

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 11 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1040

    Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1 - 2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    Single bed room which may be used to isolate patients with known

    infectious conditions; natural light and outlook is essential. Glazing to

    room front and doors is recommended for patient visibility. The Isolation

    Room - Negative Pressure will require an internal staff handwash basin,

    direct access to ensuite toilet and shower facilities, and an Anteroom or

    Airlock to maintain air pressurisation.

    Acoustics: Acoustic privacy is required.

    Body Protected electrical area

    Amendment 24.10.10, - First Draft

    13.04.11, - FE & Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1400 clear opening

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    to corridor side

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    UAE Domain

    Provided by HAAD for :

    Page 12 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1040

    Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    1252 Blind: Venetian integral Furniture/ Fitting 3 to external, internal windows & door

    glazing, 2 way controls to internal

    windows

    1

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV2

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 3 1 at desk3

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near entry2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 washable seat covering; with drawers

    under

    1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ elbow action levers___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    5050 Pressure: negative HVAC

    6001 General: colour corrected Lighting

    6065 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    UAE Domain

    Provided by HAAD for :

    Page 13 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1040

    Room Name 1 Bed Room - Isolation - Negative Pressure Room Code: 1 BR-IS-N-U

    ID Description Service Category Qty Selection / Remarks

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 to desk

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 3 1 adjacent to patient chair; 1 to cupboard; 1 to

    wall near entry

    9000 GPO: Single Power 1 Bedhead low level, for electric bed

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 14 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1050

    Room Name 1 Bed Room - Mental Health Room Code: 1 BR-MH-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1-2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    Single bed room for general mental health patients; natural light and

    outlook is essential; The room is to be internally lockable with a master

    keyed lock from the outside; All fittings are to have a breaking strain of not

    more than 15kg. All glazing (including external windows) is to comply with

    standards for Mental Health Facilities.

    The 1 Bed Room - Mental Health may vary in configuration to suit different

    Ensuite options including:

    - 1 BR-MH-A Inboard Ensuite

    - 1 BR-MH-B Shared Ensuite, access from corridor

    - 1 BR-MH-C Back-to-Back Ensuites

    Acoustics: Acoustic privacy is required.

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    13.04.11, - Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    9006 Doors Solid Core/

    Safety glass

    Paint Single leaf,

    observation panel

    1150mm clear inward &

    outward opening; lockable

    1149 Floor finish Carpet 90/10 Wool/

    Nylon

    Broadloom, 48 oz. Vinyl also acceptable

    7045 Observation Safety glass Powdercoat Internal window with integral Venetians,

    control to corridor side,

    window optional

    2010 Skirting Vinyl Prefinished Feather edged,

    150 mmH

    or floor vinyl coved skirting

    3067 Wall finish Laminate Prefinished for TV where required

    3000 Wall finish Paint Acrylic,

    washable

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    7001 Windows Essential

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    UAE Domain

    Provided by HAAD for :

    Page 15 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1050

    Room Name 1 Bed Room - Mental Health Room Code: 1 BR-MH-U

    ID Description Category Group Qty Selection / Remarks

    690 Bed: domestic, single Furniture/ Fitting 13

    1260 Blind: holland Metalwork 1 to external windows, curtains optional3

    2010 Chair: lounge, foam type Furniture/ Fitting 2 patient & visitors chairs3

    2655 Chair: visitor Furniture/ Fitting 1 plastic light weight3

    4330 Cupboard: wardrobe Furniture/ Fitting 1 with fixed shelves1

    4900 Curtain track: window Metalwork 1 to external window, optional1

    5910 Desk: built in Furniture/ Fitting 1 laminate1

    12750 Lounge: 2 seat Furniture/ Fitting 1 foam type3

    13730 Mirror: acrylic Metalwork 1 optional1

    17360 Pinboard: fabric covered Furniture/ Fitting 1 (velcro compatible) or artwork, optional1

    22690 Table: bedside Furniture/ Fitting 1 heavy3

    22801 Table: coffee Furniture/ Fitting 2 soft furnishings3

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ______3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    5000 Airconditioning HVAC

    6000 General fluorescent Lighting

    6065 Special: night lights Lighting blue

    6050 Special: reading Lighting vandal proof

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, Duress call (optional)

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9000 GPO: Single Power 3 1 over desk; 2 on wall

    9000 GPO: Single Power 4 2 to each side of bed

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 16 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1060

    Room Name 1 Bed Room - Special Room Code: 1 BR-SP-U-A

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 visitors, 1-2 staff intermittently

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room - Special will accommodate one patient for the delivery of

    nursing and medical care and treatment. It will be a larger room to

    accommodate special needs patients such as Palliative Care, Sub-acute

    Care, Rehabilitation and High Dependency. The additional floor area

    allows for larger or additional furniture and equipment. It also permits

    overnight stay by relatives. Natural light and outlook is essential; the room

    requires the ability to view out of the window from either the chair or bed.

    Bedrooms for Palliative Care may also include a beverage making area

    with a small refrigerator.

    Acoustics: Acoustic privacy is required.

    Body protected electrical area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening;

    latch set, H/O device

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved Carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    UAE Domain

    Provided by HAAD for :

    Page 17 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1060

    Room Name 1 Bed Room - Special Room Code: 1 BR-SP-U-A

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 medical air3

    480 Bassinet Furniture/ Fitting 1 optional3

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 11

    2050 Chair: lounge, sofa bed Furniture/ Fitting 1 optional3

    2150 Chair: patient Furniture/ Fitting 2 1 to desk3

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near basin2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    17360 Pinboard: fabric covered Furniture/ Fitting 1 optional; above desk2

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ refer to BHWS-B-U (sim)___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting up/down light

    UAE Domain

    Provided by HAAD for :

    Page 18 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1060

    Room Name 1 Bed Room - Special Room Code: 1 BR-SP-U-A

    ID Description Service Category Qty Selection / Remarks

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 desk

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 1 adjacent to patient chair

    9000 GPO: Single Power 1 Bedhead low level, for electric bed

    9000 GPO: Single Power 1 Fridge (optional)

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 19 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1070

    Room Name 1 Bed Room - Special, CCU Room Code: 1 BR-SP-U-B

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 visitors, 1-2 staff intermittently

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room - Special, Coronary Care will accommodate one patient for

    the delivery of cardiac care treatment. Glazed doors and partition walls are

    recommended for patient visibility and privacy. Natural light and outlook is

    essential; the room requires the ability to view out of the window from

    either the chair or bed.

    Acoustics: Acoustic privacy is required.

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    13.04.11, - FF & Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9110 Doors Solid Core Paint 1 1/2 leaf 1400mm clear opening;

    latch set, observation

    panel optional

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved Carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7055 Observation Alum/ Glass Powdercoat Internal window,

    double glazed

    with integral venetian

    blinds

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    Timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    UAE Domain

    Provided by HAAD for :

    Page 20 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1070

    Room Name 1 Bed Room - Special, CCU Room Code: 1 BR-SP-U-B

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    1252 Blind: Venetian integral Furniture/ Fitting 1 to internal window1

    1480 Bracket: ECG monitor Furniture/ Fitting 13

    1465 Bracket: suction bottle Furniture/ Fitting 22

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV1

    2050 Chair: lounge, sofa bed Furniture/ Fitting 1 optional3

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near basin2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 23

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 23

    22000 Suction bottle Furniture/ Fitting 23

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 with drawers under1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ refer to BHWS-B (sim)___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    36050 Monitor: cardiac 1 yes ___ ___ ___ ___ ___ ___ may be telemetryopt3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1120 Monitor connection facilities and

    cabling

    Communications 1 optional

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    UAE Domain

    Provided by HAAD for :

    Page 21 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1070

    Room Name 1 Bed Room - Special, CCU Room Code: 1 BR-SP-U-B

    ID Description Service Category Qty Selection / Remarks

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 2

    7040 Suction Medical Gases 2

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 1 desk

    9010 GPO: Emergency power, single Power 8 Bedhead

    9000 GPO: Single Power 3 1 adjacent to patient chair; 2 on walls

    9000 GPO: Single Power 1 Bedhead low level, for electric bed

    9000 GPO: Single Power 1 fridge (optional)

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 22 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1073

    Room Name 1 Bed Room - Super VIP Room Code: 1 BR-SVIP-U

    Net Room Area Briefed 50.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 50.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; Up to 10 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room - Super VIP will accommodate one VIP patient for the

    delivery of nursing and medical care and treatment; natural light and

    outlook is essential; requires ability to view out of the window from either

    the chair or bed. The 1 Bed Room - Super VIP may also be used as an

    Isolation Room - Class S (Standard Pressure). Door glazing and an

    internal window is recommended with this option. The Super VIP room

    will include superior level of finishes and fittings. An Ensuite will be

    located within the space. The Super VIP room will have access to a

    Waiting room, Family/Carer Room and a Pantry.

    Acoustics: Acoustic privacy required

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    13.04.11, - FF, FE & Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5005 Ceiling Plasterboard Paint Coffered, special optional

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    9110 Doors Solid Core Paint 1 1/2 leaf 1600mm clear opening

    9001 Doors Solid Core Paint Single leaf to Lounge / Dining - Super

    VIP; sliding

    1161 Floor finish Carpet 90/10 Wool/

    Nylon

    Broadloom,

    decorative feature

    may include custom made

    motif

    1250 Floor finish Tiles Polished Stone/ Marble

    15mm

    under basin

    949496 Skirting Timber Paint 150mmH x 20mm

    thick, nominal

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin; colour back glass

    splashback also

    acceptable

    3084 Wall finish Timber

    veneer

    Sealed Panel

    3057 Wall finish Vinyl Prefinished Vinyl wall paper

    full height

    4045 Wall protection Timber Clear finish Corner guards where required

    7001 Windows natural light & outlook

    essential.

    UAE Domain

    Provided by HAAD for :

    Page 23 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1073

    Room Name 1 Bed Room - Super VIP Room Code: 1 BR-SVIP-U

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    350 Artwork Furniture/ Fitting 3 as required3

    530 Basin vanity top Furniture/ Fitting 11

    1260 Blind: holland Metalwork 2 double blinds to external window;

    curtains also acceptable

    3

    1465 Bracket: suction bottle Furniture/ Fitting 12

    2050 Chair: lounge, sofa bed Furniture/ Fitting 1 optional3

    2200 Chair: recliner Furniture/ Fitting 1 patient chair3

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 entertainment & refrigerator cabinet1

    4391 Cupboard: special Furniture/ Fitting 1 to conceal bedhead services1

    4391 Cupboard: special Furniture/ Fitting 1 to handwash basin1

    4330 Cupboard: wardrobe Furniture/ Fitting 21

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 2 double track if curtain set provided1

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set; blinds also acceptable3

    5400 Curtain: window, sheer Furniture/ Fitting 1 set; blinds also acceptable3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 12

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 13

    20000 Shelving unit: adjustable Furniture/ Fitting 1 for flowers & display1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 with drawers under1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    3120 Basin: vanity 1 ___ yes ___ yes yes yes ______1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ___ custom size___3

    18610 DVD player 1 yes ___ ___ ___ ___ ___ ___ in entertainment cabinet___3

    42800 Radio / CD player 1 yes ___ ___ ___ ___ ___ ___ in entertainment cabinet___3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    50955 Speaker: ceiling mounted 4 yes ___ ___ ___ ___ ___ ___ surround speakers for

    entertainment systems

    installed

    ___1

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ in entertainment cabinet___3

    UAE Domain

    Provided by HAAD for :

    Page 24 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1073

    Room Name 1 Bed Room - Super VIP Room Code: 1 BR-SVIP-U

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 4 1-patient services panel; 1-desk; 1 in

    entertainment cabinet; 1-near patient chair; 1

    outlet for telephone to each panel

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6046 Indirect lighting Lighting

    6200 Light switches Lighting sensor operated room lights

    45570471 Special: decorative Lighting may include chandelier or pendant lighting

    6030 Special: downlights Lighting recessed

    6060 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    6045 Wall washers Lighting

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 5 2 to desk; 2 in entertainment cabinet; 1 near

    patient chair

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;

    1-refrigerator in cupboard

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 25 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1075

    Room Name 1 Bed Room - VIP Room Code: 1 BR-VIP-U

    Net Room Area Briefed 30.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 30.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1-2 staff; 1-2 visitors

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 1 Bed Room - VIP will accommodate one patient for the delivery of

    nursing and medical care and treatment; natural light and outlook is

    essential; requires ability to view out of the window from either the chair or

    bed. The 1 Bed Room - VIP may also be used as an Isolation Room -

    Class S (Standard Pressure). Door glazing and an internal window is

    recommended with this option.

    The 1 Bed Room - VIP may vary in configuration to suit different Ensuite

    options including:

    - 1 BR-ST-A Inboard Ensuite

    - 1 BR-ST-B Outboard Ensuite

    - 1 BR-ST-C Shared Ensuite

    Acoustics: Acoustic privacy required

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    13.04.11, - FF & Services modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1150mm (single door)/

    1400mm (1+1/2 door) clear

    opening, half leaf optional;

    obs panel for Isolation use

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    optional, to rooms with an

    outboard ensuite

    7010 Observation Glass Clear Through door/s for Isolation Room use

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    UAE Domain

    Provided by HAAD for :

    Page 26 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1075

    Room Name 1 Bed Room - VIP Room Code: 1 BR-VIP-U

    Fabric RemarksSpecificationFinishMaterialID Selection

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards where required

    7001 Windows natural light & outlook

    essential.

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 1 Medical air3

    530 Basin vanity top Furniture/ Fitting 11

    480 Bassinet Furniture/ Fitting 1 optional3

    1252 Blind: Venetian integral Furniture/ Fitting 1 if internal observation window

    provided, 2 way control

    1

    1465 Bracket: suction bottle Furniture/ Fitting 12

    23410 Bracket: television, wall mount Metalwork 1 flat screen TV2

    2000 Chair: lounge Furniture/ Fitting 23

    2150 Chair: patient Furniture/ Fitting 13

    2650 Chair: visitor, patient Furniture/ Fitting 13

    4391 Cupboard: special Furniture/ Fitting 1 for refrigerator1

    4391 Cupboard: special Furniture/ Fitting 1 to conceal bedhead services1

    4330 Cupboard: wardrobe Furniture/ Fitting 11

    4600 Curtain track: bed screen Metalwork 11

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 13

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    5910 Desk: built in Furniture/ Fitting 11

    6152 Dispenser: disposable glove Furniture/ Fitting 12

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 1 mobile, 2 lockable top drawers3

    88553415 Ottoman sofa Furniture/ Fitting 13

    16250 Oxygen flowmeter Furniture/ Fitting 13

    19800 Shelf: laminate Furniture/ Fitting 1 for flowers1

    21950 Suction adapter Furniture/ Fitting 13

    22000 Suction bottle Furniture/ Fitting 13

    22800 Table: low Furniture/ Fitting 13

    16200 Table: overbed Furniture/ Fitting 13

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    24604 Window seat: built-in Furniture/ Fitting 1 optional; with drawers under1

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    UAE Domain

    Provided by HAAD for :

    Page 27 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1075

    Room Name 1 Bed Room - VIP Room Code: 1 BR-VIP-U

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData 3120 Basin: vanity 1 ___ yes ___ yes yes yes ___ Type B; refer to BHWS-B

    (sim)

    ___1

    3700 Bed: inpatient, electric 1 yes ___ ___ ___ ___ ___ ______3

    43800 Refrigerator: under-bench, 120 Litre 1 yes ___ ___ ___ ___ ___ ___ optional___3

    54510 Telephone: handset, standard 1 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 1 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 1

    1006 Voice / Data outlet: double Communications 2 1-patient services panel; 1-desk; 1 outlet for

    telephone to each panel

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting Up/down light

    7020 Medical Air (MA) Medical Gases 1

    7000 Oxygen (O2) Medical Gases 1

    7040 Suction Medical Gases 1

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 1 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 1 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9001 GPO: Double Power 2 1 to desk; 1 to low table

    9010 GPO: Emergency power, single Power 4 Bedhead

    9000 GPO: Single Power 4 Bedhead

    9000 GPO: Single Power 4 1 adjacent to patient chair; 3 on walls

    9000 GPO: Single Power 2 1-Bedhead low level, for electric bed;

    1-refrigerator in cupboard

    9060 GPO: Special: for equipment Power 1 TV

    UAE Domain

    Provided by HAAD for :

    Page 28 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1080

    Room Name 2 Bed Room Room Code: 2 BR-ST-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy Up to 2 patients; 1-2 visitors each; 1-2 staff

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 2 Bed Room will accommodate two patients with similar nursing needs

    for the delivery of nursing and medical care. Each space will be individually

    curtained and allow for treatment of patients either in bed or sitting beside

    the bed in a comfortable chair; natural light and outlook is essential;

    patients require the ability to view out of the window from either the chair or

    bed. The room may also be used for obstetric care, either pre or post

    natal, and may include bassinets.

    Each room is to have direct access to Ensuite toilet and shower facilities

    and the Unit corridor. The room layout is to allow movement of equipment

    around bedspaces.

    The 2 Bed Room may vary in configuration to suit different Ensuite options

    including:

    - 2 BR-ST-A-U Inboard Ensuite

    - 2 BR-ST-B-U Outboard Ensuite

    - 2 BR-ST-C-U Shared Ensuite

    Acoustics: Acoustic privacy is required.

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    8010 Door protection Composite Prefinished

    PVC

    Protection plate to

    900 AFFL

    8040 Door protection Composite Prefinished

    PVC

    To door frame

    9125 Doors Solid Core/

    Glass

    Paint 1 1/2 leaf,

    observation panel

    1400mm clear opening

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved Carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    with integral blinds,

    optional to outboard

    ensuite rooms

    UAE Domain

    Provided by HAAD for :

    Page 29 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1080

    Room Name 2 Bed Room Room Code: 2 BR-ST-U

    Fabric RemarksSpecificationFinishMaterialID Selection

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3067 Wall finish Laminate Prefinished wall panels

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 2 Medical air3

    480 Bassinet Furniture/ Fitting 2 optional, if used for post-natal care3

    1252 Blind: Venetian integral Furniture/ Fitting 1 optional; to internal window if provided1

    1465 Bracket: suction bottle Furniture/ Fitting 22

    23410 Bracket: television, wall mount Metalwork 2 flat screen TVs2

    2150 Chair: patient Furniture/ Fitting 23

    2650 Chair: visitor, patient Furniture/ Fitting 23

    4330 Cupboard: wardrobe Furniture/ Fitting 21

    4600 Curtain track: bed screen Metalwork 21

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 23

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near basin2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 2 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 23

    19800 Shelf: laminate Furniture/ Fitting 2 for flowers1

    21950 Suction adapter Furniture/ Fitting 23

    22000 Suction bottle Furniture/ Fitting 23

    16200 Table: overbed Furniture/ Fitting 23

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ elbow action levers___1

    3700 Bed: inpatient, electric 2 yes ___ ___ ___ ___ ___ ______3

    54510 Telephone: handset, standard 2 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 2 yes ___ ___ ___ ___ ___ ___ wall mounted___3

    Services

    UAE Domain

    Provided by HAAD for :

    Page 30 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1080

    Room Name 2 Bed Room Room Code: 2 BR-ST-U

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 2 1 / bed

    1006 Voice / Data outlet: double Communications 2 1 / bed; one outlet for telephone, each bed

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting 2 Up/down light

    7020 Medical Air (MA) Medical Gases 2 1 / bed

    7000 Oxygen (O2) Medical Gases 2 1 / bed

    7040 Suction Medical Gases 2 1 / bed

    8080 Emergency call Nurse Call 1 + indicator button & light

    8005 Patient call handset Nurse Call 2 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 2 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 2 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9010 GPO: Emergency power, single Power 8 4 / bed

    9000 GPO: Single Power 8 4 / bed

    9000 GPO: Single Power 4 1 adjacent to each patient chair; 2 on walls

    9000 GPO: Single Power 2 Bedhead low level, for electric bed/s

    9060 GPO: Special: for equipment Power 2 TVs

    UAE Domain

    Provided by HAAD for :

    Page 31 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1090

    Room Name 2 Bed Room - Mental Health Room Code: 2 BR-MH-U

    Net Room Area Briefed 28.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 28.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient, 1 - 2 visitors, 1 - 2 staff intermittently

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 2 Bed Room for general mental health patients; natural light and outlook

    is essential; The room is to be internally lockable with a master keyed lock

    from the outside; All fittings are to have a breaking strain of not more than

    15kg. All glazing (including external windows) is to comply with standards

    for Mental Health Facilities.

    The 2 Bed Room - Mental Health may vary in configuration to suit different

    Ensuite options including:

    - 2 BR-MH-A-U Inboard Ensuite

    - 2 BR-MH-B-U Shared Ensuite with access off the corridor

    - 2 BR-MH-D-U Back to Back Ensuites

    Acoustics: Acoustic privacy is required.

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    9006 Doors Solid Core/

    Safety glass

    Paint Single leaf,

    observation panel

    1150mm clear inward &

    outward opening, lockable

    1149 Floor finish Carpet 90/10 Wool/

    Nylon

    Broadloom, 48 oz. vinyl also acceptable

    7045 Observation Safety glass Powdercoat Internal window with integral Venetians,

    control to corridor side;

    observation window

    desirable

    2010 Skirting Vinyl Prefinished Feather edged,

    150 mmH

    or floor vinyl coved skirting

    3000 Wall finish Paint Acrylic,

    washable

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    7001 Windows Essential

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    690 Bed: domestic, single Furniture/ Fitting 23

    UAE Domain

    Provided by HAAD for :

    Page 32 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1090

    Room Name 2 Bed Room - Mental Health Room Code: 2 BR-MH-U

    ID Description Category Group Qty Selection / Remarks

    1260 Blind: holland Metalwork 1 to external window (curtains optional)3

    1252 Blind: Venetian integral Furniture/ Fitting 2 to observation window if provided &

    door glazing

    1

    2150 Chair: patient Furniture/ Fitting 2 foam lounge type3

    2655 Chair: visitor Furniture/ Fitting 2 lightweight plastic type3

    4330 Cupboard: wardrobe Furniture/ Fitting 2 with fixed shelves1

    4900 Curtain track: window Metalwork 1 to external window, optional1

    5910 Desk: built in Furniture/ Fitting 21

    13730 Mirror: acrylic Metalwork 1 optional1

    17360 Pinboard: fabric covered Furniture/ Fitting 2 optional, secure fixings1

    22690 Table: bedside Furniture/ Fitting 2 heavy3

    Services

    ID Description Service Category Qty Selection / Remarks

    5000 Airconditioning HVAC

    6000 General fluorescent Lighting

    6065 Special: night lights Lighting blue

    6050 Special: reading Lighting to each bed

    8000 Patient/ Staff call Nurse Call 2 + indicator buttons & light; 1 per bed

    8010 Staff/ Nurse assist call Nurse Call 1 + indicator button & light, Duress call (optional)

    9015 GPO: Cleaner Power 1

    9000 GPO: Single Power 11 4 per bed at bedhead; 1 per desk; 1 on wall

    UAE Domain

    Provided by HAAD for :

    Page 33 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1100

    Room Name 4 Bed Room Room Code: 4 BR-ST-U

    Net Room Area Briefed 49.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 49.00 M2

    Hours of Operation 24 Hours

    Occupancy Up to 4 patients; 1-2 visitors each; 1-2 staff

    Also covers these

    Rooms

    Description/

    Special Requirements

    A 4 Bed Room will accommodate four patients with similar nursing needs

    for the delivery of nursing and medical care and treatment. Each space will

    be individually curtained and allow for treatment of patients either in bed or

    sitting beside the bed in a comfortable chair; natural light and outlook is

    essential; patients require the ability to view out of the window from either

    the chair or bed.

    Each room is to have direct access to ensuite toilet and shower facilities,

    and a staff handwash basin, either within the room or immediately

    adjacent.

    The 4 Bed Room may vary in configuration to suit different Ensuite options

    including:

    - 4 BR-ST-A Inboard Ensuite

    - 4 BR-ST-B Outboard Ensuite

    - 4 BR-ST-C Inboard/ Outboard Ensuite

    Acoustics: Acoustic privacy is required.

    Body Protected electrical area

    Amendment 24.10.10, - First Draft

    20.04.11, - FF modified

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5010 Ceiling Plasterboard Paint,

    washable

    Flush set,

    suspended

    6025 Cornice Aluminium Powdercoat shadow line

    1000 Floor finish Vinyl Standard slip

    resistant

    Seamless, coved Carpet also acceptable

    1045 Floor finish Vinyl, non slip Textured Seamless, coved under basin

    7030 Observation Alum/ Glass Powdercoat Internal window,

    door height

    with integral venetian,

    optional in outboard ensuite

    rooms

    2000 Skirting Vinyl Prefinished Floor vinyl coved,

    150 mmH

    timber skirting if carpeted

    3000 Wall finish Paint Acrylic,

    washable

    3022 Wall finish Resinate,

    6mm

    Prefinished Splashback to basin

    UAE Domain

    Provided by HAAD for :

    Page 34 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1100

    Room Name 4 Bed Room Room Code: 4 BR-ST-U

    Fabric RemarksSpecificationFinishMaterialID Selection

    3092 Wall protection MDF Laminate Bed protection

    wall panel

    4045 Wall protection Timber Clear finish Corner guards Where required

    7001 Windows Natural light & outlook

    essential.

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    150 Air flowmeter Furniture/ Fitting 4 Medical air3

    1252 Blind: Venetian integral Furniture/ Fitting 1 to internal window if provided1

    1465 Bracket: suction bottle Furniture/ Fitting 42

    23400 Bracket: television, ceiling Metalwork 4 for flat screen TVs2

    2150 Chair: patient Furniture/ Fitting 43

    4330 Cupboard: wardrobe Furniture/ Fitting 41

    4600 Curtain track: bed screen Metalwork 41

    4900 Curtain track: window Metalwork 11

    5000 Curtain: bed screen Furniture/ Fitting 43

    5410 Curtain: window, drapes Furniture/ Fitting 1 set3

    6152 Dispenser: disposable glove Furniture/ Fitting 1 near entry2

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 1 to basin2

    6156 Dispenser: soap Furniture/ Fitting 1 to basin2

    6158 Dispenser: soap antiseptic Furniture/ Fitting 1 to basin2

    12450 Locker: bedside Furniture/ Fitting 4 mobile, 2 lockable top drawers3

    16250 Oxygen flowmeter Furniture/ Fitting 43

    1679 Seat: built-in Furniture/ Fitting 4 or visitor chairs1

    19800 Shelf: laminate Furniture/ Fitting 4 for flowers1

    21950 Suction adapter Furniture/ Fitting 43

    22000 Suction bottle Furniture/ Fitting 43

    16200 Table: overbed Furniture/ Fitting 43

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to basin3

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    2800 Basin: handwash, Type B 1 ___ yes ___ yes yes yes ___ elbow action levers___1

    3700 Bed: inpatient, electric 4 yes ___ ___ ___ ___ ___ ______3

    54510 Telephone: handset, standard 4 ___ ___ ___ ___ ___ ___ ___yes3

    3031 Television: flat screen 4 yes ___ ___ ___ ___ ___ ___ ceiling mounted___3

    Services

    ID Description Service Category Qty Selection / Remarks

    1090 TV: MATV Communications 4 1 / bed

    1006 Voice / Data outlet: double Communications 4 1 / bed; one outlet for telephone, each bed

    5000 Airconditioning HVAC

    6001 General: colour corrected Lighting

    6060 Special: night lights Lighting

    6050 Special: reading Lighting 4 Up/down lights

    UAE Domain

    Provided by HAAD for :

    Page 35 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1100

    Room Name 4 Bed Room Room Code: 4 BR-ST-U

    ID Description Service Category Qty Selection / Remarks

    7020 Medical Air (MA) Medical Gases 4 1 / bed

    7000 Oxygen (O2) Medical Gases 4 1 / bed

    7040 Suction Medical Gases 4 1 / bed

    8080 Emergency call Nurse Call 2 + indicator button & light

    8005 Patient call handset Nurse Call 4 call button & light switch on the handset

    8000 Patient/ Staff call Nurse Call 4 + indicator button & light

    8010 Staff/ Nurse assist call Nurse Call 4 + indicator button & light

    9040 Body protected Power

    9015 GPO: Cleaner Power 1

    9010 GPO: Emergency power, single Power 16 4 / bed

    9000 GPO: Single Power 16 4 / bed

    9000 GPO: Single Power 5 1 adjacent to each patient chair (optional); 1

    on wall

    9000 GPO: Single Power 4 Bedhead low level, for electric bed/s

    9060 GPO: Special: for equipment Power 4 TVs, ceiling

    UAE Domain

    Provided by HAAD for :

    Page 36 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1105

    Room Name Ablution Room (Prayer Room) Room Code: ABLR-U

    Net Room Area Briefed 13.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 13.00 M2

    Hours of Operation 24 Hours

    Occupancy 2-10

    Also covers these

    Rooms

    Description/

    Special Requirements

    The Ablution room is an airlock entry prior to the Prayer Room where

    visitors and patients can wash-up prior to entering the prayer room.

    Separate Ablution Room shall be provided for male and female and direct

    access to prayer room is recommeded.

    Acoustics: Sound attenuation level - medium; acoustic privacy required.

    Body Protected Electrical Area

    Amendment 24.10.10, - First Draft

    Room Fabric and outline specifications

    Fabric RemarksSpecificationFinishMaterialID Selection

    5030 Ceiling Plasterboard Prefinished Drop-in tiles,

    600x1200

    6025 Cornice Aluminium Powdercoat shadow line

    8000 Door protection Vinyl Prefinished Kickplate, 300mm

    high

    9001 Doors Solid Core Paint Single leaf 920mm clear

    1175 Floor finish Tiles Non-slip Ceramic non slip vinyl floor also

    acceptable

    2145 Skirting Tiles To match floor Coved or floor vinyl coved skirting

    3000 Wall finish Paint Acrylic,

    washable

    3090 Wall finish Tiles Glazed vinyl also acceptable; to

    1000mm high around

    wash-up area

    Fittings and Furniture (FF)

    ID Description Category Group Qty Selection / Remarks

    2655 Chair: visitor Furniture/ Fitting 13

    3400 Coathook Metalwork 101

    6154 Dispenser: paper/ hand towel Furniture/ Fitting 2 to each wash-up station2

    6156 Dispenser: soap Furniture/ Fitting 1 shared by wash-up stations2

    13700 Mirror Metalwork 1 full height, dressing1

    19750 Rack: shoe Furniture/ Fitting 1 for 20 pairs of shoes1

    21699 Stool: fixed Furniture/ Fitting 2 marble seat fixed for each washing

    station

    1

    24100 Waste bin: paper, 20 Litre Furniture/ Fitting 1 to wash-up area3

    UAE Domain

    Provided by HAAD for :

    Page 37 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1105

    Room Name Ablution Room (Prayer Room) Room Code: ABLR-U

    Fixtures, Equipment and associated Services (FE)

    ID Description QtyGroup Ele CdW HtW WmW Tap Dns Gas Selection / RemarksData

    480 Ablutions washing outlet & tap 2 ___ yes ___ yes yes yes ___ per washing station___1

    3003 Bidet handset 2 ___ ___ ___ yes yes ___ ___ per washing station___1

    Services

    ID Description Service Category Qty Selection / Remarks

    5000 Airconditioning HVAC

    5019 Exhaust HVAC

    4033 Floor waste Hydraulics 2

    6000 General fluorescent Lighting

    9015 GPO: Cleaner Power 1

    UAE Domain

    Provided by HAAD for :

    Page 38 of 802

    11 Apr 2014Print Date:

    Issue Date:

    Issue No: 3

    11 Apr 2014

  • Room Data Sheets

    HAAD Health Facility Guidelines Milestone: Version 3.3

    Department Standard Components Room Tag: 1110

    Room Name ADL Bathroom Room Code: ADLB-U

    Net Room Area Briefed 12.0 M2

    No of Rooms 1

    Subtotal of Briefed Area 12.00 M2

    Hours of Operation 24 Hours

    Occupancy 1 patient; 1 - 2 staff

    Also covers these

    Rooms

    Description/

    Special Requirements

    A bathroom for patient 'Activities of Daily Living' assessment and training.

    The ADL Bathroom provides for training of patients to use a domestic bath,

    patient dressing, undressing, grooming and handwashing. Facilities

    include a domestic bath installed in a corner of the room, accessible toilet

    and handbasin and a separate shower within the room. A low height

    adjustable shower is required over the bath.

    Additional Design Requirements:

    - The shower area must not have a raised hob.

    - The entrance to the bathroom is to be flush with the adjoining corridor