ROOF PLAN GENERAL NOTES - Floyd Construction
Transcript of ROOF PLAN GENERAL NOTES - Floyd Construction
ROOF PLAN GENERAL NOTESA
B
C
D
E
F
G
ROOF PLAN NOTES #
1
2
3
4
5
6
7
ROOFING SUPPLIERS, MANUFACTURERS, & INSTALLERS SHALL REVIEW ALL ROOFING DETAILS & ADVISE THE ARCHITECT ON ANY RECOMMENDED CHANGES.
UNLESS NOTIFIED OTHERWISE, ROOFING SUPPLIERS, MANUFACTURERS AND INSTALLERS WILL BE ASSUMED TO HAVE REVIEWED AND APPROVED THE DETAILS SHOWN. PROVIDE FLASHING AND SEALANT PER ROOFING MANUFACTURER RECOMMENDATION AT ALL CONDUIT & HVAC LINES PENETRATING THE ROOF.
CONTRACTOR & ALL SUBTRADES SHALL BE AWARE & EXERCISE THE NECESSARY CARE TO PREVENT DAMAGE TO OR PUNCTURE OF THE ROOF. THIS SHALL INCLUDE ALL MATERIALS, TOOLS, DELETERIOUS MATERIALS.
REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL FOR ITEMS. COORDINATE AS REQUIRED INCLUDING NECESSARY FRAMING, BLOCKING, ETC.
VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND REPORT DISCREPANCIES IMMEDIATELY
REMOVE EXISTING ROOFING MATERIAL AND SAW CUT ROOF DECK AS REQUIRED FOR INSTALLATION OF NEW EXHAUST FANS.
TAPERED ROOF INSULATION - 1/4" PER FT.
ROOF SCUPPER AND DOWNSPOUT. REFER TO DETAL 4/AE201.
FULLY ADHERED WHITE TPO ROOFING MEMBRANE AND ASSEMBLY, SLOPE @ 1/4" PER FT.
30' X 30" WALK PADS.
EXISTING MECHANICAL EQUIPMENT TO BE REINSTALLED ON NEW ROOF. SEE MECHANICAL DRAWINGS.
PROVIDE PIPE PORTAL, SEE MECHANICAL DRAWINGS.
CLEARANCE AREA FOR RTU OUTSIDE AIR INTAKE.
2ND FLOOR ADDITION
SHADE INDICATES EXISTING AREA BEYOND PRIMARY SCOPE OF WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
AE2011
AE2012
3AE311
1AE301
REMOVABLE ROOF PANEL
3AE301
2AE301
1
1
1
1
2
2
9AE321
AE1056
AE1057HIGH
LOW
AE1058
AE1059
HIGH
LOW
3
3
4
1/4":12"
1/4":12"
1/4":12"
8 AE105
AE105
9
TYP.
4
TYP.
1C-RTU
5
5
5
1C-CU1
1C-CU26
5
55
7
EXISTING 4TH FLOOR TO REMAIN
EXISTING 4TH FLOOR TO REMAIN
1
5
5
8" M
IN.
GASKET
SHEET METAL COVER
SURFACED CAP SHEET
INTERPLY
3/4" PROTECTION BOARD
6" MIN TAPERED RIGID INSULATION
WOOD BLOCKING
CANT STRIP
ROOFING MEMBRANE
METAL DECKRE: STRUCTURAL
3/4" COVER BOARD
6" MIN TAPERED RIGID INSULATION
WOOD BLOCKING
METAL DECK,RE: STRUCTURAL
INTERPLY
ROOFING MEMBRANE
CAPPED, GASKETED FASTENERS
SLOPE PIPE AWAY FROM HOOD,RE: MECHANICAL
SHEET METAL ENCLOSURE
2"
EXISTING CONSTRUCTION
NEW COPING
EXISTING STONE BANDING BELOW TO REMAIN. WHERE BANDING INTERFERES WITH NEW CONSTRUCTION, REMOVE A PORTION TO ACCOMMODATE
NEW STONE BANDING BELOW
ROOF SURFACE
2" BELLOWS EJ COVER. TO EXTEND UP ADJACENT EXISTING CONSTRUCTION AND UNDER NEW PARAPET COPING
2" BELLOWS EJ COVER. TO EXTEND UP ADJACENT EXISTING CONSTRUCTION AND UNDER NEW PARAPET COPING
EXISTING CONSTRUCTION
EXISTING STONE BANDING BELOW TO REMAIN. WHERE BANDING INTERFERES WITH NEW CONSTRUCTION, REMOVE A PORTION TO ACCOMMODATE
NEW STONE BANDING BELOW
ROOF SURFACE
2"
2" BELLOWS EJ COVER. TO EXTEND UP ADJACENT EXISTING CONSTRUCTION AND UNDER NEW PARAPET COPING
1/4"
FIRE SAFING INSULATION
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
(1) LAYER 5/8" EXTERIOR SHEATHING AND (2) LAYERS 5/8" TYPE 'X' GWB (INTERIOR SIDE) ON 6" MTL STUDS @ 16"O.C.
FLUID APPLIED AIR BARRIER
FOIL FACED BATT INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
5 3/4"
1' - 4
1/4"
1' - 1
0"
ROOF MEMBRANE
NEW STONE COPING
NEW STONE BANDING BELOW
EXISTING GUTTER TO REMAIN
ROOF SURFACE
NEW METAL COPING
STEP DOWN BELOW GUTTER TO MEET NEW WALL. SEE 4/AE301.
ROOF SURFACE
NEW STONE BANDING BELOW
2" BELLOWS EJ COVER. TO EXTEND UP ADJACENT EXISTING CONSTRUCTION AND UNDER NEW PARAPET COPING
2"
FIRE SAFING INSULATION
2' - 0"1' - 4 1/4" 7 3/4"FACE BRICK VENEER TO
MATCH EXISTING SIZE AND COURSING
(1) LAYER 5/8" EXTERIOR SHEATHING AND (2) LAYERS 5/8" TYPE 'X' GWB (INTERIOR SIDE) ON 6" MTL STUDS @ 16"O.C.
FLUID APPLIED AIR BARRIER FOIL FACED BATT INSULATION
R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
ROOF MEMBRANE
BEYOND PROJECT BOUNDARY, NIC
ARCHITECTURAL ROOF PLAN LEGEND
ROOF EXHAUST FAN C.U. = CONDENSING UNIT
ROOF WALKING PAD
R.T.U. = ROOF TOP UNIT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE105
4TH FLOOR AND ROOF PLANGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1" = 100'-0"KEYPLAN ISOMETRIC
SCALE: 1/8" = 1'-0"AE1051 4TH FLOOR AND ROOF PLAN
SCALE: 1 1/2" = 1'-0"AE1054 TYPICAL ROOF CURB DETAIL
SCALE: 1 1/2" = 1'-0"AE1055 TYPICAL THROUGH ROOF PIPING DETAIL
SCALE: 1 1/2" = 1'-0"AE1056 ROOF CONNECTION TO ELEVATOR DETAIL - HIGH
SCALE: 1 1/2" = 1'-0"AE1057 ROOF CONNECTION TO ELEVATOR DETAIL - LOW
SCALE: 1 1/2" = 1'-0"AE1058 ROOF CONNECTION @ SLOPE DETAIL - HIGH
SCALE: 1 1/2" = 1'-0"AE1059 ROOF CONNECTION @ SLOPE DETAIL - LOW
NOT TO SCALEAE1053 PERSPECTIVE @ ROOF - EAST
NOT TO SCALEAE1052 PERSPECTIVE @ ROOF - SOUTH
2AE301
3AE311
8AE321
8AE321
SIM.
7AE321
8AE321
Revisions: Date:
REFLECTED CEILING PLAN GENERAL NOTES
REFLECTED CEILING PLAN SPECIFIC NOTES1
2
3
4
5
6
7
8
9
10
MODIFY EXISTING CEILING GRID AND TILE INTO NEW AREA FOR A SEAMLESS TRANSITION.
ADJUST LOCATION OF CURVED CEILING BULKHEAD AS REQUIRED TO MAINTAIN INDICATED RELATIONSHIP TO COLUMN CENTERLINES AS INDICATED. COORDINATE WITH COR AND ARCHITECT.
APPROXIMATE LOCATION OF CENTER OF RADIUS OF INDICATED ELEMENTS.
ALIGN EDGES OF BULKHEADS AS INDICATED.
REFER TO DETAIL 2/AE111 FOR BULKHEAD CONDITION.
NO CEILING IN THIS AREA.
SEE MEP DRAWINGS FOR ABOVE CEILING WORK. CONTRACTOR IS REQUIRED TO REMOVE PORTIONS OF CEILINGS AS REQUIRED TO ACCOMMODATE DEMOLITION AND NEW WORK, AND PROVIDE NEW CEILINGS AND FINISH TO MATCH EXISTING EXACTLY UPON COMPLETION OF ABOVE CEILING WORK.
MATCH TYPICAL PATIENT ROOM CEILING 9/AE501.
PROVIDE BULKHEAD ABOVE CABINETS.
PROVIDE ACCESS PANEL, COORDINATE EXACT LOCATION WITH ENGINEERING DRAWINGS AND VA.
#
A
B
C
D
E
F
G
H
THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE ARCHITECTURAL AND ENGINEERING ELEMANTS ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS ANY DISCREPANCIES TO ARCHITECT AND COR.
SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL INFORMATION. COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS, UNLESS OTHERWISE NOTED.
ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED TO ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS AND BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE LIGHTING LAYOUT. THE LIGHTING SHALL BE CENTERED IN ROOMS.
CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.) SHALL BE CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.
ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.
CEILING TILE REMOVED IN ORDER TO COMPETE ABOVE CEILING WORK SHALL BE STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES SHALL BE REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND NEW FINISH APPLIED TO MATCH EXISTING.
REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON GYPSUM BOARD PAINT FINISH.
WHERE NEW CEILINGS ARE INSTALLED AND SPRINKLERS ARE EXISTING TO REMAIN, SPRINKLERS SHALL BE ADJUSTED TO NEW CEILING HEIGHTS, WHEN APPLICABLE.
A
TYPE GRAPHIC DESCRIPTION
B 2x2 ACOUSTICAL CEILING TILE (AP2)
GYPSUM BOARD CEILING. CEILING PAINT.
REFLECTED CEILING PLAN LEGEND
C 2x4 ACOUSTICAL WASHABLE GASKETED CEILING TILE (AP1)
1
1
PT-9A
66
1' - 6"
1' - 6
"
1' - 6
"
CHASE
PT-9A
10
2ND FLOOR ADDITION
SHADE INDICATES EXISTING AREA BEYOND PRIMARY SCOPE OF WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
2' - 0
"1"
5/8" GYPSUM BOARD
3 5/8" METAL STUD @ 16" O.C.
CEILING (AP-1) - SEE REFLECTED CEILING PLANS
EXISTING WINDOW
EXISTING STRUCTURE
1' - 5"
8"
6" M
IN.
VARI
ES
2 1/2" METAL STUD BRACING ON BOTH SIDES AT 48" O.C. - MIN. 3 LOCATIONS. ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
4 7/8"
3-5/8" METAL STUD FRAMING AT 16" O.C. ANCHOR TO STRUCTURE ABOVE
BOTTOM OF BULKHEADVARIES
BOTTOM OF CEILINGVARIES
REFER TO REFLECTED CEILING PLANVARIES
2 1/2" METAL STUD BRACING AT 32" O.C. ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD FRAMING AT 16" O.C. ANCHOR TO STRUCTURE ABOVE
TYPICAL WALL CONSTRUCTION, RE: FLOOR PLAN AND WALL TYPES FOR ADDITIONAL INFORMATION
BOTTOM OF BULKHEADVARIES
BOTTOM OF CEILINGVARIES
@ A
CT O
NLY
6" M
IN.
VARI
ES
2 1/2" METAL STUD BRACING AT 32" O.C. ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD FRAMING AT 16" O.C. ANCHOR TO STRUCTURE ABOVE
VARI
ES6"
MIN
.
REFER TO REFLECTED CEILING PLANVARIES
BOTTOM OF BULKHEADVARIES
BOTTOM OF CEILINGVARIES
5/8" TYPE "X" GYPSUM BOARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE111
2ND FLOOR CEILING PLANGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE1111 2ND FLOOR CEILING PLAN
SCALE: 1" = 100'-0"KEYPLAN ISOMETRIC
SCALE: 1 1/2" = 1'-0"AE1112 TYPICAL IN-ROOM BULKHEAD AT WINDOW
SCALE: 1 1/2" = 1'-0"AE1113 TYPICAL BULKHEAD DETAIL - SINGLE STUD
SCALE: 1 1/2" = 1'-0"AE1114 TYPICAL BULKHEAD DETAIL
SCALE: 1 1/2" = 1'-0"AE1115 TYPICAL BULKHEAD DETAIL
Revisions: Date:
JJ
REFLECTED CEILING PLAN GENERAL NOTES
REFLECTED CEILING PLAN SPECIFIC NOTES1
2
3
4
5
6
7
8
9
10
MODIFY EXISTING CEILING GRID AND TILE INTO NEW AREA FOR A SEAMLESS TRANSITION.
ADJUST LOCATION OF CURVED CEILING BULKHEAD AS REQUIRED TO MAINTAIN INDICATED RELATIONSHIP TO COLUMN CENTERLINES AS INDICATED. COORDINATE WITH COR AND ARCHITECT.
APPROXIMATE LOCATION OF CENTER OF RADIUS OF INDICATED ELEMENTS.
ALIGN EDGES OF BULKHEADS AS INDICATED.
REFER TO DETAIL 2/AE111 FOR BULKHEAD CONDITION.
NO CEILING IN THIS AREA.
SEE MEP DRAWINGS FOR ABOVE CEILING WORK. CONTRACTOR IS REQUIRED TO REMOVE PORTIONS OF CEILINGS AS REQUIRED TO ACCOMMODATE DEMOLITION AND NEW WORK, AND PROVIDE NEW CEILINGS AND FINISH TO MATCH EXISTING EXACTLY UPON COMPLETION OF ABOVE CEILING WORK.
MATCH TYPICAL PATIENT ROOM CEILING 9/AE501.
PROVIDE BULKHEAD ABOVE CABINETS.
PROVIDE ACCESS PANEL, COORDINATE EXACT LOCATION WITH ENGINEERING DRAWINGS AND VA.
#
A
B
C
D
E
F
G
H
THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT OF ALL CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION OF THE ARCHITECTURAL AND ENGINEERING ELEMANTS ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD CONDITIONS AND REPORTS ANY DISCREPANCIES TO ARCHITECT AND COR.
SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE FOR REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL INFORMATION. COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS, UNLESS OTHERWISE NOTED.
ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED TO ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS AND BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE LIGHTING LAYOUT. THE LIGHTING SHALL BE CENTERED IN ROOMS.
CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.) SHALL BE CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.
ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.
CEILING TILE REMOVED IN ORDER TO COMPETE ABOVE CEILING WORK SHALL BE STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES SHALL BE REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND NEW FINISH APPLIED TO MATCH EXISTING.
REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON GYPSUM BOARD PAINT FINISH.
WHERE NEW CEILINGS ARE INSTALLED AND SPRINKLERS ARE EXISTING TO REMAIN, SPRINKLERS SHALL BE ADJUSTED TO NEW CEILING HEIGHTS, WHEN APPLICABLE.
A
TYPE GRAPHIC DESCRIPTION
B 2x2 ACOUSTICAL CEILING TILE (AP2)
GYPSUM BOARD CEILING. CEILING PAINT.
REFLECTED CEILING PLAN LEGEND
C 2x4 ACOUSTICAL WASHABLE GASKETED CEILING TILE (AP1)
2ND FLOOR ADDITION
SHADE INDICATES EXISTING AREA BEYOND PRIMARY SCOPE OF WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
4AE112
4AE112
TYP.
1
55 5
5
5
5
5
5
5
5
5
PT-9A
PT-9A
PT-7 PT-7
PT-1
PT-1
PT-1
PT-4
PT-4
PT-4
PT-9A
PT-9A
PT-7
PT-7
PT-7
PT-7
PT-7
PT-9A PT-9A
PT-1
PT-1
PT-1
PT-1
PT-4
PT-9A
PT-4
PT-9A
PT-9APT-9A
PT-9A
PT-1
PT-3
PT-3
PT-4
PT-4
PT-7
PT-7
PT-7
PT-7
PT-7
PT-1
PT-9A
PT-7
PT-4
6
6
2AE111
TYP.
5
5
5
AE1122
AE1123
AE5019
1
CHASE
7' - 2"
8
8
88
8
8
8
8
9
8
PT-1
PT-1
PT-1
15AE804
2
3
3' - 0
"
2
3
PT-3PT-4
3' - 0"
10 1/
4"4'
- 2 1/
2"
10' - 8" 3' - 1 3/4"
EQEQ
3
3
3' - 0"
5' - 8
3/4"
1' - 0
"
4' - 2" 2' - 1" 2' - 2"
5' - 5
3/4"
9' - 3 3/4"
EQEQ 3' - 0"
PT-4
PT-3
10 3/4"
1"1'
- 6"
1' - 5"5/8" GYPSUM BOARD
3 5/8" METAL STUDS @ 16" O.C.
CEILING (AP-1) -SEE REFLECTED CEILING PLANS
EXISTING WINDOW
EXISTING STRUCTURE
8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE112
3RD FLOOR CEILING PLANGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1" = 100'-0"KEYPLAN ISOMETRIC
SCALE: 1/8" = 1'-0"AE1121 3RD FLOOR CEILING PLAN
SCALE: 1/4" = 1'-0"AE1122 ENLARGED CEILING PLAN - ABOVE NURSE STATION 1
SCALE: 1/4" = 1'-0"AE1123 ENLARGED CEILING PLAN - ABOVE NURSE STATION 2
SCALE: 1 1/2" = 1'-0"AE1124 CEILING BULKHEAD AT CORRIDOR
Revisions: Date:
EXTERIOR ELEVATION LEGENDDESCRIPTIONCODE
FACE BRICK TO MATCH EXISTING, SEE SPECIFICATIONS. PROVIDE MR-1.
BR-1
QUIONS TO MATCH EXISTINGQU-1
CAST STONE BANDING TO MATCH EXISTINGCS-1
EXISTING ARCHITECTURAL METAL PANEL, USED TO PATCH/REPAIR AS REQUIRED, OR FOR BID DEDUCT SEE GI102.
MP-1
CONTROL JOINT LOCATION, VERIFY IN FIELD EXACT LOCATIONCJ
2" BELLOWS TYPE EXPANSION JOINT LOCATIONEJ
3AE301
EXIS
TING
ADDI
TION
EXISTING ADDITION
BR-1
BR-1
QU-1, TYP.
CS-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
± 4' - 6"± 18' - 8"± 18' - 8"± 4' - 6"CJ CJ CJEJ
TOOTH IN NEW BRICK WHERE WINDOWS WERE REMOVED
1AE301
2AE301
EXIS
TING
ADDI
TION
BR-1
BR-1
QU-1, TYP.
CS-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
STRUCTURAL BRACE
LOCATIONS, REFER TO
DETAIL 5/AE322
± 16' - 0" ± 4' - 8" ± 20' - 0"
CJ CJCJ
EJ
2AD301
2ND FLOOR ADDITION
SHADE INDICATES EXISTING AREA BEYOND PRIMARY SCOPE OF WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM SHEATHING
FLUID APPLIED AIR BARRIER
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
1' - 3"
TOP OF COPING143' - 5 1/2"
2' - 0"
PROFILED STONE BAND. MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" MIN. TAPERED RIGID INSULATION SLOPED 1/4" PER FOOT TO SCUPPER(R-30 MIN.)
PROTECTION BOARD
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS
2' - 8
"
TOP OF BRICK142' - 8 1/2"
PROFILED STONE COPING. MATCH EXISTING
METAL FLASHING
FULLY ADHERED MEMBRANE ROOFING SYSTEM
TERMINATION BAR AND SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT WOOD BLOCKING
EXTEND ROOFING MEMBRANE UP AND OVER WOOD BLOCKING
8 3/4"
(2) LAYERS 5/8" TYPE X GYPSUM BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE COPING SECURED TO WOOD BLOCKING
7 3/4"
SCUPPER
CONTINUOUS SEALANT
METAL COUNTER FLASHING
METAL SCUPPER SLEEVE WITH DRIP EDGE
ALUMINUM DOWNSPOUT
1' - 4"6 3/4"
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM SHEATHING
FLUID APPLIED AIR BARRIER
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
1' - 3"
TOP OF COPING143' - 5 1/2"
2' - 0"
PROFILED STONE BAND. MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" MIN. TAPERED RIGID INSULATION SLOPED 1/4" PER FOOT TO SCUPPER(R-30 MIN.)
PROTECTION BOARD
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS
2' - 8
"
TOP OF BRICK142' - 8 1/2"
PROFILED STONE COPING. MATCH EXISTING
METAL FLASHING
FULLY ADHERED MEMBRANE ROOFING SYSTEM
TERMINATION BAR AND SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT WOOD BLOCKING
EXTEND ROOFING MEMBRANE UP AND OVER WOOD BLOCKING
8 3/4"
(2) LAYERS 5/8" TYPE X GYPSUM BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE COPING SECURED TO WOOD BLOCKING
7 3/4"
CONTINUOUS SEALANT
METAL COUNTER FLASHING
METAL OVERFLOW SCUPPER SLEEVE WITH DRIP EDGE, INSTALL 2" ABOVE SCUPPER LINE FLOW
1' - 4"
6 3/4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE201
BUILDING ELEVATIONSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE2011 BUILDING ELEVATION - NORTH
SCALE: 1/8" = 1'-0"AE2012 BUILDING ELEVATION - WEST
SCALE: 1" = 100'-0"KEYPLAN ISOMETRIC
NOT TO SCALEAE2013 PERSPECTIVE MASSING - NEW
SCALE: 1 1/2" = 1'-0"AE2014 WALL SECTION DETAIL - PARAPET SCUPPER AND DOWNSPOUT
SCALE: 1 1/2" = 1'-0"AE2015 WALL SECTION DETAIL - PARAPET OVERFLOW SCUPPER
Revisions: Date:
AE3111
EXISTING 1ST FLOOR TO REMAIN
EXISTING RENOVATED 2ND FLOOR
EXISTING RENOVATED 3RD FLOOR
AE31123
AE3011
AE301AE321
10 AE3111
TYP.
AE3115
NEW METAL COPING
NEW STONE COPING
BUILDINGADDITION
EXISTINGBUILDING
EXPANSION JOINT
EXPANSION JOINT
EXISTINGBUILDING
BUILDINGADDITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE301
BUILDING SECTIONSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE3011 EAST/WEST BUILDING SECTION 1
SCALE: 1/8" = 1'-0"AE3013 NORTH/SOUTH BUILDING SECTION
SCALE: 1/8" = 1'-0"AE3012 EAST/WEST BUILDING SECTION 2
NOT TO SCALEAE3014 BUILDING CONNECTION ISOMETRIC
NOT TO SCALEAE3015 BUILDING CONNECTION ISOMETRIC 2
Revisions: Date:
AE3211
AE3212
EXISTING 1ST FLOOR
TOP OF COPING143' - 4 3/4"
AE3218
4" FRAME DEPTH ARCHITECTURAL GRADE EXTERIOR WINDOW W/ INSULATED GLAZING, SEE ELEVATIONS, TYP.
AE3211
TYP.
AE3212
TYP.
AE2014
AE2015
ALIGN FACE OF NEW BRICK WITH FACE OF EXISTING BELOW
SIM.
SIM.
EXISTING 1ST FLOOR
EXISTING 1ST FLOOR
NEW COMPRESSIVE INSULATIONEXISTING STRUCTURAL ELEMENTS
NEW METAL DECK, RE: STRUCTURAL
AE3217
AE3214
TOP OF EXISTING COPING+/- 143' - 4 3/4"
EXISTING STRUCTURE
NEW STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS
CONTINUOUS COMPRESSIBLE INSULATION AT EJ PERIMETER
2 HR. EXPANSION JOINT COVER - BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
CEILING, SEE CEILING PLANS FOR TYPES AND LOCATIONS
2 HR. CEILING EXPANSION JOINT COVER
WALL EXPANSION JOINT COVER BEYOND
AE3213
PROVIDE NEW JOINT COVER IN EXISTING SLABS
NEW STEEL SUPPORT ANGLE ACROSS NEW OPENING AND SET INTO BRICK EITHER SIDE, REFER TO STRUCTURAL
EXISTING BRICK VENEER
10' -
9 1/2"
APPR
OXIM
ATE
EXISTING 1ST FLOOR
EXISTING 1ST FLOOR
AE3217
TYP.
NEW SHAFT
EXISTING SHAFT
NEW SHAFT
AE3216
AE3215
AE3221
EXISTING STRUCTURE
NEW STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS
CONTINUOUS COMPRESSIBLE INSULATION AT EJ PERIMETER
2 HR. EXPANSION JOINT COVER - BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
CONTINUOUS COMPRESSIBLE INSULATION AT EJ PERIMETER
2 HR.EXPANSION JOINT COVER -BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
DOOR TO ROOF, SEE DOOR SCHEDULE
EXISTING CONSTRUCTION
1:12 RAMP TO LEVEL OUT NEW CONSTRUCTION IN 1C AND EXISTING BUILDING 1
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE311
WALL SECTIONSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 3/4" = 1'-0"AE3111 EXTERIOR WALL SECTION
SCALE: 3/4" = 1'-0"AE3112 INTERIOR WALL SECTION
SCALE: 3/4" = 1'-0"AE3113 INTERIOR SHAFT WALL SECTION
SCALE: 3/4" = 1'-0"AE3115 WALL SECTION @ ELEVATOR LOBBY
Revisions: Date:
EXISTING 1ST FLOOR
8" H. PROFILED STONE WINDOW SILL VENEER - MATCH EXISTING SIZE AND COURSING(1) LAYER 5/8" EXTERIOR SHEATHING
FLUID APPLIED AIR BARRIER
FOIL FACED BATT INSULATION R-13 MIN.RIGID CONT. INSULATION R-13 MIN.
EXISTING CONCRETE SLAB, RE: STRUCT
EXISTING FACE BRICK AND STONE BANDING
2X FRT BLOCKING AS REQUIRED
PROVIDE WEEP VENTS @ 24" O.C.
(2) LAYERS 5/8" TYPE 'X' GWB ON 6" MTL STUDS @ 16"O.C.
MORTAR NET
THRU WALL FLASHING EXTENDED 6" ABOVE MORTAR NET
HEMMED DRIP EDGE
1' - 3"
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
3/4" SOLID SURFACE SILL1/4"
CONT. SEALANT
2X WOOD FRT BLOCKING
CONT. SEALANT
ALUM. FLASHING W/ HEMMED EDGE OVER SILL
FULLY ADHERED SEAM TAPE OVER BLOCKING, ONTO SHEATHING, AND UP 6" MIN. BOTH SIDES OF JAMB
4" FRAME DEPTH ARCHITECTURAL GRADE EXTERIOR WINDOW W/ INSULATED GLAZING, SEE ELEVATIONS, TYP.
1/2" 2' - 0"
5 1/2"
SEE GI101 FOR WALL RATING AND UL REFERENCE
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM SHEATHING
FLUID APPLIED AIR BARRIER
FOIL FACED BATT INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
(2) LAYERS 5/8" TYPE 'X' GWB ON 6" MTL STUDS @ 16"O.C.
1' - 4 1/4"
9" 7 1/4"2' - 0"
STRUCTURAL FLOOR, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-3/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL D703
SEE CEILING PLAN FOR CEILING TYPES AND LOCATIONS
PROVIDE WEEP VENTS @ 24" O.C.MORTAR NET
THRU WALL FLASHING EXTENDED 6" ABOVE MORTAR NET
HEMMED DRIP EDGE
4" FRAME DEPTH ARCHITECTURAL GRADE EXTERIOR WINDOW W/ INSULATED GLAZING, SEE ELEVATIONS, TYP.
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-1 1/2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL X701
5 1/2"1' - 3"
FACE BRICK VENEER TO MATCH EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM SHEATHING
FLUID APPLIED AIR BARRIERFOIL FACED BATT INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
1' - 3"
TOP OF COPING143' - 5 1/2"
2' - 0"
PROFILED STONE BAND. MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" ROOF INSULATION (R-30 MIN.)
TAPERED ROOF INSULATION DIRECTING DRAINAGE TO SCUPPER
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS
2' - 8
"
TOP OF BRICK142' - 8 1/2"
PROFILED STONE COPING. MATCH EXISTING
MEMBRANE FLASHING
FULLY ADHERED MEMBRANE ROOFING SYSTEM
COVERBOARD
TERMINATION BAR AND SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT WOOD BLOCKING
EXTEND ROOFING MEMBRANE UP AND OVER WOOD BLOCKING
8 3/4"
(2) LAYERS 5/8" TYPE X GYPSUM BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE COPING SECURED TO WOOD BLOCKING
7 3/4"
3"
EXISTING STRUCTURE
NEW STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS
CONTINUOUS COMPRESSIBLE INSULATION AT EJ PERIMETER
EXPANSION JOINT COVER - BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
STRUCTURAL FLOOR, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-3/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL D703
REMOVE A PORTION OF THE EXISTINGSTRUCTURAL SLAB TO INSTALL EXPANSION JOINT COVER
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-1 1/2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL X701
EXISTING PROFILED STONE BANDING
3-5/8" METAL STUDS @ 24" O.C.
TERMINATION BAR AND SEALANT
ROOFING MEMBRANE, EXTEND UP PARAPET
6" ROOF INSULATION (R-30 MIN.)
2" BILLOWS EXPANSION JOINT COVER - BILCO BRBS-1-2-CSE
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-1 1/2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL X701
5/8" GLASS MAT FACED GYPSUM SHEATHING
V.I.F
.1'
- 1 1/
2"
EXISTING STONE CAP
COVERBOARD
MEMBRANE FLASHING
4"
COMPRESSIBLE INSULATION
TERMINATION BAR AND SEALANT
EXISTING STONE BANDING AND GUTTER CONSTRUCTION TO REMAIN
2" BILLOWS EXPANSION JOINT COVER - BILCO BRBS-1-2-CSE
FULLY ADHERED MEMBRANE ROOFING SYSTEM
1' - 8
1/4"
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-1 1/2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL X701
COVERBOARDMEMBRANE FLASHING
3-5/8" METAL STUDS @ 16" O.C.
5/8" GLASS MAT FACED GYPSUM SHEATHING
6" ROOF INSULATION
DEFLECTION TRACK
STEEL BENT PLATE
4"
TERMINATION BAR AND SEALANT
2" BILLOWS EXPANSION JOINT COVER - BILCO BRBS-1-2-CSE
FULLY ADHERED MEMBRANE ROOFING SYSTEM
STONE BANDING TO BE CUT AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION
COUNTER FLASHING W/ HEMMED EDGE OVER TERMINATION BAR
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701
6" ROOF INSULATION
COVERBOARD
MEMBRANE FLASHING
3-5/8" METAL STUDS @ 24" O.C.
5/8" GLASS MAT FACED GYPSUM SHEATHING
LAP SEALANT
LAP SEALANT
4"
EXISTING 1ST FLOOREXISTING
1ST FLOOR
EXISTING STRUCTURE
PROVIDE NEW EXPANSION JOINT COVER - BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
REMOVE A PORTION OF THE EXISTINGCONSTRUCTION TO INSTALL EXPANSION JOINT COVER
EXISTING STRUCTURE
NEW FLOORING
NEW COMPRESSIBLE INSULATION
PROVIDE ALL REQUIRED INFILL CONSTRUCTION TO PROVIDE A SUITABLE CONDITION FOR JOINT COVER
CONTINUOUS COMPRESSIBLE INSULATION AT EJ PERIMETER
EXPANSION JOINT COVER -BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
EXISTING STRUCTURAL SLAB
EXISTING 1ST FLOOR
CONCRETE LANDING
NEW STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS
EXPANSION JOINT COVER -BASIS OF DESIGN AL-200HD BY CONSTRUCTION SPECIALTIES
STRUCTURAL FLOOR, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-3/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL D703
REMOVE A PORTION OF THEEXISTING STRUCTURAL SLABTO INSTALL EXPANSION JOINT COVER.
STRUCTURAL BEAM, SEESTRUCTURAL DRAWINGS. PROVIDE2 HR RATING, +/- 1 1/2" THICK SPRAYAPPLIED FIRE RESISTIVE MATERIAL.BASIS OF DESIGN UL X701.
3"
CONTINUOUS COMPRESSIBLEINSULATION AT EJ PERIMETER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE321
WALL SECTION DETAILSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1 1/2" = 1'-0"AE3211 WALL SECTION DETAIL - 2ND FLOOR EXTERIOR
SCALE: 1 1/2" = 1'-0"AE3212 WALL SECTION DETAIL - 3RD FLOOR EXTERIOR
SCALE: 1 1/2" = 1'-0"AE3218 WALL SECTION DETAIL - PARAPET
SCALE: 1 1/2" = 1'-0"AE3214 WALL SECTION DETAIL - 3RD FLOOR INTERIOR
SCALE: 1 1/2" = 1'-0"AE3217 WALL SECTION DETAIL - INTERIOR PARAPET 1
SCALE: 1 1/2" = 1'-0"AE32110 WALL SECTION DETAIL - ROOF TRANSITION
SCALE: 1 1/2" = 1'-0"AE3219 WALL SECTION DETAIL - INTERIOR PARAPET 2
SCALE: 1 1/2" = 1'-0"AE3213 WALL SECTION DETAIL - 2ND FLOOR INTERIOR
SCALE: 1 1/2" = 1'-0"AE3215 WALL SECTION DETAIL - 2ND FLOOR TRANSITION
SCALE: 1 1/2" = 1'-0"AE3216 WALL SECTION DETAIL - 3RD FLOOR TRANSITION
Revisions: Date:
NEW 5/8" GWB
EXISTING 6" METAL STUDS
EXISTING 5/8" GYP. SHEATHING
EXISTING WEATHER BARRIER
EXISTING 3/4" GALV. SUBGIRT
EXISTING 1 1/2" METAL PANEL
STRUCTURAL DECK, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL BASIS OF DESIGN UL P701
5/8" GYPSUM DECKBOARD
RIGID INSULATION
COVERBOARD
ROCKWOOLBATT INSULATION
4" BILLOWS EXPANSION JOINT COVER - BILCO BRBS
LAP SEALANT
TPO ROOF MEMBRANELAP SEALANT
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/- 1 1 /2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL, BASIS OF DESIGN UL X701
STRUCTURAL BEAM, SEE STRUCTURAL DRAWINGS. PROVIDE 2 HR RATING, +/- 1 1 /2" THICKNESS OF SPRAY APPLIED FIRE RESISTIVE MATERIAL, BASIS OF DESIGN UL X701
METAL FLASHING
4"
11"
4"
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD FRAMINGAT 16" O.C.
FRAME CONCEALED BY FEATHERED JOINT COMPOUND
EXPANSION JOINT ASSEMBLY
5 1/8" 5 1/8"
VERIFY WITH MANUFACTURER'S INSTRUCTIONS1' - 2 1/4"
COORDINATE FRAMING REQUIREMENTS WITH MANUFACTURES INSTRUCTIONS
WALL FRAMING BEYOND
BASIS OF DESIGN: CONSTRUCTION SPECIALTIES FLUSH TWINLINE MODEL SGW
EXPANSION JOINT ASSEMBLY
4" ACOUSTICAL PANEL CEILING
ANCHOR TIES TO STRUCTURAL DECK ABOVE
BASIS OF DESIGN: CONSTRUCTION SPECIALTIES FLUSH THINLINE MODEL FCF
20 GA. METAL STUDS WRAPPED WITH 20 GA. TRACK ON BOTH SIDES -CONTINUOUS FROM FLOOR TO DECK
CORNER BEAD AT ALLOUTSIDE CORNERS (TYPICAL)
STRUCTURAL BRACING BEHIND GWB ENCLOSURE, REFER TO STRUCTURAL
EXTERIOR WINDOW, SEE ELEVATIONS
PROVIDE METAL STUD AND GWB ENCLOSURE FOR STRUCTURAL BRACING AS INDICATED, INTENT IS TO LEAVE AS OPEN AS POSSIBLE FOR WINDOW.
PROVIDE HEADER AS HIGH AS POSSIBLE
184 m
m (7
1/2"
)
156 m
m (6
1/4"
)
2,500
mm
(100
")MI
N 44
5 mm
(17 3
/4")
DEPTH = 205 mm (8 1/4")345 mm (13 3/4")
H
A
E
F
C
GI
B
KJ
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE322
BUILDING DETAILSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1 1/2" = 1'-0"AE3221 WALL SECTION DETAIL - ROOF TO LOBBY
SCALE: 3" = 1'-0"AE3222 2HR. RATED EXPANSION JOINT COVER - WALL
SCALE: 3" = 1'-0"AE3223 EXPANSION JOINT COVER - CEILING
SCALE: 3" = 1'-0"AE3224 TYPICAL CORNER FRAMING DETAIL
SCALE: 3/8" = 1'-0"AE3225 WINDOW AND BRACING COORDINATION DETAIL
SCALE: NTSAE3226 PATIENT LIFT TRACK LOCK SYSTEM DETAIL
SCALE: NTSAE3227 DOOR HEADER HOIST PASSTHROUGH
SCALE: NTSAE3228 PATIENT LIFT TRACK HOIST DETAIL
SCALE: NTSAE3229 PATIENT LIFT TRACK SLING DETAIL
Revisions: Date:
JJ
J
AE801
13
13' - 2 1/2"
11 1/2" 10' - 10 3/4" 1' - 4 1/4"
9 1/2"
6' - 5
3/4"
9' - 6
1/2"
3' - 0
"
4' - 9"
2' - 6
1/2"
3' - 2
"
AE801
6
AE801
7
AE8018
9
10
TYP. OF 9
TYP. OF 6
9' - 4
"1'
- 0"
6' - 6 3/4"
1' - 1
0"
AE801
10
TYP. OF (4)
O2, AIR
3AE311
AE801
2
1 AE801
SIM24
1AD301
3
SIM
1
SIM
3
SIM 4
MECHANICAL CHASE
MECHANICAL CHASE
TYP.
17' - 3 1/4" 3' - 5 1/2" 20' - 6" 1' - 3" 3' - 0 1/2"
2' - 0
"15
' - 6 1
/2"6'
- 4 3/
4"
5 3/4"
15' -
2"1'
- 0 3/
4"
AE801
21
22
23
24
AE803
58
6
7
1' - 6
"5'
- 4"
1' - 6
"5'
- 3"
EQEQ
CENTERLINE OF BED
TYP.
TYP.
5'-0" CLEAR MIN.+/- 8' - 9 1/2" +/- 5' - 8 3/4"
ALIGN WITH EXISTING
2AE104
SLOPE FLOOR TO DRAINS AS INDICATED, TYP. SEE SECTION CUT SLOPE FLOOR
FROM DOOR OPENING INTO ROOM. SEE SECTION CUT
SLOPE FLOOR TO DRAINS AS INDICATED, TYP. SEE SECTION CUT
9' - 1
3/4"
ADDITIONAL BLOCKING REQUIRED.
9' - 5
"
AE801
SIM23
2' - 8
"
HAND SANITIZER OUTSIDE OF ROOM NEAR DOOR, TYPICAL IN PAITENT ROOMS. COORDINATE EXACT LOCATION WITH VA.
AE801
33
34
AE801
12
11
3' - 11" 3' - 10 3/4"
7' - 8
"1'
- 8 3/
4"
1' - 0
"
AE801SIM
8
3' - 0"
O.C.
39" -
41"
O.C.39" - 41"
3' - 6" 1' - 0"
TO R
EFL E
CTIV
E3'
- 4" M
AX
7" - 9" O.C.
2' - 0"
1 1/2"
MIN
TO T
OP3'
- 0"
6" 3' - 0"
MAX
TO B
UTTO
N44
" - 48
" MAX
TA7TA2
TA3
TA1
TA5
TA4
TA9
TA6
MAX
TO O
UTLE
T44
" - 48
" MAX
TA8
MOUNTING HEIGHTS ARE TYPICAL AND APPLY TO FIXTURES INSTALLED IN NEW RESTROOMS. VERIFY MOUNTING HEIGHTS WITH VENDOR SPECIFIC MOUNTING HEIGHTS.
TYPICAL MOUNTING HEIGHTS AND INTERIOR ELEVATIONS ARE FOR USE IN COORDINATION OF FIXTURES. NOTE NOT EVERY FIXTURES MAY BE REPRESENTED IN INTERIOR ELEVATIONS. COORDINATE PROJECT REQUIREMENTS WITH THE FLOOR PLAN AND ENLARGED FLOOR PLANS.
COORDINATE INSTALLATION OF EQUIPMENT WITH PLUMBING FIXTURES AND PLUMBING DRAWINGS. REFER TO PLUMBING PLANS FOR INFORMATION ON PLUMBING ACCESSORIES AND FIXTURES.
PROVIDE EACH SINK WITHIN SCOPE WITH A PAPER TOWEL DISPENSER AND SOAP DISPENSER.
PROVIDE UNDER LAVATORY GUARD AT WALL MOUNTED HAND LAVATORIES IN SCOPE.
PROVIDE IN WALL BLOCKING FOR WALL MOUNTED TOILET ACCESSORIES.
PROVIDE IN WALL BLOCKING FOR WALL MOUNTED SWING GRAB BAR FOR SECURE INSTALLATION.
TYPICAL TOILET ACCESSORY MOUNTING HEIGHTSSCALE: 1/4" = 1'-0"
TOILET ACCESSORY GENERAL NOTESA
B
C
D
E
F
G
15" M
IN
TOP
OF B
AR3'
- 0"
TA12
1' - 6"
2' - 9
"
1' - 6"
DASH LINE INDICATES NURSE STATION WALL BELOW WORKING COUNTER OR TRANSACTION COUNTER
DIMENSION CROSS REFERENCES TO RADIUS / DIAMETER OF NURSE STATION WALL / PEDESTAL BELOW
FILE CABINET BELOW - SEE INTERIOR ELEVATIONS
SINGLE RAIL J-TRACK PATIENT LIFT SYSTEM - MIN. 770 LB CAPACITY, SEE DETAIL 10/AE503.
TRAVERSE RAIL PATIENT LIFT SYSTEM - MIN. 770 LB CAPACITY, SEE DETAIL 5/AE503.
ENLARGED PLANS NOTES1
2
3
4
5
#
FOR LEGEND REFERENCE OF FURNITURE / EQUIPMENT TAGS, SEE SHEETS QH101 AND / OR QH102
AE801
5
O2, AIR
6' - 7
1/4"
14' -
2"7'
- 4 3/
4"
11' - 1"
5' - 0" 4' - 11 3/8"
FACE
OF
FINI
SH5'
- 0" C
LEAR
1' - 6
"5'
- 4"
1' - 6
"
CENTERLINE OF BED
1' - 6"
2' - 6"
EQEQ
5
5
4
EQ.E
.Q.
BLANK
BLANK
SLIDE
POWER
POWER
POWER
E POWER
E POWER
E POWER
CODE BLUE
MED AIR
LIGHTING CONTROLS
OXYGENOXYGENVACUUM
VITAL SIGNS MONITOR
DATA
E POWER
3' - 3"
1' - 0 1
/2"
1' - 1"
2' - 1"
15
BENT PLANT OUTSIDE CORNER
3 5/8" METAL STUDSAT 16" O.C.
PORCELAINTILE, T-1
PORCELAINTILE, T-1
B.4
FULL HEIGHT & WIDTH INSULATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE501
ENLARGED PLANS AND TOILETACCESSORY SCHEDULEGUIDON DESIGN INC.
1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/4" = 1'-0"AE5014 ENLARGED FAMILY SPACE
SCALE: 1/4" = 1'-0"AE5011 ENLARGED STAFF LOUNGE AND TOILET
SCALE: 1/4" = 1'-0"AE5013 ENLARGED RT SHARED OFFICE
SCALE: 1/4" = 1'-0"AE5015 2ND FLOOR ENLARGED PLAN - MED TEAM
SCALE: 1/4" = 1'-0"AE5012 ENLARGED TYPICAL PATIENT ROOM
SCALE: 1/4" = 1'-0"AE5016 ENLARGED PUBLIC TLT 329
SCALE: 1/4" = 1'-0"AE5017 ENLARGED STAFF TLT / SHWR C215A
TOILET ACCESSORY SCHEDULEMARK DESCRIPTION MANUFACTURER MODEL
RESPONSIBLEPARTY COMMENTS
TA1 42" HORIZONTAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 42 CFCITA2 36" HORIZONTAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 36 CFCITA3 18" VERTICAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 18 CFCITA4 TOILET PAPER DISPENSER - SURFACE
MOUNTEDBOBRICK WASHROOM EQUIPMENT, INC B-4288
TA5 SANITARY NAPKIN DISPOSAL TOUGH GUY 2NXW1 OFCITA6 TOILET SEAT COVER DISPENSER BOBRICK WASHROOM EQUIPMENT, INC B-221 OFCI Mounted at 2'-0" O.C. AFF. Refer to ADA front end sheet
for dimensional constraints.TA7 SOAP DISPENSER BOBRICK WASHROOM EQUIPMENT, INC 818615TA8 PAPER TOWEL DISPENSER BOBRICK WASHROOM EQUIPMENT, INC B-4262TA9 18"x36" MIRROR BOBRICK WASHROOM EQUIPMENT, INC B-2908TA10 GARMENT HOOK BOBRICK WASHROOM EQUIPMENT, INC B-6727 CFCITA12 SWING UP GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-4998 CFCI
SCALE: 1/4" = 1'-0"AE5018 ENLARGED SOILED AND STORAGE
SCALE: 1/2" = 1'-0"AE50111 2ND FLOOR RAMP PLAN
SCALE: 1/4" = 1'-0"AE5019 TYPICAL ENLARGED PATIENT ROOM CEILING PLAN
SCALE: 1 1/2" = 1'-0"AE50110 TYPICAL HEADWALL ELEVATION
SCALE: 1 1/2" = 1'-0"AE50112 PLAN DETAIL - TLT 369
Revisions: Date:
10' - 6" 1' - 5 3/4"
3' - 1
1 1/2"
4' - 1
0"
11' - 11" 5' - 9"
2' - 0 1/2"
6' - 1
1 1/4"
8' - 1
3/4" AE801
25
3' - 4
3/4"
5' - 6
3/4"
1' - 3
3/4"
2' - 10 1/2"
3' - 6"
AE80132
31
1' - 3 3/4" 5' - 10 1/4"
3' - 1
0 3/4"
4' - 1
0 1/4"
8' - 2 1/2"
3AE311
AE80129
1AD301
AE801
SIM
29O.H.
AE801
30
9' - 6 1/4" 6' - 8 1/4" 7' - 7 3/4"
10' -
8"11
' - 6 3
/4"
CHASE
AE801
17
16
AE80120
19
AE80114
AE801
15
15AE804
7"
1
2
3
3
1
3
1
1
2' - 1
"2'
- 1 1/
2"
CENTER OF RADIUS
AE802
2
2' - 0
1/4"
2' - 1
1 1/2"
6' - 3 1/4"
CENTER OF RADIUS
4' - 2" 4' - 0 1/4"
13' -
1 1/2"
7' - 3
1/2"
5' - 8 1/4"
6 3/4"
3' - 1"
TYP.
+/- 1'
- 1 3
/4"
AE802
3
AE802
1
+/- 3
' - 11
3/4" 8"
TYP.
6' - 2
1/4"
18
6' - 8 1/4"
3' - 0
"3'
- 0"
2' - 8
3/4"
AE80420
AE8026
AE802
3
1
2' - 9" 13' - 9 1/2" 3' - 3 1/2"
7
3' - 7
3/4"
1' - 8"
AE803
4
PROVIDE FILTER WITH ICE AND WATER MACHINE AS NOTED.
7' - 10 3/4" 2' - 7
1/2"
12' -
11 1/
2"
3' - 7
3/4"
3' - 4
"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
3
Office ofConstructionand FacilitiesManagement
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDA/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE502
ENLARGED PLANSGUIDON DESIGN INC.1221 N PENNSYLVANIA STREETINDIANAPOLIS, IN 46202(317)-800-6388
CMTA CONSULTING ENGINEERS10411 MEETING STREETPROSPECT, KY 40059(502)-326-3085
VA WICHITA - MED/SURG BEDSFOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020
BID DOCUMENTS
SCALE: 1/4" = 1'-0"AE5022 ENLARGED BARIATRIC PATIENT ROOM
SCALE: 1/4" = 1'-0"AE5023 ENLARGED PATIENT ROOM
SCALE: 1/4" = 1'-0"AE5024 ENLARGED STAFF TLT
SCALE: 1/4" = 1'-0"AE5025 ENLARGED PHYSICAL THERAPY
SCALE: 3/8" = 1'-0"AE5026 ENLARGED NURSE STATION 1
SCALE: 3/8" = 1'-0"AE5027 ENLARGED NURSE STATION 2
Revisions: Date: