RMG_324_20_GB_2011_02

15
Zero-pressure gas regulator RMG 324 324.20 Serving the Gas Industry Worldwide OPERATING AND MAINTENANCE INSTRUCTIONS/ SPARE PARTS Version 03/2011

description

http://www.rmg.com/uploads/myth_download/RMG_324_20_GB_2011_02.pdf

Transcript of RMG_324_20_GB_2011_02

Page 1: RMG_324_20_GB_2011_02

Zero-pressure gas regulator RMG 324 324.20

Serving the Gas Industry

Worldwide

OPERATING AND MAINTENANCE INSTRUCTIONS/SPARE PARTS Version 03/2011

Page 2: RMG_324_20_GB_2011_02

Contents Page

1. General information 3

1.1 Safety information 3

2. Specific maintenance instructions 4

2.1 Valve rod 4

2.2 Valve disc 4

2.3 Diaphragm 4

2.4 Tightening torques 4

2.5 Lubricants 4

3. Specific operating instructions 5

3.1 Fitting position 5

3.2 Vent line connection 5

3.3 Dirt traps (gas filters) 5

3.4 Setting the setpoint 5

3.5 Switching from internal to external measuring impulse connection (retrofit) 5

3.6 Switching from external to internal measuring impulse connection (retrofit) 5

4. Spare parts

4.1.1 Spare parts drawing for main valve DN 65, DN 80, DN 100 6

4.1.2 Spare parts list for main valve DN 65, DN 80, DN 100 7

4.2.1 Spare parts drawing for main valve DN 80 – type: part no. 10031423 8

4.2.2 Spare parts list for main valve DN 80 – type: part no. 10031423 9

4.3.1 Spare parts drawing of regulating assembly RE 2 for DN 65, DN 80, DN 100 10

4.3.2 Spare parts list of regulating assembly RE 2 for DN 65, DN 80, DN 100 11

4.4.1 Spare parts drawing of regulating assembly for DN 80 – type: part no. 10031423 12

4.4.2 Spare parts list of regulating assembly for DN 80 – type: part no. 10031423 13

5. Parts for maintenance purposes 14

324.20 p.02

Page 3: RMG_324_20_GB_2011_02

324.20 p.3

Danger of damage to property and /or the environment

Important additional information

Eye catcher used for:

Danger to life and limb

Note

Caution!!

Danger!!

1. General information

All persons involved with the assembly, operation and / or maintenance of gas pressure regulators must read and

understand all of the following documents:

– Technical product information (brochure RMG 324.00) – this RMG document contains the technical data and

dimensions of the equipment and a description of its design and mode of operation.

– General operating manual for gas pressure regulators and safety devices – this RMG document contains

information on assembly and operation as well as general information on troubleshooting.

– Operating and maintenance instructions / spare parts (brochure RMG 324.20) – this RMG document contains

more detailed information on assembly and operation of the gas pressure regulator.

There are national laws and regulations for all sorts of jobs on gas equipment, from planning to maintenance. Be sure

to comply. (In Germany, for instance, DVGW work sheets G 600, G 459/II, G 491 and G 495.)

Inspection and maintenance intervals depend mostly on operating conditions and the nature and properties of the gas.

There are no general rules or recommendations for intervals. For Germany, we recommend to consider maintenance

intervals as stated in DVGW work sheet G 495 in a first instance. However, in the mid-term, intervals must be

adapted to the requirements of each specific equipment.

During maintenance, components must be cleaned and then checked thoroughly. This is necessary even if there

have not been any unusual observations during operation and / or functional testing. Checks must focus, in particular,

on diaphragms and seals and all movable parts and their respective bearings. Any and all defective parts must be

replaced with new ones. The same applies to O rings removed during disassembly.

Do not use any spare / wear parts and/or oils & lubricants not specifically recommended in the RMG operating and

maintenance instructions for spare parts. In the event spare / wear parts and / or lubricants & oils other than those

specifically recommended are used, RMG shall not be held liable for any defects and/or consecutive damages

attributable to such use of illegal parts, lubricants, oils etc.

Item numbers mentioned in the specific operating and maintenance instructions correspond with the numbers in the

spare parts lists and drawings.

Some parts in the lists and drawings are marked with a letter “W”. We recommend to always have a reserve of those

parts in stock for maintenance purposes.

Those spare parts are put together in another separate list at the end of the spare parts list.

1.1 Safety information

In this manual, safety information is highlighted by means of the following signal words and eye catchers:

Page 4: RMG_324_20_GB_2011_02

324.20 p.04

2. Specific maintenance instructions

2.1 Valve stem (78/178)

In order to secure the diaphragm (as applicable: 58 or 58* / 158 or 158*) against unintentional movements when loosening

and / or tightening the nuts (54, 65 / 154, 165 resp.), be sure to secure the valve stem accordingly. The valve stem

(78/178) can be gripped with a wrench for that purpose.

2.4 Tightening torques MA

Screws & bolts – item no. 10 110 60/160 72/172

Tightening torques in Nm 20 15 20 8

Components Lubricants RMG part no.

All O rings and locking rings (51/151) Silicone grease 27081

All fastening screws and screwed pipe connections Assembly paste 27091

2.5 Lubricants

2.2 Valve discs (as applicable: 66, 77 / 166, 177)

With valve disc (77/177) closed, adjust valve disc (66/166) by turning hex collar nut (65/165) and hex nut (79) or special nut

(179) in such a way that both valve discs (66, 77/66, 177) sit equally well in their respective valve seats.

2.3 Diaphragm (as applicable: 58 or 58*, 158 or 158*)

Set the valve stem (78/178) with the valve discs (66, 77/166, 177) to a 100 % aperture. Then tighten the hex collar nuts

(65/165) so that the diaphragm (as applicable: 58 or 58* / 158 or 158*) will not move unintentionally.

Should it be necessary to replace diaphragm (58/158) and/or sealing ring (59/159), be sure to replace BOTH by installing

a new diaphragm (58*/158*) with integrated sealing ring. Pay good attention to correct fitting position of diaphragm (58*/158*)

inside diaphragm housing UT (74/174). With valve discs closed (66, 77/166, 177), be sure to install diaphragm (58*/158*) in

such a way that its bulge protrudes from diaphragm housing UT (74/174) and above the contact line with diaphragm housing

OT (53/153). See the sectional drawing – items 4.3.1 and 4.4.1.

Danger!! Do not carry out maintenance unless the system is safely depressurised.

Page 5: RMG_324_20_GB_2011_02

324.20 p.05

3. Specific operating instructions

RMG retrofit kit 12133693

Denomination Part no.

Threaded pin (setscrew) 101195

Screwed connection 31950

Union nut 30804

Cutting ring 30904

How to retrofit – proceed as follows:

– Unscrew the plug (12/112).

– Visually check the stepped bore: Any dirt? Obstructions? Remove and clean as required.

– Screw down the threaded pin (13/113) – all the way to the stop.

– Install the screwed connection (14, 15, 16 / 114, 115, 116). Make sure the elastomer seals are not damaged.

– Installation of the pipes of the measuring line (Ø =12 mm). Install the measuring line as described

in RMG’s general operating manual for gas pressure regulators and safety devices.

3.1 Fitting position

RMG 324 is a zero-pressure gas regulator. Be sure to fit this equipment in a horizontal position

with the spring dome DOWN. See sectional drawings 4.1.1 and 4.2.1.

3.2 Vent line connection

Never plug up the vent line connection.

Be sure to connect a vent line here (thread G 3/8), whenever there is a danger that failure of the

regulator (e.g. measuring diaphragm is damaged) releases gas to the environment.

3.3 Dirt traps (gas filters)

The user must equip the system with devices that protect the gas pressure regulator against contamination.

3.4 Setting the setpoint

To adjust the reference: turn the setpoint adjuster (67/167) clockwise (SW 13) to increase the setpoint.

Turn it ccw to decrease the setpoint.

3.5 Switching from internal to external measuring impulse connection (retrofit)

The RMG 324 comes with a standard internal measuring impulse connection. It is possible, of course, to retrofit for

an external connection if necessary for technical reasons. You will need the following RMG retrofit kit:

3.6 Switching from external to internal measuring impulse connection (retrofit)

Proceed as described for internal -> external retrofit but in reverse order (see 3.5). Make sure all retrofit parts are in good

condition. Replace with better ones, if and where necessary.

If your RMG 324 gas pressure regulator came with an external measuring impulse connection, you will need a plug (12/112)

for retrofit (RMG part no. 100851).

Note

Caution!!

Danger!!

Page 6: RMG_324_20_GB_2011_02

324.20 p.06

4.1.1 Spare parts drawing for main valve RMG 324 – DN 65, DN 80, DN 100 (Drawing shows required fitting position – spring dome DOWN)

MA Be sure to comply with tightening torques in table on page 4.

W Parts should be held in stock for maintenance purposes.

B

B

1

W2

W2

W3

4 (glued)

B – BVersion with internal pd –

measuring impulse connection

B – BVersion with external pd –

measuring impulse connection

MA

15, 16 14 13

10

11

12 10

11

MA

Page 7: RMG_324_20_GB_2011_02

Item Part no. no. Denomination Number W Materials DN 65 DN 80 DN 100

324.20 p.07

4.1.2 Spare parts list for main valve RMG 324 – DN 65, DN 80, DN 100

1 Main valve body 1 GLM 10031282 10030741 10031223

2 O ring 3 W KG 20461 20246 20518

3 O ring 1 W KG 21177 21177 21177

4 Measuring tube 1 NSt 10031286 10030788 10031227

10 Hex nut 4 St 5559 5559 5559

11 Washer 4 St 14153 14153 14153

12 Sealing cap 1 St 100851 100851 100851

Items 13 to 16 of RMG retrofit kit 1 St/NSt 12133693 12133693 12133693

13 Threaded pin (setscrew) 1 NSt 101195 101195 101195

14 Screwed connection 1 St 31950 31950 31950

15 Union nut 1 St 30804 30804 30804

16 Cutting ring 1 St 30904 30904 30904

W Parts should be held in stock for maintenance purposes.

German abbreviations stand for the following materials:

St ... steel LM ... light metal / alloy GMs ... cast brass

NSt ... stainless steel Ms ... brass GZn ... cast zinc

FSt ... spring steel GS ... cast steel AlBz ... aluminium bronze

NFSt ... stainless spring steel GGG ... spheroidal graphite cast iron K ... synthetic materials

Bz ... bronze GBz ... cast bronze KG ... gummous synthetic materials

Cu ... copper GLM ... cast light metal SSt ... foamed materials

Page 8: RMG_324_20_GB_2011_02

324.20 p.08

4.2.1 Spare parts drawing for main valve RMG 324 – DN 80 – type: part no. 10031423 (Find number on type plate attached to main valve body) (Drawing shows required fitting position – spring dome DOWN)

104 (glued)B

B

101

W 105

W 102

W 102

W 103

B – BVersion with internal

measuring impulse connection

112

111

110

110

111

B – BVersion with external

measuring impulse connection

MA Be sure to comply with tightening torques in table on page 4.

W Parts should be held in stock for maintenance purposes.

MA

113 114 115, 116

MA

Page 9: RMG_324_20_GB_2011_02

Item Part no. no. Denomination Number W Materials DN 80

324.20 p.09

4.2.2 Spare parts list for main valve RMG 324-DN 80 – type: part no. 10031423

101 Main valve body 1 GLM 10030741

102 O ring 3 W KG 20246

103 O ring 1 W KG 21177

104 Measuring tube 1 NSt 10031516

105 Sliding contact bearing 1 W K 101059

110 Hex nut 4 St 5559

111 Washer 4 St 14153

112 Sealing cap 1 St 100851

Items 113 to 116 of RMG retrofit kit 1 St/NSt 12133693

113 Threaded pin (setscrew) 1 NSt 101195

114 Screwed connection 1 St 31950

115 Union nut 1 St 30804

116 Cutting ring 1 St 30904

Page 10: RMG_324_20_GB_2011_02

SW 7

X

This side: valve seat

This side: control spring

Diaphragm housing – body

Diaphragm housing – cap

Diaphragm

324.20 p.10

4.3.1 Regulating assembly RE 2 for DN 65, DN 80, DN 100

MA Be sure to comply with tightening torques in table on page 4.

W Parts should be held in stock for maintenance purposes.

View “X”

66

65

W 64

63

62

(glued) 61

60

W 64

W 59

W 58

57

56

W 55

54

53

W 52

51

50

79

78

77

76 W

75

74

60

72

71

70

69

68

67

MA

MA

SW 13

Page 11: RMG_324_20_GB_2011_02

Item Part no. no. Denomination Number W Materials DN 65 DN 80 DN 100

324.20 p.11

4.3.2 Spare parts list of regulating assembly RE 2 for DN 65, DN 80, DN 100

50 Cap 1 K 26402 26402 26402

51 Sealing ring 1 FSt 19116 19116 19116

52 O ring 1 W KG 20588 20588 20588

53 Diaphragm cap 1 St 10031375 10031375 10031375

54 Hex nut 1 St 13199 13199 13199

55 O ring 1 W KG 18417 18417 18417

56 Spring plate 1 LM 10030750 10030750 10030750

57 Diaphragm disc 2 St 10030749 10030749 10030749

58 Diaphragm 1 W KG 10007115 10007115 10007115

59 Sealing ring 1 W KG 10031387 10031387 10031387

58 * Diaphragm 1 W KG 10031414 10031414 10031414

60 Hex screw 36 St 10065 10065 10065

61 Locking screw 4 St 101409 101409 101409

62 Locknut 1 Ms 101333 101333 101333

63 Valve rod guide 1 K 10031476 10031508 10031493

64 Sliding contact bearing 2 W K 101332 101349 101349

65 Hex collar nut 2 St 13184 13184 13184

66 Valve disc 1 K 10031474 10031512 10031494

67 Setpoint adjuster 1 Ms 10031234 10031234 10031234

from Serial No. 1101xxxxx: Index B

68 Spring plate 1 LM 10031513 10031513 10031513

69 Pressure spring 1 FSt 10031422 10031422 10031422

70 Sealing ring 1 St 19195 19195 19195

from Serial No. 1101xxxxx

71 Threaded adapter 1 K 101201 101201 101201

72 Hex nut 32 St 5559 5559 5559

74 Diaphragm housing 1 St 10030742 10030742 10030742

75 Valve seat 1 LM 10031379 10031373 10031381

76 O ring 1 W KG 21177 21177 21177

77 Valve disc 1 K 10031279 10031275 10031284

78 Valve rod 1 NSt 10031239 10031510 10031229

79 Hex nut 1 NSt 100852 100852 100852

Page 12: RMG_324_20_GB_2011_02

324.20 p.12

4.4.1 Regulating assembly for DN 80 – type: part no. 10031423

MA Be sure to comply with tightening torques in table on page 4.

W Parts should be held in stock for maintenance purposes.

MA

179

178

177

W 176

175

174

173

172

171

170

169

168

167

166

165

163

162

161 (glued)

164

160

159 W

158 W

157

156

155 W

154

153

152 W

151

150

MA

158 * W

Page 13: RMG_324_20_GB_2011_02

Item Part no. no. Denomination Number W Materials DN 80

324.20 p.13

4.4.2 Spare parts list of regulating assembly – type: part no. 10031423

150 Cap 1 K 101061

151 Sealing ring 1 FSt 19116

152 O ring 1 W KG 20588

153 Diaphragm housing UP 1 St 10030743

154 Hex nut 1 St 13199

155 O ring 1 W KG 18417

156 Spring plate 1 LM 10030750

157 Diaphragm disc 2 St 10030749

158 Diaphragm 1 W KG 10007115

159 Sealing ring 1 W KG 10031387

158 * Diaphragm 1 W KG 10031414

160 Hex screw 4 St 10011

161 Locking screw 4 St 12046

162 Locknut 1 Ms 24686

163 Flow cone 1 K 10031277

164 Pipe 4 St 10030796

165 Hex collar nut 2 St 13184

166 Valve disc 1 K 10031276

167 Setpoint adjuster 1 Ms 10031234

from Serial No. 1101xxxxx: Index B

168 Spring plate 1 LM 10030797

169 Pressure spring 1 FSt 10031422

170 Sealing ring 1 St 19195

from Serial No. 1101xxxxx

171 Threaded adapter 1 K 101201

172 Hex nut 32 St 5559

173 Hex screw 32 St 10065

174 Diaphragm housing 1 St 10030742

175 Valve seat 1 LM 10030790

176 O ring 1 W KG 21177

177 Valve disc 1 K 10031275

178 Valve rod 1 NSt 10031278

Page 14: RMG_324_20_GB_2011_02

Item Part no. no. Denomination Number W Materials DN 65 DN 80 DN 100

324.20 p.14

5. Parts for maintenance purposes

2 O ring 1 W KG 20461 20246 20518

3 O ring 3 W KG 21177 21177 21177

52 O ring 1 W KG 20588 20588 20588

55 O ring 1 W KG 18417 18417 18417

58 Diaphragm 1 W KG 10007115 10007115 10007115

59 Sealing ring 1 W KG 10031387 10031387 10031387

58 * Diaphragm 1 W KG 10031414 10031414 10031414

64 Sliding contact bearing 2 W K 101332 101349 101349

76 O ring 1 W KG 21177 21177 21177

Type: part no. 10031423

102 O ring 1 W KG 20246

103 O ring 3 W KG 21177

105 Sliding contact bearing 1 W K 101059

152 O ring 1 W KG 20588

155 O ring 1 W KG 18417

158 Diaphragm 1 W KG 10007115

159 Sealing ring 1 W KG 10031387

158 * Diaphragm 1 W KG 10031414

176 O ring 1 W KG 21177

Page 15: RMG_324_20_GB_2011_02

For More Information

To learn more about RMG´s advanced gas

solutions, contact your RMG

account manager or visit

www.rmg.com

GERMANY

Honeywell Process Solutions

RMG Regel + Messtechnik GmbH

Osterholzstrasse 45

34123 Kassel, Germany

Tel: +49 (0)561 5007-0

Fax: +49 (0)561 5007-107

Honeywell Process Solutions

RMG Messtechnik GmbH

Otto-Hahn-Strasse 5

35510 Butzbach, Germany

Tel: +49 (0)6033 897-0

Fax: +49 (0)6033 897-130

Honeywell Process Solutions

RMG Gaselan Regel + Messtechnik GmbH

Julius-Pintsch-Ring 3

15517 Fürstenwalde, Germany

Tel: +49 (0)3361 356-60

Fax: +49 (0)3361 356-836

Honeywell Process Solutions

WÄGA Wärme-Gastechnik GmbH

Osterholzstrasse 45

34123 Kassel, Germany

Tel: +49 (0)561 5007-0

Fax: +49 (0)561 5007-207

POLAND

Honeywell Process Solutions

Gazomet Sp. z o.o.

ul. Sarnowska 2

63-900 Rawicz, Poland

Tel: +48 (0)65 5462401

Fax: +48 (0)65 5462408

ENGLAND

Honeywell Process Solutions

Bryan Donkin RMG Gas Controls Ltd.

Enterprise Drive, Holmewood

Chesterfield S42 5UZ, England

Tel: +44 (0)1246 501-501

Fax: +44 (0)1246 501-500

CANADA

Honeywell Process Solutions

Bryan Donkin RMG Canada Ltd.

50 Clarke Street South, Woodstock

Ontario N4S 0A8, Canada

Tel: +1 (0)519 5398531

Fax: +1 (0)519 5373339

USA

Honeywell Process Solutions

Mercury Instruments LLC

3940 Virginia Avenue

Cincinnati, Ohio 45227, USA

Tel: +1 (0)513 272-1111

Fax: +1 (0)513 272-0211

TURKEY

Honeywell Process Solutions

RMG GAZ KONT. SIS. ITH. IHR. LTD. STI.

Birlik Sanayi Sitesi, 6.

Cd. 62. Sokak No: 7-8-9-10

TR - Sasmaz / Ankara, Turkey

Tel: +90 (0)312 27810-80

Fax: +90 (0)312 27828-23

RMG 324.20

2011-03

© 2011 Honeywell International Inc.