Risk Mitigation through Protection - Solar Dynamix Mitigation through Protection Agenda Damages to...
Transcript of Risk Mitigation through Protection - Solar Dynamix Mitigation through Protection Agenda Damages to...
© 2015 DEHN + SÖHNE / protected by ISO 16016
Risk Mitigation
through Protection
1
© 2015 DEHN + SÖHNE / protected by ISO 16016
Risk Mitigation through Protection
Agenda
Damages to PV Systems
Standards and Norms
Lightning Protection Concepts
Questions & Answers
Video: Isolated Lightning Protection System
2
© 2015 DEHN + SÖHNE / protected by ISO 16016
Reason for Lightning Damage
about 20-24 million lightning strikes per year in SA
A comprehensive approach to Lightning Protection 3
* source: BLIDS, Siemens AG, evaluation from 2000 - 2010
electrical conductive systems
© 2015 DEHN + SÖHNE / protected by ISO 16016
Reason for Lightning Damage
Direct/Nearby lightning strikes to building
A comprehensive approach to Lightning Protection 4
20 kV
IT systemPower supply
Rst
380 kV
110 kV
110 kV
230 V
20 kV
1
1b
1a
1 Direct lightning strike:
Induced voltages in loops
Voltage drop at the conventional earthing impedance Rst
1a
1b
© 2015 DEHN + SÖHNE / protected by ISO 16016
Reason for Lightning Damage
Direct/Nearby lightning strikes to power supply system
A comprehensive approach to Lightning Protection 5
20 kV
IT systemPower supply
380 kV
110 kV
110 kV
230 V
20 kV
2c
2a
Rst
2 Remote lightning strike:
2c Fields of the lightning channel
2aLightning strike in a medium-voltage overhead line
2b Travelling surge waves in overhead line due to cloud to-cloud lightning
© 2015 DEHN + SÖHNE / protected by ISO 16016
LPLCurrent
amplitude (kA)
I 200
II 150
III - IV 100
Reason for Lightning Damage
Galvanic coupling – Lighting impulse voltage
A comprehensive approach to Lightning Protection 6
Rst = 1 Ω
MEB
ûE = î · Rst
Example: ûE = 100 kA · 1 = 100 kV
ûE = impulse voltage
î = impulse current
RSt= conventional earthing resistance
1 Ω
100 kV
100 kA
MEB: main earthing busbar Ref.: IEC 62305-1
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
PV Modules Damage
Combiner Box Damage
Inverter Damage
Communication System Damage
Sensitive Equipment Damage (Trackers, Security Systems)
Damage Statistics
7
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
PV Modules Damage
source: Solarzentrum Oberland GmbH
Arcing/Short-circuiting of PV Modules due to lightning
8
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
PV Modules Damage
Broken glasses, Burned/Melted DC Cables and Combiner Box
Defective bypass diodes
9
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
Combiner Box Damage
source: R. Schüngel, Munich
Melted Combiner Boxes and DC Cables
due to Short-Circuit currents
Breakdown of sensitive and or monitoring
components inside Combiner Box
10
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
Inverter Damage
Internal component failure inside an Inverter (Central & String)
11
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
Communication System Damage
Holes in the Cable insulation
Data cables causing failure of Switches, PLC’s etc…
12
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
Damage Statistics – Comparison (Frequency of Occurence)
Causes of damage (2003-2013)
Evaluation Mannheimer Versicherung
Causes of damage (2005-2014)
Evaluation Bayerischer Versicherungsverband
source: Bayerischer Versicherungsverband 2014source: Mannheimer Versicherung 2014
South Africa has on average 10 times more lightning density (strikes/km2)
13
© 2015 DEHN + SÖHNE / protected by ISO 16016
Damages to PV Systems
Damage Statistics – Damages Costs
source: Bayerischer Versicherungsverband 2014
Costs of Damages (2005-2014)
Evaluation Bayerischer Versicherungsverband
14
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards & Norms
SANS 10313: 2012
SANS (IEC) 62305: 2010-12
EN 62305: 2009-10 (VDE 0185-305: 2012)
15
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
SANS 10313:2012 & SANS (IEC) 62305:2010-12
16
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
EN 62305: 2009-10 (VDE 0185-305: 2012)
17
© 2015 DEHN + SÖHNE / protected by ISO 16016 A comprehensive approach to Lightning ProtectionA comprehensive approach to Lightning Protection 18
IEC 62305:2010-2012, Part 2
Risk Assessment
In order to evaluate whether or not lightning protection is needed, a RISK
ASSESMENT in accordance with the procedures in IEC 62305 Part 2 shall be
made. Protection against lightning is needed if the Calculated Risk is higher than
the Tolerable Risk (RX > RT)
A comprehensive approach to Lightning Protection 18
Type of Loss RT(y)
Loss of Human Life 10e-5
Loss of Service to the Public 10e-3
Loss of Cultural Heritage 10e-3
Loss of Economic Value
Note:
10e-5 = 1 in 100 000 chance of a
fatal injury over the course of 1
year (Maximum tolerable risk)
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
Reasons why a LPS is required by Owners/Insurers
19
DETAIL DESCRIPTION
Investment (Capital) > R Millions/Billions
Life time of the plant and equipment > 20 years
Return on Investment (Business Model) Linked to kWh output
Downtime due to damaged components > Time (hrs/days)
Insurance Access payable with every claim > R 500 k
Insurance premium hikes due to claims TBD
Breakdown of equipment due to inherent effects > R xxx
Degradation of equipment and components > R xxx
Lightning and surge protection measures are essential!
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Reduction of the risk below the value of the tolerable risk RT
A comprehensive approach to Lightning ProtectionA comprehensive approach to Lightning Protection 20A comprehensive approach to Lightning Protection 20
RA RV
RB
risk
measures to
reduce the risk
tolerable risk RT
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Reduction of the risk below the value of the tolerable risk RT
A comprehensive approach to Lightning ProtectionA comprehensive approach to Lightning Protection 21A comprehensive approach to Lightning Protection 21
RA RV
RB
risk
measures to
reduce the risk
tolerable risk RT
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Reduction of the risk below the value of the tolerable risk RT
A comprehensive approach to Lightning ProtectionA comprehensive approach to Lightning Protection 22A comprehensive approach to Lightning Protection 22
RA RV
RB
risk
measures to
reduce the risk
tolerable risk RT
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Reduction of the risk below the value of the tolerable risk RT
A comprehensive approach to Lightning ProtectionA comprehensive approach to Lightning Protection 23A comprehensive approach to Lightning Protection 23
RA RV
RZ
risk
measures to
reduce the risk
tolerable risk RT
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Risk of damage (RX)
A comprehensive approach to Lightning Protection 24
NX
Frequency of
lightning
strikes
PX
Probability of
damage
(Structure)
LX
Possible
Loss
RX = NX ∙ PX ∙ LX
© 2015 DEHN + SÖHNE / protected by ISO 16016
Frequency of lightning strikes (NX)
Lightning ground flash density (NG)
A comprehensive approach to Lightning Protection 25
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
Frequency of the risk of a Lightning Strike in South Africa
26
ITEM DETAIL
Output (MWp) 75
Modules > 600k
Area (km2) 3
Lightning Density (strikes/km2) 5.8
Total Direct Lightning (year) 17.4
Rain Season (months) 5 – 6
Total Strikes in Rain Season (p/month) 3 – 3.5
Total Cost of the Plant R 2 Bil
Total Loss as a result of Lightning (year)
without Protection
R 20
Mil
Lightning and surge protection measures are essential!
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 2
Risk Analyses
The selection of the most suitable protection measures shall be made by the
authority having jurisdiction to the type and the amount of each kind of damage.
Once the Risk is defined the appropriate LPL is determined.
Also it is important to note that a LPS mitigates risk but does not eliminate it.
A comprehensive approach to Lightning Protection 27
© 2015 DEHN + SÖHNE / protected by ISO 16016
External Lightning Protection
Air-termination Systems (ATS)
Isolated LPS: Separation Distance
Down-conductor Systems (DCS)
Earth-termination System (ETS)
Photovoltaic – Causes
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
DIN EN 62305-3 suppl. 1 (VDE 0185-305-3 suppl. 1):2012-10
(translation)
The required class of LPS (I-IV) is determined by means of a risk analysis
according to DIN EN 62305-2 (VDE 0185-305-2). The class of LPS can
also be defined in consultation with the planner, owner and/or user.
Regulatory requirements frequently call for lightning protection
measures for this type of structure to prevent fire and/or to protect
persons.
If possible, a lightning protection system should be preferred which is
not directly connected to the photovoltaic power supply system and
where adequate separation distances are kept.
29
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 1
General Principles
Lightning protection
Lightning protection means protection measures against the harmful
effects of lightning strikes to structures/buildings.
An external lightning protection system consists of:
Air-termination system
Down conductor
Earth-termination system
Earth-termination system
An earth-termination system includes all measures required for
connecting an electrical part to earth and is an integral part in low-
voltage and high-voltage systems as well as for the lightning protection
system.
26.09.13 / 8494_E_1
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
IEC 62305:2010-2012, Part 1
A lightning protection system consists of an external and internallightning protection system.
Functions of an external lightning protection system:
Interception of direct lightning strikes by means of an air-terminationsystem
Conducting the lightning current to earth by means of a downconductor
Distribution of the lightning current in the earth by means of anearth-termination system
Functions of an internal lightning protection system:
Prevention of dangerous sparking in the structure by establishingequipotential bonding or keeping a separation distance between thecomponents of the lightning protection system and other conductiveelements in the structure.
31
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 3
5.2 Air-termination System (ATS)
5.2.2 Positioning
Air-termination components installed on a structure shall be located at corners,
exposed points and edges (especially on the upper level of any facades) in
accordance with one or more of the following methods.
Acceptable methods to be used in determining the position of the air-
termination system include:
the protection angle method;
the rolling sphere method;
the mesh method.
A comprehensive approach to Lightning Protection 110
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 3
Air-termination System (ATS)
A comprehensive approach to Lightning Protection 111
Class of
LPS
Protection method Down-
Conductors
distances
(m)
Rolling
sphere
r (m)
Protection angle
a (°)
Mesh
size
w (m)
I 20 5 x 5 10
II 30 10 x 10 10
III 45 15 x 15 15
IV 60 20 x 20 20
Note: The protection angle method has its limitations (height)
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
DIN EN 62305-3 suppl. 5 (VDE 0185-305-3 suppl. 5):2009-10
(translation)
5.2 External lightning protection
Based on the DIN EN 62305-3 (VDE 0185-305-3) lightning protection
standard, roof-mounted photovoltaic power supply systems should be
protected against direct lightning strikes by means of isolated air-
termination systems, as far as practicable.
NOTE If a photovoltaic power supply system is newly installed
on a structure, the existing electrical installation may have
to be adapted.
34
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 3
Annexure E
103
E.5.1.2 Isolated LPS
An isolated external LPS should be used when the flow of the lightning current
into bonded internal conductive parts may cause damage to the structure or its
contents.
NOTE 1: The use of an isolated LPS may be convenient where it is predicted that
changes in the structure may require modifications to the LPS.
An LPS that is connected to conductive structural elements and to the
equipotential bonding system only at ground level, is defined as isolated
according to 3.3.
An isolated LPS is achieved either by installing air-termination rods or masts
adjacent to the structure to be protected or by suspending overhead wires
between the masts in accordance with the separation distance of 6.3.
© 2015 DEHN + SÖHNE / protected by ISO 16016
Direct connection of roof-mounted structures
Partial lightning currents inside the structure
EB
EB
MEBServer
PC PC
PC PC
FDB: Floor Distribution Board; MEB: Main Equipotential Bonding; EB: Equipotential Bonding
FDB
FDB
104
PV Panel / Structure
© 2015 DEHN + SÖHNE / protected by ISO 16016
Protection of roof-mounted structures with isolated air-
termination system
EB
EB
MEBServer
FDB
PV Panel /
Structure
PC PC
PC PCFDB
FDB: Floor Distribution Board; MEB: Main Equipotential Bonding; EB: Equipotential Bonding
Lightning current
discharged from the
outside
106
© 2015 DEHN + SÖHNE / protected by ISO 16016
Separation distance for PV modules
18.02.13 / 4033_E_1Photovoltaic – External lightning protection
s
s
a
© 2015 DEHN + SÖHNE / protected by ISO 16016
Inductive coupling of lightning currents into PV
modules depending on the distance from the module
lightning
protection cable
variation of the
distance
impulse current
generator
150 kA 10/350 µs
PV module with
short-circuited
output terminals
measurement
of the induced
impulse current
0.5 m
20.02.13 / 4216_E_1Photovoltaic – Causes
© 2015 DEHN + SÖHNE / protected by ISO 16016
Inductive coupling of lightning currents into PV
modules depending on the distance from the module
20.02.13 / 4216_E_4
Ii[kA]
0.25 0.5 0.75 1.0 1.25 1.5 1.75
time [ms]
distance 0.5 m
distance 1 m
distance 2 m
-0.2
0.0
0.2
0.4
0.6
0.8
1.0
1.2
0
I10/350
[kA]
0.25 0.5 0.75 1.0 1.25 1.5 1.75
time [ms]
-10
0
10
20
30
40
50
60
0
induced impulse
currents in case of
different distances
primarily fed lightning
current
Photovoltaic – Causes
© 2015 DEHN + SÖHNE / protected by ISO 16016
IEC 62305:2010-2012, Part 3
Down-conductor system
94
5.3 Down-conductor systems
5.3.1 General
In order to reduce the probability of damage due to lightning current flowing in
the LPS, the down-conductors shall be arranged in such a way that from the
point of strike to earth:
a) several parallel current paths exist;
b) the length of the current paths is kept to a minimum;
c) equipotential bonding to conducting parts of the structure is
performed according to the requirements of 6.2.
NOTE 1 Lateral connection of down-conductors is considered to be good
practice. The geometry of the down-conductors and of the ring conductors
affects the separation distance (see 6.3).
© 2015 DEHN + SÖHNE / protected by ISO 16016
5.3 Down-conductor systems
5.3.1 General
NOTE 2 The installation of as many down-conductors as possible, at
equal spacing around the perimeter interconnected by ring conductors,
reduces the probability of dangerous sparking and facilitates the
protection of internal installations (see IEC 62305-4).
This condition is fulfilled in metal framework structures and in reinforced
concrete structures in which the interconnected steel is electrically
continuous.
Typical values of the preferred distance between down-conductors are
given in Table 4.
Standards and Norms
DIN EN 62305-3 suppl. 5 (VDE 0185-305-3 suppl. 5):2009-10
(translation)
42
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
IEC 62305:2010-2012, Part 3
21
5.4 Earth-termination system
5.4.1 General
When dealing with the dispersion of the lightning current (highfrequency behaviour) into the ground, whilst minimizing any potentiallydangerous overvoltages, the shape and dimensions of the earth-termination system are the important criteria.
In general, a low earthing resistance (if possible lower than 10 Ω whenmeasured at low frequency) is recommended. From the viewpoint oflightning protection, a single integrated structure earth-terminationsystem is preferable and is suitable for all purposesIn general, a low earthing resistance is recommended. Earth-terminationshall be bonded in accordance with the requirements of 6.2.
© 2015 DEHN + SÖHNE / protected by ISO 16016
Arrangements of earth electrodes
as per IEC 62305-3:2010
96
type A
Horizontal (radial) earth electrode per down conductor
type B
Ring earth electrode (at least 80% in soil) Foundation earth electrode (DIN 18014)
connector connector
min. 5 m
at least 0.5 m
at least 2.5 m
9 m
recommended
0.5 m
at least1 m
Vertical earth electrode (earth rod) per
down conductor
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
DIN EN 62305-4 suppl. 1 (VDE 0185-305-4 suppl. 1):2012-10
(translation)
4.4 Lightning current distribution in a ground-mounted PV system
Depending on the relevant class of LPS, the type of earth-termination system
and the soil resistivity, SPDs with a lightning current discharge capacity of a
some kA are sufficient for ground-mounted PV systems.
The sample calculations are based on a mesh size of 20 m x 20 m. In case of
larger mesh sizes, it is to be expected that higher partial lightning currents flow
via the d.c. SPDs.
45
© 2015 DEHN + SÖHNE / protected by ISO 16016
Internal Lightning Protection
Classification of Arresters
SCI Patented arresters for PV systems
Equipotential Bonding
Data Acquisition
Photovoltaic – Causes
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
DIN EN 62305-3 suppl. 5 (VDE 0185-305-3 suppl. 5):2009-10
(translation)
5.6 Selection of surge protective devices
5.6.2 Type 1 surge protective device, lightning current carrying capability
It is recommended to use Type 1 surge protective devices on the d.c.
side of photovoltaic power supply systems, if
an external lightning protection system is installed and
the required separation distance from elements of the
photovoltaic power supply system is not kept.
47
© 2015 DEHN + SÖHNE / protected by ISO 16016
Assumed lightning current distribution in the event of a
direct lightning strike
100%
50%
50%
230/400 V
6 mm2 Cu
31.07.13 / 4015_E_4Photovoltaic – Surge protection
SEB
M M
MEB
GJB
SEB: Service Entrance Box; MEB: Main Earthing Busbar; GJB: Generator Junction Box; M: Meter
type 1
combined arrester
© 2015 DEHN + SÖHNE / protected by ISO 16016
Maximum values of lightning parameters according to
LPL (lightning protection level)
Photovoltaic – Causes
Ref.: IEC 62305-1:2010, Table 3 (extract)
29.10.13 / 6006_E_1
First positive impulse Lightning protection level (LPL)
I II III-IV
Peak current I (kA) 200 150 100
Specific energy W/R (MJ/Ω) 10 5.6 2.5
Charge Q short (C) 100 75 50
Time parameters T1/T2 (µs/µs) 10/350
© 2015 DEHN + SÖHNE / protected by ISO 16016
Inductive coupling
05.08.13 / 1500_E_6
230/400 V SEB
M M
MEB
GJB
Photovoltaic – Causes
SEB: Service Entrance Box ; MEB: Main Earthing Busbar; GJB: Generator Junction Box; M: Meter
© 2015 DEHN + SÖHNE / protected by ISO 16016
wave form [µs] 10/350 8/20
imax [kA] 100 20
Comparison of test currents
Photovoltaic – Surge protection 30.07.13 / 916_E_3
i [kA]
1
0
20
40
50
60
80
100
t [ms]
20 400 600 800 1000
21
350
test impulse current for
lightning current
arresters
2test impulse
current for
surge arresters
200
Ref.: IEC 61643-11
© 2015 DEHN + SÖHNE / protected by ISO 16016
Video
Impact on the electrical installation
© 2015 DEHN + SÖHNE / protected by ISO 16016
Standards and Norms
DIN EN 62305-3 suppl. 5 (VDE 0185-305-3 suppl. 5):2009-10
(translation)
5.6 Selection of surge protective devices
5.6.1 General
Surge protective devices for the d.c. side must be chosen in such a way
that they enter a safe state even in case of a short-circuit without
presenting a risk of fire resulting from overload and arc formation.
The manufacturer of the surge protective devices provides evidence that
the switching device integrated in the surge protective device has the
switching capacity required for the conditions at the place of installation.
53
© 2015 DEHN + SÖHNE / protected by ISO 16016
Patented SCI principle
… suitable for PV applications (d.c.)
Combined disconnection and short-circuiting device with safe electrical
isolation in the protection module prevents fire damage resulting from d.c.
switching arcs (patented SCI principle).
11.12.13 / 8035_E_1
switching phases:
Original
state
1.Tripping of
the
disconnector
2.Active
arc
extinction
3.Safe
electrical
isolation
Three-step d.c. switching device
(patented SCI principle)
SCI SCI SCI SCI
Photovoltaic – Surge protection
© 2015 DEHN + SÖHNE / protected by ISO 16016
…enter a safe state even in case of a short-circuit without
presenting a risk of fire
with Short-Circuit Interruptwithout Short-Circuit Interrupt
Video “Disconnection with SCI“Video “Disconnection without SCI“
26
© 2015 DEHN + SÖHNE / protected by ISO 16016
Protection concept for system monitoring
NTBA modem
data
acquisition
unit
06.08.13 / 3532_E_5Photovoltaic – data acquisition
© 2015 DEHN + SÖHNE / protected by ISO 16016
Lightning Protection Concepts
PV Systems with NO external lightning protection
PV Systems with BONDED external lightning protection
PV Systems with ISOLATED lightning protection
57
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with NO external lightning protection system
30
Type 2
Type 2
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with NO external lightning protection system
29
Type 1+2
Type 1+2
Type 1+2
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with BONDED external lightning protection system
32
Type 1+2
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with BONDED external lightning protection system
`
31
Derated Type1+2
Type 1+2
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with ISOLATED external lightning protection system
SAPVIA - Risk Mitigation through Protection 34
Type 2
© 2015 DEHN + SÖHNE / protected by ISO 16016
LIGHTNING PROTECTION CONCEPTS
PV system with ISOLATED external lightning protection system
33
Type 2
Type 2
© 2015 DEHN + SÖHNE / protected by ISO 16016
DEHNconcept
Risk Assessments
Detailed Design of LPS & Earthing Systems
© 2015 DEHN + SÖHNE / protected by ISO 16016
PV system with
ISOLATED external LPS
65
© 2015 DEHN + SÖHNE / protected by ISO 16016
Questions?
SAPVIA - Risk Mitigation through Protection
ALEXIS. W. BARWISE
Managing Director (B. Eng)
DEHN AFRICA (Pty) Ltd.
Tel. +27 11 704 1487
www.dehn-africa.com
66