Ring Main Unit: 8DJH STCost efficient solution for secondary power distributionPresentation, Ver 1.0
Page 2 April 14 IC LMV MS S GIS
8DJH ST: Secondary distribution
Page 3 April 14 IC LMV MS S GIS
8DJH ST: Applications
RRR
Page 4 April 14 IC LMV MS S GIS
8DJH ST: Applications
Page 5 April 14 IC LMV MS S GIS
8DJH ST: SF6 gas for insulation
Vacuum for switching & SF6 for insulationNo toxic gases due to interruption in vacuum
Climate independent and maintenance free design
High dielectric strength thereby reducing volume of switchgear
Sealed for life
Safe and low-tolerance pressure co-ordination for pressure relief system
Page 6 April 14 IC LMV MS S GIS
8DJH ST: Technical details
Ratings up to 12kV, 630A, 21kA 3s STCInternal arc classification IAC A FLR 20kA 0.1s [21kA 1.0s available on request]Factory-assembled, type-tested, metal-enclosed switchgear according to IEC 62271-200 Blocks consisting up to 5 feeders in a single tank
Page 7 April 14 IC LMV MS S GIS
8DJH ST: Technical details
Technical features
Rated values up to 12kV, 21kA 3s
Rated frequency 50Hz
Busbar current up to 630A
Feeder current up to 630A
Busbars Single busbar
Rated power frequency withstand voltage 28kV 38kV
Rated lighting impulse withstand voltage 75kVp 95kVp
Rated making current 52.5kAp
Rated breaking current 21kA
Insulation Gas insulated
Switchgear vessel Hermetically sealed
Page 8 April 14 IC LMV MS S GIS
8DJH ST: Technical details
Classification according to IEC 62271-200
Partition class PM
Loss of service continuity category LSC 2
Accessibility to compartments Busbar compartment: Non-accessibleSwitching-device compartment: Non-accessibleCable compartment: Interlock-controlled
Degree of protection For switchgear enclosure [Indoor]: IP3XFor switchgear enclosure [Outdoor]: IP54For gas filled vessel: IP65
Internal arc classification IAC A FLR 20 kA, 0.1 sIAC A FLR 21 kA, 1.0 s
Page 9 April 14 IC LMV MS S GIS
8DJH ST: Technical details
One way typical [310mm]
Two way typical [620mm]
Three way typical [930mm]
Four way typical [1240mm]
Five way typical [1550mm]
R RK RRR RRRR RRRRR
L RR RRL RRRL LRRLL
K RL RLR LRRL LLLLL
S * LK
ME 1 $
ME 2 $
Legends: R [Ring main feeder] L [Circuit breaker feeder] K [Cable connection feeder]S [Bus coupler feeder] ME1 [Line metering feeder] ME2 [Bus metering feeder]
Extensibility options: on both side, on right hand side, on left hand sidePanel combination with metering will be on right side always. No further extensibility on right side possible with meteringBus coupler feeder will always have extensibility on both sidesWidth indicated above is for vessel
* - Width of Bus coupler feeder vessel is 620mm$ - Width of metering feeder vessel is 630mm
Page 10 April 14 IC LMV MS S GIS
8DJH ST: Technical details
Dimensions
Block width depending on number and type of panels
645mm, 955mm, 1265mm, 1575mm
Panel height 1620 mm
Operating height <1500mm
Panel depth Bottom explosion: 820 mm Top explosion: 918 mm
Page 11 April 14 IC LMV MS S GIS
8DJH ST: Vacuum circuit breaker
Technical details
Rated voltage 12kV
Rated current 630A
Basic insulation level 12kV / 28kV / 75kVp
Rated short time withstand current 21kA, 3s
Rated short circuit breaking / making current 21kA / 52.5kAp
Rated operating sequence O-3min-CO-3min-CO
Endurance class
Breaking [2,000 times mechanically without maintenance] M1 [IEC62271-100]
Breaking [2,000 times rated normal current without maintenance]
E2 [IEC62271-100]
Breaking [Low probability of restrikes] C1 [IEC62271-100]
Breaking [For cable systems] S1 [IEC62271-100]
Page 12 April 14 IC LMV MS S GIS
8DJH ST: Three position disconnector for CB
Technical details
Rated short time withstand current 21kA, 3s
Endurance class
Disconnecting [1,000 times mechanically] M0
Earthing [1,000 times mechanically]
Earthing [5 making operations through VCB] E2
Page 13 April 14 IC LMV MS S GIS
8DJH ST: Three position switch for Ring main feeder
Technical details
Rated voltage 12kV
Rated current 630A
Basic insulation level 12kV / 38kV / 95kVp
Rated short time withstand current 21kA, 3s
Rated short circuit making current 52.5kA
Rated breaking current 630A
Endurance class
Disconnecting [1,000 times mechanically] M0 [IEC62271-102]
Earthing [5 times rated short-circuit making current] E2 [IEC62271-102]
Load breaking [1,000 times mechanically] M1 [IEC 60265-1]
Load breaking [100 times rated breaking current5 times rated short-circuit making current]
E3 [IEC 60265-1]
Page 14 April 14 IC LMV MS S GIS
Standards
Switchgear IEC 62271-1IEC 62271-100
DevicesCircuit BreakersDisconnector & Earthing SwitchSwitch-disconnectorVoltage detection systems
IEC 62271-200IEC 62271-102IEC 62271-103IEC 61243-5
Degree of protection IEC 60529
Insulation IEC 60071
Instrument transformersCurrent transformerVoltage transformer
IEC 61869-2IEC 61869-3
Installation & commissioning IEC 61936-1
8DJH ST: Technical details
Page 15 April 14 IC LMV MS S GIS
8DJH ST: One way typical
Page 16 April 14 IC LMV MS S GIS
8DJH ST: Two way typical
Page 17 April 14 IC LMV MS S GIS
8DJH ST: Three way typical
Page 18 April 14 IC LMV MS S GIS
8DJH ST: Four way typical
Page 19 April 14 IC LMV MS S GIS
8DJH ST: Five way typical
Page 20 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Vessel]
Stainless steel vesselInsensitive to temperature and pressure variations
Stable dew-point behavior
Modern and safe laser welding technology
Maximum flexural and burst strength
Safe and low-tolerance pressure co-ordination for pressure relief system
Maintenance-free [leakage of 0.1% p.a.]
High quality non magnetic SS
Page 21 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Pressure detection systems]
ManometerClearly visible indication [Red/Green]
Refilling of gas possible
Optionally with signaling contact
Page 22 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Pressure detection systems]
Ready for service indication [with aux contacts]Temperature and pressure compensated gas density measurement (2)
Magnetic coupling (3) between measurement box and indication
Independent of site altitude & ambient temperature
Optionally with signaling contact
Indication:4 Not ready for service5 Ready for service
Page 23 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Cable connection]
Climate independent connection systemCable connections for bushings with outside cone
Insensitive to pollution and condensation
Switchgear or panel extension possible without gas work
Corrosion free and maintenance free connection
Page 24 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Extension]
High flexibility for creation of switchgear configurationsBusbar extension possible on all individual panels & panel blocks [optional]
Plug-in unit consisting of contact coupling & screened silicone coupling
Centering via guide bolts & stop angles
Corrosion free and maintenance free connection
Page 25 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Interlocks]
Switchgear interlocking with logical mechanical interlocksSwitching gate prevents direct operation from CLOSE to EARTH and
EARTH to CLOSE
Cable compartment can be removed only after feeder is eatthed and
operating lever removed
Active interlocks between circuit breaker and three position
disconnector
Closing and opening of circuit breaker not possible if operating lever is
inserted
Page 26 April 14 IC LMV MS S GIS
8DJH ST: Constructional features [Interlocks]
Switchgear interlocking with logical mechanical interlocksOptional
Three position disconnector can be operated only if cable cover is
closed
Closing & opening lock-out in case cable cover is removed for three
position disconnector
Padlocking in all three positions
Page 27 April 14 IC LMV MS S GIS
8DJH ST: Fault passage indicator
Short circuit / Earth fault indicatorIndication at the switchgear front
Factory assembled including sensor mounting
Manual / Automatic reset
Optical signals for a preselected pick-up values
Optionally remote electrical indication
Earth fault indicatorShort circuit indicator
Page 28 April 14 IC LMV MS S GIS
8DJH ST: Voltage detection systems
Safe to touchWith voltage indicator
Verification of safe isolation from supply phase by phase
Voltage indicator flashes in presence of high voltage
Indicator suitable for continuous operation
Measuring system and voltage indicator can be tested
Page 29 April 14 IC LMV MS S GIS
8DJH ST: SCADA compatibility
Ease of communicationMotorized VCB / LBS
Self powered numerical relay
Mini RTUs
Power pack
Control MCCBs
Pre wired auxiliary contacts
Page 30 April 14 IC LMV MS S GIS
8DJH ST: Safe and Reliable
Safe and ReliableDielectric test
Temperature rise test
Short time withstand current
Peak withstand current
Verification of IP code
Pressure withstand test for gas-filled compartment
Tightness test
Internal arc test
Alternating pressure test [10,000 cycles]
Climatic tests on components
Switching performance test
Mechanical endurance test
Disconnector switch switching test