RHEEM COMMERCIAL WATER HEATING TRAINING. TRAINING COURSE OBJECTIVES. Introduction to Rheem Commercial Booklet Range appreciation Familiarise key design / installation criteria Introduction to manifolding Introduction to sizing Value added service. Commercial Water Heating course contents. - PowerPoint PPT Presentation

Transcript of RHEEM COMMERCIAL WATER HEATING TRAINING

Page 1: RHEEM COMMERCIAL WATER HEATING TRAINING

RHEEM COMMERCIAL WATER HEATING TRAINING

Page 2: RHEEM COMMERCIAL WATER HEATING TRAINING

TRAINING COURSE OBJECTIVES

• Introduction to Rheem Commercial Booklet• Range appreciation• Familiarise key design / installation criteria• Introduction to manifolding• Introduction to sizing• Value added service

Page 3: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Water Heating course contents

• Chapter 1 - Range overview - Commercial Booklet• Chapter 2 - Heat Pump • Chapter 3 - Commercial Solar• Chapter 4 - Equaflow Manifolding • Chapter 5 - Commercial Continuous Flow• Chapter 6 - Commercial Storage Gas systems• Chapter 7 - Raypak Heating and Hot Water• Chapter 8 - Commercial Electric• Chapter 9 - Guardian Warm Water • Chapter 10 – Pump Sets• Chapter 11 - Sizing and Selecting• Chapter 12 - Commercial installation and design

Page 4: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 1

Range Overview&

Rheem Commercial Booklet

Page 5: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 2 - Commercial Heat Pump

Page 6: RHEEM COMMERCIAL WATER HEATING TRAINING

COMMERCIAL HEAT PUMP LAYOUTS

Page 7: RHEEM COMMERCIAL WATER HEATING TRAINING

COMMERCIAL HEAT PUMP LAYOUTS

Page 8: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 3 - Commercial Solar

Page 9: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar

• Terminology– Split / Pumped / Loline– Close Coupled / Thermosiphon / Hiline– Direct / Indirect (Premier Hiline)

Page 10: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Loline

Page 11: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Loline

• Pumped system– Collectors and tank are split– Fluid is pumped between collectors and tanks– Can be on same level or different levels

• Direct system– Consumed water passes through the collectors– Partial frost protection

• In series boost

Page 12: RHEEM COMMERCIAL WATER HEATING TRAINING
Page 13: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Loline

• 325L and 410L vitreous enamel storage tanks– Manifold tanks as required

• NPT200 collector– Painted aluminium selective surface– 7 riser tubes– Good performance in all regions

Page 14: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Loline• Frost– Limited frost protection– Frost sensor strategy– Electric or gas frost heater

• Secondary Solar Recirculation– Maximum solar energy use– reduces energy use

• BMS output– Run and fail status

Page 15: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Premier Hiline

Page 16: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Premier Hiline• Thermosiphon system– Collectors and tank are close coupled– Fluid rises through collectors naturally to tank– Tank is always above collectors

• Indirect system– Transfer fluid passes through the collectors and

transfers heat to tank via heat exchanger– Full frost protection

• In series or in- tank electric boost

Page 17: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial Solar Premier Hiline

• 300L stainless steel tank• Manifold systems as required• 8 systems per array, multiple arrays possible• S200 collector– Steel collector– Painted selective surface– Good performance in all regions

Page 18: RHEEM COMMERCIAL WATER HEATING TRAINING
Page 19: RHEEM COMMERCIAL WATER HEATING TRAINING

Flat Plate vs Evacuated TubeCollectors

Page 20: RHEEM COMMERCIAL WATER HEATING TRAINING

EQUA-FLOW MANIFOLDING

Chapter 4

Page 21: RHEEM COMMERCIAL WATER HEATING TRAINING

EQUA-FLOW BASICS

Page 22: RHEEM COMMERCIAL WATER HEATING TRAINING

EQUA-FLOW BASICS

In Line

• Header diameters for cold/hot to be equal• Branch diameters for cold/hot to be equal• Hydraulic water flow “In one side, out the opposite”• Balanced performance per unit. Full delivery capacity from system

Flow direction In

Flow direction

Out

Page 23: RHEEM COMMERCIAL WATER HEATING TRAINING

Back to Back

Flow direction In

Flow direction

Out

EQUA-FLOW BASICS

Page 24: RHEEM COMMERCIAL WATER HEATING TRAINING

1 1

0A

B

0+1+1=2

EQUA-FLOW BASICS

Page 25: RHEEM COMMERCIAL WATER HEATING TRAINING

11

A

B 1 1

PATH of LEAST RESISTANCE

Page 26: RHEEM COMMERCIAL WATER HEATING TRAINING

MORE EQUA-FLOW PRINCIPLES

21

2

1

A

B

0+2+1+1+2=6 1+2+1+2=6 1+2+2+1+0=6

Page 27: RHEEM COMMERCIAL WATER HEATING TRAINING

ANGLED MANIFOLD 3 + bend1

1 3 + bend

B

A

Page 28: RHEEM COMMERCIAL WATER HEATING TRAINING

BACK TO BACK MANIFOLD

0.75

H6:0.75+1+1 = 2.75

H4:0.75+1+1 = 2.75

H2:0.75+1+1 = 2.75

11

H1:0+1+1+0.75 = 2.75

H3:1+1+0.75= 2.75

H5:1+1+0.75 = 2.75

A

B

10.75 1

Page 29: RHEEM COMMERCIAL WATER HEATING TRAINING

EQUAFLOW PRINCIPLES IN PRACTICE

Page 30: RHEEM COMMERCIAL WATER HEATING TRAINING

When designing/ inspecting complicated manifolds consideration must be given to primary loops as well as hot and cold headers

COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE

Page 31: RHEEM COMMERCIAL WATER HEATING TRAINING

EQUAFLOW PRINCIPLES IN PRACTICE

Page 32: RHEEM COMMERCIAL WATER HEATING TRAINING

COMPLICATED EQUAFLOW PRINCIPLES IN PRACTICE

Page 33: RHEEM COMMERCIAL WATER HEATING TRAINING

BRANCHES• NEVER use non-return valves or pressure

limiting valves in the branch– These create imbalance in the branches

• Non-return and pressure reducing valves must be in a train on the cold water inlet

COLD WATER SUPPLY

TO WATER HEATER MANIFOLD

Page 34: RHEEM COMMERCIAL WATER HEATING TRAINING

BRANCHES• Last branch should be

a T piece, not an elbow, to maintain equal resistance in all branches

T PIECE

Page 35: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 5 - Commercial CFWH

Page 36: RHEEM COMMERCIAL WATER HEATING TRAINING

RHEEM INDOOR CFWH – FLUE SYSTEMSUSE MM AND FF ADAPTERS IF HORIZONTAL LENGTH OF HORIZONTAL TERMINATING FLUE EXCEEDS 2.7M

TRIM

RING

USE CONDENSATE DRAIN & TRAP IF VERTICAL SECTION OF HORIZONTAL TERMINATING FLUE EXCEEDS 2M

Page 37: RHEEM COMMERCIAL WATER HEATING TRAINING

Rheem Multipak, Tankpak, Commpak and Commpak PlusCommercial Continuous Flow

Hot Water Solutions

Page 38: RHEEM COMMERCIAL WATER HEATING TRAINING
Page 39: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 6 - Commercial Gas Storage

Page 40: RHEEM COMMERCIAL WATER HEATING TRAINING

RHEEM Commercial Gas Storage

• Work horse of the industry• 3 input sizes – 50, 110, 200MJ/hr• Indoor and outdoor models• Multi-fin flue technology• Flue damper• Hot Surface Ignition• Up to 82oC• Room sealed flue

Page 41: RHEEM COMMERCIAL WATER HEATING TRAINING

HD Gas Layout

Page 42: RHEEM COMMERCIAL WATER HEATING TRAINING

631275 Room Sealed Flue• Converts outdoor model to indoor room sealed• Ideal where no ventilation, contaminated air

supply or fluing to roof impractical• 3m and 3 x 90o bends• Re-use flue terminal• Kit P/No 299135

Page 43: RHEEM COMMERCIAL WATER HEATING TRAINING
Page 44: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 7 – Raypak Heating and Hot Water

Page 45: RHEEM COMMERCIAL WATER HEATING TRAINING

Raypak Layouts

Page 46: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 8 - Commercial Electric Storage

Page 47: RHEEM COMMERCIAL WATER HEATING TRAINING

RHEEM Commercial Electric Storage

• Work horse of the industry• 2 x 3 element models – 50 & 315L• 1 x 6 element model – 315L• Up to 36kW output• Indoor and outdoor installation• Heavy Duty enamel• Larger anode• Models up to 82oC

Page 48: RHEEM COMMERCIAL WATER HEATING TRAINING

HD Electric Layout

Page 49: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 9 - Rheem Guardian Warm Water

Page 50: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 10 - Pump Sets

Page 51: RHEEM COMMERCIAL WATER HEATING TRAINING

Deluxe Pump Sets

• Deluxe Models• UPS 20-60N and 32-80N pumps• Individual Auto, Off, Manual switches• Individual Run and Fail indicators• Timer control• Isolation and check valves included• BMS output

Page 52: RHEEM COMMERCIAL WATER HEATING TRAINING

Standard Pump Sets

• Standard Models• UPS 20-60N and 32-80N pumps• Single Auto, Off, Manual switch• Timer control• Isolation and check valves included

Page 53: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 11

• Sizing and selecting...

Page 54: RHEEM COMMERCIAL WATER HEATING TRAINING

Energy Consumption It takes 4.2kJ of heat energy to raise 1litre of water (or 1 kg)

of water 1 degreeE = L x 4.2 x dT

Example : To raise 500 litres by 32 degrees (from 10C to 42C)Energy consumption = 500 x 4.2 x 32 = 67,200kJ or 67.2MJ

Plant efficiency must also be considered. If the plant operates at 80% efficiency, then;Energy required = 67.2 / 0.8 = 84MJ

Page 55: RHEEM COMMERCIAL WATER HEATING TRAINING

Typical Hot Water Usage Assumptions

OfficesOffice peak period 60 minutes– Water per person 0.5 litres – Area per person 10m2

– Occupants

Gymnasium peak period 30 minutes– Water per person 25 litres

Page 56: RHEEM COMMERCIAL WATER HEATING TRAINING

Typical Hot Water Usage AssumptionsFood ServiceRestaurant Peak Period – 2 hours(temperature requirements) – Bistro per Meal 5.0 litres– Coffee Shop per Meal 3.5 litres– Auditorium per Meal 3.0 litres– Restaurant per Meal 5.5 litres– Takeaway Shop per Meal– Café per Meal 3.0 litres– Hotel Kitchen per Meal 6.0 litres

Page 57: RHEEM COMMERCIAL WATER HEATING TRAINING

Typical Hot Water Usage Assumptions

ApartmentsPeak period 60 minutes

– Bed-sitter 25 litres– 1 Bedroom 40 litres– 2 Bedroom 70 litres– 2 Bedroom w/en suite 75 litres– 3 Bedroom 80 litres– 3 Bedroom w/en suite 90 litres– 4 Bedroom 100 litres– Penthouse 150 litres

Page 58: RHEEM COMMERCIAL WATER HEATING TRAINING
Page 59: RHEEM COMMERCIAL WATER HEATING TRAINING

Typical Hot Water Usage Assumptions

MotelMotel peak period 60 minutes(Assume 2 people per room)– Shower 1 & 2 Star 20 litres /person– Shower 3 Star 25 litres /person– Shower 4 Star 30 litres /person– Shower 5 Star 45 litres /person– Shower Family/Spa 100 litres /person

Page 60: RHEEM COMMERCIAL WATER HEATING TRAINING

Sizing example...

• Motel• 100 rooms• 5 star accommodation• Central electric plant• Moderate climate• Refer to commercial booklet...

Page 61: RHEEM COMMERCIAL WATER HEATING TRAINING

Sizing example... Motel

• Showers = 50 x 2x 45 = 4,500L/1hr peak• Moderate climate = 50oC rise• Central electric plant:– 5 x 616315 with 6 x 6kW elements

Page 62: RHEEM COMMERCIAL WATER HEATING TRAINING

Hot Water Usage Assumptions

Nursing HomePeak period 180 minutes– Bedpan 2.5 litres / bed– Shower 25 litres / bed– Cleaning water 10 litres / bed– Water per meal 5.5 litres

Laundry peak 300 minutes– Laundry (1.2kg per bed) 10 litres / kg

Page 63: RHEEM COMMERCIAL WATER HEATING TRAINING

Selecting a water heating system

• Usage profiles...Have they changed?• Peak Period in Litres/hr (e.g. 1hr)• Redundancy• Daily Load in Litres (Solar)...• Water delivery Temperatures• Plant Location - Indoor or Outdoor• Flue location & termination (room sealed?)• Circulation Systems...considerations

Page 64: RHEEM COMMERCIAL WATER HEATING TRAINING

Sporting Facility Case StudyFootball Club - Tasmania

Page 65: RHEEM COMMERCIAL WATER HEATING TRAINING

Sizing example...

• Local football club• 15 shower outlets @ 6 litres per minute (hot)• 35 players inc umpires• Commercial heat pump system• Refer booklet...

Page 66: RHEEM COMMERCIAL WATER HEATING TRAINING

Sizing example...

• Players and Umpires = 35• Shower time, say 10 mins• Peak duration = 30mins• Showers = 35 x 6L/min x 10 = 2,100 litres• Plant selection:• 6 x 610430 storage tanks• 1 x 953022 heat pump• Recovery @10C ambient =244L/hr = 9hrs

Page 67: RHEEM COMMERCIAL WATER HEATING TRAINING

SELECTION & SIZING...

• Diversity...• The difference between the maximum possible load on

a water heating system if all outlets were in use at once and the “likely” load at any given time.

• Example... • In a multi story accommodation building, only a

predictable percentage of taps will be turned on at any given time, however it can be expected that all taps in a shower block of a sporting facility can be turned on at once and will require full heated water flow.

Page 68: RHEEM COMMERCIAL WATER HEATING TRAINING

SELECTION & SIZING

CFWH PLANT or STORAGE PLANT... What to consider?• Footprint availability e.g. solar• Storage volume?• Maintenance/removal• Flow rates• Gas and water pressure• Fluing• Energy/fuel types

Page 69: RHEEM COMMERCIAL WATER HEATING TRAINING

Chapter 12

• Commercial Installation and Design Requirements

Page 70: RHEEM COMMERCIAL WATER HEATING TRAINING

82oC Dead Leg Operation

Page 71: RHEEM COMMERCIAL WATER HEATING TRAINING

Primary Pump Requirements• Used for Raypak, Solar and Heat Pump• Non return valve is not required after primary pump.• Spindle must be horizontal• Pump is not weather proof – must be covered

Primary Pump

Isolation Valve

Note: Pump

shaft must be

horizontal

Page 72: RHEEM COMMERCIAL WATER HEATING TRAINING

NOT EQUA-FLOW

PUMP SPINDLE VERTICAL

Page 73: RHEEM COMMERCIAL WATER HEATING TRAINING

Clearances

Page 74: RHEEM COMMERCIAL WATER HEATING TRAINING

CASE STUDY #2Rheem Commercial Water Heating Systems

Rheem Solar preheated, gas storage with a warm water system.

Page 75: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial application – Large nursing home

Page 76: RHEEM COMMERCIAL WATER HEATING TRAINING

Including a commercial laundry

Page 77: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial kitchen

Page 78: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial sinks

Page 79: RHEEM COMMERCIAL WATER HEATING TRAINING

Electric boost on sink

Page 80: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial dishwashing machine

Page 81: RHEEM COMMERCIAL WATER HEATING TRAINING

Water must be at sanitizing temperature i.e. 77 degrees

Page 82: RHEEM COMMERCIAL WATER HEATING TRAINING

The solar arrayTo achieve the energy rating for the building, solar has been chosen.

Often solar is a preferred method to achieve the energy reduction on site.

Note - north facing collectors

Note - the fall protection

The panels are set in two arrays of 8 collectors

Page 83: RHEEM COMMERCIAL WATER HEATING TRAINING

16 Rheem solar panels – ‘primary source of heat’

Each square meter(approx) of panel requires approx. 60 litres of solar storage tank capacity!

Page 84: RHEEM COMMERCIAL WATER HEATING TRAINING

Collector connections

Page 85: RHEEM COMMERCIAL WATER HEATING TRAINING

Primary flow and return to solar panels.

Page 86: RHEEM COMMERCIAL WATER HEATING TRAINING

Temperature probe wired to solar controller and to the circulating pump. It works on a 8 degree C differential.

Page 87: RHEEM COMMERCIAL WATER HEATING TRAINING

Automatic air eliminator on the return line out of the panels.

Page 88: RHEEM COMMERCIAL WATER HEATING TRAINING

The return hot water line to storage tanks

Note the pipe insulation to reduce heat loss which is measured in ‘ watts ‘ per meter

Lagging must be UV resistant and meet AS3500.4

Page 89: RHEEM COMMERCIAL WATER HEATING TRAINING

Four Rheem 430 litre solar storage cylinders

( 1720 litre capacity )

Page 90: RHEEM COMMERCIAL WATER HEATING TRAINING

Rheem Gas boost mains pressure storage units.

Page 91: RHEEM COMMERCIAL WATER HEATING TRAINING

Rheem Solar controller

Green light indication of system cycle.

Note - the solar return pipe work from the panels.

Page 92: RHEEM COMMERCIAL WATER HEATING TRAINING

Primary flow and return from solar panels

Note – the isolation valves

Note – the pipe lagging

Page 93: RHEEM COMMERCIAL WATER HEATING TRAINING

Commercial site assistance

Page 94: RHEEM COMMERCIAL WATER HEATING TRAINING

THANK YOU FOR YOUR TIME TODAY

• We trust you have enjoyed and benefited from this training course...