Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 2 of 43
TABLE OF CONTENTS
I. EXECUTIVE SUMMARY………………………………........................ 3
II. BACKGROUND……………………………………………………….... 3
III. SCOPE OF WORKS…………………..…………………………………….. 3
IV. PROPOSAL DETAILS……………………………………………………... 4
V. PAYMENT TERMS ……………………………………………………... 5
VI. EVALUATION AND SELECTION PROCESS………………………... 5
VII. GENERAL CONDITIONS……………………………………………… 5
VIII. CONRACT CLAUSES………………………………………………….. 6
IX. CONTACT DETAILS…………………………………………………………. 7
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 3 of 43
EXECUTIVE SUMMARY
The Palau Public Utilities Corporation (PPUC) is soliciting companies for the Replace / Repair of
Existing APP Roof. Interested contractors can submit sealed proposals beginning August 15, 2014 and
no later than September 15, 2014 at 4:00pm Palau time. Sealed proposals will be accepted at address
[P.O. Box 1372, PPUC Main Office, 2nd
Floor--Oldiais Building--Koror, Palau 96940]. If you have
any inquiries please contact Sofronio ―Pons‖ Mahor at (680) 488-5320/3870 or e-mail at
[email protected]. Further details and information such as the scope of work, work duration, payment
terms, contract clauses, and other relevant details relating to the RFP are provided below and in the
following pages.
I. BACKGROUND
The Republic of Palau comprises of 350 tropical islands and islets located in the westernmost part
of Micronesia about 600 miles (960 kilometers) East of Mindanao, Philippines and some 800 miles
(1,280 kilometers) Southwest of Guam. Palau lies between 8°10’N/3°N Latitude and
132°45’/134°25’E Longitude. The main group of Palau Islands is dominated by the 150 square mile
(390 square kilometers) island of Babeldaob—Palau’s largest land mass.
PPUC was created in 1994, the same year Palau gained independence as a sovereign nation. Since
then, PPUC has been operating the national electric utility and the distribution facilities, which now
covers about 47 linear miles of 34.5KV transmission and 114 linear miles of 13.8KV distribution
lines. In June 2013, RPPL 9-4 merged electric, water and wastewater into one corporation known as
Palau Public Utilities (PPUC).
PPUC operates five power plants located at Malakal, Aimiliik, Peleliu, Anguar and Kayangel.
Malakal and Aimeliik provide power to the grid supplying Koror and Babeldaob. As well as Water
and Wastewater on this islands.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 4 of 43
II. SCOPE OF WORK
1- SCADA UPGRADE PHASE 1:
1.1 Theinitial phase will be to bring the new SCADA system at the main generator sites and
localized remote switching.
a) New Malakal Repeater.
b) Malakal Power Station.
c) Aimeliik Power Station.
d) Airai Substation.
e) Malakal Remote Substation.
f) Main SCADA at the Malakal Power Station.
g) Setup of Web Clients for SCADA System.
h) Solar Site 1.
2. Scope of Supply
a. To provide a complete new/upgrading/expansion of SCADA system that includes:
Replacement of equipment, engineering, commissioning and training PPUC Personnel
(IT, PGD Manager, Electrician and Operators, SCD Engineer and PDD Manager and
Foreman) of the new systems.
b. To provide SAP (Software Assurance Plan) which will guarantee to include upgrades and
Updates.
2.1. Engineering
The engineering tasks included in the quote:
a) Supply of all necessary communications equipment,(refer to 3.20.4 under
Communication Specification)
b) Supply new software in the development of SCADA,
c) Radio configurations. (To make sure that there is no interference with the existing
frequency)
d) Design drawings for communications and SCADA systems,(refer to Item 3.20.4
under (Communication Specification)
e) Commissioning report.
2.2. Procurement and Fabrication
The procurement and fabrication tasks include:
(a) Supply of data radios (refer to Item 3.20.4 under Communication Specification)
(b) Supply of replacement stainless steel enclosures,
(c) Supply of network switches,
(d) Supply of radio antennas and surge suppressors,
(e) Supply of DC control power supplies and UPS,
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 5 of 43
2.3. Site Works (Antenna)
The site work includes:
a) Site survey for final antenna locations,
b) Installation and supervision works on antennas.
c) Installation of enclosures.
d)Wiring installation.
e) Test and Commissioning.
2.4. Project Management
a) Developing and maintaining a project plan,
b) Attendance of monthly meetings with customer via teleconference,
c) Communication with client,
d) Management of project.
2.5. Specific Engineering
The engineering work involves the implementation of a new SCADA system which will
interface with the existing equipment and the new solar farms (Site 1).
2.5.1. Control Interface
The new SCADA system will interface with the new telemetry equipment which will be
connected to the existing protection and switchgear gear.
2.5.2. Installation Documentation
This offer includes the preparation of a detailed installation scope of work document to be used
by the PPUC.
2.5.3. Drawings
This offer includes new drawings for all the telemetry equipment at the existing site and the
new solar farms. The drawings will be based on the existing PPUC drawing set.
Single line diagrams,
General arrangements,
Termination diagrams,
Communications and network diagrams,
Wiring diagrams.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 6 of 43
2.6. Radio Calculations
The offer includes calculations for radio antenna direction to ensure accurate line of site is
obtained. This will be in the form of topographic maps with longitude, latitude, altitude and
angle.
2.7. New Repeater Site Survey
As discovered at the site investigation which determined that some sites did not have a line of
site with the existing repeaters. A survey is required to:
Finalise the positions of the new repeaters,
Finalise the position of the solar sites for the telemetry equipment,
testing between the new repeaters, solar sites and the existing remote re-closures.
2.8. Major Components Hardware List (Minimum requirements)
All other sundry items have not been listed
Part Number Item Description or its equivalent.
IC695CHS012 12 Slot Base
IC695PSA040 RX3i Power Supply 120/240V
IC695CPE305 CPE305 single Slot Processor
IC695ETM001 Ethernet Module 10/100mBTS
IC695MDL645 24VDC 16 Inputs
IC695MDL940 Relay Output Module 2A 16
IC695CHS012 12 Slot Base
Al-NFNFBHP-9 L-COM Surge Diverter
HG913Y-NF Yagi Antenna 13dBi HG913Y-NF
LP-3-00 Kingfisher LP3
T3 Option T3
T4 Option R4
TP180-124 Traco Power Supply Voltage Range 86 – 263V
NP7-12FR Batteries 7AH Yuasa Fire Retardant Batteries
TBURJR900-01002EH0 Trio J Series Radio 902-928MHz
SD-25B-12 MeanWell DC to DC Converter 24VDC to 12VDC 2.1A
7760048015 Network Switches Weidmuller 8 Port
CC-Link Interface card for Daiichii Protection
QJ71BR11 Mitsubishi Generator interface card
9. Software List
Vijeo Citect is a License exists at site and will only require upgrading.
It is highly recommendable to have the new equivalent software with a full
Maintenance support.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 7 of 43
For Vijeco Citect reference only:
Part Number Item Description
TOOLBOX 32-0 Kingfisher Toolbox 32 License
N/A Proficy Machine Addition
N/A Vijeo Citect Server License Upgrade
N/A Vijeo Citect Client Licenses
N/A TrioView Radio Configuration Tool
3. ADDITIONAL COMPONENTS:
3.1. Supply
a) Supply of new antennas:
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 8 of 43
b) Approval for new repeater sites,
c) Transport costs to site,
d) Any installation work,
e) Web client PC’s (PPUC Laptops),
f) Server (Client-Server Based Scenario)
g) Insurance for hardware transportation to site.
3.2. Assumptions
a) PPUC will give access to all sites for commissioning,
b) PPUC will supply all the power poles needed for the antenna.
c) PPUC will negotiate with PNCC of using their tower at
Malakal repeater station.
4. Detailed Cost proposal must include the following:
a. Manpower
(Engineers, Technician, Skilled personnel, IT Technician, Programmer,
Computer Specialist)
b. Equipments to be used. Specified Equipment cost (rental) and how long to be utilized.
c. Materials and Hardware (Specified Cost and material specifications)
5. Bar Schedule includes the following:
a. Design and Plan Preparation.
b. Material Submittal and Approval by PPUC.
c. Material Acquisition
d. Fabrication
e. Mobilization
f. Actual construction
g. Test and Commissioning
h. Orientation/Training of PPUC personnel from Actual Construction until
Test and Commissioning.
Additional Requirements After Contract Execution:
Contractor shall submit a detailed construction schedule.
Contractor shall submit a safety plan prior to any commencement of work.
Contractor shall responsible for securing the required permits and clearances for the
work (EQPB, Historical, Building Permit etc.). Site work shall not commence without
the required permits submitted to PPUC.
The contractor shall be required to submit within ten (10) calendar days the schedule of
values of each work item to PPUC after the issuance of a Notice to Proceed (NTP).
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 9 of 43
The contractor must submit sample, brochures or test certification (MILL) of the
materials to be used in the project for PPUC approval prior to the procurement of the
same. Material/s delivered to the site without prior PPUC approval shall not be
accepted for use in the project and shall be withdrawn from the site at the contractor’s
expense.
CONTRACTOR/BIDDER MUST DO AN ACTUAL SITE INSPECTION FOR THE
COMPLETE EXAMINATION OF THE EXISTING SCADA SYSTEM.
CERTIFICATION FROM PPUC PROJECT MANAGER THAT THE BIDDER HAS
DONE THE SITE INSPECTION.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 14 of 43
rules
IV. PROPOSAL DETAILS:
To facilitate review of the proposals, the PPUC is asking each Offeror to submit its
proposal(s) in conformance with the following:
A. Format of proposals 1. A cover page with a table of contents
2. An executive summary page that identifies:
Proposed time to start and how long it will finish the work,
including all submittals required on this RFP.
Pricing Concepts summary
Payment Terms
3. Corporate Bio and history of technical expertise.
Key personnel
Personnel to be assign to the project
4. Other Proposal features which are unique and will contribute to the
overall value of the offer or proposal.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 15 of 43
B. Proposal Addendums
1. Capability and Qualifications
Provide annual reports that contain performance data that
demonstrate Offeror’s ability to fulfill the terms of the proposal.
Provide organizational chart, and qualification of key personnel.
2. Reference list and contact information.
III. SPECIFICATIONS
MASTER STATION SPECIFICATIONS:
1. System Configuration
1.1. Master Station
1.1.1. The master station shall consist initially of a host server (SCADA server), interconnected by a
Gigabit Ethernet local-area network (LAN). The system shall support the TCP/IP protocol which will be
used for all data exchanges between the various nodes on the network.
1.2. Configuration
1.2.1. The host server(s) should be rack mountable equipped with XEON processor with at least 16 GB
RAM, minimum of 2 TB SAS HDD with RAID
1.2.2. The SCADA host software and the operator interface software shall run directly in the operating
System’s own windowing environment. X-Windows sessions or other emulations are not acceptable.
1.2.3. For communication with serial-data peripheral equipment, commonly available terminal servers shall be
provided to off-load serial communication processing from the host computers.
1.3. Communication
1.3.1. The SCADA system shall support the DNP3.0 (Distributed Network Protocol)
Level 2 (serial and TCP/IP) protocol used by the purchaser’s existing and/or proposed RTUs.
In addition, the system shall have the following open protocols available as options:
1.3.2. The above protocol/s shall be run in native mode, i.e. there shall be no need for an external protocol
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 16 of 43
converter (hardware unit) or internal converter (third party software driver), nor shall there be any need
for any kind of front-end processor.
1.3.3. The master station database editor shall allow the user to define key parameters for each
communication line: baud rate, time allowed for an RTU to respond, the number of retries, accumulator
poll interval, interval between scans, and protocol-specific configuration parameters. The
communication software shall maintain communication statistics for each RTU. These statistics shall
be available as database points so that they can be incorporated in user-defined displays, reports, and
alarms.
1.4. System Sizing
1.4.1. The system software shall be capable of accommodating in its database an unlimited quantity of status
and control points, analog input points, text points, communication lines, RTUs, IEDs, reports, graphic
symbols. No software upgrades or additional licenses shall be required to increase the number of
aforementioned items to be integrated into the system.
1.4.2. The size of the World Coordinate system map shall be up to a minimum of 1 billion x 1 billion drawing
units.
1.4.3. The system shall be able to fully process a continuous alarm throughput of 100 alarms per second for
at least 60 seconds. Both the World Coordinate map and the displays on all workstations shall be
updated and responsive to controls throughout the alarm burst.
1.4.4. Vendor shall provide documentation of 99.98% system availability in accordance with IEEE
Std C37.1-1994.
1.4.5. The host (Server) database shall utilize the latest Microsoft SQL database on 64bit architecture.
1.4.6. The host (Server) should consist of a backup schema, (tape, removable storage, NAS) both hardware and software
should be inclusive and will not require additional license; should the backup system require technical expertise
the training should be provided.
1.4.7. The system design and software architecture should be scalable and be properly turned overto enable
enhancements and upgrades should PPUC requiresfuture upgrades to original and or new offeror.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 17 of 43
2. System Hardware
2.1. Hardware Platform
2.1.1. The hardware platform encompasses all of the physical hardware devices utilized by the SCADA
system including host servers, operator workstations (local and remote), storage devices,
communication interfaces, printers, GUI devices (LCD Flat Panels) and LANs to which all the hardware
devices shall connect.
2.1.2. The system shall be implemented with industry standard general purpose devices and interfaces. The
proposed hardware devices shall be available from at least two different commercial sources (brands)
on the market.
2.1.3. All materials and equipment furnished for permanent installation in the work shall conform to applicable
standard specifications and shall be new.
2.1.4. All hosts (Servers) and clients (Workstations) shall include uninterrupted power supply not lower that the
computer(s) PS unit
2.2. Host Servers
2.2.1. The system supplier shall provide the Master Station server hardware and peripherals built by a leading
computer industry manufacturer. The servers shall be wholly designed, manufactured, warrantied, and
assembled by the computer manufacturer. Composite component computer frames assembled with
multi-vendor cards by second source manufacturers will not be accepted.
2.2.2. The host servers shall run the latest Microsoft Windows Server 2008 or 2013, 64-bit operating system
(OS). Other OS such as UNIX, Linux, OS2, and VMS will not be considered.
2.2.3. The Vendor shall provide OS patch management in accordance with NERC CIP standards. All OS
patches shall be evaluated by the Vendor and the results provided to the Purchaser within 30 days of
patch release.
2.2.4. The host servers and all nodes shall utilize Gigabit Ethernet network interface cards (NIC).
2.2.5. The host servers and associated communication equipment shall be delivered rack-mounted in
cabinets with perforated walls for easy ventilation with adequate ventilation fans.
2.2.6. The host servers shall also be equipped with the appropriate antivirus software inclusive of 3-year
subscription.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 18 of 43
2.3. Workstation Consoles
2.3.1. The system supplier shall provide workstation console hardware and peripherals built by a leading computer
industry manufacturer. The computer should consist of core i5 or i7processor with minimum of 4GB RAM and at
least 500GB HDD.
2.3.2. The workstations shall run the latest version Microsoft Windows 64-bit operating system.
2.3.3. The workstation consoles shall utilize Gigabit Ethernet network interface cards (NIC).
2.3.4. The system shall be able to support any number of workstation consoles without any need of upgrading the system
hardware and software.
2.3.5. The workstation console shall be equipped with the appropriate antivirus software with a 3-year subscription
3. System Functional Requirements
3.1. Data Acquisition
3.1.1. Monitor analog values such as Volts, Amps, Watts and VARs at each substation. Convert these values
to a digital format. Transmit changed values back to the Master Station. Convert these values into
engineering units. Display these values on single line diagrams and provide alarm limit
checking. Provide historical storage at user definable interval and retention periods.
3.1.2. The SCADA system shall be capable of providing health monitoring of the host server, Ethernet switch,
and terminal servers by means of SNMP, and the health monitoring points integrated into the SCADA
database and accessible by the world map
3.1.3. The system shall accumulate kilowatt-hour pulses from pulse initiators at each substation. Provide a
freeze of counts by RTU on a user definable interval. Transmit the counts back to the Master Station.
Convert the counts into interval and hourly deltas.
3.2. Supervisory Control
3.2.1. The system shall utilize a Select Before Operate (SBO) procedure that is fully compliant with IEEE Std
C37-.1-1994, 7.4.1 Operations Security Features.
3.2.2. The system shall require secured handshaking with the RTU before any controls are executed. In such
cases, control of a point requires the following exchange of messages:
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 19 of 43
• Master to RTU - control point selection
• RTU to Master - point address checkback
• Master to RTU - control execution
• RTU to Master - execute acknowledge
3.2.3. If the scan task does not receive proper acknowledgement of either the select request or the execute
command, a checkback failure alarm should be raised. If the acknowledgements are correct, but the
expected status change does not occur within the point’s control response timeout, a control failure
alarm should be raised. An optional multiple status change validation feature should be available to
handle cases where a control causes multiple status changes to occur.
3.3. Communication
3.3.1. The software subsystem for the proposed protocols shall implement all features of the RTUs and IED’sthat are
required by the purchaser. As a minimum, the following functions shall be included:
3.3.1.1. Rapid polling of RTUs for exceptions
3.3.1.2. Select Before Operate control execution
3.3.1.3. Variable control durations for momentary controls
3.3.1.4. Detect and report multiple changes of state between poll cycles , if the RTU does not buffer changes but
instead reports a ―multiple change detect‖ bit
3.3.1.5. Automatic interleaving of multiple priority messages, e.g. automatic ―fast scan‖ after a control and ―error
scan‖ after a communication error
3.3.1.6. Scheduled accumulator freezes and polls
3.3.1.7. Scheduled integrity (general interrogation) polls
3.3.1.8. Time synchronization of the RTUs
3.3.1.9. Sequence of events data uploading and processing
3.3.2. When a user-definable error retry count expires for an RTU, the system shall declare the RTU failed by means of
a status point and an accompanying alarm. On RTU failure, the system shall mark all points that are telemetered
by the RTU as ―telemetry failed‖. For each point, this telemetry failed quality codeshall not clear until a value is
subsequently received from the point.
3.3.3. The user shall be able to define alternate communication ports (or IP addresses) that can be used to reach the
RTUs. On a series of communication errors with an RTU, the system shall switch ports after a user-definable port
retry count expires. A separate port status point for each RTU shall be maintained to indicate which port is
currently being used to poll each RTU. If the communication line is looped, it shall be possible to determine
between which two RTUs a break exists by examining the values of the port status points.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 20 of 43
3.3.4. For each RTU, the system shall maintain communication statistics in the form of analog points that may be
viewed on displays, printed in reports, or stored in historical data files. Such statistics shall include percentage of
successful communication, number of timeouts and number of security errors.
3.4. Data Processing
3.4.1. The system shall provide support for multiple status changes that result from control commands. Foreach control
point, it shall be possible to specify a list of up to 30 status points that may change as a result of a command. If not
all the expected transitions occur within the control point response time-out, the system shall generate an alarm for
the control point as well as an additional alarm for each associated point that did not undergo the expected
transitions.
3.4.2. The system shall scan every analog input in the RTUs at predefined scanning intervals. Any failure to complete a
scan shall be marked with a data quality flag. Also the system shall scan each analog input every second and
compare that input to the previously reported input. When the difference between these values exceeds its
reporting band, the analog value shall be reported (report-by-exception).
3.4.3. The system shall be capable of checking the analog values for at least three sets of limits: warning, emergency and
reasonability. Each of these three sets of limits shall be provided with an upper limit, a lower limit and a
deadband.
3.4.4. To allow the removal of noise readings around the zero mark of the engineering scale, a range of engineering
values inside the point value range shall be specified which shall clamp the input value to zero. For example, if the
zero clamp deadband is 3.0, any input value which is converted to between +3.0 and -3.0 engineering units will be
clamped to zero.
3.4.5. The system shall provide a rate-of-change for analog input values by computing the difference between the new
and previous value and dividing this by the difference between the current time and the time the point was last
updated. The rate-of-change shall be checked against the limits for rate-of-change.
3.4.6. The system shall be able to process accumulators received from the RTUs. The system shall send a command to
freeze the accumulators either to all RTUs or to selected RTUs. However this freeze command shall not reset the
accumulators in the individual RTUs. Upon receiving the accumulator readings at the master station, the system
shall automatically calculate the difference from the last reading. The system shall retrieve the hourly
accumulators every hour from the RTUs and shall convert them to engineering units. The system shall also be
able to retrieve accumulators at user-definable intervals from 15 to 30 minute intervals.
3.5. Authentication and Access-Control
3.5.1. The system shall have the ability to temporarily disable a user account without deleting it.
3.5.2. The system shall have the ability to deny remote access for a user account.
3.5.3. User account passwords shall be a minimum 128-bit encrypted and neither stored nor transmitted in plaintext.
The system shall allow for selection of password length greater than twelve (12) characters, and have password
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 21 of 43
complexity settings for inclusion of alpha, numeric, and mixed case character requirements in the password. The
system shall allow the password frequency of change to be set to 1, 30, 90, 180, or 365 days. It shall also allow
setting the password to never expire.
3.5.4. The system shall allow a settable number of failed login attempts by an account, and a blocked timeout period of
time to block the user login if the number of failed login attempts is exceeded.
3.5.5. The system shall allow for an inactivity timeout setting to be enabled, whereas after a settable amount of time of
inactivity the account is logged out.
3.5.6. Account activity logging shall be configurable for login success and failures. The logging mechanisms shall be
configurable for the remote Syslog protocol.
3.6. User Rights
3.6.1.1. Each user account shall be assigned a set of user rights that determines the actions that the user may take.
This shall provide individual control over various operating and editing functions. These user rights shall include
the ability to: acknowledge, block, unblock, and silence alarms; edit database, maps, reports, analog limits, and
notes; manual set, control, and tag/un-tag points.
3.6.2. The proposed system shall be able to handle an unlimited number of user accounts with their corresponding user
rights and privileges.
3.7. Areas of Responsibility
3.7.1. The SCADA software shall be able to be partitioned into 128 areas (or zones) of responsibility. Theuser shall have
the ability to assign any combination of the 128 zones to each database point (telemetered or calculated) and/or to
each login account.
3.7.2. The user shall be able to create any number of zone groups containing various combinations of the 128 zones and
to give each zone group a name.
3.7.3. An operator shall be able to manipulate only those points whose zones overlap those of his login account.
3.8. Tag Management
3.8.1. The system shall allow operators to inhibit control of devices by means of a secure, multi-level tagging feature.
This feature shall allow operators to apply up to eight tags to each point, each tag being stored with a date/time
stamp and optional operator-entered description.
3.8.2. Each point shall be able to be provided with a visual attribute showing that the point has one or more tags on each
display where that point is shown. If a point is tagged, the display shall show the symbol that corresponds to the
highest-level tag on the point.
3.8.3. It shall be possible to specify that the tag dialog remembers the last choice of action, tag type, tag number and tag
description.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 22 of 43
3.8.4. The system shall provide the capability to configure a custom set of tag types that are mapped to the following
four basic types of tags: Inhibit ON and OFF controls, Inhibit ON control only, Inhibit OFF control only,
Information only (no control inhibit).
3.8.5. The system shall permit no means of bypassing the control inhibit caused by a tag. This applies to any and every
application supplied by the vendor or written by the purchaser using the vendor’s API.
3.8.6. A group tag function shall be provided that allows an operator to define a tag, select multiple points and apply the
same tag to all selected points.
3.9. World Map Display
3.9.1. The operator interface software shall provide a single world coordinates based graphical view of the system,
arranged schematically or geographically as defined by the user. It shall be possible to navigate freely in this
world map, scrolling in two dimensions (panning) and zooming in or out to view any location at any desired
degree of magnification.
3.9.2. The world map display system shall be able to accommodate a coordinate space of up to 1 billion by 1 billion
world units.
3.9.3. The operator interface shall be graphics based and shall be capable of importing DWG or DXF file formats. The
operator interface software shall include the ability to merge multiple imported maps into one SCADA display
and to edit the imported graphics.
3.9.4. The world map display shall be implemented in a multilayered structure. When a map is imported from a DWG
or DXF file, the layers that are contained in the DWG/DXF file should be preserved. There should be no upper
limit on the number layers that may be contained in the world map.
3.9.5. It shall be possible to resolve the world map coordinates for Lat/Lon by establishing the latitude and longitude
limits of the map. Data integrated into the world map via Lat/Lon coordinates shall be correctly located on the
world map.
3.9.6. The system shall support an unlimited number of graphical layers which can be de-cluttered either automatically
(based on zoom level) or manually by the operator.
3.9.7. The operator shall have the ability to override the automatic decluttering and manually either turn alayer on or off
regardless of the current zoom level. By organizing layers in a hierarchical system of folders, it shall be possible
to easily turn entire folders of layers on or off. The system of folders shall be preserved when the map is re-
imported from an updated DWG/DXF file.
3.9.8. A user-extendable library of ready-to-use symbols, colors and text styles shall be provided. It shall be possible to
import and export library items such as Pmacros (interactive graphics) and symbols for sharing with other users.
3.9.9. Methods of navigation within the world map display shall include the ability to continuously pan and zoom, to
jump to other displays at pre-defined locations and magnification levels and to snap to a view that is defined by
rubberband mouse operation, i.e. a view selection rectangle.
3.9.10. The user shall be able to specify the number of alarm lines for the unacknowledged alarms to be displayed in an
alarm banner at the bottom of any display. The alarm banner shall not resize when the operator zooms in or out
on the world map display. The operator shall be able to temporarily resize the alarm banner by dragging the
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 23 of 43
frame separator, showing more or less alarm lines. The operator shall be able to toggle the alarm banner on or off.
It shall also be possible to acknowledge and/or block the alarms that are displayed in the alarm banner via a pop-
up menu.
3.9.11. The user shall be able to represent status points with animated GIF (Graphics Interchange Format) files.
Animated GIFs are a popular way to display the change of state of a device, or motion such as a pump in
operation. The operator shall be able to set the blink rate to control the speed of the GIF file.
3.9.12. When the curser is moved over a database point on the world map, a popup tool tip will display the point name,
description, current value, and date and time the point was last updated.
3.9.13. It shall be possible to use bitmaps (image files) rather than symbols to represent status points, station points, and
pushbuttons. The displayed bitmaps should scale as the user will zoom in and out. The supported bitmap file types
shall include GIF, JPG and BMP.
3.9.14. For any analog point on the world map, the user shall be able to select displaying the values of Avg, Min, Max,
Min Time, and Max Time for Current and Previous: 15 Min., Hour, Day, and either Week or Month. These
values shall be automatically recorded for all analog points within the system and available for display on the
world map.
3.9.15. The user shall have the ability to create any number of views within the world map display. The viewsmay be
accessed via a scrollable list box or via pushbutton (poke points) on the world map display. For ease of navigation
in the views list box, it shall be possible to organize the views in a hierarchical system of folders. Both the folders
and the views themselves shall be preserved when the map is re-imported from an updated DWG/DXF file.
3.10. IED Control Panel Templates
3.10.1. The system shall support Intelligent Electronic Device (IED) control panel templates that graphicallyrepresent
IED’s within the database. The template will allow dynamic elements and database values to be superimposed
over a graphic representation of the IED faceplate. The template shall support multiple pages of IED information.
3.10.2. The user shall be able to copy and paste a template instance on the world map, and reassign the template to a new
IED, with all database values automatically updated to the new IED. When edit changes are made to the template,
all instances of the template on the world map will be updated.
3.10.3. The user shall be able to create custom templates using the same editing tools available for editing theworld map.
The user shall be able to import and export templates for sharing with other system users.
3.10.4. The vendor shall provide in their proposal a complete list of all templates that are currently available for the
system. Any associated costs for adding templates to the system will be detailed and listed as options in the price
proposal.
3.11. Full Graphics Editor
3.11.1. A full graphics editor shall be provided as an integral part of the database and display building tools. Access to the
editing capabilities shall be available at all local and remote consoles, however it shall be password-protected.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 24 of 43
3.11.2. A copy of the world map and supporting libraries shall reside on each workstation console, such thatwhen viewed
in live mode, only dynamic data such as point values and alarms shall be retrieved from the host server in order to
minimize network traffic and make feasible dial-up connections even with large displays..
3.11.3. The system shall allow the reservation of the world map and associated resources so that only the
userimplementing the reservation can edit those resources. If another user attempts to edit a reserved world map,
they will be notified that it is reserved and the username and workstation of the user holding the reservation.
3.11.4. The system shall allow the publishing and updating of the world map and associated resources. Whenthe world
map is published or at a user settable time interval, all client workstations will be notified that a new world map is
available.
3.11.5. The full graphics editor shall allow the user to create any number of layers and displays of the worldmap. The
editor shall allow the user to assign zoom levels to each layer for automatic decluttering. The editor shall allow
the user to specify an image file for any display that is to be used as a background for the display. The image file
formats that can be used for this shall include JPG, GIF and BMP.
3.11.6. The full graphics editor shall contain easy-to-use tools for re-layering, re-coloring and re-styling (text) aswell as
duplication (copy/cut and paste), stretch and re-size. It shall include a Find and Replace function that finds all
instances of a text string anywhere on the world map, and allows automatic replacement by another text string.
3.11.7. The full graphics editor utility shall provide topological support. It shall perform consistency checksbetween the
graphical display and the topology database. Connectivity shall be dynamically calculated based on topology and
current status of breakers and switches, and displayed with user-defined color-coding.
3.12. Drawing Tools
3.12.1. The proposed system shall include drawing tools as part of a full graphics editor to allow the user to addto and/or
modify the drawings that were imported via DWG/DXF file. The editor shall support at least 99 undo and redo
editing changes.
3.12.2. The system should include an initial ready-to-use set of such libraries. On import of a DWG/DXF file, thecolors,
text styles and symbols that are contained in the DWG/DXF file should be imported into the libraries, where they
may be customized or just used as is.
3.12.3. The proposed system shall provide the capability to display a telemetered or calculated analog value inthe form of
a numeric string, horizontal or vertical bar graph (the length of a bar graph reflects the value of the analog point),
or in an analog gauge. Both numeric strings and bar graphs shall be color-coded to reflect any violation of alarm
limits. Analog gauges shall have the capability to represent a meter or dial type gauge. The user-definable
properties of gauges shall include: angle start, angle length, dial color, dial direction, label properties, limits
properties, major/minor divisions, needle properties, and the radius.
3.13. Notes
3.13.1. The displays shall support a system of ―post-it‖ notes that allows operators to add and remove noteicons on any
display. Clicking on a note icon shall cause a pop-up window to appear to show free-form notes on any topic.
The notes can be entered and modified in this window.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 25 of 43
3.13.2. The system shall also support notes that are specific to database points. Such notes shall beaccessible from a
pushbutton in the point dialog box that appears when the point is selected. When a point has some notes, the
pushbutton icon in the dialog box shall be highlighted.
3.13.3. Point-specific notes shall also be accessible from the alarms display. When a point-related alarm is selected, a
pushbutton in the tool bar should highlight if there are notes for the selected point. Clicking on this pushbutton
shall bring up the point’s notes.
3.14. Database Editor
3.14.1. The database editor shall provide a graphical tree-like representation of the complete database and shall support
easy navigation throughout the database to the desired items to be edited. Database items to be edited in this way
shall include Stations, Communication Lines, Communication Channels, RTUs, IEDs, as well as all the individual
database points (analog values, status indications, accumulators, etc).
3.14.2. The database editor shall operate as a ―client‖ program which communicates with a ―server‖ programrunning on
the host computer. However the database editor shall be able to run on any computer that is connected to the host
server via the network. With this arrangement, it shall be possible to manage the database maintenance from any
suitably configured PC on the network without being necessary to go to the control room to do it.
3.14.3. The database editor shall include features which will make it easy to create and modify the database such as:
using the Station Cloning feature to create an entire new station and all its points, based on an existing
station;
copying, cutting and pasting in the Windows environment;
using a model feature to create points and other database items that are based on previously created ones;
using a Station Rename feature to copy a portion of an existing display, and to reassign all those dynamic
points to points in a different station, all in one operation;
editing or modifying the database on an MS Excel spreadsheet and importing it into the system real-time
database;
deleting existing database points;
deleting an entire station with all associated points
3.14.4. All changes and updates of the database shall be completed and validated while the system is in onlineoperation.
Under no circumstances shall the real-time system operation be interrupted or disturbed by the database editing
and maintenance process.
3.15. IED Wizard Templates
3.15.1. The system shall support Intelligent Electronic Device (IED) wizard templates for automating thecreation of
points for IEDs on the system.
3.15.2. The user shall be able to select from a list of available templates, define the IED name, communicationline, IED
address, and communication statistics for total message count, good message count, bad message count received
from the IED.
3.15.3. The template shall contain all available points for the given IED and allow the user to select the pointsto be
included in the database. All of the telemetry and control addresses and RTU-to-IED mapping shall be
automatically generated.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 26 of 43
3.15.4. The Vendor shall provide an application that allows the user to create new IED templates and edit existing
templates.
3.15.5. It shall be possible to create IED templates for IEC 61850 devices.
3.15.6. The vendor shall provide in their proposal a complete list of all templates that are currently available forthe
system. Any associated costs for adding templates to the system will be detailed and listed as options in the price
proposal.
3.16. Alarms
3.16.1. Alarms and operational events shall be continuously synchronized in real-time to the standby hostserver, in the
case of a dual-redundant system configuration.
3.16.2. The proposed system shall be able to handle a minimum of 100 alarms or events per second per operator consoles
regardless of the other workload.
3.16.3. The system shall provide at least ten (10) alarm priority levels. Alarms with priority zero - the lowest, shall be
considered to be pre-acknowledged. Such alarms shall neither sound any audio alarm signals nor cause points to
flash on the display.
3.16.4. For each analog point, the user shall be able to define three sets of nested upper and lower alarm limits, with a
separate deadband for each limit. In addition, analog points shall be able to generate an alarm when a rate of
change is exceeded, either in the increasing or decreasing direction, or both. Each alarm limit shall support a
separate alarm priority.
3.16.5. The system shall provide the operator with a visible ―telemetry failure‖ indication when the value of anydisplayed
point is not currently being updated by the system because of an RTU or communication line failure. Any points
that are calculated using, as inputs, the values of other telemetry failed points, shall also be marked telemetry
failed.
3.16.6. The user shall be able to specify any Windows sound file (*.WAV) to be used for the audio alarm signal.The
system shall allow the user to browse for sounds and to test play the selected sounds. The system shall allow
different sounds for each alarm type and a different set of sounds for each workstation.
3.16.7. The system shall provide summary lists for all unacknowledged, acknowledged, blocked, suppressed and for all
alarms. The user shall be able to perform alarm filtering based on certain parameters or filters. The filtering of
alarm summary lists shall be performed from a template where the operator can enter the filtering parameters and
obtain the filtered lists.
3.17. Reports
3.17.1. The system shall support a report generation capability that will allow the user a high level of flexibilityin the
definition, formatting and scheduling of on-demand and periodic reports. The reports shall include data from both
the real-time database and historical database. The system will allow the user to schedule reports for automatic
printing or saving to hard disk files for subsequent transfer to CD or tape.
3.17.2. A report editor shall be available to allow the user to define reports by specifying a database table, a setof desired
data fields and the selection criteria for retrieving records from the database table.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 27 of 43
3.17.3. A graphical report in the form of scheduled prints of selected views of the world map shall also beprovided.
3.17.4. The system shall include a scheduling facility that will allow the operator to define the schedules and destinations
for all reports. It shall be possible to direct a scheduled report to multiple printers, one or more of which can be
directories on disk.
3.18. Data Collection and Storage
3.18.1. The system will provide a historical data collection facility that allows the user to define the points that are to be
sampled, the sample frequency and how long to retain the sample data. In each dataset, the oldest samples should
be overwritten by the newest.
3.18.2. The historical data software shall be capable of sampling at intervals as low as 1 second. There shouldbe no upper
bound on the duration of samples within each dataset, and thus no upper bound on the amount of historical data
that can be stored other than the limitation imposed by available disk space.
3.18.3. The historical data software shall allow the user to specify recording of statistics in the sample records.The
statistics shall include time averages, summations, maximums and minimums, and times of maximums and
minimums and shall be based on user-definable observation intervals.
3.18.4. The system shall also allow the user to create ―secondary‖ datasets that extract information fromprimary datasets.
For example, a primary dataset could contain 15-second samples for several days. A secondary dataset could
extract daily maximums and minimums, as well as the times of the maximums and minimums and record these for
ten years.
3.19. Data Trending
3.19.1. The proposed system shall provide the ability to store and view any data value from the database in atrend
graphical format. The system shall bring up pixel-resolution trend graphs of historical data. Sample rates as low
as 1 second must be supported.
3.19.2. Trend graphs shall be displayed in separate windows that can be moved, re-sized and minimized to anicon. The
trend graph window shall include tools that allow the user to configure and customize the graph display.
3.19.3. A trend graph window shall have the ability to plot at least ten (10) points from the historical database.The trend
graph displays shall be interactive allowing the operator to quickly adjust the time frame, duration and resolution
of the graph.
3.19.4. In cases where there are more samples in the dataset than can be displayed in the graph window, it shall be
possible to scroll back in time. It shall be possible to see the numeric values and time-stamp of the traces at any
time position in the graph by manipulating a time cursor inside the trend graph.
3.19.5. The user shall be able to display trend comparison graphs from left to right, for at least ten (10)comparison trends.
In trend comparison graphs, the time origin at the extreme left of the graph is a fixed time of the day; however it
may be a different day for each trend. The purpose of this is to allow the user to observe the build-up of the
current day’s trace, e.g. a load curve, against that of other days in the past, typically the days that contained the
last week peak or the current month peak, etc. The trend comparison graph shall have an option to set a start time
and day of the week so that the trend graph is automatically launched.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 28 of 43
3.20. Interface to Microsoft Excel
3.20.1. The system shall support current and historical database access from clients running MS Excel. It shallbe possible
to directly connect to the SCADA host from within MS Excel by defining the Host name and valid user account
with username and password. The client application shall support redundant Host and automatically reconnect to
the active Host upon failover. All current and historical tables and fields shall be accessible through this interface.
3.20.2. For current data, the user shall be able to select a database table, data fields within the table, and logiccriteria (<,
>, =, AND, OR) for point selection. In addition, the user shall be able to browse for points and drag-drop them
into the point selection dialog. The user shall be able to select the MS Excel worksheet, start row, and start
column for where the data will be populated, and to include the column headings from the database table. The
user shall be able to optionally define a time interval at which the current data is automatically updated on the
worksheet.
3.20.3. For Historical data, the user shall be able to select points contained within an historical dataset. The user shall be
able to define a time type by defining the start and finish date and time, or the number of previous days, hours,
and minutes. The use shall be able to select data condition codes to be included with the samples. The user shall
be able to select the MS Excel worksheet, start row, and start column for where the data will be populated, and to
include the column headings from the database table.
3.20.4. It shall be possible to save current and historical queries as defined above as reports available in theworld map
operator interface.
Ethernet
SCADA HMI
Laser printer
SCADA System response times are the following:
Dispatcher Interface Requirements Response time
Requests for call-up of displays shall be acknowledged with an Within 2 sec
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 29 of 43
indication of request being processed
Any real time display and application display (except RDBMS
displays) on workstation console, Complete display &
data values shall appear on screen
Within 3 sec after
acknowledgement of
request
Manual Data entry of the new value shall appear on screen Within 2 sec
Display update rate Every 2 sec for 4
displays together
Panning of a world display from one end of screen to other end of
screen in a continuous manner
Within 2sec
Response time for display of Alarm and event after receipt in
SCADA system
Within 2 sec of
receipt in system
Alarm and event acknowledgement Within 2 sec
Requests for printing of displays shall be acknowledged with an
indication of request is being processed
Within 2 sec
Requests for generation of reports shall be acknowledged with an
indication of request is being processed
Within 2 sec
COMMUNICATION SPECIFICATION:
Use of a radio system that can be used for point-to-point and point-to-multi point system
Use of a radio system that supports a protected mode (redundancy)
Use of a radio system that supports Ethernet bridging, IP to serial and serial to serial communication
Use of a radio system that can cover distances of up to 50 miles
Use of a radio system with AES-128 bit data encryption
Use of a radio system with lower power consumption with sleep mode for solar and battery powered
applications
Compatible with multiple industry protocols including Modbus, Modbus TCP and DNP3.
Transmit power up to 5 watts
Equipped with 2 serial ports and 1 ethernet port
Enclosed in a rugged die-cast aluminum casing
Temperature -40 to 70C
Humidity at 95%
How the communication network is configured would include providing a redundant setup from MALAKALPP
to the Repeater Site and providing a point-to-multipoint configuration for the remote sites.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 30 of 43
REMOTE TERMINAL UNIT SPECIFICATION:
Concept: Each substation/plant would have to be equipped with a Remote Terminal Unit and not a PLC as the
remote station. Specification would be the following:
- Industrial Computer specially designed for substation use. (no moving parts)
- 32-bit microprocessor unit with support circuitry for VME bus cardwith a Realtime Operating System
- Communication ports - 2- HDLC links and 7 RS232 ports and 2 ethernet ports
- Universal powersupply for AC (110/220vAC) and/or DC (125vDC) input.
- Capable for distributed peripheral modules for DI, DO, and AI, or Combination module equipped with
digital inputs, analogs and digital outputs
- Self-diagnostic capability
- Maintenance/ servicing port
- Equipped with various protocols for upstream/downstream interconnectivity the list below are
mandatory:
1. DNP3.0 level 3 (HOST AND IED connectivity)
2. Modbus RTU/ASCII
3. Spabus
4. IEC 870-5-101/103
The SCADA System shall be able to monitor PPUC s Network via the Communication System from multi-
ported RTUs located in the Substations. The SCADA shall be designed and implemented to scan 500%
of the number of RTUs that will be linked. The SCADA shall communicate with the RTUs using the
DNP 3.0 (level 2) protocol at data transmission rate of at least 19200 bps using digital interfaces.
The SCADA shall make scan requests to all the RTUs for the most current status and/or analog data. Such
requests shall be made on a sequential basis for those RTUs on the same communication channel, and
on a parallel basis for those RTUs on different communication channels. The scan rates for all RTUs
shall be user-adjustable between 1 second and 1 hour.
Analog values shall be retrieved periodically. Each data source shall be periodically checked for status changes
(status change checking). If changes are reported, the source shall immediately be interrogated and the
details of the changes shall be retrieved within the same scan period. An integrity scan of the status
data shall be performed periodically. Accumulators shall be scanned periodically. Each scan reply shall
be immediately checked for certain basic error conditions, including incorrect response, data buffer
overwrite error, telemetry failure as detected by hardware checking of message security codes, etc. A
detected error shall be recorded for maintenance purposes. Attempts shall be made to recover from the
error conditions by repeating the particular data scan for a pre-determined number of times. If no more
errors are detected in at least one of the retries, then the earlier error shall be considered as a
recoverable error. Otherwise, it shall be considered as a non-recoverable error. Statistics (number of
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 31 of 43
detected errors per pre-defined time) shall be kept on recoverable errors. The detection of a non-
recoverable error or the occurrence of a high number of recoverable-errors (e.g., 30%; programmable
parameter) shall be considered as channel-failure and shall result in the suspension of scanning for the
particular RTU. The channel shall be periodically tested to see if communication can be restored and
the RTU returned to scanning after one good scan. Appropriate alarm and event messages shall be
generated. The Dispatcher shall be able to restart the scanning as well.
The SCADA shall be designed so that the periodic scan and control requirements of the system in its ultimate
configuration can be met without any data point being periodically sampled less frequently than its
designated minimum scan frequency.
The capability to deactivate and reactivate the scanning of a given RTU upon Dispatcher command shall be
provided.
The data retrieved shall be subject to data conversion, alarm checking, and/or limit checking. The hardware and
software must be designed such that scan reply data will not be lost because of insufficient buffer size
or insufficient time to service the reply data. If the data conversion and checking functions have not
been completed for a certain data or data group before the new data value(s) for the same data or data
group are received in the next scan, appropriate diagnostic messages shall be output.
METERS
Digital meters are to be supplied as needed as part of the IED requirements of the two
powerplants/substations. The specifications of the meters are the following:
- MULTIFUNCTION ELECTRICAL MEASUREMENT PANEL MOUNTED (ansi 4‖)
- RATED INPUT VOLTAGE: 120V AC
- RATED INPUT CURENT: 1 or 5A nominal to maximum of 2A or 10A (overload), split core option for
5A nominal
- POWER SUPPLY: Universal 48-250vDC/55-240vAC nominal
- ACCURACY CLASS 0.25% CLASS REVENUE CERTIFIABLE ENERGY AND DEMAND
- EASY TO MOUNT WITH STANDARD 4‖ ROUND METER
- 3-LINER LED DISPLAY, TOUCH SENSE BUTTONS FOR EASY SET UP AND SCROLLING
FROM FRONT PANEL DISPLAY, 5 DIGIT PER LINE DISPLAY
COMMUNICATION PROTOCOLS:
- DNP3.0 OR MODBUS PROTOCOL; CONFIGURABLE RS232/RS485 SERIAL PORT
- DATA COMM PORT: RS485 PORT FROM 9600 TO 115.2KBPS (CONFIGURABLE)
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 32 of 43
- RJ45 10/100 MBPS PORT FOR SERVICE PORT FUNCTION (OPTION FOR MODBUS OR DNP3
TCP/IP PROTOCOL SUPPORT)
BASIC MEASUREMENTS PARAMETERS:
- MW, MVAR, MVA, MWHR, MVARHR
- VOLTAGE L-L 3 PHASE, VOLTAGE L-N 3 PHASE
- CURRENT 3 PHASE WITH NEUTRAL
- PF, FREQ
ENCLOSURE
The RTU/IEDs to be supplied under the SCADA Project will be housed in an enclosure suitable to the
SCADA equipment to be installed at each substation. The Enclosure or Panel can be a freestanding or
wall mounted type so long as the equipment provided will be properly enclosed with sufficient space
and ventilation. In addition, a canopy will also be provided as added protection.
The Panels provided will have the following specifications:
Material: Electro-galvanized steel
Protection Category: IP54
Color: Epoxy powder painted in RAL7032
Other specifications includes:
- Welded frame
- Side panels
- Solid front door mounted w/ stiffeners 4 pt. locking system and keyed alike swing handle lock.
- Rear panel (if applicable)
- Bottom gland plates
- Humidifier
- Inside lighting
- Circuit breaker
- Grounding bar
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 33 of 43
Hardware and Materials in Details
5010 PLC Hardware
PART NUMBER Description
Malakal Repeater
Al-NFNFBHP-9 L-COM Surge Diverter
Coax Cable RJB price per meter
HG913Y-NF Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Stainless Steel Enclosure
SD-25B-12 DC to DC Converter Meanwell
Malakal Generator House
Al-NFNFBHP-9 L-COM Surge Diverter
Coax Cable RJB price per meter
HG913Y-NF Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
SD-25B-12 DC to DC Converter Meanwell
Traco Power Supply
NP7-12FR Batteries 7AH
J Series Radio
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 34 of 43
IC695CHS012 12 Slot Base
IC695PSA040 RX3i Power Supply 120/240V
IC695CPE305 CPE305 single Slot Processor
IC695ETM001 Ethernet Module 10/100mBTS
IC695MDL645 24VDC 16 Inputs
IC695MDL940 Relay Output Module 2A 16
Malakal Remote Substation
Ethernet cable install by PPUC or
Coax Cable RJB price per meter
RS485 to ethernet converter
Connectors Adaptors
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Airai Substation
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Aimeliik Substation
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 35 of 43
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Misubishi Comms Module
Daiichi Relay Module CC Link
IC695CHS012 12 Slot Base
IC695PSA040 RX3i Power Supply 120/240V
IC695CPE305 CPE305 single Slot Processor
IC695ETM001 Ethernet Module 10/100mBTS
IC695MDL645 24VDC 16 Inputs
IC695MDL940 Relay Output Module 2A 16
SD-25B-12 DC to DC Converter Meanwell
M124 Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
M55 Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 36 of 43
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
BabelDaob Repeater
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Stainless Steel Enclosure 800 X 800 X 300
SD-25B-12 DC to DC Converter Meanwell
Kokusai Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Asahi Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 37 of 43
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Mau Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Melkeok Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 38 of 43
CHS Remote Re-closure
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Tool Box License
PC to RTU Serial Port Cable
SD-25B-12 DC to DC Converter Meanwell
Repeater 1 for
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Stainless Steel Enclosure 800 X 800 X 300
SD-25B-12 DC to DC Converter Meanwell
Repeater 2 for
L-COM Surge Diverter
Coax Cable RJB price per meter
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 39 of 43
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
Stainless Steel Enclosure 800 X 800 X 300
SD-25B-12 DC to DC Converter Meanwell
ZM-9099 Solar Panel 175W ZM9099 24VDC
Rails
End clamps
Repeater 3 for
L-COM Surge Diverter
Coax Cable RJB price per meter
Yagi Antenna 13dBi HG913Y-NF
Connectors Adaptors
Kingfisher LP3
Option T3
Option R4
RG58 Adaptor
Intruder Switch
Traco Power Supply
Batteries 7AH
Trio Radio Modem J Type
SD-25B-12 DC to DC Converter Meanwell
ZM-9099 Solar Panel 175W ZM9099 24VDC
Rails
End clamps
IV. PAYMENT TERMS
Payment terms shall be determined as follows:
a. After evaluation per proposal
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 40 of 43
b. After negotiations with the winning offeror.
c. All payments shall be made after receipt of original invoice from contractor for each
work phase, certified by a duly authorized PPUC representative
V. EVALUATION AND SELECTION PROCESS
All proposals received shall be evaluated by a specially convened committee. The following criteria
(NOT Necessarily in Order) will be used to evaluate proposals:
1. Proposed Project Time-Frame
2. Proposed Project Cost
3. Compliance with specifications stated in this RFP
4. Part quality and authenticity assurance certificates.
5. Other details including but not limited to added-value packages and warranty provisions
Selections will be made and announced within 45 days after Bid Closing Date.
VI. GENERAL CONDITIONS
A. Vendors are required to submit their proposals based upon the conditions expressed in these
instructions
i. Assignment of Contract: The contract shall not be assigned to any party without prior written
consent from PPUC.
ii. RFP Modification: This RFP does not commit PPUC to award a contract, to pay any costs
incurred in the preparation of the proposal under this request, or to procure or contract for
services. PPUC also reserves the right to accept or reject any or all proposals received under
this request, to negotiate with qualified offeror, or to cancel in whole or in part this RFP, if it is
in the best interest of PPUC to do so. Offerors under this RFP may be required to participate in
negotiations and to submit any price, or technical revisions to their proposals as may result
from the negotiation process.
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 41 of 43
iii. Performance Bond: PPUC requires that all contractors with contracts in excess of $50,000
should acquire performance and payment bonds tendered in a manner and through a surety
acceptable to the PPUC General Manager, which guarantees satisfactory completion of a
project. The performance and payment bonds shall be in an amount equal to the total price
specified in the contract.
iv. Transfer of property: All proposals shall become PPUC property.
v. Conformity: The PPUC procurement regulations shall apply to all proposals and bids and all
winning bidders and contractors shall be bound by them.
vi. All proposals shall be submitted in the following format:
1. A cover page with a table of contents
2. An executive summary page that summarizes the corporate history,
contractor’s ability to satisfy the requirements of this RFP, project cost and a synopsis of
salient details required in this RFP.
3. The proposals shall be sealed in a package and should include:
a. The Contractors information (i.e., Name, Address, and Contact) on the outside package
b. The RFP# on the outside of the package that should be submitted NO LATER THAN
4:00 PM of CLOSING DATE-Palau Time.[Note: The RFP # should be in big fonts.]
c. The sealed package should include the original plus five (5) copies of the proposal.
vii. Inquiries: Any inquiries, requests, clarification, or additional information pertaining to this
RFP shall be made in writing, by email or fax through the contacts provided
VII. CONTRACT CLAUSES
A. All contracts shall, at a minimum, contain the following clauses:
1. Governing Regulations
2. Penalties for Violation of Regulations
3. Contract Disputes
4. Gratuities
5. Kickbacks
6. Representation of Contractor Concerning Contingent Fees
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 42 of 43
7. Changes
8. Stop Work Order
9. Termination for Defaults or Convenience
10. Approvals, Certificates, Permits and Licenses
11. Laws and Regulations
12. PPUC’s right to inspect
13. Commencement of Work
14. Liquidated Damages
15. Schedule
16. Clear Title
17. Taxes
18. Force Majeure
19. Relationship
20. Entire Agreement
21. Assignment
22. Subcontracts .
23. Contracting Officer
VIII. CONTACT DETAILS
Tito Cabunagan PPUC EPD/SCD Manager Tel: (680) 488-0510 Email: [email protected]
Punssen Imetengel PPUC IT Manager Tel: (680) 488-0642 Email: [email protected]
Sofronio “Pons” Mahor PPUC Contracting Officer PPUC Procurement Division Tel: (680) 488-5320 Fax: (680) 488-4499 Email: [email protected]
Jacqui Alexander PPUC Chief Financial Officer PPUC Accounting and Finance Division Tel: (680) 488-5320 Fax: (680) 488-4499 Email: [email protected]
Request for Proposals
PUC14-013 [PPUC SCADA Upgrade]
Page 43 of 43
Tmetuchel Baules PPUC Administrative Assistant PPUC Administrative Office Tel: (680) 488-3870/72/77 Fax: (680) 488-3878 Email: [email protected]