FIRE PROTECTION
COVER SHEET
FP0-01
FP0-01 FIRE PROTECTION COVER SHEET
2/13/17
5
0
%
C
D
S
E
T
x
FIRE PROTECTION SHEET INDEX
ISSUE LOG
TITLE#
DATE
FP1-01 FIRE PROTECTION - SPRINKLER - 1ST FLOOR
FP1-02 FIRE PROTECTION - SPRINKLER - 2ND & 3RD FLOOR
FP1-03 FIRE PROTECTION - SPRINKLER - 4TH FLOOR
FP2-00 FIRE PROTECTION - DETAILS
x
x
x
x
FIRE PROTECTION GENERAL NOTES
1. SCOPE OF WORK
A. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, AND LABOR REQUIRED TO SATISFY A COMPLETE WORKING SYSTEM
WHETHER SPECIFIED OR IMPLIED.
B. THE WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH NFPA 13 (2012 EDITION), ALL CODES AND OTHER NFPA REGULATIONS
GOVERNING WORK OF THIS NATURE.
C. THE CONTRACTOR SHALL EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR HIMSELF THE CONDITIONS THAT MAY EFFECT THE
WORK BEFORE SUBMITTING ANY PROPOSAL. NO ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO MAKE SUCH
EXAMINATIONS.
D. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR AN "APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT.
E. BUILDING TO BE FULLY SPRINKLERED PER NFPA 13. FIRE STANDPIPES REQUIRED AS PER IFC 2009 SEC. 905.3.1 AND INSTALLED IN
ACCORDANCE WITH NFPA 14.
2. PERMITS
A. THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS AND PAY ANY AND ALL FEES.
B. THE CONTRACTOR SHALL BE A LICENSED FIRE SPRINKLER CONTRACTOR.
C. AUTOMATIC SPRINKLER SYSTEM CONTRACTOR SHALL SUBMIT PLANS FOR EVALUATION AND APPROVAL PRIOR TO COMMENCEMENT OF
NEW WORK.
3. SHOP DRAWINGS
A. SUBMIT A MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR EQUIPMENT TO THE ARCHITECT/ENGINEER AND STATE FIRE MARSHALL
FOR APPROVAL. THE CONTRACTOR SHALL SUBMIT SIX SETS OF SHOP DRAWINGS AND THEY SHALL BE CLEARLY LABELED.
4. SPRINKLER HEADS
A. WHERE SPRINKLER HEADS ARE INSTALLED IN ACOUSTICAL CEILING TILES, HEADS SHALL BE CENTERED IN THE TILE.
B. SPRINKLER HEADS ARE TO BE PROVIDED IN THE STYLE AND COLOR/FINISH AS SPECIFIED ON THE DRAWING. HOWEVER, CONTRACTOR
TO CONFIRM WITH OWNER/ARCHITECT PRIOR TO PURCHASE THAT THE SPECIFIED COLOR/FINISH IS ACCEPTABLE.
5. SPRINKLER PIPING
A. PIPE SHALL BE MADE TO ANY OF THE SPECIFICATIONS LISTED. WELDING WILL NOT BE PERMITTED IF THERE ARE ANY SPRINKLERS
CONNECTED THERETO.
ASTM A53
ASTM A120
ASTM A135
ASTM F441
B. PIPING MATERIAL MAY BE SCHEDULE 10 (THINWALL) PROVIDED JOINTS ARE MADE BY ROLL-GROOVE COUPLING. THREADING WILL NOT
BE PERMITTED ON SCHEDULE 10 (THINWALL).
C. PIPING MATERIAL MAY BE SCHEDULE 40 WITH FLANGED, ROLL-GROOVED COUPLINGS, OR THREADED JOINTS.
D. DRY SPRINKLER PIPING SHALL BE SLOPED TO DRAIN. LOW POINT DRAINS SHALL BE PROVIDED AT ANY CHANGE IN PITCH.
6. PIPE SUPPORTS
A. ALL HANGERS MUST BE AN NFPA 13 APPROVED TYPE. NO SPRINKLER PIPING IS TO BE SUPPORTED FROM ANY MECHANICAL OR
ELECTRICAL DEVICES.
B. ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN A NEAT AND WORKMANLIKE MANNER. VERTICAL RISERS SHALL BE
SUPPORTED AT EACH FLOOR LEVEL WITH STEEL PIPE CLAMPS. THE USE OF WIRE OR STRAP METAL HANGERS TO SUPPORT PIPES WILL
NOT BE PERMITTED. HANGING PIPES FROM OTHER PIPES WILL NOT BE PERMITTED. PIPING SHALL BE CAREFULLY COORDINATED
BEFORE INSTALLATION WITH OTHER SYSTEMS AND EQUIPMENT IN CHASES AND OTHER CONGESTED AREAS.
C. SEISMIC PERFORMANCE: FIRE-SUPPRESSION PIPING BRACING SHALL BE IN ACCORDANCE TO NFPA 13.
7. WORKING PLANS
A. THE DRAWINGS INCLUDED AS PART OF THIS SET OF CONSTRUCTION DOCUMENTS ARE TO PROVIDE ENGINEERING DESIGN INTENT.
THE CONTRACTOR SHALL PREPARE WORKING DRAWINGS (AS DEFINED BE NFPA 13) WHICH SHALL INCLUDE HYDRAULIC CALCULATIONS
AND WILL BE SUBMITTED TO THE ENGINEER AND FIRE MARSHALL FOR APPROVAL.
8. TESTS
A. ACCEPTANCE AND HYDROSTATIC TESTS TO BE PERFORMED IN ACCORDANCE WITH CHAPTER 10 OF NFPA 13.
9. MISCELLANEOUS
A. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS AT THE JOB SITE.
B. THE SPRINKLER PLANS ARE INTENDED TO BE DIAGRAMMATIC. THEY ARE NOT INTENDED TO SHOW EVERY ITEM IN ITS EXACT
LOCATION.
10. GUARANTEE
A. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED FOR PERIOD OF ONE(1) YEAR FROM DATE OF ACCEPTANCE.
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED AT THE SPRINKLER CONTRACTOR'S EXPENSE.
ABBREVIATIONS
AFC - ABOVE FINISHED CEILING
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALV - ALARM VALVE
BMS - BUILDING MANAGEMENT SYSTEM
Cr - CROSS
DPV - DRY PIPE VALVE
E - 90 DEGREE ELBOW
FACP- FIRE ALARM CONTROL PANEL
FBO - FURNISHED BY OTHERS
FP - FIRE PUMP
GV - GATE VALVE
JP - JOCKEY PUMP
NTS - NOT TO SCALE
FA - FIRE ALARM
EE - 45 DEGREE ELBOW
BFP - BACK FLOW PREVENTER
BFG - BELOW FINISH GRADE
AHJ - AUTHORITY HAVING JURISDICTION
BV - BUTTERFLY (wafer) CHECK VALVE
CV - SWING CHECK VALVE
DeL V - DELUGE VALVE
(E) - EXISTING
FS - FLOW SWITCH
GC - GENERAL CONTRACTOR
NIC - NOT IN CONTRACT
IAW - IN ACCORDANCE WITH
PAV - PREACTION VALVE
PIV - POST INDICATOR VALVE
SYMBOLS
PENDANT SPRINKLER
Lt.E - LONG TURN ELBOW
PA - PUBLIC ADDRESS
OS&Y - OUTSIDE SCREW & YOKE
OC - ON CENTER
St - STRAINER
T- TEE-FLOW TURNED 90 DEGREES
TS - TAMPER SWITCH
UG - UNDERGROUND
UNO - UNLESS NOTED OTHERWISE
WCV - BUTTERFLY (wafer) CHECK VALVE
FIRE PROTECTION LEGEND
DRY PENDANT SPRINKLER
FLOW SWITCH
UPRIGHT SPRINKLER
STANDPIPE
DDCA - DOUBLE DETECTOR CHECK VALVE ASSEMBLY
FDC - FIRE DEPARTMENT CONNECTION
PENDANT SPRINKLER
HORIZONTAL SIDEWALL SPRINKLER
HORIZONTAL SIDEWALL SPRINKLERPENDANT SPRINKLER
HORIZONTAL SIDEWALL SPRINKLER
HORIZONTAL SIDEWALL SPRINKLER
HOSE CONNECTION
2/1
/2
01
7 5
:1
4:2
9 P
M
El P
aso, T
exas
TR
U b
y H
ilto
n - E
l P
as
o
Tru H
otel P
artners, LLC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
Release Date:
Project No.:
9
0
%
C
D
S
E
T
x
x
x
x
x
3/13/17
HAZARD CLASSIFICATIONS
A. OFFICES AND CONFERENCE AREAS: LIGHT HAZARD
B. GUEST ROOMS: LIGHT HAZARD
C. MECHANICAL EQUIPMENT ROOMS: ORDINARY HAZARD, GROUP 2
D. LAUNDRY ROOM: ORDINARY HAZARD, GROUP 1
E. PORTE COCHERE ORDINARY HAZARD, GROUP 1
F. ELECTRICAL ROOM: ORDINARY HAZARD, GROUP 1
FLOW TEST DATA
DATA PROVIDE BY: EL PASO WATER UTILITES
DATE: 5.9.2017
TEST PERFORMED BY: JESUS HALLER
TEST HYDRANT: 10177 & 10337
STATIC PRESSURE: 66 PSI
RESIDUAL PRESSURE: 63 PSI
FLOW: 1245 GPM
REQUIRED CONDITIONS:
DESIGN AREA #1: 60 PSI @ 350 GPM (W/ 100 GPM HOSE ALLOWANCE)
DESIGN AREA #2: 44 PSI @ 191 GPM (W/ 100 GPM HOSE ALLOWANCE)
DESIGN AREA #3: 60 PSI @ 274 GPM (W/ 100 GPM HOSE ALLOWANCE)
DESIGN AREA #4: 44 PSI @ 192 GPM (W/ 100 GPM HOSE ALLOWANCE)
DESIGN AREA #5: 58 PSI @ 441 GPM (W/ 250 GPM HOSE ALLOWANCE)
SAFETY FACTOR: 10% (MINIMUM 10% REQUIRED)
ADEQUATE WATER SERVICE AVAILABLE: YES
DRY SYSTEM VOLUME: 17 GALLONS
1
0
0
%
C
D
S
E
T
x
x
x
x
x
5/15/17
J
J
J
14
14
15
15
16
16
17
17
D D
C C
A A
B B
E E
F F
13
13
12
12
11
11
10
10
6
6
7
7
8
8
9
9
5
5
4
4
3
3
1
1
2
2
G G
0.a 0.a
COMMAND
CENTER
1001
VESTIBULE
1000
WORK ZONE
1002
LOUNGE
1003
FITNESS
1009
WATER/ICE
1008
GAME ZONE
1005
DINING
1004
PBX
1028
OFFICE
1030
G.M. OFFICE
1029
PANTRY
1027
CORRIDOR
1026
STAIR 2
S102
MECH
1024
RISER ROOM
1025
ELEVATOR
LOBBY
1006
WOMEN
1010
MEN
1011
EMPLOYEE
BREAK ROOM
1013
COORIDOR
1007A
ELEV. EQUIP
1015
LAUNDRY
1017
LINEN STORAGE
1016
DRYERS
019
WATER ROOM
1021
PASSAGE
1020
JANITOR
1022
ELECTRICAL
1023
STAIR 1
S101
GUEST
CORRIDOR
1007B
2
TYP
D
KING
102
104
QQ HEARING
106
108
101
103
105
ACC KING
SHOWER
HEARING
107
109
BREAKFAST
005
J
J
J
JJ
J
J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
PA-305
TYP.
PA-305
TYP.
ACT 03L 03
TYP.
L 03
TYP.
FIRE MAIN ENTERS BUILDING
SEE SHEET FP2.00 FOR RISER DETAIL
FIRE MAIN (SEE CIVIL FOR CONTINUATION)
SLEEVE PIPE WALL-PENETRATION
WATERTIGHT
ELECTRONIC ALARM BELL
4" CLASS 1 COMBINATION
WET STANDPIPE
4" CLASS 1 MANUAL
WET STANDPIPE
ALL SPRINKLER BRANCH LINES LOCATED IN
MAIN LOBBY AREA TO BE COORDINATED
WITH 2ND-FLOOR FLOOR JOISTS
UPRIGHTS TO BE INSTALLED
ABOVE CLOUDS (TYPICAL OF 10)
DESIGN AREA #1
DESIGN AREA #5
1" LINE DOWN TO
INSPECTORS TEST PORT
4"
2-1/2"
2" 2" 2" 2" 2" 2"
1"
1"1"
1"
1"
2"
BFP
1-1/2" 1-1/2" 1-1/2"
1"
1"
1"
1"
1"
FP1-01
1
SCALE: 1/8"= 1'-0"
FIRE PROTECTION - SPRINKLER - 1ST FLOOR
FIRE PROTECTION
SPRINKLER
1ST FLOOR
FP1-01
FIRE PROTECTION PLAN NOTES
1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE
ALARM SYSTEM.
2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF
SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.
3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON
DRAWING.
4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.
5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE
ASSEMBLIES ( SEE SHEET FP2-00 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.
6. COORDINATE ALL SPRINKLER BRANCH LINES AND MAINS IN THE LOBBY AREA
WITH ALL TRADES. SPACE IS LIMITED AND CAREFUL COORDINATION WILL BE
REQUIRED.
2/1
/2
01
7 5
:1
4:2
9 P
M
El P
aso, T
exas
TR
U b
y H
ilto
n - E
l P
as
o
Tru H
otel P
artners, LLC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
Release Date:
Project No.:
14 15 16 17
D D
C C
A A
B B
E E
cen cen
F F
131211106 7 8 95431 2
G G
ELEVATOR
LOBBY
2001
LINEN DROP
2002
LINEN AND
STORAGE
2004
STAIR 1
S101
STAIR 2
S102
CORRIDOR
2000
D8' - 0"
KING
202
204
206
208
ACC QUEEN
210
QQ CONNECTOR
212
KING
214
KING
216
KING
218
QQ HEARING
220
222
KING
224
KING
226
KING
227
KING
225
KING
223
KING HEARING
221
KING
219
KING
217
KING HEARING
215
KING
213
211
QQ CONECTOR
209
ACC KING
207
205
203
201
4" CLASS 1 COMBINATION
WET STANDPIPE
4" CLASS 1 MANUAL
WET STANDPIPE
14
14
15
15
16
16
17
17
D D
C C
A A
B B
E E
cen cen
F F
13
13
12
12
11
11
10
10
6
6
7
7
8
8
9
9
5
5
4
4
3
3
1
1
2
2
G G
ELEVATOR
LOBBY
3001
LINEN DROP
3002
LINEN AND
STORAGE
3004
STAIR 1
S101
STAIR 2
S102
CORRIDOR
3000
D8' - 0"
KING
302
304
306
308
ACC QUEEN
310
QQ CONNECTOR
312
KING
314
KING
316
KING
318
QQ HEARING
320
322
KING
324
KING
326
KING
327
KING
325
KING
323
KING HEARING
321
KING
319
KING
317
KING HEARING
315
KING
313
311
QQ CONECTOR
309
ACC KING
307
305
303
301
4" CLASS 1 COMBINATION
WET STANDPIPE
4" CLASS 1 MANUAL
WET STANDPIPE
FP1-02
1
SCALE: 1/8"= 1'-0"
FIRE PROTECTION - SPRINKLER - 2ND FLOOR
FIRE PROTECTION
SPRINKLER
2ND & 3RD FLOOR
FP1-02
FP1-02
2
SCALE: 1/8"= 1'-0"
FIRE PROTECTION - SPRINKLER - 3RD FLOOR
2/1
/2
01
7 5
:1
4:2
9 P
M
El P
aso, T
exas
TR
U b
y H
ilto
n - E
l P
as
o
Tru H
otel P
artners, LLC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
Release Date:
Project No.:
FIRE PROTECTION PLAN NOTES
1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE
ALARM SYSTEM.
2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF
SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.
3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON
DRAWING.
4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.
5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE
ASSEMBLIES ( SEE SHEET FP2-00 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.
6. COORDINATE ALL SPRINKLER BRANCH LINES AND MAINS IN THE LOBBY AREA
WITH ALL TRADES. SPACE IS LIMITED AND CAREFUL COORDINATION WILL BE
REQUIRED.
14 15 16 17
D D
C C
A A
B B
E E
cen cen
F F
131211106 7 8 95431 2
G G
ELEVATOR
LOBBY
4001
LINEN DROP
4002
LINEN AND
STORAGE
4004
STAIR 1
S101
STAIR 2
S102
CORRIDOR
4000
D8' - 0"
KING
402
404
406
408
ACC QUEEN
410
QQ CONNECTOR
412
KING
414
KING
416
KING
418
QQ HEARING
420
422
KING
424
KING
426
KING
427
KING
225
KING
423
KING HEARING
421
KING
419
KING
417
KING HEARING
415
KING
413
411
QQ CONECTOR
409
ACC KING
407
405
403
401
4" CLASS 1 COMBINATION
WET STANDPIPE
4" CLASS 1 MANUAL
WET STANDPIPE
DESIGN AREA #2
DESIGN AREA #3
DESIGN AREA #4
2-1/2"
2-1/2" 2-1/2"
2"
2" 2"
2"
2" 2"
1-1/4" 1-1/4"
1-1/4"
1-1/4"
1-1/4"
FIRE PROTECTION
SPRINKLER
4TH FLOOR
FP1-03
FP1-04
1
SCALE: 1/8"= 1'-0"
FIRE PROTECTION - SPRINKLER - 4TH FLOOR
2/1
/2
01
7 5
:1
4:2
9 P
M
El P
aso, T
exas
TR
U b
y H
ilto
n - E
l P
as
o
Tru H
otel P
artners, LLC
16105
Revision Schedule
Rev.
Num. Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
Release Date:
Project No.:
FIRE PROTECTION PLAN NOTES
1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE
ALARM SYSTEM.
2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF
SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.
3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON
DRAWING.
4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.
5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE
ASSEMBLIES ( SEE SHEET FP2-00 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.
6. COORDINATE ALL SPRINKLER BRANCH LINES AND MAINS IN THE LOBBY AREA
WITH ALL TRADES. SPACE IS LIMITED AND CAREFUL COORDINATION WILL BE
REQUIRED.
FIRE PROTECTION
RISER DIAGRAM
FP2-00
SCALE: NONE
RISER DETAIL
PIPE
FIRE RESISTANT
SILICONE FOAM SEALER
CUT OPENING IN MASONRY WALL
LARGER THAN SLEEVE, THEN FORM &
FILL WITH EXPANSIVE TYPE GROUT.
PIPE INSULATION (WHERE REQ'D)
ESCUTCHEON PLATE ON ONE
OR BOTH SIDES WHERE
PIPING IS EXPOSED
PIPE SLEEVE
ANCHOR LUGS (MIN. 3 REQ'D)
EXISTING POURED CONCRETE
OR C.M.U. WALL.
NOTES:
1. FOR INTERIOR WALLS
AND BELOW GRADE
WALLS.
SEAL SPACE AROUND
PIPE WITH FIREPROOF
CAULKING.
PIPE SLEEVE
FINISHED FLOOR
5/8" ∅ BOLT
FURNISH LEAD
SHIELDS FOR BRASS
OR COPPER PIPING
PIPE
3/8" THK. STEEL X 1/2" MIN.
PIPE CLAMP WITH EXTENTION
ARMS
SCALE: NONE
PIPE RISER SUPPORT DETAIL
SCALE: NONE
PIPE SLEEVE THROUGH WALL DETAIL
SCALE: NONE
UPRIGHT & PENDANT INSTALLATION DETAIL
PENDANT
SPK'R. HEAD
1" BRANCH
LINE
1" BRANCH
LINE
INCREASER
UPRIGHT
SPK'R. HEAD
BRANCH LINE
SPRINKLER MAIN
WELDED.
EMERY PAPER. ATTACHMENT MAY BE SPOT
SMOOTH SCREW HEADS WITH FILE OR
SHEET METAL SCREWS AT 2" ON CENTER.
A
FRONT ELEVATION
SECTION A-A
6"
RADIUS.
CHUTE
WALL
1"
20 GAUGE STEEL
SPRINKLER
SHIELD
3"
18 "
SCALE: NONE
PENDANT HEAD IN LAUNDRY CHUTE DETAIL
FINISHED FLOOR
2 1/2" FDV (WITH 1-1/2" ADAPTER)
4" FIRE MAIN
2" DRAIN RISER
SECTIONAL DRAIN VALVE
TEST VALVE
UNION WITH CORROSION RESISTANT ORIFICE
SIGHT GLASS
3" 3"
TO SYSTEM
WATERFLOW SWITCH-VANE TYPE
INDICATING TYPE FLOOR CONTROL
VALVE WITH TAMPER SWITCH
CHECK VALVE
INSPECTOR'S TEST CONNECTION
TO SYSTEM
TYPICAL FLOOR CONTROL VALVE DETAIL
SCALE: NONE
FIRE SERVICE PIPING
12" A.F.F.
BLIND FLANGE UNTIL READY
TO CONNECT TO INSIDE FIRE
PIPING
CAST IRON FLANGE
AND SPIGOT PIECE
CAST IRON BELL
AND SPIGOT PIPE
RODS
TYPICAL FLOOR PENETRATION DETAIL
SCALE: NONE
4" FIRE MAIN
SPRINKLER MAIN
1" BRANCH
LINE
SEMI-RECESSED
PENDANT SPK'R. HEAD
FINISHED SURFACE
FINISHED SURFACE
1" BRANCH
LINE
SIDEWALL PENDANT DETAIL
SCALE: NONE
VICTAULIC 7C7 RISER MOUNTED
AIR COMPRESSOR (1/6 HP)
TO CLASS 1 MANUAL STANDPIPE SYSTEM
TO CLASS 1 COMBINATION STANDPIPE SYSTEM
VICTAULIC 768 2-1/2" DRY SYSTEM VALVE
TO 1ST FLOOR WET SYSTEM WITH
FLOOR CONTROL VALVE
VIKING J-1 4" RISER CHECK VALVE
MONITORED BUTTERFLY VALVE (TYP.)
SYSTEM DRAIN
6" CITY MAIN
FINISHED FLOOR
SPRINKLER HEAD SCHEDULE
SYMBOL
QTY
MFG. SIN TYPE RESPONSE TEMPERATURE K-FACTOR DESCRIPTION
97 VIKING VK302 PENDANT
QUICK
155 °F 5.6
SEMI-RECESSED, WHITE
9 VIKING VK176 PENDANT
QUICK
200 °F 5.6
DRY PENDANT, BRASS
113 VIKING VK302 PENDANT
QUICK
155 °F 5.6
SEMI-RECESSED, WHITE
12 VIKING VK300 UPRIGHT
QUICK
155 °F 5.6
UPRIGHT, BRASS
90 VIKING VK460 SIDEWALL
QUICK
155 °F 5.6
HORIZONTAL SIDEWALL, WHITE
27 VIKING VK638 SIDEWALL
QUICK
155 °F 8.0
CORRIDOR SPECIAL SPRINKLER, WHITE
4 VIKING VK305 SIDEWALL
QUICK
155 °F 5.6
HORIZONTAL SIDEWALL, BRASS
4 VIKING VK302 PENDANT
QUICK
155 °F 5.6
LAUNDRY CHUTE, BRASS
3 VIKING VK277 SIDEWALL
QUICK
200 °F 8.0
DRY SIDEWALL, BRASS
ALARM FLOW SWITCH (TYP)
METAL PIPE THROUGH GYPSUM WALL ASSEMBLY
SECTION A-A
FRONT VIEW
T RATING = 0-HR.
F RATING = 1-HR., 2-HR., 3-HR., OR 4-HR.
U.L. SYSTEM NO. W-L-1252
SEE HILTI FIRESTOP INSTALLATION MANUAL FOR ADDITIONAL INSTRUCTIONS
HILTI, INC. TULSA, OK 1-800-879-8000
NOT TO SCALE
1. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED U400, V400 OR W400 SERIES)
(1-HR., 2-HR., 3-HR., OR 4-HR FIRE-RATING) (4-HR. SHOWN)
2. STEEL STUDS TO BE MINIMUM 3-1/2" (SPACED MAXIMUM 24" OC).
3. PENETRATING ITEM:
A. MAXIMUM 4" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER)
4. HILTI FS-ONE MAX OR FS-ONE FIRESTOP SEALANT:
A. MINIMUM 5/8" DEPTH , FOR A 1-HR. OR 2-HR. FIRE-RATING
B. MINIMUM 1" DEPTH , FOR A 3-HR. OR 4-HR. FIRE-RATING
5. MINIMUM 1/2" BEAD HILTI FS-ONE MAX OR FS-ONE INTUMESCENT FIRESTOP
SEALANT APPLIED AT POINT OF CONTACT.
NOTES:
1. MAXIMUM DIAMETER OF OPENING = 5-3/4"
2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 7/8"
SECTION A-A
A
A
2
1
5
3
L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ FT
L-RATING AT 400F = LESS THAN 1 CFM/SQ FT
4
PIPE PENETRATION DETAIL
SCALE: NONE
NOT TO SCALE
CHECK VALVE
FDC
2/1
/2
01
7 5
:1
4:2
9 P
M
El P
aso, T
exas
TR
U b
y H
ilto
n - E
l P
as
o
Tru H
otel P
artners, LLC
16105
Revision Schedule
Rev.
Num.Rev. Date Revision Description
AEED,
Advanced Energy Engineering & Design, Inc
CHATTANOOGA, TN 37405
BUS. (423) 752-3438
FAX (423) 752-1369
P.O. BOX 4934
408 McCALLIE AVE
inc.
AEED JOB NO.001-17
COPYRIGHT NOTICE
THE DRAWINGS ARE THE
PROPERTY OF RIVER STREET
ARCHITECTURE LLC. ANY USE,
REUSE, REPRODUCTION,
DISPLAY OR SALE OF THESE
DRAWINGS WITHOUT THE
EXPRESS WRITTEN CONSENT
OF THE ARCHITECT IS
STRICTLY PROHIBITED.
Release Date:
Project No.: