Revisd Load Calculations Orchid Hospital

download Revisd Load Calculations Orchid Hospital

of 11

Transcript of Revisd Load Calculations Orchid Hospital

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    1/11

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    2/11

    Connected Load

    2.0TR 1.5TR 2.0TR 2.6TR 3.0TR Total Load in Watts Utilization Factor Effective Load

    0 0 0 0 0

    2200 1650 2200 2800 3300

    0 0 0 0 0 950 0.7 665

    0 0 0 0 0

    2200 1650 2200 2800 3300

    0 0 0 0 0 3800 0.8 3040

    1 0 0 2 0

    2200 0 0 2800 0

    2200 0 0 5600 0 11350 0.9 10215

    0 0 1 0 2

    2200 1650 2200 2800 3300

    0 0 2200 0 6600 8800 0.9 7920

    2 0 0 0 0

    2200 1650 2200 2800 3300

    4400 0 0 0 0 9850 0.5 4925

    2 2 0 0 0

    2200 1650 2200 2800 3300

    4400 3300 0 0 0 10300 0.65 6695

    0 0 0 0 0

    2200 1650 2200 2800 3300

    0 0 0 0 0 8050 0.8 6440

    0 0 0 0 0

    2200 1650 2200 2800 3300

    0 0 0 0 0 1650 0.25 412.5

    53100 40312.5

    Cassette

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    3/11

    30000

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    4/11

    Floor Wattage

    Basement 900

    Ground Floor 900

    Ground Floor Exterior Lighting 750

    First Floor 900Second Floor 900

    Third Floor 900

    Fourth Floor 900

    Fifth Floor 900

    Terrace Floor 500

    Total Lighting Load 7550

    Lighting Load Calculations

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    5/11

    Description of Load Nos. Load in Watts

    Bore Pump 5HP 1 3750

    Water Pump 3HP 1 2250

    Motors for Medical Gases 3HP 2 4500

    6 Passanger Lift 6HP 1 4500Stretcher Lift 12HP 1 9000

    Illuminated Signages 1 1500

    Fire Detection and Alarm Panel 1 250

    RO Plant on Terrace 1 750

    EPABX 1 150

    Music System / PA System 1 250

    Computer Networking Rack 1 1000

    Xerox Machine 1 1600

    CCTV System 1 250

    Kitchen Equipment - Oven 1 1500

    Kitchen Equipment - Refrigerator 1 500

    Kitchen Dish Washer 1 2000

    Kitchen Vending Machine 1 2200

    Kitchen Juicer / Mixer 1 750

    Drug Store Refrigerator Basement 2 750

    Pharmacy Store Refrigerator 1 250

    Autoclave Unit 1 15000

    Suction Pump 1HP Operation Theatre 1 750

    Operation Theater Lights 1 500

    Ventilator 1 1750

    Water Cooler 1 500

    Pressure Pump / Booster Pump 1 0

    Total Load in Watts 56200

    Load Calculati

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    6/11

    Utilization Factor Effective Load Type of Supply Type of Supply

    0.2 750 Normal Normal

    0.2 450 Normal Normal

    0.75 3375 DG Normal/DG

    0.8 3600 DG Normal/DG0.6 5400 DG Normal/DG

    0.25 375 Normal Normal

    1 250 DG NORMAL/UPS/DG

    1 750 DG Normal/DG

    1 150 DG NORMAL/UPS/DG

    0.5 125 DG NORMAL/UPS/DG

    1 1000 DG NORMAL/UPS/DG

    0.1 160 Normal Normal

    1 250 DG NORMAL/UPS/DG

    0.25 375 Normal Normal

    1 500 Normal Normal

    0.2 400 Normal Normal

    0.2 440 Normal Normal

    0.2 150 Normal Normal

    1 1500 Normal Normal

    1 250 Normal Normal

    0.2 3000 Normal Normal

    0.25 187.5 DG Normal/DG

    0.25 125 DG NORMAL/UPS/DG

    0.3 525 DG Normal/DG

    1 500 Normal Normal

    0.5 0 Normal Normal

    24587.5

    n Common Services

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    7/11

    Computer Wattage Total Printers Wattage Total Fans Wattage Total

    Basement 8 125 1000 4 165 660 6 55 330

    Ground Floor 1 125 125 1 165 165 6 55 330

    First Floor 7 125 875 1 165 165 3 55 165

    Second Floor 3 125 375 2 165 330 6 55 330

    Third Floor 1 125 125 3 165 495 10 55 550Fourth Floor 1 125 125 1 165 165 7 55 385

    Fifth Floor 10 125 1250 1 165 165 10 55 550

    Terrace 0 125 0 0 165 0 1 55 55

    Total 31 3875 13 2145 49 2695

    3875 2145

    I

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    8/11

    Exhaust Fans Wattage Total Geyser Wattage Total LCD TV Wattage Total

    0 45 0 0 2000 0 0 100 0

    1 45 45 0 2000 0 0 100 0

    1 45 45 1 2000 2000 4 100 400

    3 45 135 1 2000 2000 1 100 100

    1 45 45 0 2000 0 1 100 1004 45 180 4 2000 8000 5 100 500

    2 45 90 1 2000 2000 1 100 100

    1 45 45 1 2000 2000 0 100 0

    13 585 8 16000 12 1200

    / Electrical Devices

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    9/11

    Floorwise Total Wattage

    1990

    665

    3650

    3270

    13159355

    4155

    2100

    26500

    10500

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    10/11

    Summary of Connected Load Watts

    AC Installations 53100

    Lighting Load 7550

    Common Load 56200

    Computers/ Printers /Fans/ LCD etc. 10500

    Geysers 16000Total Load in Watts 143350

    Add Load of 6A Receptacles - 12 Nos X 6 Floors 7200

    Add Load of 16A Receptacles - 3 Nos X 6 Floors 18000

    Add Fire Pump 0

    Total Load 168550

    Total Load after 90% Diversity 151695

    1) 2 Nos. of Lifts, 1 No. for Bore and 1 No. Water Pump

    2) Remainimg Load / ( Maximum Possible )

    Rating of Probable Equipment Sizing

    UPS - 15KVA Minimum - 20KVA Maximum with 3Phase Input and Single

    DG Set - 100KVA Minimum - 125KVA Maximum with AMF Panel

    Try Two Separate Connections for

  • 8/13/2019 Revisd Load Calculations Orchid Hospital

    11/11

    Effective Load

    40312.5

    5662.5

    24587.5

    6300

    400080862.5

    1440

    1800

    0

    84102.5

    75692.25

    20HP

    85KW / 90KW

    Phase Output