>> runpf('case5') MATPOWER Version 5.1, 20-Mar-2015 -- AC Power Flow (Newton) Newton's method power flow converged in 3 iterations. Converged in 0.70 seconds ================================================================================ | System Summary | ================================================================================ How many? How much? P (MW) Q (MVAr) --------------------- ------------------- ------------- ----------------- Buses 5 Total Gen Capacity 1530.0 -1147.5 to 1147.5 Generators 5 On-line Capacity 1530.0 -1147.5 to 1147.5 Committed Gens 5 Generation (actual) 1005.0 371.3 Loads 3 Load 1000.0 328.7 Fixed 3 Fixed 1000.0 328.7 Dispatchable 0 Dispatchable -0.0 of -0.0 -0.0 Shunts 0 Shunt (inj) -0.0 0.0 Branches 6 Losses (I^2 * Z) 5.03 50.27 Transformers 0 Branch Charging (inj) - 7.7 Inter-ties 0 Total Inter-tie Flow 0.0 0.0

description

dfgh

Transcript of Result Power Flow

Page 1: Result Power Flow

>> runpf('case5')

MATPOWER Version 5.1, 20-Mar-2015 -- AC Power Flow (Newton)

Newton's method power flow converged in 3 iterations.

Converged in 0.70 seconds

================================================================================

| System Summary |

================================================================================

How many? How much? P (MW) Q (MVAr)

--------------------- ------------------- ------------- -----------------

Buses 5 Total Gen Capacity 1530.0 -1147.5 to 1147.5

Generators 5 On-line Capacity 1530.0 -1147.5 to 1147.5

Committed Gens 5 Generation (actual) 1005.0 371.3

Loads 3 Load 1000.0 328.7

Fixed 3 Fixed 1000.0 328.7

Dispatchable 0 Dispatchable -0.0 of -0.0 -0.0

Shunts 0 Shunt (inj) -0.0 0.0

Branches 6 Losses (I^2 * Z) 5.03 50.27

Transformers 0 Branch Charging (inj) - 7.7

Inter-ties 0 Total Inter-tie Flow 0.0 0.0

Page 2: Result Power Flow

Minimum Maximum

------------------------- --------------------------------

Voltage Magnitude 0.989 p.u. @ bus 2 1.000 p.u. @ bus 4

Voltage Angle -0.76 deg @ bus 2 4.11 deg @ bus 5

P Losses (I^2*R) - 1.77 MW @ line 1-2

Q Losses (I^2*X) - 17.67 MVAr @ line 1-2

================================================================================

| Bus Data |

================================================================================

Bus Voltage Generation Load

# Mag(pu) Ang(deg) P (MW) Q (MVAr) P (MW) Q (MVAr)

----- ------- -------- -------- -------- -------- --------

1 1.000 3.273 210.00 30.73 - -

2 0.989 -0.759 - - 300.00 98.61

3 1.000 -0.492 323.49 194.65 300.00 98.61

4 1.000 0.000* 5.03 184.12 400.00 131.47

5 1.000 4.112 466.51 -38.21 - -

-------- -------- -------- --------

Total: 1005.03 371.29 1000.00 328.69

Page 3: Result Power Flow

================================================================================

| Branch Data |

================================================================================

Brnch From To From Bus Injection To Bus Injection Loss (I^2 * Z)

# Bus Bus P (MW) Q (MVAr) P (MW) Q (MVAr) P (MW) Q (MVAr)

----- ----- ----- -------- -------- -------- -------- -------- --------

1 1 2 249.77 21.60 -248.01 -4.64 1.767 17.67

2 1 4 186.50 -13.61 -185.44 23.58 1.063 10.63

3 1 5 -226.27 22.74 226.60 -22.55 0.331 3.31

4 2 3 -51.99 -93.97 52.12 93.39 0.125 1.25

5 3 4 -28.63 2.65 28.65 -3.08 0.025 0.25

6 4 5 -238.19 32.15 239.91 -15.66 1.716 17.16

-------- --------

Total: 5.027 50.27