Inspection Report Restaurant Property Address: 19 Indian Trail Lilburn Rd Norcross GA South East Building Consultants Ray Thoroman Atlanta GA Page 1 of 43 19 Indian Trail Lilburn Rd

Transcript of Restaurant · scope it should be disclosed in your agreement. A PCR is a written report, prepared...

  • Inspection Report

    Restaurant

    Property Address:19 Indian Trail Lilburn Rd

    Norcross GA

    South East Building Consultants

    Ray Thoroman Atlanta GA

    Page 1 of 4319 Indian Trail Lilburn Rd

  • 678-410-3005

    Serving Atlanta GA and the Entire South East

    Page 2 of 4319 Indian Trail Lilburn Rd

  • Table of Contents

    Cover Page

    Table of Contents

    Intro Page

    1 General Physical Condition

    2 Utilities

    3 Structural Frame and Building Envelope

    4 Mechanical and Electrical System

    5 Common Areas (Interior)

    6 Additional Considerations

    Summary

    Invoice

    Page 3 of 4319 Indian Trail Lilburn Rd

  • Date: 6/24/2013 Time: 09:45 AM Report ID: 062413-4

    Property:19 Indian Trail Lilburn RdNorcross GA

    Customer:Restaurant

    Real Estate Professional:

    Executive Summary:

    This is a Property Condition Report "PCR" using the ASTM E2018 as a standard guideline to describe the condition of building or buildings for the property inspected. This process involves observation of the property by a person or entity. It can include interviews of sources, and reviews of available documentation for the purpose of developing an opinion and preparing a PCR of a commercial real estate's current physical condition. At the option of the user, a PCA may include a higher level of inquiry and due diligence than the

    baseline scope described within this guide or, at the users option, it may include a lower level of inquiry or due diligence than the baseline scope described in this guide. If there are such deviations from this guides scope it should be disclosed in your agreement. A PCR is a written report, prepared in accordance with the recommendations contained in this guide, that outlines the consultants observations, opinions as to the subject property"s condition.

    In defining good commercial and customary practice for conducting a baseline PCA, the goal is to identify and communicate physical deficiencies to a user. The term physical deficiencies means the presence of conspicuous defects or material deferred maintenance of a subject property material systems, components,

    or equipment as observed during the field observers walk-through survey. This definition specifically excludes deficiencies that may be remedied with routine maintenance, miscellaneous minor repairs, normal operating maintenance, etc., and excludes de minimis conditions that generally do not present material physical deficiencies of the subject property. A walk-through survey, conducted during the field observers site visit of the subject property, that consists of nonintrusive visual observations, survey of readily

    accessible, easily visible components and systems of the subject property. Concealed physical deficiencies are excluded. It is the intent of this guide that such a survey should not be considered technically exhaustive. It excludes the operation of equipment by the field observer and is to be conducted without the aid of special protective clothing, exploratory probing, removal of materials, testing, or the use of equipment, such as scaffolding, metering/testing equipment, or devices of any kind, etc. It is literally the

    field observers visual observations while walking through the subject property.

    The purpose of the PCA is to observe and report, to the extent feasible pursuant to the processes prescribed herein, on the physical condition of the subject property.

    Deviations from the Guide: Please see signed agreement proposal.

    Recommendations: It is recommended that the user of this report review both summaries and the entire

    report. The complete report may include additional information of concern.

    This property and subsequent building (s) has been inspected by Ray Thoroman of South East Building Consultants.

    Comment Key and Definitions:

    The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair, replace, or require immediate attention suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair

    Page 4 of 4319 Indian Trail Lilburn Rd

  • or replacement of item, component or unit should be considered before you purchase the

    property.

    Inspected: This term means I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing normal wear and

    tear. The notation does not mean that the item is perfect but does meet a reasonable standard on the day of inspection.

    Repair or Replace: The item, component or unit is not functioning as intended or needs further

    inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

    Requires Immediate Attention: The item, component or unit needs immediate attention by a qualified professional or contractor for the safety or health of the occupants of the building.

    Could cause further major deterioration, or complete failure of a system or component. Worsen appreciably, cause damage, or be a serious hazard.

    Not Inspected: I did inspect this item, component or unit and made no representations of

    whether or not it was functioning as intended and will state a reason for not testing or operating

    Building Use:

    Restaurant

    Construction Type:

    Frame and Stucco

    Number of floors/stories:

    1- Story

    Age Of building:

    Approximately built in 1985

    Client Is Present:

    No

    Weather:

    Part Cloudy

    Temperature:Over 75

    Page 5 of 4319 Indian Trail Lilburn Rd

  • 1. General Physical Condition

    Items

    A. Basic Information Inspected

    Hello Kari,

    Thank you for allowing me to inspect your future building again! During the time you own the building you may call me anytime

    for information about anything in this report, or anything else you need to know or understand.

    This Inspection Report will be uploaded to my web server for 3 years after I email it to you, the report can be forwarded to anyone

    by simply forwarding the email sent to view the report.If you have any questions please do not hesitate in calling or email with any further help regarding the inspection.

    Thank You,

    Ray Thoroman

    South East Building Consultants [email protected] 404-698-0404

    B. Purpose and Scope Inspected

    You have contracted with us to through verbal communication and email(s) to perform an inspection inaccordance with ASTM industry standards for the commercial inspection profession. This is differentfrom our technically exhaustive inspection which takes several days to complete, involves the use of

    specialized instruments, the dismantling of equipment, video scanning, destructive testing andlaboratory analysis of possible contaminates. Our purpose is to identify defects or adverse conditionsthat need repair or replacement, are safety concerns or may lead to costs that would significantly affectyour evaluation of the property at the time of this inspection.

    The purpose of the Inspection is to document in a narrative format the condition of the building at thetime of the inspection. The inspection is a visual snapshot in time regarding the condition of the

    systems and components of the building at the time of the inspection and is not a warranty nor aninsurance policy, but that should not deter you purchasing such a policy.

    As with all building systems, components, items, etc; need to be maintained properly though the years. We do not document items which are cosmetic in nature or would be apparent to the average person or document items that pertain to an 30 year old building such as loose door knobs, paint, interior walls, scratches or items of that nature. Pictures are placed in the report as a courtesy to help you understand

    the reason for the narrative.

    There is an summary at the end of this report which you could use as a check-list if needed. Pleaseread the entire report.

    C. Topography

    Inspected

    The grounds are generally level around the building with positive drainage away from the structure.

    Page 6 of 4319 Indian Trail Lilburn Rd

  • C. Item 1(Picture) C. Item 2(Picture)

    D. Paving, Curbing and Parking Repair or Replace

    Asphalt parking lot was in general good condition. Several small depressions and average small cracking, you may want to seal these cracks. Some of the concrete curbing was damaged and/or cracked. Recommend general repairs of curbing as needed.

    D. Item 1(Picture) D. Item 2(Picture)

    D. Item 3(Picture) D. Item 4(Picture)

    E. Flatwork (sidewalks, plazas, patios) Repair or Replace

    Page 7 of 4319 Indian Trail Lilburn Rd

  • Concrete walkways/sidewalks had a few cracks in a few areas. Recommend repairing to prevent further

    damage or injury.

    E. Item 1(Picture)

    F. Landscaping and Appurtenances Repair or Replace

    As a courtesy the drive thru sign had noticeable damage. Recommend repair as needed.

    F. Item 1(Picture) F. Item 2(Picture)

    G. DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS Inspected

    Styles & Materials

    General Topography: Flat

    Page 8 of 4319 Indian Trail Lilburn Rd

  • 2. Utilities

    Items

    A. Water Inspected

    The water source is the public utility company. Main water shut-off was located in rear storage area.

    A. Item 1(Picture)

    B. Electricity Inspected

    The source for electricity is the public utility company.

    C. Natural gas Inspected

    The fuel source is natural gas and is supplied by the public utility company.

    C. Item 1(Picture)

    D. Sanitary Sewer Inspected

    Sanitary waste discharges into the municipal sewer at the street.

    Page 9 of 4319 Indian Trail Lilburn Rd

  • Styles & Materials

    Water Source: Public Utility

    Electric source: Power company Public Utility

    Gas supply: Natural Gas

    Sanitary Sewer: Public sewer system

    Page 10 of 4319 Indian Trail Lilburn Rd

  • 3. Structural Frame and Building Envelope

    Items

    A. Foundation Inspected

    B. Building Frame Immediate Attention!

    There was evidence of water stains at drop ceiling above the main electrical service panels. There was also evidence of water damage (deterioration) and stains at the roof plywood decking in the same area (below the roof electric weather head). Recommend repair the structure damage by qualified roof contractor. Repair all other damage as needed by qualified contractor.

    B. Item 1(Picture) B. Item 2(Picture)

    B. Item 3(Picture)

    B. Item 4(Picture)

    C. Sidewall System (exterior wall cladding and components) Repair or Replace

    (1) Stucco cladding was in good condition overall. There were several small hairline cracks around window/door openings. Recommend seal cracks to prevent moisture intrusion.

    Page 11 of 4319 Indian Trail Lilburn Rd

  • C. Item 1(Picture) C. Item 2(Picture)

    (2) Landscape ground cover has caused small negative sloping toward the building. It is also in contact with the exterior cladding and lower windows. Recommend correcting issues to prevent moisture damage or wood destroy insects.

    C. Item 3(Picture) C. Item 4(Picture)

    C. Item 5(Picture)

    D. Fenestration System (i.e. windows, openings, doors etc.) Inspected

    E. Parapets (protective wall barriers at balcony, roof etc.) Repair or Replace

    Page 12 of 4319 Indian Trail Lilburn Rd

  • Roof parapets had several small hairline cracks at stucco cladding. Sealant at metal cap seams were

    failing, several areas. Recommend small repairs to prevent further damage or moisture intrusion by qualified contractor.

    E. Item 1(Picture) Small cracks E. Item 2(Picture) Small cracks

    E. Item 3(Picture) Repair sealant E. Item 4(Picture)

    F. Roofing

    Repair or Replace

    (1) Roof coverings consisted of front metal pitched roof and TPO (Thermoplastic Polyolefin membrane) at flat roof.

    The metal roofing was in average condition. I recommend a new sealant coat for protection.

    The TPO roofing was in good condition for its age. I estimate it to be approximately 10 years old. Average life span of this roofing material varies significantly, but I would reasonably estimate at least

    10 more years life. No major leaking was noted. However there was several small puddles of water (from improper condensation piping not draining off roof) which can cause moisture intrusion. Routine maintainece and/or inspections of the covering are recommended. Recommend obtaining estimates for repairing the small dips at TPO covering to prevent moisture damage.

    Page 13 of 4319 Indian Trail Lilburn Rd

  • F. Item 1(Picture) Faded at metal roofing.

    Recommend new sealant coat.

    F. Item 2(Picture) Small dips in TPO covering

    F. Item 3(Picture) General roof views

    (2) Small lower roof canopy roofs had peeling paint or damaged top coat sealant. Recommend repair as needed.

    F. Item 4(Picture) F. Item 5(Picture)

    G. Gutters and downspouts Repair or Replace

    Rear gutters had some debris and standing water. Recommend cleaning and adjust slope.

    Page 14 of 4319 Indian Trail Lilburn Rd

  • G. Item 1(Picture)

    G. Item 2(Picture)

    Styles & Materials

    Foundation: Masonry Slab

    Building Type: EIFS (Exterior Insulation Finish System)

    Roof-Type: Gable Flat

    Roof Structure: Engineered wood trusses Plywood

    Sheathing

    Attic Insulation: None

    Ventilation: None found

    Exterior Entry Doors: Insulated glass

    Window Types: Thermal/Insulated

    Siding Style: Cement stucco

    Siding Material: EIFS

    Roof Covering: Metal

    TPO

    Viewed roof covering from: Ground

    Ladder Walked roof

    Page 15 of 4319 Indian Trail Lilburn Rd

  • 4. Mechanical and Electrical System

    Items

    A. Plumbing water supply and Distribution and Fixtures Immediate Attention!

    Water leak noted at main water piping below main shut-off. Recommend repair by qualified plumber.

    A. Item 1(Picture)

    B. Plumbing Drain, Waste and Vent Systems Inspected

    C. Domestic hot water production Not Inspected

    (1) Fresh air intake was noted at roof for rear storage (where tank-less water heater was located)

    room. This may not be needed as it was likely used for the old tank water heater system.

    C. Item 1(Picture)

    (2) Tank-less water heater had stored items in front of it and shelving was in direct contact with unit. Minimum 4 inch clearance is required. Gas line did not have a proper shut-off valve. Recommend correct issues by qualified contractor to prevent injury or damage.

    Page 16 of 4319 Indian Trail Lilburn Rd

  • C. Item 2(Picture) C. Item 3(Picture)

    C. Item 4(Picture)

    D. Heating & Air conditioning and Ventilation Equipment Repair or Replace

    (1) There were 4 roof top HVAC packaged units. Three were in use and one was not in use or operable. The one not in use was 28 years old. I recommend removing the system from the roof. There was one

    additional stand alone AC unit (small) and it was approximately 6 years old.

    The other 3 units were 6,8 and 13 years old. The average life of these units are approximately 10-20 years. I recommend budget replacement accordingly.

    Page 17 of 4319 Indian Trail Lilburn Rd

  • D. Item 1(Picture) D. Item 2(Picture) Old unit not in use.

    Recommend removing.

    D. Item 3(Picture) Small AC unit D. Item 4(Picture)

    D. Item 5(Picture) D. Item 6(Picture)

    (2) Roof HVAC unit condensation piping was damaged or did not properly discharge off the roof for all units. Suction line insulation was aged/damaged for all units. General wear/dust was noted at filter,

    blower motor and service compartments. Electrical wiring conduit was faded/aged/cracked. I recommend general service and repair these items by licensed HVAC contractor.

    Page 18 of 4319 Indian Trail Lilburn Rd

  • D. Item 7(Picture) Broken condensate line

    causing standing water

    D. Item 8(Picture) Broken condensate line

    causing standing water

    D. Item 9(Picture) Condensate line not properly connected

    D. Item 10(Picture)

    D. Item 11(Picture) D. Item 12(Picture)

    Page 19 of 4319 Indian Trail Lilburn Rd

  • D. Item 13(Picture) D. Item 14(Picture) Replace suction line

    insulation

    D. Item 15(Picture) Replace electrical conduit wiring where needed

    D. Item 16(Picture)

    (3) HVAC thermostat controls.

    Page 20 of 4319 Indian Trail Lilburn Rd

  • D. Item 17(Picture) D. Item 18(Picture)

    D. Item 19(Picture)

    E. Electric Service and Meter Immediate Attention!

    (1) The electrical service conductors at roof weather head are frayed at wire sheathing. There were screws and a neutral wire in contact with the main conductor wiring. This is considered an safety issue.

    Recommend immediate repair by qualified licensed electrician.

    Page 21 of 4319 Indian Trail Lilburn Rd

  • E. Item 1(Picture) Frayed outside sheathing E. Item 2(Picture) Frayed outside sheathing

    E. Item 3(Picture) Safety issue E. Item 4(Picture) Safety issue

    (2) Electrical service was a 3- phase 600 amp 208/120v system.

    There were multiple issues noted at the main electrical service panels in rear storage room. One service panel was blocked off with storage shelving (needs 3ft clearance) and the other panels had open knock outs, breakers were not properly identified, and multiple double taps. Right panel C had evidence of excessive heat at several breakers including evidence of water damage from an old roof leak above.

    Further damage or injury may occur. Recommend correct all issues by licensed electrician.

    Page 22 of 4319 Indian Trail Lilburn Rd

  • E. Item 5(Picture) Double tapping E. Item 6(Picture) Double tapping

    E. Item 7(Picture) E. Item 8(Picture)

    E. Item 9(Picture) Inaccessible panel. I could not inspect this panel.

    E. Item 10(Picture) Double tapping

    Page 23 of 4319 Indian Trail Lilburn Rd

  • E. Item 11(Picture) Water damage

    E. Item 12(Picture) Example of missing knock-

    outs

    E. Item 13(Picture) E. Item 14(Picture)

    Page 24 of 4319 Indian Trail Lilburn Rd

  • E. Item 15(Picture) E. Item 16(Picture)

    E. Item 17(Picture) Inaccessible panel.

    E. Item 18(Picture) Improper fasteners used for panel cover

    Page 25 of 4319 Indian Trail Lilburn Rd

  • E. Item 19(Picture) E. Item 20(Picture)

    E. Item 21(Picture)

    F. Electric Distribution Repair or Replace

    (1) Conduit electrical wiring at roof was aged and deteriorated for mechanical equipment, including loose connectors. One section had open end wiring. Recommend repair issues by licensed electrician.

    F. Item 1(Picture) Open wiring F. Item 2(Picture) Loose/failing connection

    (2) Open J-boxes noted at parking lot lights. Recommend correct by qualified electrician.

    Page 26 of 4319 Indian Trail Lilburn Rd

  • F. Item 3(Picture) F. Item 4(Picture)

    (3) Electrical wiring and receptacle near wash station was not properly secured. Receptacles were damaged/defective. Recommend correct issues by licensed electrician.

    F. Item 5(Picture)

    G. Exhaust, Vents Repair or Replace

    (1) Rooftop kitchen exhaust vent had grease build-up (left side). Recommend clean/maintenance. Also it appears that the old (brown) exhaust system was not in use or it had parts (belts) that were disconnected. Either repair this unit if in use or disconnect it as it is wasting electricity.

    Middle kitchen exhaust vent also had parts missing or not functioning properly. Recommend repair as needed.

    Page 27 of 4319 Indian Trail Lilburn Rd

  • G. Item 1(Picture) Recommend cleaning G. Item 2(Picture) Newer exahaust

    G. Item 3(Picture) Middle exhaust G. Item 4(Picture) Loose/damaged parts for middle exhaust

    Page 28 of 4319 Indian Trail Lilburn Rd

  • G. Item 5(Picture) Old brown exhaust had

    missing/loose parts

    G. Item 6(Picture)

    G. Item 7(Picture)

    (2) I did not inspect any refrigeration, chiller, or ice maker equipment at the roof. However as a courtesy several issues were noted with this equipment and general service or maintainece is needed/recommended.

    Page 29 of 4319 Indian Trail Lilburn Rd

  • G. Item 8(Picture) G. Item 9(Picture)

    G. Item 10(Picture) G. Item 11(Picture) Aged chiller equipment

    G. Item 12(Picture)

    Page 30 of 4319 Indian Trail Lilburn Rd

  • Styles & Materials

    Plumbing Water Supply

    (into building): Not visible

    Plumbing Water Distribution

    (inside building): Copper

    Plumbing Waste: PVC

    Water Heater Power Source: Gas (quick recovery)

    Water Heater Capacity: Tankless

    Water Heater Manufacturer: NORITZ

    Water Heater Location: Utility Room

    Heat Type: Forced Air

    Number of Heat Systems (excluding wood): Three

    Energy Source for Heat: Natural gas

    Heat System Brand: LENNOX

    TRANE

    Ductwork: Non-insulated

    Cooling Equipment Type: Air conditioner unit

    Cooling Equipment Energy Source: Electricity

    Central Air Manufacturer: LENNOX

    TRANE

    THERMA ZONE

    Number of AC Only Units: Four

    Electrical Service Conductors: Overhead service

    Aluminum 3 Phase

    Panel capacity: 100 AMP

    2 -225 AMP

    Panel Type: Circuit breakers

    Electric Panel Manufacturer: ITE

    Page 31 of 4319 Indian Trail Lilburn Rd

  • 5. Common Areas (Interior)

    Items

    A. Ceiling, Walls, Floors Inspected

    (1) General interior views. Dinning room was in general good condition. Bathrooms were in general

    good condition. Rear storage room and kitchen areas were in average condition.

    A. Item 1(Picture) A. Item 2(Picture)

    A. Item 3(Picture) A. Item 4(Picture)

    Page 32 of 4319 Indian Trail Lilburn Rd

  • A. Item 5(Picture) A. Item 6(Picture)

    A. Item 7(Picture) A. Item 8(Picture)

    Page 33 of 4319 Indian Trail Lilburn Rd

  • A. Item 9(Picture) A. Item 10(Picture)

    A. Item 11(Picture)

    (2) Suspended drop ceiling had several areas of damage at tile, frame and tracks. Recommend repair issues as needed to prevent possible injury or further damage.

    Page 34 of 4319 Indian Trail Lilburn Rd

  • A. Item 12(Picture) A. Item 13(Picture)

    A. Item 14(Picture)

    B. Building Amenities or special features (if any, i.e. spas, fountains, restaurants, etc.) Inspected

    C. Windows and Doors Repair or Replace

    Men bathroom door had some damage. Repair as needed.

    Page 35 of 4319 Indian Trail Lilburn Rd

  • C. Item 1(Picture)

    Styles & Materials

    Ceiling Materials: Suspended ceiling panels

    Wall Material: Paneling

    Floor Covering(s): Carpet Tile

    Page 36 of 4319 Indian Trail Lilburn Rd

  • 6. Additional Considerations

    Additional Considerations:

    There may be additional or conditions at a property that users may wish to assess in connection with commercial real

    estate that are outside the scope of this guide (Out of Scope considerations). Outside Standard Practices. Whether or not a user elects to inquire into non-scope considerations in connection with this guide or any other PCA is not

    required for compliance by this guide. Other standards or protocols for assessment of conditions associated with non-scope conditions may have been developed by governmental entities, professional organizations, or other private

    entities.

    Additional Issues:

    Following are several non-scope considerations that users may want to assess in connection with E 2018 commercial real estate. No implication is intended as to the relative importance of inquiry into such non-scope considerations,

    and this list of non-scope considerations is not intended to be all-inclusive: Seismic Considerations, Design Consideration for Natural Disasters (Hurricanes, Tornadoes, High Winds, Floods, Snow, etc.), Insect/Rodent

    Infestation, Environmental Considerations, ADA Requirements, FFHA Requirements, Indoor Air Quality, and Property

    Security Systems.

    Items

    A. Document Review and Interviews Not Inspected

    No documents were reviewed and no one was present to interview. Only a shift manager was present

    with limited broken english.

    B. Out of Scope Considerations Not Inspected

    Activity Exclusions—The activities listed below generally are excluded from or otherwise represent limitations to the scope of a PCA prepared in accordance with this guide. These should not be construed

    as all-inclusive or imply that any exclusion not specifically identified is a PCA requirement under this guide. Removing or relocating materials, furniture, storage containers, personal effects, debris material or finishes; conducting exploratory probing or testing; dismantling or operation. This should include material life-safety/building code violations. ing of equipment or appliances; or disturbing personal items or property, that obstructs access or visibility. Preparing engineering calculations (civil, structural,

    mechanical, electrical, etc.) to determine any system’s, component’s, or equipment’s adequacy or compliance with any specific or commonly accepted design requirements or building codes, or preparing designs or specifications to remedy any physical deficiency. Taking measurements or quantities to establish or confirm any information or representations provided by the owner or user, such as size and dimensions of the subject property or subject building; any legal encumbrances, such as easements;

    dwelling unit count and mix; building property line setbacks or elevations; number and size of parking spaces; etc. Reporting on the presence or absence of pests such as wood damaging organisms, rodents, or insects unless evidence of such presence is readily apparent during the course of the field observer’s walk-through survey or such information is provided to the consultant by the owner, user, property manager, etc. The consultant is not required to provide a suggested remedy for treatment or

    remediation, determine the extent of infestation, nor provide opinions of probable costs for treatment or remediation of any deterioration that may have resulted. Reporting on the condition of subterranean conditions, such as underground utilities, separate sewage disposal systems, wells; systems that are either considered process related or peculiar to a specific tenancy or use; wastewater treatment plants; or items or systems that are not permanently installed. Entering or accessing any area of the premises

    deemed to pose a threat of dangerous or adverse conditions with respect to the field observer or to perform any procedure, that may damage or impair the physical integrity of the property, any system, or component. Providing an opinion on the condition of any system or component, that is shutdown, or whose operation by the field observer may increase significantly the registered electrical demand-load; however, the consultant is to provide an opinion of its physical condition to the extent reasonably

    possible considering its age, obvious condition, manufacturer, etc. Evaluating acoustical or insulating characteristics of systems or components. Providing an opinion on matters regarding security of the subject property and protection of its occupants or users from unauthorized access. Operating or

    Page 37 of 4319 Indian Trail Lilburn Rd

  • witnessing the operation of lighting or other systems typically controlled by time clocks or that are

    normally operated by the building’s operation staff or service companies. Providing an environmental assessment or opinion on the presence of any environmental issues such as asbestos, hazardous wastes, toxic materials, the location and presence of designated wetlands, IAQ, etc.Warranty, Guarantee, and Code Compliance Exclusions: By conducting a PCA and preparing a PCR, the consultant merely is providing an opinion and does not warrant or guarantee the present or

    future condition of the subject property, nor may the PCA be construed as either a warranty or guarantee of any of the following: Any system’s or component’s physical condition or use, nor is a PCA to be construed as substituting for any system’s or equipment’s warranty transfer inspection; Compliance with any federal, state, or local statute, ordinance, rule or regulation including, but not limited to, building codes, safety codes, environmental regulations, health codes or zoning ordinances

    or compliance with trade/design standards or the standards developed by the insurance industry; however, should there be any conspicuous material present violations observed or reported based upon actual knowledge of the field observer or the PCR reviewer, they should be identified in the PCR; Compliance of any material, equipment, or system with any certification or actuation rate program, vendor’s or manufacturer’s warranty provisions, or provisions established by any standards that are

    related to insurance industry acceptance/approval, such as FM, State Board of Fire Underwriters, etc. Additional/General Considerations: Further Inquiry: There may be physical condition issues or certain physical improvements at the subject property that the parties may wish to assess in connection with a commercial real estate transaction that are outside the scope of this guide. Such issues are referred to as non-scope considerations and if included in the PCR, should be identified.

    Out of Scope Considerations: Whether or not a user elects to inquire into non-scope considerations in connection with this guide is a decision to be made by the user. No assessment of such non-scope considerations is required for a PCA to be conducted in compliance with this guide. Other Standards: There may be standards or protocols for the discovery or assessment of physical deficiencies associated with non-scope considerations developed by government entities, professional

    organizations, or private entities, or a combination thereof.

    Additional Issues: No implication is intended as to the relative importance of inquiry into such non-scope considerations,and this list of non-scope considerations is not intended to be all-inclusive: Seismic Considerations, Design Consideration for Natural Disasters (Hurricanes, Tornadoes, High Winds,

    Floods, Snow, etc.), Insect/Rodent Infestation, Environmental Considerations, ADA Requirements, FFHA Requirements, Indoor Air Quality, and Property Security Systems.

    C. Opinions of probable costs to remedy physical deficiencies Not Inspected

    This was not part of the scope or our agreement.

    Uncertainty Not Eliminated—No PCA can wholly eliminate the uncertainty regarding the presence of physical deficiencies and

    the performance of a subject property’s building systems. Preparation of a PCR in accordance with this guide is intended to reduce, but not eliminate, the uncertainty regarding the potential for component or system failure and to reduce the potential that such component or system may not be initially observed. This guide also recognizes the inherent subjective nature of a consultant’s opinions as to such issues as workmanship, quality of original installation, and estimating the RUL of any given

    component or system. The guide recognizes a consultant’s suggested remedy may be determined under time constraints, formed without the aid of engineering calculations, testing, exploratory probing, the removal of materials, or design. Furthermore, there may be other alternate or more appropriate schemes or methods to remedy the physical deficiency. The consultant’s opinions generally are formed without detailed knowledge from those familiar with the component’s or system’s

    performance. Not Technically Exhaustive—Appropriate due diligence according to this guide is not to be construed as technically exhaustive. There is a point at which the cost of information obtained or the time required to conduct the PCA and prepare the PCR may outweigh the usefulness of the information and, in fact, may be a material detriment to the orderly and timely completion of a commercial real estate transaction. It is the intent of this guide to attempt to identify a balance between limiting

    the costs and time demands inherent in performing a PCA and reducing the uncertainty about unknown physical deficiencies resulting from completing additional inquiry.

    Page 38 of 4319 Indian Trail Lilburn Rd

  • Summary

    South East Building Consultants

    Atlanta GA678-410-3005

    Serving Atlanta GA and the Entire South East

    CustomerRestaurant

    Address19 Indian Trail Lilburn Rd

    Norcross GA

    This summary will provide you with a preview of the components or conditions that need service, repair or a second opinion, but other items in the report may disclose valuable information that could influence your decision. Therefore, I recommend you read the full report in it's entirety.

    1. General Physical Condition

    D. Paving, Curbing and Parking

    Repair or Replace

    Asphalt parking lot was in general good condition. Several small depressions and average small cracking, you may want to seal these cracks. Some of the concrete curbing was damaged and/or

    cracked. Recommend general repairs of curbing as needed.

    E. Flatwork (sidewalks, plazas, patios)

    Repair or Replace

    Concrete walkways/sidewalks had a few cracks in a few areas. Recommend repairing to prevent further damage or injury.

    3. Structural Frame and Building Envelope

    B. Building Frame

    Immediate Attention!

    There was evidence of water stains at drop ceiling above the main electrical service panels. There

    was also evidence of water damage (deterioration) and stains at the roof plywood decking in the

    Page 39 of 4319 Indian Trail Lilburn Rd

  • 3. Structural Frame and Building Envelope

    same area (below the roof electric weather head). Recommend repair the structure damage by

    qualified roof contractor. Repair all other damage as needed by qualified contractor.

    C. Sidewall System (exterior wall cladding and components)

    Repair or Replace

    (1) Stucco cladding was in good condition overall. There were several small hairline cracks around window/door openings. Recommend seal cracks to prevent moisture intrusion.

    (2) Landscape ground cover has caused small negative sloping toward the building. It is also in contact with the exterior cladding and lower windows. Recommend correcting issues to prevent

    moisture damage or wood destroy insects.

    E. Parapets (protective wall barriers at balcony, roof etc.)

    Repair or Replace

    Roof parapets had several small hairline cracks at stucco cladding. Sealant at metal cap seams were failing, several areas. Recommend small repairs to prevent further damage or moisture intrusion by qualified contractor.

    F. Roofing

    Repair or Replace

    (1) Roof coverings consisted of front metal pitched roof and TPO (Thermoplastic Polyolefin membrane) at flat roof.

    The metal roofing was in average condition. I recommend a new sealant coat for protection.

    The TPO roofing was in good condition for its age. I estimate it to be approximately 10 years old.

    Average life span of this roofing material varies significantly, but I would reasonably estimate at least 10 more years life. No major leaking was noted. However there was several small puddles of water (from improper condensation piping not draining off roof) which can cause moisture intrusion. Routine maintainece and/or inspections of the covering are recommended. Recommend obtaining estimates for repairing the small dips at TPO covering to prevent moisture damage.

    (2) Small lower roof canopy roofs had peeling paint or damaged top coat sealant. Recommend repair as needed.

    4. Mechanical and Electrical System

    A. Plumbing water supply and Distribution and Fixtures

    Immediate Attention!

    Water leak noted at main water piping below main shut-off. Recommend repair by qualified plumber.

    C. Domestic hot water production

    Not Inspected

    (2) Tank-less water heater had stored items in front of it and shelving was in direct contact with unit. Minimum 4 inch clearance is required. Gas line did not have a proper shut-off valve. Recommend correct issues by qualified contractor to prevent injury or damage.

    D. Heating & Air conditioning and Ventilation Equipment

    Repair or Replace

    Page 40 of 4319 Indian Trail Lilburn Rd

  • 4. Mechanical and Electrical System

    (2) Roof HVAC unit condensation piping was damaged or did not properly discharge off the roof for all units. Suction line insulation was aged/damaged for all units. General wear/dust was noted at filter, blower motor and service compartments. Electrical wiring conduit was faded/aged/cracked. I

    recommend general service and repair these items by licensed HVAC contractor.

    E. Electric Service and Meter

    Immediate Attention!

    (1) The electrical service conductors at roof weather head are frayed at wire sheathing. There were screws and a neutral wire in contact with the main conductor wiring. This is considered an safety issue. Recommend immediate repair by qualified licensed electrician.

    (2) Electrical service was a 3- phase 600 amp 208/120v system.

    There were multiple issues noted at the main electrical service panels in rear storage room. One service panel was blocked off with storage shelving (needs 3ft clearance) and the other panels had

    open knock outs, breakers were not properly identified, and multiple double taps. Right panel C had evidence of excessive heat at several breakers including evidence of water damage from an old roof leak above. Further damage or injury may occur. Recommend correct all issues by licensed electrician.

    F. Electric Distribution

    Repair or Replace

    (1) Conduit electrical wiring at roof was aged and deteriorated for mechanical equipment, including loose connectors. One section had open end wiring. Recommend repair issues by licensed electrician.

    (2) Open J-boxes noted at parking lot lights. Recommend correct by qualified electrician.

    (3) Electrical wiring and receptacle near wash station was not properly secured. Receptacles were

    damaged/defective. Recommend correct issues by licensed electrician.

    G. Exhaust, Vents

    Repair or Replace

    (1) Rooftop kitchen exhaust vent had grease build-up (left side). Recommend clean/maintenance. Also it appears that the old (brown) exhaust system was not in use or it had parts (belts) that were disconnected. Either repair this unit if in use or disconnect it as it is wasting electricity.

    Middle kitchen exhaust vent also had parts missing or not functioning properly. Recommend repair as needed.

    (2) I did not inspect any refrigeration, chiller, or ice maker equipment at the roof. However as a courtesy several issues were noted with this equipment and general service or maintainece is needed/recommended.

    5. Common Areas (Interior)

    A. Ceiling, Walls, Floors

    Inspected

    Page 41 of 4319 Indian Trail Lilburn Rd

  • 5. Common Areas (Interior)

    (2) Suspended drop ceiling had several areas of damage at tile, frame and tracks. Recommend

    repair issues as needed to prevent possible injury or further damage.

    Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Ray Thoroman

    Page 42 of 4319 Indian Trail Lilburn Rd

  • INVOICE

    South East Building Consultants Atlanta GA

    678-410-3005Serving Atlanta GA and the Entire South

    East Inspected By: Ray Thoroman

    Inspection Date: 6/24/2013 Report ID: 062413-4

    Customer Info: Inspection Property:

    Restaurant StreetNorcross GA

    Customer's Real Estate Professional:

    19 Indian Trail Lilburn Rd

    Norcross GA

    Inspection Fee:

    Service Price Amount Sub-Total

    Building Inspection 1440.00 1 1440.00

    Tax $0.00

    Total Price $1440.00

    Payment Method: Check

    Payment Status: PaidNote:

    Page 43 of 4319 Indian Trail Lilburn Rd