RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

12
LEGEND - PIPING REFER DESCRIPTION DOMESTIC COLD WATER PIPING DOMESTIC HOT WATER PIPING DOMESTIC HOT WATER RECIRC. PIPING VENT PIPING V SANITARY PIPING ABOVE FLOOR SANITARY PIPING BELOW FLOOR GAS PIPING G FORCE MAIN FM STORM PIPING ABOVE FLOOR STORM PIPING BELOW FLOOR S S CONDENSATE PIPING C PUMPED DISCHARGE PIPING PD TEMPERED WATER PIPING T CAPPED PIPE FLOOR DRAIN FD FUNNEL FLOOR DRAIN HUB DRAIN HD ROOF DRAIN RD CLEAN OUT (IN FLOOR) CO CO CLEAN OUT (IN LINE OR STACK) FLANGE M WATER METER GAS METER PIPE DOWN PIPE UP ISOLATION VALVE HOSE BIB C/W VACUUM BREAKER HB THROTTILING VALVE STRAINER WH WALL HYDRANT BACK WATER VALVE BWV VENT THROUGH ROOF VTR CHECK VALVE 3-WAY VALVE S TEMPERATURE AND PRESSURE RELIEF VALVE SOLENOID VALVE PRESSURE GAUGE P T THERMOMETER PIPE TEE PORTABLE FIRE EXTINGUISHER (WALL HUNG / SURFACE MOUNTED) PORTABLE FIRE EXTINGUISHER IN CABINET FEX FEC TEE ELBOW - 90° ELBOW - 45° WYE REDUCER / INCREASER UNION PUMP VERTICAL INLINE PUMP 3-WAY CONTROL VALVE 2-WAY CONTROL VALVE CIRCUT BALANCING VALVE CBV SAFETY (S) OR RELIEF (R) VALVE DC DRAIN COCK FFD OR M POST HYDRANT PH GRAY / NON-POTABLE WATER GW LEGEND - HVAC REFER DESCRIPTION POSITIVE PRESSURE (SUPPLY) DUCT UP POSITIVE PRESSURE (SUPPLY) DUCT UP NEGATIVE PRESSURE (RETURN/EXHAUST) DUCT UP NEW DUCT WORK FLEXIBLE DUCTWORK APPROVAL REQ. FOR USE (1500mm MAX.) CROSSHATCHING ON DUCTWORK INDICATES 1" (25mm) DUCT LINING AS SPECIFIED FIRE DAMPER FD MOTORIZED DAMPER MD BALANCING DAMPER BD SUPPLY AIR DIFFUSER (SQUARE) SUPPLY AIR DIFFUSER (LAMINAR FLOW) LINEAR OR SLOT DIFFUSER WITH PLENUM SIDEWALL GRILLE RETURN/EXHAUST GRILLE FULL RADIUS DUCT CONNECTION TAP-IN DUCT CONNECTION ROUND DUCT CONNECTION TURNING VANES VOLUME DAMPER VD SPLITTER DAMPER SP OPEN ENDED DUCT COMPLETE WITH SCREEN THERMOSTAT / SENSOR OED T UNDERCUT UC S OCCUPANCY SENSOR T THERMOSTAT c/w TAMPERPROOF COVER CAP CAP SILENCER CROSS TALK SILENCER POSITIVE PRESSURE (SUPPLY) DUCT DOWN NEGATIVE PRESSURE (RETURN/EXHAUST) DUCT DOWN THERMAL INSULATION GENERAL NOTES: 1. PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS AND BULLETINS, ETC., LATEST EDITIONS, AND TO THE LOCAL AUTHORITIES REQUIREMENTS. 2. IT IS THE CONTRACTOR’S RESPONSIBILITY TO VERIFY AND CHECK THE EXISTING CONSTRUCTION PRIOR TO AND DURING CONSTRUCTION. ANY CHANGES AND/OR DISCREPANCIES SHALL BE REPORTED AND REVIEWED BY THE ENGINEER AND/OR PROJECT MANAGER PRIOR TO PROCEEDING. 3. THE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE SPECIFICATIONS AND THE DOCUMENTS PERTAINING TO THE WORK OF OTHER TRADES. 4. OBTAIN EXACT DIMENSIONS FROM SITE MEASUREMENTS. DO NOT SCALE THESE DRAWINGS. 5. PENETRATIONS OF EITHER THE FIRE OR SMOKE BARRIERS SHALL BE SLEEVED AND SEALED AGAINST THE PASSAGE OF FLAME AND/OR SMOKE WITH A SUITABLE NON-COMBUSTIBLE MATERIAL EQUAL TO THE CONSTRUCTION PENETRATED. 6. CHECK AND VERIFY THE LOCATIONS OF ALL PIPES, DUCTS, AND EQUIPMENT WITH THE WORK OF OTHER TRADES TO PREVENT INTERFERENCE. REMOVAL AND RELOCATION OF ANY SUCH WORK INTERFERING WITH THE WORK OF OTHER TRADES IS THE RESPONSIBILITY OF THE MECHANICAL TRADE(S), UNLESS OTHERWISE APPROVED IN WRITING. 7. PROVIDE ACCESS DOORS AS REQUIRED FOR ALL CONCEALED SERVICEABLE COMPONENTS, LOCATED ABOVE, BEHIND OR BELOW INACCESSIBLE CONSTRUCTION. 8. PROVIDE A CLEANOUT AT THE BOTTOM OF EVERY SANITARY AND STORM STACK THAT CONNECTS TO A HORIZONTAL PIPE. 9. ALL PLUMBING FIXTURES AND DRAINS SHALL BE TRAPPED AND VENTED IN ACCORDANCE WITH THE ONTARIO BUILDING CODE, PART 7. 10. CONTRACTOR SHALL PROVIDE TRAP SEAL PRIMERS AS SPECIFIED. COORDINATE PRIMER REQUIREMENT WITH OTHER TRADES AS REQUIRED. PROJECT CLIENT CONSULTANT KEY PLAN ISSUE/REVISION SHEET NUMBER SHEET TITLE PROJECT NUMBER ISSUED FOR TENDER Last Plotted: Filename: Printed on ___% Post-Consumer Recycled Content Paper Project Management Initials: Designer: Checked: Approved: ISO A1 594mm x 841mm 2 3 4 5 1 2 3 4 5 D C B A 1 ELGIN AREA WATER SUPPLY SYSTEM AECOM 250 York Street, Suite 410 London, Ontario N6A 6K2 519.676.0510 tel 519.673.5975 fax www.aecom.com 235 North Centre Road, Suite 200 London Ontario N5X 4E7 519.930.3505 tel 519.474.0451 fax www.watersupply.london.ca 2013-10-09 0 10/4/2013 9:15:09 AM C:\Users\kohlers\Documents\Revit Local Files\60246477-MOD-30-0000-M-CF_kohlers.rvt MANAGEMENT 43665 Dexter Line FACILITY RESIDUALS Central Elgin, Ontario N0L 2L0 ELGIN AREA WATER TREATMENT PLANT MECHANICAL GENERAL NOTES AND LEGENDS M600 60246477 Checker Designer Approver I/R DATE DESCRIPTION 60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Transcript of RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

Page 1: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

LEGEND - PIPING

REFER DESCRIPTIONDOMESTIC COLD WATER PIPING

DOMESTIC HOT WATER PIPING

DOMESTIC HOT WATER RECIRC. PIPING

VENT PIPINGV

SANITARY PIPING ABOVE FLOOR

SANITARY PIPING BELOW FLOOR

GAS PIPINGG

FORCE MAINFM

STORM PIPING ABOVE FLOOR

STORM PIPING BELOW FLOOR

S

S

CONDENSATE PIPINGC

PUMPED DISCHARGE PIPINGPD

TEMPERED WATER PIPINGT

CAPPED PIPE

FLOOR DRAINFD

FUNNEL FLOOR DRAIN

HUB DRAINHD

ROOF DRAINRD

CLEAN OUT (IN FLOOR)CO

CO CLEAN OUT (IN LINE OR STACK)

FLANGE

M WATER METER

GAS METER

PIPE DOWN

PIPE UP

ISOLATION VALVE

HOSE BIB C/W VACUUM BREAKERHB

THROTTILING VALVE

STRAINER

WH WALL HYDRANT

BACK WATER VALVEBWV

VENT THROUGH ROOFVTR

CHECK VALVE

3-WAY VALVE

S TEMPERATURE AND PRESSURE RELIEF VALVE

SOLENOID VALVE

PRESSURE GAUGEP

T THERMOMETER

PIPE TEE

PORTABLE FIRE EXTINGUISHER (WALL HUNG / SURFACE MOUNTED)

PORTABLE FIRE EXTINGUISHER IN CABINET

FEX

FEC

TEE

ELBOW - 90°

ELBOW - 45°

WYE

REDUCER / INCREASER

UNION

PUMP

VERTICAL INLINE PUMP

3-WAY CONTROL VALVE

2-WAY CONTROL VALVE

CIRCUT BALANCING VALVECBV

SAFETY (S) OR RELIEF (R) VALVE

DC DRAIN COCK

FFD

OR

M

POST HYDRANTPH

GRAY / NON-POTABLE WATERGW

LEGEND - HVAC

REFER DESCRIPTIONPOSITIVE PRESSURE (SUPPLY) DUCT UP

POSITIVE PRESSURE (SUPPLY) DUCT UP

NEGATIVE PRESSURE (RETURN/EXHAUST) DUCT UP

NEW DUCT WORK

FLEXIBLE DUCTWORK APPROVAL REQ. FOR USE (1500mm MAX.)

CROSSHATCHING ON DUCTWORK INDICATES 1" (25mm) DUCT LINING AS SPECIFIED

FIRE DAMPERFD

MOTORIZED DAMPERMD

BALANCING DAMPERBD

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (LAMINAR FLOW)

LINEAR OR SLOT DIFFUSER WITH PLENUM

SIDEWALL GRILLE

RETURN/EXHAUST GRILLE

FULL RADIUS DUCT CONNECTION

TAP-IN DUCT CONNECTION

ROUND DUCT CONNECTION

TURNING VANES

VOLUME DAMPERVD

SPLITTER DAMPERSP

OPEN ENDED DUCT COMPLETE WITH SCREEN

THERMOSTAT / SENSOR

OED

T

UNDERCUTUC

S OCCUPANCY SENSOR

T THERMOSTAT c/w TAMPERPROOF COVER

CAPCAP

SILENCER

CROSS TALK SILENCER

POSITIVE PRESSURE (SUPPLY) DUCT DOWN

NEGATIVE PRESSURE (RETURN/EXHAUST) DUCT DOWN

THERMAL INSULATION

GENERAL NOTES:

1. PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS ANDBULLETINS, ETC., LATEST EDITIONS, AND TO THE LOCAL AUTHORITIES REQUIREMENTS.

2. IT IS THE CONTRACTOR’S RESPONSIBILITY TO VERIFY AND CHECK THE EXISTING CONSTRUCTIONPRIOR TO AND DURING CONSTRUCTION. ANY CHANGES AND/OR DISCREPANCIES SHALL BEREPORTED AND REVIEWED BY THE ENGINEER AND/OR PROJECT MANAGER PRIOR TOPROCEEDING.

3. THE DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE SPECIFICATIONS AND THEDOCUMENTS PERTAINING TO THE WORK OF OTHER TRADES.

4. OBTAIN EXACT DIMENSIONS FROM SITE MEASUREMENTS. DO NOT SCALE THESE DRAWINGS.

5. PENETRATIONS OF EITHER THE FIRE OR SMOKE BARRIERS SHALL BE SLEEVED AND SEALEDAGAINST THE PASSAGE OF FLAME AND/OR SMOKE WITH A SUITABLE NON-COMBUSTIBLEMATERIAL EQUAL TO THE CONSTRUCTION PENETRATED.

6. CHECK AND VERIFY THE LOCATIONS OF ALL PIPES, DUCTS, AND EQUIPMENT WITH THE WORK OFOTHER TRADES TO PREVENT INTERFERENCE. REMOVAL AND RELOCATION OF ANY SUCH WORKINTERFERING WITH THE WORK OF OTHER TRADES IS THE RESPONSIBILITY OF THE MECHANICALTRADE(S), UNLESS OTHERWISE APPROVED IN WRITING.

7. PROVIDE ACCESS DOORS AS REQUIRED FOR ALL CONCEALED SERVICEABLE COMPONENTS,LOCATED ABOVE, BEHIND OR BELOW INACCESSIBLE CONSTRUCTION.

8. PROVIDE A CLEANOUT AT THE BOTTOM OF EVERY SANITARY AND STORM STACK THAT CONNECTSTO A HORIZONTAL PIPE.

9. ALL PLUMBING FIXTURES AND DRAINS SHALL BE TRAPPED AND VENTED IN ACCORDANCE WITHTHE ONTARIO BUILDING CODE, PART 7.

10. CONTRACTOR SHALL PROVIDE TRAP SEAL PRIMERS AS SPECIFIED. COORDINATE PRIMERREQUIREMENT WITH OTHER TRADES AS REQUIRED.

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:0

9 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL GENERAL NOTESAND LEGENDS

M600

60246477

Che

cker

Des

igne

rAp

prov

er

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 2: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

FEX

FEX

COABOVE

FD3ABOVE

FD3ABOVE

CO

COABOVE

FD3ABOVE

FD3ABOVE

CO

S1ABOVE

S2ABOVE

75ø @2.00%

PENETRATION LINKSEAL

75ø @1.00%

100Ø SANITARY UP

32Ø DCWS RISERS UP

NEW 150Ø INCOMINGWATER SERVICE BYGENERAL TRADES

M

INCOMING WATER SERVICE.REFER TO SCHEMATIC ONDRAWING No. M611

BACKWASH EQUALIZATIONBASIN 1

BACKWASH EQUALIZATIONBASIN 2

CLARIFIER SLUDGEEQUALIZATION TANK No. 2

CLARIFIER SLUDGEEQUALIZATION TANK No. 1

THICKENED SLUDGE TANKNo. 2

THICKENED SLUDGE TANKNo. 1

601

603COABOVE75ø @2.00%

NOTES:

-ALL PIPING LOCATED WITHIN PROCESS TANKSSHALL BE PVC PIPE WITH SOLVENT WELDEDFITTINGS, AS SPECIFIED, AND SHALL BECONCRETE ENCASEDFD3

ABOVE

FD3ABOVE

DENOTES OPENINGABOVE

CO

CO

CO

INVERT AT BUILDINGWALL 211.560+-.

FINISHED FLOORELEVATION 204.55+-

75ø @2.00% 75ø @2.00%

FD3ABOVE

BY DIVISION 15

1500 MAX. BY GENERAL TRADES

EST. LOAD 2.1LPS(33.5 FIXTURE UNITS)

100ø @1.00%

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:1

2 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL LOWER FLOOR PLAN- PLUMBING AND DRAINAGE

M601

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M601 REF: D613

1 LOWER FLOOR-PLUMBING AND DRAINAGE

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 3: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

FEX

FEX

FEX

FEX

FEX

FEX

FEX

FEX

S2CO

FD3

DENOTES MEZZANINEABOVE

FD3

FD3

19ø 32ø 32ø 19ø 32ø 32ø

CO

100Ø SANITARY DOWN

GWH

S1

P-1

E1

E3

UH-5

UH-1

IFR-1

IFR-2

FEX

607

606

608610

609

611

612

613

605

604

615

614

603

CO

CO

ROUTE 32Ø DCWSAND DHWS ALONG WALL

UH-3

UH-4

L1

W-1

L1

W-1

FD3

FD3

G

G

G

G

G

G

50Ø, 13.8 KPa (2 PSI) NATURALGAS RISER UP

100Ø NATURAL GASRISER UP THROUGH ROOF

50ø

50ø

50ø19ø

75Ø NATURAL GASRISER UP THROUGHROOF

75ø

50ø

32ø

32ø

50ø

50ø

65ø

50Ø NATURAL GAS

CO

CBV(3.8LPM)

CBV(3.8LPM)

32Ø DCWS DOWN

EXTENT OF DENOTESOPENING ABOVE

FD3

MNEW NATURAL GAS METER ANDREGULATOR ASSEMBLY TO THELOCAL AUTHORITY REQUIREMENTS.COORDINATE INSTALLATION ASREQUIRED. ESTIMATED LOAD1127.6 KW (3851.0 MBH)

FEX

75ø

50ø

50ø

50ø

G

PWH-3

PWH-2

PWH-1

65ø

E2

65ø

T

19ø19ø25ø

UH-2

CO

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:1

6 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL MAIN FLOOR PLAN -PLUMBING AND DRAINAGE

M602

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M602 REF: D613

1 MAIN FLOOR-PLUMBING AND DRAINAGE

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 4: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

RTU-2

RTU-3

IFR-4

IFR-3

MUA-1

EF-1EF-2

617

603

616

G G G G

GG

G G

32ø

32ø

50ø

G

G

G

50Ø NATURAL GASRISER DOWN

G (13.8KPa) (13.8KPa) (13.8KPa)

1800

MIN

.

32ø

50ø 32ø 32ø 32ø 32ø

75ø

19ø

19ø25ø19ø

19ø 25ø

19ø19ø

(13.

8KP

a)

PRV-5PRV-4

PRV-3PRV-2

PRV-1

100Ø LOW PRESSURE NATURALGAS RISER DOWN

75Ø LOW PRESSURE NATURALGAS RISER DOWN

PRV-6

50Ø, 13.8 KPa NATURALGAS RISER THROUGHPARAPET

FEX

FEX

FEX

FEX

RTU-1

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:2

1 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL UPPER FLOOR -PLUMBING AND DRAINAGE

M603

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M603 REF: D613

1 UPPER FLOOR-PLUMBING AND DRAINAGE

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 5: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

F2543 AT 300mm A.F.F.L

F2543 AT 5000mm A.F.F.L

FD650x300 EXHAUST DUCT UP

FD

B11085

B11085

1000x350 SUPPLY DUCT UP

1000x350

T MUA-1

TEMPERATURE SENSORWITH INSULATED SUB-BASE

FD

F2543AT 5000mm A.F.F.L

F2543AT 300mm A.F.F.L

650x300

650x300 EXHAUST DUCT UP

601

603

BACKWASH EQUALIZATIONBASIN 1

BACKWASH EQUALIZATIONBASIN 2

CLARIFIER SLUDGEEQUALIZATION TANK No. 2

CLARIFIER SLUDGEEQUALIZATION TANK No. 1

THICKENED SLUDGE TANKNo. 2

THICKENED SLUDGE TANKNo. 1

WALL MOUNTED OCCUPANCYSENSOR (TYPICAL)

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:2

4 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL LOWER FLOORPLAN- HVAC

M604

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M604 REF: D613

1 LOWER FLOOR-HVAC

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 6: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

DENOTES MEZZANINEABOVE

EF-9 EF-5

EF-12

IFR-1

IFR-2

EF-4

F31994

950x350 EXHAUSTDUCT DOWNF3

1994950x350 EXHAUSTDUCT DOWN

AT 300mmA.F.F.L

AT 300mmA.F.F.L

OA OA

L43976

L43976

MD MD

EAEA EA EA

650x

30065

0x30

0

650x300 EXHAUSTDUCT DOWN TOLOWER LEVEL

650x300 EXHAUSTDUCT DOWN TOLOWER LEVEL

150Ø COMBUSTIBLE AIRINTAKE AND FLUE GASVENT UP

EF-3

EA

F1165

AT 300mmA.F.F.L

OA

L1165

AT 2400mmA.F.F.L

MD

100Ø COMBUSTION AIRINTAKE AND FLUE GASVENT

CONCENTRIC ADAPTERBOX (TYP.)

TS CL2

150Ø COMBUSTION AIRINTAKE AND FLUE GASVENT (FIRE WRAPPED)

CONCENTRIC ADAPTERBOX (TYP.)

B2236

B2236

B2236

B2236

350ø 350ø

E3944

BD BD

600x250 RETURN AND450x300 SUPPLY DUCTSUP TO RTU-2

1650x300 DUCTUP TO MUA-1

FD

1000x350

FD

1000x350 DUCT DOWNTO LOWER LEVEL

E41276

900x300

400ø

B2319

900x300 RETURN AND700x350 SUPPLY DUCTSUP TO RTU-3

T

RTU-3

E271

200x200 GENERALEXHAUST UP TO EF-1

200x200 SANITARYEXHAUST UP TO EF-2

A2135

A294

A148

200ø

300x250

150ø

150ø

150ø

300x250

200ø

200x100

200x200

200x100UC

UC

UC

UC

OED SVTRTU-1

FD

FD

E1218

E228

E228

BD BD

G194

600x250 RETURN AND450x300 SUPPLY DUCTSUP TO RTU-1

TS NOX

OUTDOOR AIRVENT CAP (TYP.)

100ø

100ø

EA

OA

OA

L21015

L21015

F22030

AT 300mmA.F.F.L

950x350 EXHAUSTDUCT DOWN

WALL THIMBLE(TYP.)

FLUE GAS VENTTERMINAL (TYP.)

MD

MD

TS NOX

FF-2

FF-1

3KW

3KW

UH-5

UH-1

100ø

100ø

605

607608

609

610 611

612

613

603

615

614

604

606

UH-4

E1218

150Ø COMBUSTION AIRINTAKE AND FLUE GASVENT

150Ø COMBUSTION AIRINTAKE AND FLUE GASVENT

UH-3

GWH

A124

100ø100ø

CONCENTRIC ADAPTERBOX (TYP.)

BD

BDBD

A2135

BD BD

B2319

B2319

B2295

BD

BD

S CO

S CO

WALL MOUNTED OCCUPANCYSENSOR (TYPICAL)

T

T

EF1 SPEEDCONTROLLER

T

THERMOSTAT WITHINSULATE SUB-BASE(TYP.)

RTU-2

600x300

PWH-3

PWH-2

PWH-1

125mmØ CONCENTRICVENT (TYP. OF 3)

FD

FD

FD

UH-2

400ø

BD FD

A124

UC

250x200

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:2

9 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL MAIN FLOOR PLAN -HVAC

M605

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M605 REF: D613

1 MAIN FLOOR-HVAC

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 7: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

1

3

4

5

A B C

2

D

RTU-3

RTU-2

DS-1 DS-2 DS-3

OA

106 LPSMIN.

OA35 LPSMIN.

OA59 LPSMIN.

OA

MUA-1

100ø

100ø

OUTDOOR AIRVENT CAP (TYP.)

EF-10

EF-11ABOVE

ABOVE

1994OED

1994OED

EF-7ABOVE

1652OED

EF-6ABOVE

1652OED

EF-2EF-1

900

MIN

. (TY

P)

IFR-3

IFR-4

200Ø CONCENTRICVENT TERMINATION

150Ø COMBUSTION AIRINTAKE AND FLUE GAS VENT (FIRE WRAPPED)DOWN, CONCENTRIC ADAPTER BOX AND200Ø CONCENTRIC VENT UP

T

OA

OA

L31652

L31652

MD

MD100ø

100ø

T

603616

617

150Ø CONCENTRICVENT TERMINATION

WALL MOUNTED OCCUPANCYSENSOR (TYPICAL)

RTU-1

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:3

5 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL UPPER FLOOR PLAN- HVAC

M606

60246477

Che

cker

Des

igne

rAp

prov

er

SCALE: 1 : 100M606 REF: D613

1 UPPER FLOOR-HVAC

ROOM SCHEDULENumber Name601 PUMP GALLERY602 STAIR WELL No.1603 STAIR WELL No.2604 SLUDGE THICKENER605 POLYMER STORAGE AND

MAKEUP ROOM606 STORAGE ROOM607 ELECTRICAL ROOM608 CONTROL ROOM AND LAB609 JANITORY/STORAGE ROOM610 LAB STORAGE ROOM611 WAITING ROOM612 WC613 WC614 TRUCK BAY615 DECHLORINATION ROOM616 THICKENER ROOM617 CENTRIFUGE ROOM618 STORAGE ROOM

N

0mm

2500 5000

SCALE: 1:100

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 8: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

DESTRATIFICATION FAN SCHEDULE

TAG LOCATION MANUF. MODEL FAN TYPE MOTORRPM

NOMINALMOTORPOWER POWER MOCP

OPER.WT. LBS

/ KgCONTROLLED BY ACCESSORIES

W HP

DS-1 DS-2DS-3

THICKENER[616] BIG ASS FANS POWERFOIL

X2.0 2.4M (8'-0")Ø 113MAXIMUM 746 1.00 208/3/60 10.0 269 / 122 DIGITAL WALL KEYPAD SAFETY YELLOW WINGLET, MILL FINISH ALUMINUM AND SMART

SENSE 365

DIFFUSER, REGISTER & GRILLE SCHEDULETAG BASIS OF DESIGN

MANUFACTURER MODEL APPLICATIONSIZE NECK SIZE AIR FLOW

NC RANGE ACCESSORIES / COLOURMM INS MM INS LPS CFM

A1 KRUEGER 51400-04-06-F12-12x12-00-44

4 WAY CEILINGDIFFUSER 300x300 12x12 150Ø 6Ø UP TO

83UP TO

175 30 MAX. 4 CONE, WHITE, ALUMINUM CEILING DIFFUSER

A2 KRUEGER 51400-04-08-F23-24x24-00-44

4 WAY PANELMOUNTED CEILING

DIFFUSER600x600 24x24 200Ø 8Ø 87 - 142 185 - 300 30 MAX. 4 CONE, WHITE, PANEL MOUNTED, ALUMINUM CEILING DIFFUSER

B1 KRUEGER 5880-H-36-12-F22-NONE-01-02-00-10

DUCT MOUNTEDSUPPLY AIR GRILLE 900x300 36x12 - - UP TO 1,180 UP TO 2,500 40 MAX. DOUBLE DEFLECTION, 19MM SPACING, ALUMINUM SIDEWALL

GRILLE, ALUMINUM OPPOSED BLADE DAMPER

B2 KRUEGER DMGDR-H-20-08-X-01-81 DUCT MOUNTEDSUPPLY AIR GRILLE 500x200 20x8 - - UP TO 413 UP TO

875 40 MAX. DOUBLE DEFLECTION, 19MM SPACING, ALUMINUM SIDEWALLGRILLE, EXTRACTOR, (X = 14 & 16)

E1 KRUEGER EG5-24-06-FTB-NONE-44 CEILING RETURN AIRGRILLE 600x150 24x6 - - UP TO 319 UP TO 675 30 MAX. ALUMINUM EGG CRATE RETURN WITH CHANNEL FRAME

E2 KRUEGER EGC5-06-06-F23-12x24-00-00-00-44

CEILING EXHAUST AIRGRILLE 150x150 6x6 - - UP TO

94UP TO

200 30 MAX. ALUMINUM PANEL MOUNTED, EGG CRATE RETURN

E3 KRUEGER EGC5-24-24-F22-NONE-03-00-04-10

DUCT MOUNTEDRETURN GRILLE 600x600 24x24 - - 944 2,000 40 MAX. ALUMINUM EGG CRATE RETURN, KNURLED FASTENERS, 25MM

FILTER FRAME AND FILTERS

E4 KRUEGER EGC5-30-30-F22-NONE-03-00-04-10

DUCT MOUNTEDRETURN GRILLE 750x750 30x30 - - 1,276 2,700 40 MAX. ALUMINUM EGG CRATE RETURN, KNURLED FASTENERS, 25MM

FILTER FRAME AND FILTERS

F1 KRUEGER AFS580-HZ-10-10-F22-NONE-01-15-00-10

DUCT MOUNTEDEXHAUST GRILLE 250X250 10X10 - - 165 350 40 MAX. FIXED ALUMINUM, SINGLE DEFLECTION, 19MM SPACING, 0°

DEFLECTION, ALUMINUM OPPOSED BLADE DAMPER

F2 KRUEGER AFS580-HZ-24-12-F22-NONE-01-15-00-10

DUCT MOUNTEDEXHAUST GRILLE 600x450 24x16 - - 543 1,150 40 MAX. FIXED ALUMINUM, SINGLE DEFLECTION, 19MM SPACING, 0°

DEFLECTION, ALUMINUM OPPOSED BLADE DAMPER

F3 KRUEGER AFS580-HZ-36-24-F22-NONE-01-15-00-10

DUCT MOUNTEDEXHAUST GRILLE 900x600 36x24 - - UP TO 2,018 UP TO 4,275 40 MAX. FIXED ALUMINUM, SINGLE DEFLECTION, 19MM SPACING, 0°

DEFLECTION, ALUMINUM OPPOSED BLADE DAMPER

DOMESTIC WATER HEATER SCHEDULE

TAG LOCATION MANUFACTURER MODEL TYPETEMP. RISE FLOW

FUELGAS INLETPRESSURE INPUT EFFICIENCY OPER. WT.

ELECTRICAL REMARKSC F LPS GPM kPA IN WC kW BTUH PERCENT Kg LBS

GWHJANITORY /STORAGE

[609]JOHN WOOD JWT-910 TANKLESS,

DIRECT VENT 27 80 0.50 7.6 NATURALGAS

1.3 5.0

111.4 380,000 80.2 51 112 115 / 1 / 60

VERTICAL CONCENTRIC VENT & INTAKEKITS, DIRECT VENT CONVERSION KIT,BACKFLOW PREVENTER, RAIN CAPS ANDVERTICAL DRAIN TEE

TO TO

2.6 10.5

EXHAUST FAN SCHEDULE

TAG LOCATION FUNCTION MANUF. MODEL FAN TYPEMAXIMUMCAPACITY

MINIMUMCAPACITY STATIC PRESSURE FAN

RPMMOTOR

RPM

NOMINAL MOTORPOWER POWER SOUND

DATA CONTROLLED BY ACCESSORIESLPS CFM LPS CFM Pa IN WC W HP

EF-1 LOW ROOF CONTROL ROOM [608]GENERAL EXHAUST PENNBARRY DOMEX

DX08SDIRECT DRIVECENTRIFUGAL 71 150 71 150 31 0.13 N/A 1,300 15 0.02 120/1/60 2.2

SONES MANUAL SPEED CONTROLLERVIBRATION ISOLATION, WEATHERPROOF SAFETY DISCONNECT,SPEED CONTROLLER, 350MM A.F.R. PREFABRICATED ROOF CURB,ALUMINUM BIRD SCREEN AND GRAVITY BACKDRAFT DAMPER.

EF-2 LOW ROOFSERVICE ROOM [609], W/R [611]

& W/R [612] SANITARYEXHAUST

PENNBARRY DOMEXDX08S

DIRECT DRIVECENTRIFUGAL 85 180 85 180 24 0.10 N/A 1,300 15 0.02 120/1/60 2.2

SONESINTERLOCKED WITH SPACE

LIGHTING BY DIV. 16

VIBRATION ISOLATION, WEATHERPROOF SAFETY DISCONNECT, UNITMOUNTED SPEED CONTROLLER, TIME DELAY RELAY, 350MM A.F.R.PREFABRICATED ROOF CURB, ALUMINUM BIRD SCREEN ANDGRAVITY BACKDRAFT DAMPER.

EF-3 DECHLOR. ROOM[615]

DECHLORONATION ROOM [614]GENERAL EXHAUST PENNBARRY FUMEX

WFX08BBELT DRIVE

CENTRIFUGAL 165 350 83 175 36 0.14 765 1,725 187 0.25 575/3/60 5.8SONES

CONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON GAS (CL2) DETECTION

WALL MOUNTING KIT, VARIABLE FREQUENCY DRIVE, BELTTENSIONER, ALUMINUM BIRD SCREEN, AND WEATHERPROOFSAFETY DISCONNECT SWITCH.

EF-4EF-5

THICKENERROOM[604]

PUMP GALLERY [601] GENERALEXHAUST PENNBARRY FUMEX

WFX13BBELT DRIVE

CENTRIFUGAL 1,086 2,300 543 1,150 58 0.23 1,408 1,725 560 0.75 575/3/60 16.9 SONES

CONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON OCCUPANCY SENSORACTIVATION

WALL MOUNTING KIT, VARIABLE FREQUENCY DRIVE, BELTTENSIONER, ALUMINUM BIRD SCREEN, AND WEATHERPROOFSAFETY DISCONNECT SWITCH.

EF-6EF-7 HIGH ROOF CENTRIFUGE ROOM [616]

GENERAL EXHAUST PENNBARRY DOMEXDX14B

BELT DRIVECENTRIFUGAL 1,652 3,500 826 1,750 3 0.01 1,287 1,725 560 0.75 575/3/60 18.7

SONES

CONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON OCCUPANCY SENSORACTIVATION

VIBRATION ISOLATION, VARIABLE FREQUENCY, DRIVE BELTTENSIONER, ALUMINUM BIRD SCREEN, WEATHERPROOF SAFETYDISCONNECT SWITCH, 350MM A.F.R. PREFABRICATED ROOF CURB.

EF-8EF-9

THICKENERROOM[604]

PROCESS AREA [604] LOWLEVEL GENERAL EXHAUST PENNBARRY FUMEX

WFX16BBELT DRIVE

CENTRIFUGAL 1,994 4,225 997 2,113 38 0.15 1,116 1,725 1119 1.50 575/3/60 19.9 SONES

CONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON OCCUPANCY SENSORACTIVATION

WALL MOUNTING KIT, VARIABLE FREQUENCY DRIVE, BELTTENSIONER, ALUMINUM BIRD SCREEN, AND WEATHERPROOFSAFETY DISCONNECT SWITCH.

EF-10EF-11 MIDDLE ROOF PROCESS AREA [604] HIGH

LEVEL GENERAL EXHAUST PENNBARRY DOMEXDX16B

BELT DRIVECENTRIFUGAL 1,994 4,225 997 2,113 3 0.01 1,015 1,725 746 1.00 575/3/60 17.9 SONES

CONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON OCCUPANCY SENSORACTIVATION

VIBRATION ISOLATION, VARIABLE FREQUENCY, DRIVE BELTTENSIONER, ALUMINUM BIRD SCREEN, WEATHERPROOF SAFETYDISCONNECT SWITCH, 350MM A.F.R. PREFABRICATED ROOF CURB.

EF-12 TRUCK LOADING[614]

TRUCK BAY [613] GENERALEXHAUST PENNBARRY FUMEX

WFX16BBELT DRIVE

CENTRIFUGAL 2,030 4,300 1,015 2,150 38 0.15 1,136 1,725 1119 1.50 575/3/60 19.9 SONESCONTINUOUS LOW SPEEDOPERATION, HIGH SPEED

UPON GAS DETECTION

WALL MOUNTING KIT, VARIABLE FREQUENCY DRIVE, BELTTENSIONER, ALUMINUM BIRD SCREEN, AND WEATHERPROOFSAFETY DISCONNECT SWITCH.

LPS

LPS

LPS

LPS

LPS

LPS

LPS

LPS

LPS

LPS

LPS

KRUEGER 5600A-12-12-00-10 DOOR GRILLE 300x300 12x12 - - UP TO 130 UP TO 275 30 MAX. ALUMINUM DOOR GRILLE, DOUBLE FLAT FRAME, NO SCREWHOLESLPS

G1

PWH-2POLYMER

ROOM[605]

JOHN WOOD JWT-910 TANKLESS,DIRECT VENT 28.7 85 0.40 7.1 NATURAL

GAS 111.4 380,000 80.2 51 112 115 / 1 / 60

HORIZONTAL CONCENTRIC VENT & INTAKEKITS, DIRECT VENT CONVERSION KIT,BACKFLOW PREVENTER, AND EASY-LINKSYSTEM

TO TO

2.6 10.5

PWH-1

PWH-3

1.3 5.0

LOUVRE SCHEDULETAG BASIS OF DESIGN

MANUFACTURER MODEL APPLICATION FREE AREASIZE VELOCITY AIR FLOW

ACCESSORIES / COLOURMM INS MPS FPM LPS CFM

L1 VENTEX 2425STORMPROOF

OUTDOOR INTAKELOUVRE 53% 500x500 20x20 <2.0 <400 165 350

ALUMINUM BIRDSCREEN, EXTENDED SLEEVES, FILTER RACKS, ANDFILTERS (25MM DISPOSABLE)

COLOUR: NATURAL BRICK (TO CONFIRMED IN SHOPDRAWING SUBMISSION PHASE)

L2 VENTEX 2425STORMPROOF

OUTDOOR INTAKELOUVRE 53% 900x1200 36x48 <2.0 <400 1,015 2,150

L3 VENTEX 2425STORMPROOF

OUTDOOR INTAKELOUVRE 53% 900x1800 36x72 <2.0 <400 1,652 3,500

L4 VENTEX 2425STORMPROOF

OUTDOOR INTAKELOUVRE 53% 2400x1600 96x64 <2.0 <400 3,976 8,425

NATURAL GAS FIRED INFRARED HEATER

TAG LOCATION MANUFACTURER MODEL

CAPACITY

POWER FLAOPER. WT.

REMARKSINPUT OUTPUT

KW MBH KW BTUH Kg LBS

IFR-1IFR-2

TRUCK LOADING[614] ROBERTS GORDON VANTAGE

HE-150 43.9 150.0 35.1 120.0 115V / 1PH 4.8 140.6 310HEAT EXCHANGER TUBING (3.0M ALUMI-THERMTUBING, 12.0M HEAT TREATED ALUMINIZED STEEL,STAINLESS STEEL REFLECTORS, SIDE REFLECTORSAND END CAPS, FRESH AIR INTAKE & VENT TERMINAL ANDCAPS, VENT ADAPTER, WALLTHIMBLE, AND FLEX HOSE.

IFR-3IFR-4

CENTRIFUGE[617] ROBERTS GORDON VANTAGE

HE-150 43.9 150.0 35.1 120.0 115V / 1PH 4.8 140.6 310

THRU-THE-BASE ELECTRICAL CONNECTION, HINGEDACCESS PANELS, BACnet COMPATIBLE CONTROLLER,VARIABLE FREQUENCY DRIVE, AND 350MM A.F.R.PREFABRICATED ROOF CURB

1543700575/3/6030:1MODUL.64.018.0-6.0-21.0373.0109.2450.0131.810265.002.80

15/15FC

DIDW0.942172300 /

46001086 /2171

ENGINEERED AIRDJE60MUA-1

LBSKGMOCPFLAPOWERSUPPLY800040002000100050025012563FDBCDBFDBCDBMBHkWMBHkWINS.W.C.PaCFMLPS

STAGESLATEATOUTPUTINPUTFAN

SPEEDRPM

MOTORSIZEHP

BHPFAN TYPEESPAIR VOLUME REMARKS/ACCESSORIES

OPERATING WEIGHTELECTRICALSOUND POWER

HEATING PERFORMANCESUPPLY FAN

MANUFACTURER / MODELTAG

MAKE-UP AIR UNIT SCHEDULE

12.3 207277778183858583

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:3

8 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL SCHEDULES

M607

60246477

Che

cker

Des

igne

rAp

prov

er

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 9: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

NATURAL GAS FIRED UNIT HEATER SCHEDULE

TAG LOCATION MANUFACTURER/ MODEL

AIR FLOWCAPACITY

MOTORSIZEHP

MOTORSPEED RPM

POWERSUPPLY FLA

OPERATING WEIGHTREMARKS / ACCESSORIESINPUT OUTPUT

LPS CFM KW MBH KW MBH KG LBS

UH-1 DECHLOR.ROOM[615]

REZNORUDAS-45 297 629 13.2 45.0 10.9 37.4 0.03 1550 115/1/60 2.4 27.2 60.0 STAINLESS STEEL HEAT EXCHANGER, TWO STAGE

NATURAL GAS VALVE, VIBRATION ISOLATION,HORIZONTAL OR VERTICAL VENT KIT (AS PERDRAWINGS), CONCENTRIC ADAPTER, AND DOWNTURNNOZZLES

UH-2UH-3UH-4UH-5

THICKENERROOM[604]

REZNORUDAS-350 2116 4483 102.5 350.0 85.1 290.5 0.50 1050 115/1/60 11.0 133.8 295.0

ROOFTOP UNIT SCHEDULE

TAG MANUFACTURER / MODEL

SUPPLY FAN COOLING PERFORMANCE HEATING PERFORMANCE

SOUND POWERAIR VOLUME ESP

FAN TYPE BHPMOTOR

SIZEHP

FANSPEED

RPM

SENSIBLE TOTAL EAT LATREFRIG. SEER /

EER

INPUT OUTPUT EAT LATSTAGES

LPS CFM Pa INS.W.C. kW MBH kW MBH CDB /CWB

FDB /FWB

CDB /CWB

FDB /FWB kW MBH kW MBH CDB FDB CDB FDB RATING 63 125 250 500 1000 2000 4000 8000

RTU-1CARRIER

WEATHERMASTER48HCDA04E0M5-2B3F

472 1000 53 0.23 DIFC10x10 0.25 0.50

730DIRECTTAP 3

8.0 27.3 11.2 38.4 28/19 82/66 14/13 58/56 R410a 15.00 /12.50 21.1 72.0 16.4 56.0 13.0 55.0 31.0 87.0 2 76.0 78.2 78.0 74.2 73.3 70.6 66.0 62.4 56.9

RTU-2CARRIER

WEATHERMASTER48HCDB05A2M5-2B3F

944 2000 75 0.33 DIFC10x10 1.02 1.50 1,090

BELT 12.9 44.0 16.1 55.1 28/19 82/66 14/13 58/56 R410a 15.60 /13.00 21.1 72.0 16.4 56.0 13.0 55.0 31.0 87.0 2 78.0 84.7 83.6 77.1 74.6 72.3 68.3 64.7 60.9

RTU-3CARRIER

WEATHERMASTER48HCDB07A1M5-2B3F

1274 2700 89 0.39 DIFC10x10 1.08 1.5 656

BELT 29.2 61.9 37.9 80.3 28/19 82/66 14/13 58/56 R410a - /12.00 21.1 72.0 27.8 59.0 13.0 55.0 31.0 87.0 2 82.0 90.1 82.6 81.0 79.4 77.0 73.0 70.4 66.7

PUMP SCHEDULE

TAG LOCATION FUNCTION TYPE MANUFACTURER MODEL MEDIUMFLOW HEAD MOTOR MOTOR

RPM POWEROPER. WT.

REMARKSLPM GPM M FT kW HP Kg LBS

P-1 SERVICE ROOM[609]

DOMESTIC HOTWATER

RECIRCULATIONIN-LINE

CIRCULATOR S. A. ARMSTRONG ASTRO 50B-TA POTABLEWATER 7.6 2.0 5.6 18.4 0.037 0.05 2800 115/1/60 3.4 7.4 AQUASTAT AND TIMER

ELECTRICAL OPERATING WEIGHTREMARKS/ACCESSORIES

POWERSUPPLY FLA MOCP KG LBS

575/3/60 8.7 15.0 344 758

THRU-THE-BASE ELECTRICAL CONNECTION, HINGEDACCESS PANELS, HAIL GUARD, BACnet COMPATIBLECONTROLLER, DIFFERENTIAL TEMPERATUREECONOMIZER, BAROMETRIC RELIEF, WEATHERPROOFNON-FUSED DISCONNECT SWITCH, AND 350MM A.F.R.PREFABRICATED ROOF CURB

575/3/60 9.0 15.0 409 901

THRU-THE-BASE ELECTRICAL CONNECTION, HINGEDACCESS PANELS, HUMIDI-MIZER, HAIL GUARD, BACnetCOMPATIBLE CONTROLLER, DIFFERENTIALTEMPERATURE ECONOMIZER, BAROMETRIC RELIEF,WEATHERPROOF NON-FUSED DISCONNECT SWITCH,AND 350MM A.F.R. PREFABRICATED ROOF CURB

575/3/60 13.0 20.0 534 1178

THRU-THE-BASE ELECTRICAL CONNECTION, HINGEDACCESS PANELS, HUMIDI-MIZER, HAIL GUARD, BACnetCOMPATIBLE CONTROLLER, DIFFERENTIALTEMPERATURE ECONOMIZER, BAROMETRIC RELIEF,WEATHERPROOF NON-FUSED DISCONNECT SWITCH,AND 350MM A.F.R. PREFABRICATED ROOF CURB

ROOFTOP UNIT SCHEDULE cont`d

ELECTRIC FORCE FLOW HEATER SCHEDULETAG LOCATION MANUFACTURER MODEL

AIR FLOW CAPACITY POWERREMARKS

LPS CFM KW MBH V/PH/Hz HP

FF-1 STAIR NO. 1[602] OUELLET OAS03036 241 510 3.0 10.2 575/3/60 0.03 WALL MOUNT BRACKET, DISCONNECT SWITCH, AND

WALL THERMOSTAT

FF-2 STAIR NO. 2[603] OUELLET OAS03036 241 510 3.0 10.2 575/3/60 0.03 WALL MOUNT BRACKET, DISCONNECT SWITCH, AND

WALL THERMOSTAT

PLUMBING FIXTURE CONNECTION SCHEDULETAG FIXTURE NAME

SANITARY VENT DCWS DHWS TEMPERED NON-POTABLEREMARKS

MM INS MM INS MM INS MM INS MM INS MM INS

W1 FLUSH VALVEWATERCLOSET 75 3.00 38 1.50 25 1 - - - - - -

L1 WALL HUNG LAVATORY 32 1.25 32 1.25 13 0.50 13 0.50 13 0.5 - -

S2 ONE COMPARTMENTSTAINLESS STEEL SINK 38 1.50 32 1.25 13 0.50 13 0.50 - - - -

S1 SERVICE SINK 75 3.00 38 1.50 19 0.75 19 0.75 - - - -

E1 EMERGENCY EYE/FACEWASH 32 1.25 - - 19 0.75 19 0.75 19 0.75 - -

E2 & E3 EMERGENCY EYE/FACEWASH - - - - 32 & 19 1.25 &

0.75 32 & 19 1.25 &0.75 32 & 19 1.25 &

0.75 - -

FD2 FLOOR DRAIN 50 2.00 - - - - - - - - - - ALL FLOOR DRAINS SHALL BE GANG TRAPPEDPER FLOOR LEVEL IN ACCORDANE WITHO.B.C. 7.4.5.1.(3). EACH GANG TRAP SHALLINCLUDE A TRAP SEAL PRIMER.FD3 / FFD3 FLOOR DRAIN & FUNNEL

FLOOR DRAIN 75 3.00 - - - - - - - - - -

SANITARY TO SERVICE SINK S1

PRESSURE REGULATOR SCHEDULE

TAGFLOW RATE

M /HR CFH3

INLET PRESSURE

kPa PSI

OUTLET PRESSURE

kPa INS. W.C.

MANUFACTURER(CANADIAN METER)

PRV-1

PRV-2

PRV-3

PRV-4

PRV-5

PRV-6

53.4 1885.0

2.0 72.0

12.7 450.0

2.0 72.0

2.0 72.0

21.1 1680.0

13.8 2.0 3.5 14.0 1813C: 38Ø OUTLET, 13mm ORIFICE

1813C: 19Ø OUTLET, 5mm ORIFICE

1813C: 19Ø OUTLET, 8mm ORIFICE

1813C: 19Ø OUTLET, 5mm ORIFICE

1813C: 19Ø OUTLET, 5mm ORIFICE

1813C: 38Ø OUTLET, 13mm ORIFICE

13.8 2.0 3.5 14.0

13.8 2.0 3.5 14.0

13.8 2.0 3.5 14.0

13.8 2.0 3.5 14.0

13.8 2.0 3.5 14.0

OUTDOORAIR VOLUME

LPS CFM

57 120

101 215

31 65

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:4

1 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL SCHEDULES

M608

60246477

Che

cker

Des

igne

rAp

prov

er

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 10: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

OUTDOOR AIR

EXHAUST AIR

EVFD-10EFC-10

EF-10

EF-8 EF-9

EXHAUST AIR EXHAUST AIR

EXHAUST AIR

EVFD-11EFC-11

EF-11

EVFD-8EFC-8

EVFD-9EFC-9

UH-2 UH-3

T

UH-5UH-4

SPACE OCCUPANCY SENSOR (TYP.)(4 GROUND FLOOR / 2 MEZZANINE)

TEMPERATURE SENSOR (TYP.)

MOTORIZEDDAMPER

GRAVITY BACKDRAFTDAMPER (TYP.)

T TT

OUTDOOR AIR

OA

T

FDP

FILTER

SUPPLY AIR

SVFD-1SFC-1

H

G

HXV

EXHAUST AIR

EVFD-4EFC-4

EF-4

EXHAUST AIR

EVFD-5EFC-5

EF-5

MUA-1

SPACE MOUNTEDTEMPERATURE SENSOR

SPACE OCCUPANCYSENSOR (TYP.)

T

EXHAUST AIR

EF-3

EVFD-3EFC-3

UH-1

TEMPERATURE SENSOR

OCCUPANCY SENSOR

OUTDOOR AIR

GRAVITY BACKDRAFTDAMPER

T

OUTDOOR AIR

EXHAUST AIR

EVFD-6EFC-6

EF-6

IFR-3 IFR-4

SPACE OCCUPANCY SENSOR (TYP.)

TEMPERATURE SENSOR (TYP.)

GRAVITY BACKDRAFTDAMPER (TYP.)

EXHAUST AIR

EVFD-7EFC-7

EF-7

TT

OUTDOOR AIR

OUTDOOR AIR

IFR-1 IFR-2

EF-12

EVFD-12EFC-12

EXHAUST AIR

MOTORIZED DAMPER(TYP.)

NOx + CO GAS DETECTIONSENSOR(S) TYPICAL

TEMPERATURE SENSOR (TYP.)

T T

ABBREVATION DESCRIPTIONEFCEVFDFDP

EXHAUST FAN MOTOR CURRENTEXHAUST VARIABLE FREQUENCY DRIVEFILTER DIFFERENTIAL PRESSURE

HXV NATURAL GAS FIRED INDIRECT HEAT EXCHANGERIFR INFRARED HEATERMUA MAKE-UP AIR UNITOAT OUTDOOR AIR TEMPERATURE SENSORSFCSVFD

SUPPLY AIR MOTOR CURRENTSUPPLY AIR VARIABLE FREQUENCY DRIVE

UH UNIT HEATERRTU ROOF TOP UNITMUA MAKE-UP AIR UNITEF EXHAUST FANIFR INFRARED HEATERUH UNIT HEATERCP STAND A LONE CONTROLLER CONTROL PANEL

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:4

4 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL CONTROLSCHEMATICS

M609

60246477

?S

HS

H

M609 SCALE: N.T.S

1 SCHEMATIC - SLUDGE THICKENER RM. 604 CONTROL

M609 SCALE: N.T.S

2 SCHEMATIC - PUMP GALLERY RM. 601 CONTROL

M609 SCALE: N.T.S

3 SCHEMATIC - DECHLORINATION RM. 615 CONTROL

M609 SCALE: N.T.S

4 SCHEMATIC - CENTRIFUGE RM. 617 CONTROL

M609 SCALE: N.T.S

5 SCHEMATIC - TRUCK BAY RM. 614 CONTROL

BUILDING AUTOMATION POINTS LISTANALOGUE IN ANALOGUE OUT DIGITAL IN DIGITAL OUT SOFTWARE PROGRAMS

TEM

PER

ATU

RE

HU

MID

ITY

DIF

FER

EN

TIAL

PR

ESS

UR

E

FLO

W

CO

NC

ENTR

ATIO

N

0 - 1

0 V

OLT

S

4 - 2

0Ma

STAT

US

FILT

ER

HIG

H L

EVEL

FIR

E

FLO

W

OC

CU

PAN

CY

STAR

T / S

TOP

ENAB

LE /

DIS

ABLE

OPE

N /

CLO

SE

ALA

RM

TIM

E S

CH

EDU

LE

EN

THAL

PY

RE

SE

T

EV

EN

T PR

OG

RA

M

MA

INTE

NA

NC

E

GR

APH

IC

ROOFTOP UNIT [RTU-1] (CP-1) X X

SUPPLY FAN X X X X X X

GAS FIRED HEAT EXCHANGER X X X X X

CONDENSER X X X X

OUTDOOR AIR DAMPER X X

FILTERS X X X

AIR QUALITY SENSOR X X X

TEMPERATURE SENSORS X

ROOFTOP UNITS [RTU-2] & [RTU-3] (CP-2) & (CP-3) X X

SUPPLY FAN X X X X X X

GAS FIRED HEAT EXCHANGER X X X X X

CONDENSERS X X X X

OUTDOOR AIR DAMPER X X

FILTERS X X X

TEMPERATURE SENSORS X

HUMIDITY SENSORS X X X

PUMP GALLERY [601] (CP-4) X

SUPPLY FAN [MUA-1] X X X X X

GAS FIRED HEAT EXCHANGER [MUA-1] X X X X X

FILTERS [MUA-1] X X X

EXHAUST FANS [EF-4] & [EF-5] X X X X X

TEMPERATURE SENSOR X X

OCCUPANCY SENSORS X X

SLUDGE THICKENER [604] (CP-5) X

UNIT HEATERS [UH-2], [UH-3], [UH-4] & [UH-5] X X X X X X

EXHAUST FANS [EF-8], EF-9], [EF-10] & [EF-11] X X X X X

TEMPERATURE SENSOR X X

OCCUPANCY SENSORS X X

OUTDOOR AIR DAMPERS X

TRUCK BAY [614] (CP-6) X

INFRARED HEATERS [IFR-1] & [IFR-2] X X X X X X

EXHAUST FAN [EF-12] X X X X X X

TEMPERATURE SENSORS X X

GAS DETECTION SENSORS X X

OUTDOOR AIR DAMPERS X

DECHLORINATION ROOM [615] (CP-7) X

UNIT HEATER [UH-1] X X X X X X

EXHAUST FAN [EF-3] X X X X X

TEMPERATURE SENSOR X X

OCCUPANCY SENSOR X X

CENTRIFUGE ROOM [617] (CP-8) X

INFRARED HEATERS [IFR-3] & [IFR-4] X X X X X X

EXHAUST FANS [EF-6] & [EF-7] X X X X X

TEMPERATURE SENSOR X X

OCCUPANCY SENSORS X X

OUTDOOR AIR DAMPERS X

GEN

ERAL

ALA

RM

TO

SC

ADA

X

X

X

X

X

X

X

X

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 11: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

3"(75mm) 1"(25mm)2"(50mm)

18"(450mm)

1"(25mm)3"(75mm) 2"(50mm)

36"(900mm)

HOT WATER HEATING

HOT WATER HEATING

SECONDARY COLOR BAND

PRIMARY COLOR

DIRECTION ARROW

LEGEND

LEGEND

DIRECTION ARROW

PRIMARY COLOR

SECONDARY COLOR BAND

VALVE

TT

HOT WATER

COLD WATERTEMPERED WATER

ISOLATION VALVE

SURFACE MOUNTEDSTAINLESS STEELCABINET

THERMOMETER

THERMOSTATIC WATERCONTROLLER c/w INTEGRALCHECK STOPS.

32Ø32Ø

EMERGENCY FIXTURE

(75m

m)

(200

mm

)

(450mm)

(150mm)

PORTABLE PIPE SUPPORT

DIAMETER

HOOD

3" 8"

18"2"(50mm)

6"

D + 4" MIN.(100mm)SLEEVE DIAMETER

D = PIPE

1/4" x 6"(6.5 x 150mm)CLAMPING COLLAR

FLASHING BYGENERALCONTRACTOR

CLAMP TO PIPE

COPPER WEATHER

REFER TO STRUCTURAL DRAWINGSFOR ROOF CONSTRUCTION

S.P. (in. wg.)

-5.00-4.75-4.50-4.25-4.00-3.75-3.50-3.25-3.00

-1.00-1.25-1.50-1.75-2.00-2.25-2.50-2.75

-0.25-0.50-0.75

0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00 4.25 4.50 4.75 5.00 8.50

8.137.757.387.006.636.255.885.505.134.754.384.003.633.252.882.502.131.751.381.00

2.131.751.38

5.134.754.384.003.633.252.882.5

5.505.886.256.637.007.387.758.138.50

H (in.) H1 (in.)

3.002.882.752.632.502.382.252.132.00

1.001.131.251.381.501.631.751.88

0.630.750.88

0.500.630.750.881.001.131.251.381.501.631.751.882.002.132.252.382.502.632.752.883.00

OUTLET (TRAP INLET)WHERE S.P. DENOTES STATIC PRESSURE AT DRAIN

H = 1.5 x S.P. +1"H1 = 0.5 x S.P. +0.5"

SUCTION SIDE (-ve SP)

DISCHARGE SIDE (+ve SP)

H

H1

H

FLOW

FLOW

DRAIN PLUG

H1

INTERIOR WALLS

EXTERIOR WALLS

TERMINATE SLEEVE FLUSH WITH FINISHED WALLSURFACES

SEAL OR CAULK SLEEVE THROUGH FIRE WALLS INA SMOKE TIGHT MANNER

CONCEALED PIPING

COAT EXTERIOR SURFACES WITH TAR COMPOUND

CENTER PIPE IN SLEEVEFILL VOID WITH NONSHRINK HYDRAULIC GROUT

STANDARD WEIGHT STEEL PIPE POURED IN PLACE

SEALING (WATERSTOP), AND ANCHORING COLLAR

STANDARD WEIGHT STEEL PIPE SLEEVE OF SIZE TO PASS PIPE ANDINSULATION

FINISHED ESCUTCHEON PLATE FLUSH AGAINST WALL AND OF SIZETO COMPLETELY COVER OPENING

PIPE AND INSULATION TO BE CENTERED IN SLEEVE. DO NOT SUPPORTPIPE FROM SLEEVE

FINISHED WALLSURFACE

PIPING EXPOSED TO VIEW

EXTERIOR

CONCRETE WALL CONSTRUCTION

NOTE: BRICK & BLOCK WALL CONSTRUCTION TO BE SIMILAR.

SEAL SLEEVE WITH LINK SEAL

INTERIOR

NON-SHRINK GROUT

1/4"(6mm) THICK STEEL PLATEWELDED TO PIPE SLEEVE

EXISTING FLOOR SLAB

MIN. 2" (50mm)

MIN. 3" (76mm)

PIPE WITH / WITHOUT INSULATION

FIRE STOP SEALANT1/4"(6mm) THICK STEEL PIPESLEEVE 2"(50mm) LONGERTHAN DIAMETER OF PIPEINCLUDING INSULATION

NOTE:

ALL APPLICATIONS TO BE VERIFIED WITH STRUCTURAL ENGINEER.

REFER TO REQUIREMENTS FOR SERVICE PENETRATIONS ANDFIRE STOP SYSTEMS.

BRANCH DUCT

SINGLE LEAF BALANCING DAMPER

TAPERED SIDE TAKE-OFF

SUPPLY AIR PLENUMAIR FLOW

`X'

`X'

D

D2

D112"

`L'

SECONDARY BRANCH

SLOPE NOT TO

D1 VOLUME IN MAIN DUCT AFTER TAKE-OFF

D2 VOLUME IN SECONDARY BRANCHRATIO

R= D2 + 3/4 D

FULL HEIGHT LOCKABLE SPLITTER DAMPER

MAIN SUPPLY DUCT

(300mm)MINIMUMAIR FLOW

`L' = 1-1/2 D2 FOR 8" (200mm) TO 24" (600mm)

`L' = 1-1/4 D2 FOR D2 OVER 24" (600mm)

=

R= 3/4 D

BRANCH DUCTSTYPICAL ALLVOLUME DAMPER

EXCEED 1 IN 7

PWH-1

INSTANTANEOUSWATER HEATER

NA

TUR

AL

GA

SG

DIRT POCKETTYP.

50Ø

S

TO FFD3

PWH-2

INSTANTANEOUSWATER HEATER

NA

TUR

AL

GA

SG

50Ø

S

TO FFD3

PWH-3

INSTANTANEOUSWATER HEATER

NA

TUR

AL

GA

SG

50Ø

S

TO FFD332Ø 32Ø

75Ø

32Ø 32Ø 32Ø

BY

DIV

. 15

BY

DIV

. 11

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:4

8 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL SCHEMATICS ANDDETAILS

M610

60246477

Che

cker

Des

igne

rAp

prov

er

M610 SCALE: N.T.S

1 DETAIL - PIPING IDENTIFICATIONM610 SCALE: N.T.S

2 SCHEMATIC - MIXING VALVE AND CABINETM610 SCALE: N.T.S

3 DETAIL - GAS PIPING THROUGH ROOF

M610 SCALE: N.T.S

4 DETAIL - TRAPS FOR AIR HANDLING UNITSM610 SCALE: N.T.S

5 DETAIL - PIPE WALL PENETRATIONM610 SCALE: N.T.S

6 DETAIL - PIPE FLOOR PENETRATION

M610 SCALE: N.T.S

8 DETAIL - ROUND DUCT TAKE-OFFM610 SCALE: N.T.S

7DETAIL - FULL RADIUS ELBOW BRANCHTAKE-OFF

M610 SCALE: N.T.S

9 DETAIL - SCHEMATIC OF PROCESS GAS-FIRED WATER HEATER

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf

Page 12: RESIDUALS MANAGEMENT FACILITY - London, … - 90 ° elbow - 45° wye ...

D

R=D+3/4 D

R=3/4 D

STRAIGHT

FLOW

AIR

12"(300mm)

FULL HEIGHT LOCKABLE SPLITTER DAMPER

`L'=1-1/2 D FOR 8" (200mm) TO 24" (600mm)

`L'=1-1/4 D FOR OVER 24" (600mm)

`L' MINIMUM

SLOPE 1 IN 7

CURVED FOR 45°

BRANCH DUCTSTYPICAL ALL

VOLUME DAMPER

D

R=D+3/4 D

R=3/4 D

STRAIGHT

FLOW

AIR

VOLUME DAMPERTYPICAL ALL BRANCH DUCTS

CURVED FOR 45°

SLOPE 1 IN 7

`L' = 1-1/2 D2 FOR 8" (200mm) TO 24" (600mm)`L' = 1-1/4 D2 FOR D2 OVER 24" (600mm)

MINIMUMFLOW

AIR

HINGE

SPLITTER RODCLAMP

BRANCH DUCT

MAIN DUCT

D1

D2

`L' 12" (300mm)

CONNECTION TOBREAKAWAY

COLLAR AND

DUCT WITH

FILLER PIECE ATBLADE HEAD.

OF DAMPER

4. INSTALL DAMPER SQUARE AND PLUMB.

TO ENSURE FREE MOVEMENT.8. CYCLE DAMPER AFTER INSTALLATION

OR DAMPER DIRECTLY TO WALL.

5. DO NOT CAST DAMPER IN PLACE.

6. DO NOT CAULK OR SEAL DAMPERTO WALL. ENSURE THAT EXPANSION

7. DO NOT FASTEN RETAINING ANGLES

CLEARANCES ARE KEPT.

3. INSTALL DAMPER IN PLANE OF FIRE SEPARATION.

FRAMED PARTITIONS OR WALLS.

NOTES:

1. FIRE DAMPERS TO BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

2. INSPECT WALL OPENINGS PRIOR TO DAMPERINSTALLATION TO VERIFY SIZE OF OPENINGAND PROPER PREPARATION. REFER TOMANUFACTURER'S INSTALLATION INSTRUCTIONS

FOR PREPARATION OF OPENINGS IN STUD

DUCT

RETAINING ANGLE IN ACCORDANCE

INSTALLATION INSTRUCTIONS.WITH MANUFACTURER'S

1" (25mm) OVERLAP

INSTALLATION INSTRUCTIONS.

CENTRE LINE

INSTALLATION INSTRUCTIONS.ACCORDANCE WITH MANUFACTURER'SFASTEN COLLAR TO DAMPER IN

FASTEN ANGLE TO COLLAR IN

COLLAR

MAXIMUM 1/2" (13mm) SPACE FOR EXPANSION

ACCORDANCE WITH MANUFACTURER'S

DUCT WITH BREAKAWAY CONNECTIONTO COLLAR AND FILLER PIECE AT BLADEHEADE

FASTEN ANGLE TO COLLAR INACCORDANCE WITH MANUFACTURERSINSTALLATION INSTRUCTIONS

MAXIMUM 1/2" (13mm) SPACEFOR EXPANSION

CENTRE LINE OF DAMPER

FASTEN COLLAR TO DAMPER INACCORDANCE WITH MANUFACTURERSINSTALLATION INSTRUCTIONS

RETAINING ANGLE IN ACCORDANCEWITH MANUFACTURERSINSTALLATION INSTRUCTIONS

STAINLESS STEEL SPRING CLOSURE

SLEEVE

COLLAR

1" (25mm)OVERLAP

DUCT

4. INSTALL DAMPER SQUARE AND PLUMB.

TO ENSURE FREE MOVEMENT.8. CYCLE DAMPER AFTER INSTALLATION

OR DAMPER DIRECTLY TO WALL.

5. DO NOT CAST DAMPER IN PLACE.

6. DO NOT CAULK OR SEAL DAMPERTO WALL. ENSURE THAT EXPANSION

7. DO NOT FASTEN RETAINING ANGLES

CLEARANCES ARE KEPT.

3. INSTALL DAMPER IN PLANE OF FIRE SEPARATION.

NOTES:

1. FIRE DAMPERS TO BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

2. INSPECT FLOOR OPENINGS PRIOR TO DAMPERINSTALLATION TO VERIFY SIZE OF OPENINGAND PROPER PREPARATION. REFER TOMANUFACTURER'S INSTALLATION INSTRUCTIONS

DUCT COLLAR

BREAKAWAY JOINT

DUCT

MAXIMUM 1/2" SPACE FOR EXPANSION

FASTEN COLLAR TO DAMPER INACCORDANCE WITH MANUFACTURER'SINSTALLATION INSTRUCTIONS.

INSTALLATION INSTRUCTIONS.WITH MANUFACTURER'SRETAINING ANGLE IN ACCORDANCE

1. FIRE DAMPERS TO BE INSTALLED IN STRICTACCORDANCE WITH MANUFACTURER'SINSTALLATION INSTRUCTIONS.

2. INSPECT FLOOR OPENINGS PRIOR TO DAMPERINSTALLATION TO VERIFY SIZE OF OPENINGAND PROPER PREPARATION. REFER TOMANUFACTURER'S INSTALLATION INSTRUCTIONSFOR PREPARATION OF OPENINGS IN STUDFRAMED PARTITIONS OR WALLS.

3. INSTALL DAMPER IN PLANE OF FIRE SEPARATION.

4. INSTALL DAMPER SQUARE AND PLUMB.

5. DO NOT CAST DAMPER IN PLACE.

6. DO NOT CAULK OR SEAL DAMPER TO WALLENSURE THAT EXPANSION CLEARANCES ARE KEPT.

7. DO NOT FASTEN RETAINING ANGLES OR DAMPERDIRECTLY TO WALL.

8. CYCLE DAMPER AFTER INSTALLATION TO ENSUREFREE MOVEMENT.

NOTES:

32Ø 19Ø

T T T

DW

HS

DC

WS

DH

WR

NA

TUR

AL

GA

SG

GWH-1

INSTANTANEOUSWATER HEATER

DIRT POCKET

50Ø

AQUASTAT

P-1

TEMPERATURE ANDPRESSURE RELIEF VALVE

TIMER

TO SERVICE SINK

S.A. ARMSTRONGAST.5 (OR EQUAL)EXPANSION TANK

FOR LOCATIONS OF VOLUME DAMPERSREFER TO FLOOR PLAN FOR

1-1/2 D

CV 1-1/2

C

NOTEV = 1-1/2 C + 2"C & D ARE AS NOTED ON FLOOR PLAN

P

P

150Ø

150Ø POTABLE WATER SERVICEFROM VALVE CHAMBER

PVC SS

STAIRWELL

100x150

150x32 RED

150-UW-SS

100x150

BY DIV. 11 BY DIV. 15

TO FD

150 SERVICE WATER

32 POTABLE WATER

REDUCED PRESSUREBACKFLOW PREVENTERS

FLOOR ELEV. 204.55

SEE MEC. DWGS

WATER METERBY DIV. 11

TO FD

BY

DIV

. 15

BY

DIV

. 11

PROJECT

CLIENT

CONSULTANT

KEY PLAN

ISSUE/REVISION

SHEET NUMBER

SHEET TITLE

PROJECT NUMBER

ISSUED FOR TENDER

Last

Plo

tted:

File

nam

e:

Printed on ___% Post-ConsumerRecycled Content Paper

Proj

ect M

anag

emen

t Ini

tials

:Des

igne

r:C

heck

ed:

Appr

oved

:IS

O A

1 59

4mm

x 8

41m

m

2345

12345

D

C

B

A

1

ELGIN AREA WATERSUPPLY SYSTEM

AECOM250 York Street, Suite 410London, Ontario N6A 6K2519.676.0510 tel 519.673.5975 faxwww.aecom.com

235 North Centre Road, Suite 200 LondonOntario N5X 4E7519.930.3505 tel 519.474.0451 faxwww.watersupply.london.ca

2013-10-090

10/4

/201

3 9:

15:5

0 AM

C:\U

sers

\koh

lers

\Doc

umen

ts\R

evit

Loca

l File

s\60

2464

77-M

OD

-30-

0000

-M-C

F_ko

hler

s.rv

t

MANAGEMENT

43665 Dexter Line

FACILITY

RESIDUALS

Central Elgin, Ontario N0L 2L0

ELGIN AREA WATER TREATMENT PLANT

MECHANICAL SCHEMATICS ANDDETAILS

M611

60246477

Che

cker

Des

igne

rAp

prov

er

M611 SCALE: 1 : 1

5 DETAIL - SUPPLY TAP-IN CONNECTION

M611 SCALE: 1 : 1

2 DETAIL - RETURN TAP-IN CONNECTIONM611 SCALE: N.T.S

3 DETAIL - SPLITTER DAMPER

M611 SCALE: 1 : 1

4DETAIL - TYPE B FIRE DAMPERINSTALLATION VERTICAL

M611 SCALE: 1 : 1

1DETAIL - TYPE B FIRE DAMPERINSTALLATION HORIZONTAL

M611 SCALE: N.T.S

7DETAIL - SIDE WALL FIRE DAMPERINSTALLATION

M611 SCALE: N.T.S

9DETAIL - SCHEMATIC OF GAS-FIREDWATER HEATER

M611 SCALE: N.T.S

6 DETAIL - CONICAL TEE CONNECTION

M611 SCALE: N.T.S

8 SCHEMATIC - PLANT SERVICE WATER

I/R DATE DESCRIPTION

60246477-Elgin RMF_M600s_2013-10-04_Rev0 For TENDER.pdf