1 Communities of Interest A Review of Comments in the Arizona IRC Record February 7, 2004.
RESIDENTIAL PLAN REVIEW 2018 IRC - ICC · ©Colorado Code Consulting, LLC 2020 4 2018 IRC Plan...
Transcript of RESIDENTIAL PLAN REVIEW 2018 IRC - ICC · ©Colorado Code Consulting, LLC 2020 4 2018 IRC Plan...
RESIDENTIAL PLAN REVIEW 2018 IRC
©Colorado Code Consulting, LLC 2020 1
2018 IRC Plan Review
RESIDENTIAL PLAN REVIEW 2018 IRC
© 2020 Colorado Code Consulting, LLC 2
INSTRUCTOR Gil Rossmiller
• In the construction industry for over 40 years
• ICC – IRC Plumbing & Mechanical Code Development Committee
• ICC- IECC Commercial Energy Code Development Committee
• 2003-2016 Building Official Parker, Colorado
INTERACTIVE CLASS
© 2020 Colorado Code Consulting, LLC 3
TOOLS/EQUIPMENT
Code Book!
Other Resources
© 2020 Colorado Code Consulting, LLC 4
©Colorado Code Consulting, LLC 2020 2
2018 IRC Plan Review
ELECTRONIC CODE RESOURCES
ICC Publications I-Quest
I-Codes PDF
New online codes format
NFPA Publications
Federal Requirements
© 2020 Colorado Code Consulting, LLC 5
EFFECTIVE USE OF THE 2018 IRC
Chapter 44 Referenced Standards
© 2020 Colorado Code Consulting, LLC 6
INFORMATION ON CONSTRUCTION DOCUMENTS – 106.1.1
Construction documents shall be drawn upon suitable material.
Electronic media documents are permitted to be submitted when approved by the building official.
© 2020 Colorado Code Consulting, LLC 7
TOOLS/EQUIPMENT
Drafting Table
Calculator
Architect Scale
Engineer Scale
© 2020 Colorado Code Consulting, LLC 8
©Colorado Code Consulting, LLC 2020 3
2018 IRC Plan Review
TOOLS/EQUIPMENT -ELECTRONIC
9
• Software
• Monitor (usually larger than the typical)
• Electronic stamps
• Electronic signature
© 2020 Colorado Code Consulting, LLC
• Professional manner
• Courteous
• Prompt
• Good frame of mind
• Refrain from criticism
• Work to limit complaints
© 2020 Colorado Code Consulting, LLC 10
• Unskilled people
• Be patient
• Expect to spend more time
• Use opportunity to educate about the codes
© 2020 Colorado Code Consulting, LLC 11 © 2020 Colorado Code Consulting, LLC 12
• Project
• Project Location/Address
• Date of Review
• Based on Plans Dated
• Designer/Architect
• Review Contacts
• Total floor area • May include options
• Stories
• Automatic fire Suppression
• Code used for review
©Colorado Code Consulting, LLC 2020 4
2018 IRC Plan Review
DISCLAIMER
This report does not purport to review, interpret, apply, or certify compliance with the accessibility requirements set forth within the Americans with Disabilities Act (ADA). The application, interpretation and enforcement of the ADA are vested with the Federal Department of Justice. Applicants are encouraged to seek professional review to ensure compliance with the ADA
© 2020 Colorado Code Consulting, LLC 13 © 2020 Colorado Code Consulting, LLC 14
• Note number
• Sheet number
• Room/area number
• Correction item
• Code section
• Don’t forget mannersB-3 Refer to sheet A-2.2:
a. Please provide a smoke detector located in the immediate vicinity of bedroom #1. 2018 IRC R314.1
b. It appears the hallway to bedrooms #2 and #3 will not meet the minimum 36” dimension. R311.6
EFFECTIVE USE OF THE 2018 IRC
The IRC is a prescriptive-oriented (specification) code with some examples of performance code language. It has been said that the IRC is the complete cookbook for residential construction.
© 2020 Colorado Code Consulting, LLC 15 © 2020 Colorado Code Consulting, LLC 16
EFFECTIVE USE OF THE 2018 IRC
The International Residential Code (IRC) was created to serve as a complete, comprehensive code regulating the construction of single-family houses, two-family houses (duplexes) and buildings consisting of three or more townhouse units.
©Colorado Code Consulting, LLC 2020 5
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC
R101.2 SCOPE
The provisions of the IRC shall apply to:
Construction Repair
Alteration Equipment
Movement Use and Occupancy
Enlargement Location
Replacement Removal and Demolition
of detached one and two family dwellings and multiple single-family dwellings (townhouses) not more than 3 stories in height with a separate means of egress and their accessory structures not more than 3 stories in height.
17 © 2020 Colorado Code Consulting, LLC 18
R101.2 SCOPE (2018)Exception: The following shall be permitted to be constructed in accordance with this code where provided with a residential fire sprinkler system complying with Section P2904:
1. Live/work units located in townhouses and complying with the requirements of Section 419 of the International Building Code.
2. Owner-occupied lodging houses with five or fewer guestrooms.
3. A care facility with five or fewer persons receiving custodial care within a dwelling unit.
4. A care facility with five or fewer persons receiving medical care within a dwelling unit.
5. A care facility for five or fewer persons receiving care that are within a single-family dwelling.
DEFINITIONS - R202 (2018)
ACCESS (TO) That which enables a device, an appliance or equipment to be reached by ready access or by a means that first requires the removal or movement of a panel, door or similar obstruction.
© 2020 Colorado Code Consulting, LLC 19
DEFINITIONS - R202 (2018)
ATTIC The unfinished space between the ceiling assembly and the roof assembly
ATTIC, HABITABLE A finished or unfinished habitable space within an attic
© 2020 Colorado Code Consulting, LLC
©Colorado Code Consulting, LLC 2020 6
2018 IRC Plan Review
DEFINITIONS - R202 (2018)
CHANGE OF OCCUPANCY. A change in the use of a building or portion of a building that involves a change in the application of the requirements of this code.
© 2020 Colorado Code Consulting, LLC 21
DEFINITIONS - R202 (2018)
READY ACCESS (TO).
That which enables a device, appliance or equipment to be directly reached, without requiring the removal or movement of any panel, door or similar obstruction.
© 2020 Colorado Code Consulting, LLC 22
DEFINITIONS - R202 (2018)
VAPOR DIFFUSION PORT
A passageway for conveying water vapor from an unvented attic to the outside atmosphere
Applies to new unvented roof assemblies in climate zones 1, 2 and 3
© 2020 Colorado Code Consulting, LLC 23
DEFINITIONS - R202
© 2020 Colorado Code Consulting, LLC 24
Dwelling Unit
A single unit providing complete independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation.
©Colorado Code Consulting, LLC 2020 7
2018 IRC Plan Review
DEFINITIONS - R202
TownhouseA single-family dwelling unit constructed in a group of three or more attached units in which each unit extends from foundation to roof and with open space on at least two sides.
© 2020 Colorado Code Consulting, LLC 25
TOWNHOUSE DEFINITION• Originally based on the Boston Row
House
© 2020 Colorado Code Consulting, LLC
Plan View
TOWNHOUSE DEFINITION
• Modified to permit “groups”
© 2020 Colorado Code Consulting, LLC
50% CCC Interpretation
DEFINITION
GRADE PLANE
A reference plane representing the average of the finished ground level adjoining the building at all exterior walls. Where the finished ground level slopes away from the exterior walls, the reference plane shall be established by the lowest points within the area between the building and the lot line or, where the lot line is more than 6 feet from the building between the structure and a point 6 feet from the building.
© 2020 Colorado Code Consulting, LLC 28
©Colorado Code Consulting, LLC 2020 8
2018 IRC Plan Review
DEFINITION
STORY ABOVE GRADE PLANE. Any story having its finished floor surface entirely above grade plane, or in which the finished surface of the floor next above is either of the following:
1. More than 6 feet above grade plane
2. More than 12 feet above the finished ground level at any point
© 2020 Colorado Code Consulting, LLC 29
THREE STORY…..
© 2020 Colorado Code Consulting, LLC 30
R325.6 HABITABLE ATTIC 2018
A habitable attic shall not be considered a story where complying with all of the following requirements:
1. The occupiable floor area is not less than 70 square feet (17 m2), in accordance with Section R304.
2. The occupiable floor area has a ceiling height in accordance with Section R305.
3. The occupiable space is enclosed by the roof assembly above, knee walls (if applicable) on the sides and the floor-ceiling assembly below.
4. The floor of the occupiable space shall not extend beyond the exterior walls of the floor below.
© 2020 Colorado Code Consulting, LLC 31
SUBMITTAL DOCUMENTS
Site/Plot Plan
Soils report
Floor Plan
Elevations
Sections
Details
Structural
Plumbing
Mechanical
Electrical
Energy
Supporting Documents© 2020 Colorado Code Consulting, LLC 32
©Colorado Code Consulting, LLC 2020 9
2018 IRC Plan Review
Soils ReportTruss DesignsTruss LayoutsEnergy Path DocumentsManual JManual SManual DManufacturer’s
SpecificationsEvaluation Reports – ES
Report
© 2020 Colorado Code Consulting, LLC 33 © 2020 Colorado Code Consulting, LLC 34
R106.1.2 MANUFACTURER’S INSTALLATION INSTRUCTIONS.
R106.1.2 Manufacturer’s installation instructions.
Manufacturer’s installation instructions……shall be available on the job site at the time of inspection.
© 2020 Colorado Code Consulting, LLC 35
DESIGN CRITERIA - TABLE R301.2(1)
l. In accordance with Figure R301.2(4)A, where there is local historical data documenting unusual wind conditions, the jurisdiction shall fill in this part of the table with “YES” and identify any specific requirements. Otherwise, the jurisdiction shall indicate “NO” in this part of the table.
m. In accordance with Section R301.2.1.2.1, the jurisdiction shall indicate the wind-borne debris wind zone(s). Otherwise, the jurisdiction shall indicate “NO” in this part of the table. © 2020 Colorado Code Consulting, LLC 36
DESIGN CRITERIA - TABLE R301.2(1) 2018
n. The jurisdiction shall fill in these sections of the table to establish the design criteria using Table 1a or 1b from ACCA Manual J or established criteria determined by the jurisdiction.
Note: See Table 10A for altitude Correction Factor
Wind speeds are averages/system defaults during non-storm conditions
15 7.5 30% 45%-50%High (H)
70° 75°39° N 90°-3°
59
0.84 73
©Colorado Code Consulting, LLC 2020 10
2018 IRC Plan Review
PLAN REVIEW- DESIGN LOADS R301
© 2020 Colorado Code Consulting, LLC 37
SITE/PLOT PLAN
An overhead diagram of the property including property lines the building outline, and other improvements on the property
Dimensions to building
© 2020 Colorado Code Consulting, LLC 38
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302
R302.1 Exterior walls. Construction, projections, openings and penetrations of exterior walls of dwellings and accessory buildings shall comply with Table R302.1(1); or dwellingsequipped throughout with an automatic sprinkler system ……shall comply with Table R302.1(2).
© 2020 Colorado Code Consulting, LLC 39
TABLE R302.1(1) NEW FOOTNOTES (2018)
© 2020 Colorado Code Consulting, LLC 40
1 hour—tested in accordance with ASTM E119, UL 263 or Section 703.3 of the International Building Code with exposure from both sides
Building without fire sprinklers
©Colorado Code Consulting, LLC 2020 11
2018 IRC Plan Review
TABLE R302.1(1) NEW FOOTNOTES (2018)
© 2020 Colorado Code Consulting, LLC 41
1 hour on the underside, or heavy timber, or fire-retardant-treated wood a, b
Building without fire sprinklers
TABLE R302.1 (1) FOOTNOTE: A
© 2020 Colorado Code Consulting, LLC 42
TABLE R302.1 (1) FOOTNOTE: B
© 2020 Colorado Code Consulting, LLC 43
Gable vent not allowed
TABLE R302.1(2) NEW FOOTNOTES (2018)
© 2020 Colorado Code Consulting, LLC 44
©Colorado Code Consulting, LLC 2020 12
2018 IRC Plan Review
TABLE R302.1(2)FOOTNOTE: A
• For residential subdivisions where all dwellings are equipped throughout with an automatic sprinkler systems installed in accordance with Section P2904, the fire separation distance for nonrated exterior walls and rated projections shall be permitted to be reduced to 0 feet, and unlimited unprotected openings and penetrations shall be permitted, where the adjoining lot provides an open setback yard that is 6 feet or more in width on the opposite side of the property line.
© 2020 Colorado Code Consulting, LLC 45
6 ft.
© 2020 Colorado Code Consulting, LLC 46
PLAN REVIEW – FACE OF WALL TO PROPERTY LINE
Prop
erty
Lin
e
R302.2TOWNHOUSES (2018)
Walls separating townhouse units shall be constructed in accordance with Section R302.2.1 or R302.2.2.
© 2020 Colorado Code Consulting, LLC 47
R302.2.1 DOUBLE WALLS (2018)
Each townhouse shall be separated by two 1-hour fire-resistance-rated wall assemblies tested in accordance with ASTM E119, UL 263 or Section 703.3 of the International Building Code.
© 2020 Colorado Code Consulting, LLC 48
©Colorado Code Consulting, LLC 2020 13
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 49
R302.2.2TOWNHOUSES (2015/2018)
• Common walls separating townhouses shall be assigned a fire-resistance rating in accordance with Section R302.2, Item 1 or 2.
• 1. Sprinklers = 1-hour
• 2. No Sprinklers = 2 hours
• 2018 added IBC section 703.3
CONTINUITYR302.2.3 (UNCHANGED)
• The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosedaccessory structures.
© 2020 Colorado Code Consulting, LLC 50
PARAPETR302.2.4 (UNCHANGED)
• Where roof surfaces adjacent to the wall or walls are at the same elevation, the parapet shall extend not less than 30 inches above the roof surfaces.
© 2020 Colorado Code Consulting, LLC 51
PARAPETR302.2.4 (UNCHANGED)
• A parapet is not required in two situations• Roof is covered with a minimum class C roof covering• Roof sheathing is noncombustible materials or approved fire-
retardant-treated wood for a distance of 4 feet on each side of the wall or walls,
• or one layer of 5 /8 -inch Type X gypsum board is installed directly beneath the roof sheathing for a distance of 4 feet on each side of the wall or walls.
© 2020 Colorado Code Consulting, LLC 52
©Colorado Code Consulting, LLC 2020 14
2018 IRC Plan Review
PARAPETR302.2.4 (UNCHANGED)
© 2020 Colorado Code Consulting, LLC 53
A parapet is not required:
• Different elevations and the higher roof is more than 30 inches above the lower roof.
• Common wall construction from the lower roof to the underside of the higher roof deck shall not have less than a 1-hour fire-resistive rating.
Dwelling “A” Dwelling “B”
>30”
roof
roof
One-hourwall
1 HR
STRUCTURAL INDEPENDENCER302.2.4 (2015)
• Each townhouse shall be structurally independent
• Exceptions:• foundations
• roof & wall sheathing may fasten to common wall
• nonstructural wall coverings
• flashing
• Townhouses separated by a common wall as provided in Section R302.2.2, Item 1 or 2.
© 2020 Colorado Code Consulting, LLC 54
R302.4.2 MEMBRANE PENETRATIONS (2018)
New exception:
4. Ceiling membrane penetrations by listed luminaires or by luminaires protected with listed materials that have been tested for use in fire resistance-rated assemblies and are installed in accordance with the instructions included in the listing.
© 2020 Colorado Code Consulting, LLC 55
GARAGES & CARPORTSR302.5
• No openings into sleeping room
• Other openings• solid wood door 1 3/8”
• honeycomb core steel door 1 3/8”
• 20-minute fire-rated
• Self-closing
• Ducts• 26 gauge or other approved material
© 2020 Colorado Code Consulting, LLC 56
©Colorado Code Consulting, LLC 2020 15
2018 IRC Plan Review
R302.6 DWELLING/GARAGE SEPARATION
© 2020 Colorado Code Consulting, LLC 57
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302.6
R302.6 Dwelling-garage fire separation. The garage shall be separated as required by Table R302.6. Openings in garage walls shall comply with Section R302.5. Attachment of gypsum board shall comply with Table R702.3.5………
© 2020 Colorado Code Consulting, LLC 58
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302.7
Enclosed space under stairs that is accessed by a door or access panel shall have walls, under-stair surface and any soffits protected on the enclosed side with 1/2-inch gypsum board
© 2020 Colorado Code Consulting, LLC 59
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302.11
R302.11 Fireblocking.
In combustible construction,
fireblocking shall be provided…….vertical
and horizontal
concealed draft openings…….fire
barrier between
stories……top story and the roof space.
© 2020 Colorado Code Consulting, LLC 60
©Colorado Code Consulting, LLC 2020 16
2018 IRC Plan Review
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302.12
R302.12 Draftstopping. In combustible construction where there is
usable space both above and
below the concealed space of a
floor-ceiling assembly, draftstops
shall be installed so the…space does
not exceed 1,000 square feet…..assembly
is enclosed by a floor membrane above and a ceiling membrane below, draftstopping shall be provided in….
1. Ceiling is suspended under the floor framing.
2. Floor framing is constructed of truss-type open-web or perforated members.
© 2020 Colorado Code Consulting, LLC 61
PLAN REVIEW FIRE-RESISTANT CONSTRUCTION R302.13
R302.13 Fire protection of floors.
Floor assemblies that are
not required elsewhere…
to be fire-resistance rated,
shall be provided with a
1/2-inch gypsum wallboard
membrane, 5/8-inch wood
structural panel membrane, or equivalent on the underside of the floor framing member. Penetrations or openings for ducts, vents, electrical outlets, lighting, devices, luminaires, wires, speakers, drainage, piping and similar openings or penetrations shall be permitted.
© 2020 Colorado Code Consulting, LLC 62
R302.13 – FIRE PROTECTION OF FLOORS
• Exception 1
• Floor assemblies located directly over a space protected by fire sprinklers
• P2904
• NFPA 13d
63© 2020 Colorado Code Consulting, LLC
R302.13 – FIRE PROTECTION OF FLOORS (2018)
• Exception 2
• Floor assemblies located directly over a crawl space not intended for storage or fuel-fired equipment or electric-powered heating appliances
64© 2020 Colorado Code Consulting, LLC
©Colorado Code Consulting, LLC 2020 17
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 65
R302.13 – FIRE PROTECTION OF FLOORS • Exception 3
• Permits unprotected floor assemblies when:
• 80sf area or less per story in aggregate
• Fire blocking is provided in the cavity between the protected and unprotected portions
• Intended to address mechanical areas with piping, ducts or other penetration issues.
R302.13 – FIRE PROTECTION OF FLOORS
• Exception 4
• Wood floor assemblies using 2x10 or greater dimension solid or composite lumber.
• Also permits testing for equivalency to these materials.
66© 2020 Colorado Code Consulting, LLC
© 2020 Colorado Code Consulting, LLC 67
PLAN REVIEW LIGHT, VENTILATION & HEATING R303
Definition:
[RB] HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces.
© 2020 Colorado Code Consulting, LLC 68
PLAN REVIEW LIGHT, VENTILATION & HEATING R303R303.1 Habitable rooms.
Habitable rooms shall have….
glazing area of not less than 8% of the floor area of such rooms.
Natural ventilation……..
openable area to the
outdoors shall be not
less than 4% of the floor
area being ventilated.
©Colorado Code Consulting, LLC 2020 18
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 69
PLAN REVIEW LIGHT, VENTILATION & HEATING R303R303.1 Habitable rooms.
Exceptions:
1. The glazed areas need not be openable where the opening is not required by Section R310 and a whole-house mechanical ventilation system is installed in accordance with Section M1507
2. The glazed areas need not be installed in rooms where Exception 1 is satisfied and artificial light is provided that is capable of producing an average illumination of 6 foot candles over the area of the room at a height of 30 inches above the floor level.
PLAN REVIEW LIGHT, VENTILATION & HEATING R303.3
R303.3 Bathrooms.
Bathrooms, water closet
compartments and other similar
rooms shall have area in windows
a minimum of 3 square feet
one half of which must be openable.
Exception:…not required where
artificial light and a local exhaust
system are provided…..exhaust rates
shall be determined with M1507.
Exhaust air….shall be exhausted directly to the outdoors.
© 2020 Colorado Code Consulting, LLC 70
PLAN REVIEW LIGHT, VENTILATION & HEATING R303.4
R303.4 Mechanical ventilation.
Where the air infiltration rate of a
dwelling unit is 5 air changes per hour
or less where tested with
a blower door at a pressure
of 0.2 inch w.c (50 Pa)…
the dwelling unit shall have
whole-house mechanical
ventilation in accordance with Section M1507.3.
© 2020 Colorado Code Consulting, LLC 71
M1507 MECHANICAL VENTILATION
• Outdoor air is required to be provided by the system.
• Must be provided with controls that enable manual override.
• Continuous per Table 1507.3.3(1)
• Intermittent per Table 1507.3.3(2)
© 2020 Colorado Code Consulting, LLC 72
©Colorado Code Consulting, LLC 2020 19
2018 IRC Plan Review
M1507 MECHANICAL VENTILATION
© 2020 Colorado Code Consulting, LLC 73
Math: (Number of bedrooms + 1 x 7.5) + (0.01 x conditioned floor area)
THREE BASIC TYPES OF WHOLE HOUSE VENTILATION SYSTEMS
Exhaust Only
© 2020 Colorado Code Consulting, LLC 74
THREE BASIC TYPES OF WHOLE HOUSE VENTILATION SYSTEMS
Supply Only
© 2020 Colorado Code Consulting, LLC 75
THREE BASIC TYPES OF WHOLE HOUSE VENTILATION SYSTEMS
Balanced (with heat recovery) HRV or ERV
© 2020 Colorado Code Consulting, LLC 76
©Colorado Code Consulting, LLC 2020 20
2018 IRC Plan Review
PLAN REVIEW LIGHT, VENTILATION & HEATING R303.7
R303.7 Interior stairway illumination.
Interior stairways
shall be provided with an
artificial light source to
Illuminate the landings and
treads. The light source…..
illuminating treads and landings…
not less than 1foot-candle…
center of treads and landings.
wall switch at each floor level…
stairway has six or more risers.
© 2020 Colorado Code Consulting, LLC 77
PLAN REVIEW LIGHT, VENTILATION & HEATING R303.8
R303.8 Exterior stairway illumination.
Exterior stairways…
with an artificial light
source located at the
top landing of the
stairway.
© 2020 Colorado Code Consulting, LLC 78
PLAN REVIEW LIGHT, VENTILATION & HEATING R303.9R303.9 Required heating.
Where the winter design temperature
is below 60°F every dwelling unit shall
be provided with heating capable of
maintaining a minimum 68°F at a point
3 feet above the floor and
2 feet from exterior walls in
habitable rooms….
. …portable space heaters not allowed
© 2020 Colorado Code Consulting, LLC 79
PLAN REVIEW MINIMUM ROOM AREA/DIMENSIONS 304
R304.1 Minimum area
Habitable rooms floor area
of not less than 70 square feet
Exception: Kitchens.
R304.2 Minimum dimensions
Habitable rooms not less than 7 feet
in any horizontal dimension.
Exception: Kitchens
R305.1 Minimum height. Habitable space, hallways and portions of basements containing these spaces shall have a ceiling height of not less than 7 feet. Bathrooms, toilet rooms and laundry rooms shall have a ceiling height of not less than 6 feet 8 inches.
© 2020 Colorado Code Consulting, LLC 80
©Colorado Code Consulting, LLC 2020 21
2018 IRC Plan Review
PLAN REVIEW CEILING HEIGHT R305R305.1.1 Basements.
Portions of basements
that do not contain
habitable space or
hallways shall
have a ceiling height of
not less than 6 feet 8
inches .
Exception:
At beams, girders, ducts or other obstructions, the ceiling height shall be not less than 6 feet 4 inches from the floor.
© 2020 Colorado Code Consulting, LLC 81
PLAN REVIEW SANITATION R306
R306.1 Toilet facilities
Every dwelling unit shall be
provided with a water closet,
lavatory, and a bathtub or shower.
R306.2 Kitchen.
Each dwelling unit shall be
provided with a kitchen area
and every kitchen area shall be
provided with a sink.
© 2020 Colorado Code Consulting, LLC 82
FIGURE R307.1 MINIMUM FIXTURE CLEARANCES
• Bathtub and shower floors and walls above bathtubs with installed shower heads and in shower compartments shall be finished with a nonabsorbent surface.
• 6 feet above the floor.
© 2020 Colorado Code Consulting, LLC 83
PLAN REVIEW GLAZING R308
R308.4 Hazardous locations
The locations specified in
Sections R308.4.1 through
R308.4.7 shall be considered
to be specific hazardous
Locations…
© 2020 Colorado Code Consulting, LLC 84
©Colorado Code Consulting, LLC 2020 22
2018 IRC Plan Review
PLAN REVIEW GLAZING R308
R308.4.1 Glazing in doors
Glazing in fixed and operable
panels of doors
© 2020 Colorado Code Consulting, LLC 85
PLAN REVIEW GLAZING R308
© 2020 Colorado Code Consulting, LLC 86
R308.4.2 Glazing adjacent to doorsGlazing in an individual fixed or operable panel adjacent to a door..where the bottom exposed edgeof the glazing is less than 60 inchesabove the floor or walking surface and it meets either of the following conditions:
© 2020 Colorado Code Consulting, LLC 87
1. Where the glazing is within 24 inches (610 mm) of either side of the door in the plane of the door in a closed position.
© 2020 Colorado Code Consulting, LLC 88
R308.4.2 GLAZING ADJACENT TO DOORS (2018)
• 2. Where the glazing is on a wall is less than 180° from the plane of the door in a closed position and within 24 inches of the hinge side of an in-swinging door.
Yes
NoNo
No
Less than 180°
©Colorado Code Consulting, LLC 2020 23
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 89
Exceptions:Where there is an intervening wall or other permanent barrier between the door and the glazing.
© 2020 Colorado Code Consulting, LLC 90
PLAN REVIEW GLAZING R308
R308.4.3 Glazing in windows
Glazing in an individual fixed
or operable panel that meets all…
considered to be a hazardous location:
1. The exposed area of an individual pane is larger than 9 square feet
2. The bottom edge of the glazing is less than 18 inches above the floor
3. The top edge of the glazing is more than 36 inches above the floor
4. One or more walking surfaces are within 36 inches measured horizontally and in a straight line, of the glazing.
© 2020 Colorado Code Consulting, LLC 91
PLAN REVIEW GLAZING R308
R308.4.4 Glazing in guards and railings
Glazing in guards and railings,
including structural baluster
panels and nonstructural in-fill
panels, regardless of area or
height above a walking surface
shall be considered to be a
hazardous location.
© 2020 Colorado Code Consulting, LLC 92
©Colorado Code Consulting, LLC 2020 24
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 93
R308.4.4.1 STRUCTURAL GLASS BALUSTER PANELS Guards with structural glass baluster panels shall be installed with an attached top rail or handrail. The top rail or handrail shall be supported by not less than three glass baluster panels, or shall be otherwise supported to remain in place should one glass baluster panel fail.
Exception: An attached top rail or handrail is not required where the glass baluster panels are laminated glass with two or more glass plies of equal thickness and of the same glass type.
© 2020 Colorado Code Consulting, LLC 94
R308.4.5 Glazing and wet surfaces
Glazing in walls, enclosures or fences containing or facing hot tubs, spas, whirlpools, saunas, steam rooms, bathtubs, showers and indoor or outdoor swimming pools where the bottom exposed edge of the glazing is less than 60 inches measured vertically above any standing or walking surface shall be considered to be a hazardous location. This shall apply to single glazing and each pane in multiple glazing.
© 2020 Colorado Code Consulting, LLC 95
© 2020 Colorado Code Consulting, LLC 96
©Colorado Code Consulting, LLC 2020 25
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 97
© 2020 Colorado Code Consulting, LLC 98
R308.4.6 Glazing adjacent to stairs and ramps
Glazing where the bottom exposed edge of the glazing is less than 36 inches above
the plane of the adjacent
Walking surface of
stairways, landings
between flights of stairs
and ramps shall be
considered to be a
hazardous location.
© 2020 Colorado Code Consulting, LLC 99
© 2020 Colorado Code Consulting, LLC 100
©Colorado Code Consulting, LLC 2020 26
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 101
R308.4.7 Glazing adjacent to the bottom stair landing Glazing adjacent to the
landing at the bottom of a
stairway where the glazing
is less than 36 inches above
the landing and within a
60-inch horizontal arc less
than 180 degrees from the
bottom tread nosing shall be
considered to be a hazardous location.
R308.4.7 GLAZING ADJACENT TO THE BOTTOM STAIR LANDING
Glazing adjacent to the landing at the bottom of a stairway where the glazing is less than 36 inches above the landing and within a 60-inch horizontal arc less than 180 degrees from the bottom tread nosing shall be considered to be a hazardous location.
© 2020 Colorado Code Consulting, LLC 102
Less than 180°
PLAN REVIEW EMERGENCY ESCAPE AND RESCUE OPENINGS R310
R310.1 Emergency escape and rescue opening required.
Basements, habitable attics and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room. Emergency escape and rescue openings shall open directly into a public way, or to a yard or court that opens to a public way.
© 2020 Colorado Code Consulting, LLC 103
© 2020 Colorado Code Consulting, LLC 104
PLAN REVIEW EMERGENCY ESCAPE AND RESCUE OPENINGS
R310.2.1 Minimum opening area
net clear opening of 5.7 square feet
height opening 24 inches
width 20 inches
Exception:
Grade floor or below
grade openings shall
have a net clear opening
of not less than 5 square feet
©Colorado Code Consulting, LLC 2020 27
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 105
PLAN REVIEW EMERGENCY ESCAPE AND RESCUE OPENINGS
R310.2.2 Window sill height
sill height of not more than 44 inches
≤ 44 Inches
© 2020 Colorado Code Consulting, LLC 106
PLAN REVIEW EMERGENCY ESCAPE AND RESCUE OPENINGS
R310.2.3 Window wells
The horizontal area of the
window well minimum
9 square feet, with
a horizontal projection
and width of 36 inches
window well shall allow the
emergency escape and
rescue opening to be fully opened.
© 2020 Colorado Code Consulting, LLC 107
R310.2.1 LADDER AND STEPSWindow wells with a vertical depth greater than 44 inches shall be equipped with a permanently affixed ladder or steps usable with the window in the fully open position.
Not required to comply with Sections R311.7 and R311.8.
Ladders or rungs - inside width of at least 12 inches
Must project at least 3 inches from the wall Must be spaced not more than 18 inches on center vertically for the full height of the window well.
PLAN REVIEW EMERGENCY ESCAPE AND RESCUE OPENINGS
R310.2.3.2 Drainage
Window wells
shall have
drainage
© 2020 Colorado Code Consulting, LLC 108
Link to plans
©Colorado Code Consulting, LLC 2020 28
2018 IRC Plan Review
R310.3EMERGENCY ESCAPE/RESCUE DOORS (2018) Where a door is provided as the required emergency escape and rescue opening, it shall be permitted to be a side-hinged door or a slider
Where the opening is below the adjacent ground elevationgrade, it shall be provided with a bulkhead enclosure an area
well.
© 2020 Colorado Code Consulting, LLC 109
R310.3.1 MINIMUM DOOR OPENING SIZE
• The minimum net clear height opening for any door that serves as an emergency and escape rescue opening shall be in accordance with Section R310.2.1. (Egress openings)
© 2020 Colorado Code Consulting, LLC 110
R310.3.2 AREA WELLS
Area wells shall have a width of not less than 36 inches. The area well shall be sized to allow the emergency escape and rescue door to be fully opened
© 2020 Colorado Code Consulting, LLC 111
R310.3.2.1 LADDERS AND STEPS (2018)
Required if area well greater than 44” deep
Need not comply with R311.7 (Stairways)
Ladders or rungs
Inside ≥ 12”
Project ≥ 3”
Rung spacing ≤ 18”
© 2020 Colorado Code Consulting, LLC 112
©Colorado Code Consulting, LLC 2020 29
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 113
PLAN REVIEW MEANS OF EGRESS R311
R311.1 Means of egress
Dwellings shall be provided
with a means of egress…..
shall provide a continuous
and unobstructed path of
vertical and horizontal from
all portions of the dwelling
to the egress door without travel through a garage…..
The egress door shall open directly
into a public way, yard or court that opens to a public way.
© 2020 Colorado Code Consulting, LLC 114
R311.2 Egress door
A minimum of one
egress door shall be side-hinged
clear width of not less than 32 inches
where measured face of the door and the stop,
door open at 90 degrees
The clear height of the door opening
shall be not less than 78 inches
Egress doors shall be readily openable from inside the dwelling without the use of a key or special knowledge or effort.
Link to plans
R310.2.4 EMERGENCY ESCAPE WINDOWS UNDER DECKS AND PORCHES
• Escape and rescue window must open fully and the path is not less than 36 inches in height to yard or court.
© 2020 Colorado Code Consulting, LLC 115 © 2020 Colorado Code Consulting, LLC 116
R311.3 Floors and landings at exterior doors
There shall be a landing or
floor on each side of each
exterior door….
width shall be not less
than the door served.
Every landing shall be not less
than 36 inches measured
in the direction of travel
slope at exterior landings shall not exceed 1/4 inch per foot
©Colorado Code Consulting, LLC 2020 30
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 117
R311.3.1 Floor elevations at the required egress doors.
maximum threshold
height 1 ½ inches
© 2020 Colorado Code Consulting, LLC 118
R311.3.1 Floor elevations at the required egress doors.
Exception:
The landing or floor
on the exterior side
can be a maximum
7 ¾ inches below the
top of the threshold
provided the door does
not swing over the
landing or floor.
© 2020 Colorado Code Consulting, LLC 119
FLOOR ELEVATIONS FOR OTHER EXTERIOR DOORS - R311.3.2
Doors other than the required egress door shall be provided with landings or floors not more than 7 ¾ inches below the top of the threshold.Exception: A top landing is not required where a stairway of not more than two risers is located on the exterior side of the door, provided that the door does not swing over the stairway.
© 2020 Colorado Code Consulting, LLC 120
R311.4 Vertical egress
Egress from habitable levels..
not provided with an
egress door shall be by a
ramp or stairway
©Colorado Code Consulting, LLC 2020 31
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 121
R311.6 Hallways
The width of a hallway
minimum of 3 feet
© 2020 Colorado Code Consulting, LLC 122
R311.7 Stairways.
R311.7.1 Width
Minimum 36 inches above
handrail below the required
headroom height Handrails shall not
project more than 4 ½ inches
on either side
R311.7.2 Headroom
shall be not less than 6 feet 8 inches
from the sloped line adjoining the tread
nosing or floor surface
R311.7.4 (2018)
© 2020 Colorado Code Consulting, LLC 123
The walkline across winder treads and landings shall be concentric to the turn and parallel to the direction of travel entering and exiting the turn. The walkline shall be located 12 inches from the inside of the turn. The 12-inch dimension shall be measured from the widest point of the clear stair width at the walking surface. Where winders are adjacent within a flight, the point of the widest clear stair width of the adjacent winders shall be used.
© 2020 Colorado Code Consulting, LLC 124
R311.7.5.1 Risers
Maximum riser height 7 ¾ inches
Cannot vary more than 3/8 inch
Be vertical or sloped
not more than 30 degrees
Open risers are permitted
the openings located more than
30 inches vertically to the floor
do not permit the passage of a
4-inch-diameter sphere
©Colorado Code Consulting, LLC 2020 32
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 125
R311.7.5.2 Treads
depth shall be not less than 10 inches
The tread depth measured
From nosing to nosing
right angle to the
tread’s leading edge
Largest cannot exceed the
smallest by more 3/8 inch
© 2020 Colorado Code Consulting, LLC 126
R311.7.6 Landings for stairways
landing at the top and bottom of each stairway
Landings of shapes other than square or
Rectangular are permitted provided that
radius equal to the required landing width
stairways with a straight run 36 inches depth
in the direction of travel
Exception: not required at the top of an interior flight of stairs, including stairs in an enclosed garage, provided that a door does not swing over the stairs.
© 2020 Colorado Code Consulting, LLC 127
PLAN REVIEW MEANS OF EGRESS R311
R311.7.8 Handrails
provided on not less than
one side of each continuous
run of treads or flight with
four or more risers.
R311.7.8.1 Height
34 inches to 38 inches
Vertically from top of
handrail to stair nosing
© 2020 Colorado Code Consulting, LLC 128
PLAN REVIEW MEANS OF EGRESS R311
R311.7.8.2 Continuity
Handrails for stairways shall be continuous for the full length of the flight, from a point directly above the top riser of the flight to a point directly above the lowest riser of the flight. Handrail ends shall be returned or shall terminate in newel posts or safety terminals. Handrails adjacent to a wall shall have a space of not less than 1-1/2 inches (38 mm) between the wall and the handrails.
©Colorado Code Consulting, LLC 2020 33
2018 IRC Plan Review
R311.7.8.3 Grip-size. Required handrails shall be of one of the following types or provide equivalent graspability.
© 2020 Colorado Code Consulting, LLC 129
© 2020 Colorado Code Consulting, LLC 130
R312.1.1 WHERE REQUIRED
GUARDS (2018)
• Guards shall provided for those portions of open-sided walking surfaces, including stairs, ramps and landings, that are located more than 30 inches measured vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side.
• Insect screening shall not be considered as a guard.
© 2020 Colorado Code Consulting, LLC 131
R312.1.3 Opening limitations
guards shall not have openings that allow passage of a sphere 4 inches in diameter
© 2020 Colorado Code Consulting, LLC 132
R312.2 WINDOW FALL PROTECTION
R312.2.1 Window sills
top of the sill is located less
than 24 inches above the
finished floor and greater
than 72 inches above the
finished grade or other
surface below on the
exterior of the building,
the operable window shall comply with one of the following:
©Colorado Code Consulting, LLC 2020 34
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 133
PLAN REVIEW GUARDS & FALL PROTECTION R312
1. Operable windows with openings that will not allow a 4 inch-diameter (102 mm) sphere to pass through the opening where the opening is in its largest opened position.
2. Operable windows that are provided with window fall prevention devices that comply with ASTM F 2090.
3. Operable windows that are provided with window opening control devices that comply with Section R312.2.2.
PLAN REVIEW GUARDS & FALL PROTECTION R312
© 2020 Colorado Code Consulting, LLC 134
PLAN REVIEW GUARDS & FALL PROTECTION R312
© 2020 Colorado Code Consulting, LLC 135 © 2020 Colorado Code Consulting, LLC 136
R313.2 One- and two-family dwellings automatic fire systems.
An automatic residential
fire sprinkler system shall
be installed in one- and
two-family dwellings.
AUTOMATIC FIRE SPRINKLER SYSTEMS R313
©Colorado Code Consulting, LLC 2020 35
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 137
PLAN REVIEW SMOKE ALARMS R314
R314.2.1 New construction
Smoke alarms shall be provided
in dwelling units.
R314.3 Location
In each sleeping room
Outside each separate sleeping
each additional story of the dwelling
R314.4 Interconnection
in such a manner that the actuation of one alarm will activate all of the alarms
R314.6 Power source
receive their primary power from the building wiring with battery backup
© 2020 Colorado Code Consulting, LLC 138
PLAN REVIEW CARBON MONOXIDE ALARMS R315R315.2.1 New construction
carbon monoxide alarms shall
be provided in dwelling units where…
1. The dwelling unit contains
a fuel-fired appliance.
2. The dwelling unit has an
attached garage with an
opening that communicates
with the dwelling unit.
© 2020 Colorado Code Consulting, LLC 139
CARBON MONOXIDE ALARMS R315.5 INTERCONNECTIVITY (2018)
When more than one required
Shall be interconnected (same as Smoke Detectors)
Exception:
Interconnection of carbon monoxide alarms in existing areas shall not be required where alterations or repairs do not result in removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available that could provide access for interconnection without the removal of interior finishes.
© 2020 Colorado Code Consulting, LLC 140
PLAN REVIEW CARBON MONOXIDE ALARMS R315R315.3 Location. Carbon monoxide alarms in dwelling units shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms. Where a fuel burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide alarm shall be installed within the bedroom.
R315.6 Power source. Carbon monoxide alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and, where primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection.
©Colorado Code Consulting, LLC 2020 36
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 141
PLAN REVIEW FOAM PLASTIC R316
R316.3 Surface burning characteristics
foam plastic or foam plastic cores used as a component in manufactured assemblies shall have a flame spread index of not more than 75 and shall have a smoke-developed index of not more than 450 when tested in the maximum thickness and density intended for use in accordance with ASTM E 84 or UL 723.
© 2020 Colorado Code Consulting, LLC 142
PLAN REVIEW FOAM PLASTIC R316R316.4 Thermal barrier
Unless otherwise allowed in Section R316.5, foam plastic shall be separated from the interior of a building by an approved thermal barrier of not less than 1/2-inch gypsum wallboard, 23/32-inch wood structural panel or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.
© 2020 Colorado Code Consulting, LLC 143
PLAN REVIEW FOAM PLASTIC R316R316.5.3 Attics
The thermal barrier specified in Section R316.4 is not required where all of the following apply:
1. Attic access is required by Section R807.1.
2. The space is entered only for purposes of repairs or maintenance.
© 2020 Colorado Code Consulting, LLC 144
PLAN REVIEW FOAM PLASTIC R3163.The foam plastic insulation has been tested in accordance with Section R316.6 or the foam plastic insulation is protected against ignition using one of the following ignition barrier materials:3.1. 11/2-inch-thick mineral fiber insulation.3.2. 1/4-inch-thick wood structural panels.3.3. 3/8-inch particleboard.3.4. 1/4-inch hardboard.3.5. 3/8-inch gypsum board.3.6. Corrosion-resistant steel base metal thickness of 0.016 inch3.7. 11/2-inch-thick cellulose insulation3.8. 1/4-inch fiber-cement panel, soffit or backer board.
©Colorado Code Consulting, LLC 2020 37
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 145
PLAN REVIEW FOAM PLASTIC R316R316.5.4 Crawl spaces.
The thermal barrier specified in Section R316.4 is not required where all of the following apply:
1. Crawl space access is required by Section R408.4
2. Entry is made only for purposes of repairs or maintenance.
© 2020 Colorado Code Consulting, LLC 146
PLAN REVIEW FOAM PLASTIC R316
R316.5.11 Sill plates and headers
Foam plastic shall be permitted to be spray applied to sill plates and headers or installed in the perimeter joist space without the thermal barrier specified in Section R316.4 subject to all of the following:
© 2020 Colorado Code Consulting, LLC 147
PLAN REVIEW FOAM PLASTIC R3161. Thickness ≤ 3 1/4 inches
2. Density shall be 0.5 to 2.0 pounds per cubic foot
3. Flame spread index of 25 or less and smoke-developed index of 450 or less when tested in accordance with ASTM E 84 or UL 723.
© 2020 Colorado Code Consulting, LLC 148
PLAN REVIEW PROTECTION OF WOOD AGAINST DECAY R317
Wood joists or wood structural floor less than 18 inches
or wood girders less than 12 inches
to the exposed ground in
crawl spaces or
within the periphery of the
building foundation.
©Colorado Code Consulting, LLC 2020 38
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 149
PLAN REVIEW PROTECTION OF WOOD AGAINST DECAY R317
Wood framing members
that rest on concrete or
masonry exterior
foundation walls and
are less than 8
inches from the
exposed ground
PLAN REVIEW PROTECTION OF WOOD AGAINST DECAY R317
Sills and sleepers on a
concrete or masonry slab
that is in direct contact
with the ground unless
separated from such slab
by an impervious
moisture barrier.
© 2020 Colorado Code Consulting, LLC 150
PLAN REVIEW PROTECTION OF WOOD AGAINST DECAY R317
wood girders entering
exterior masonry or
concrete walls having
clearances of less than
1/2 inch on tops, sides
and ends.
© 2020 Colorado Code Consulting, LLC 151
© 2020 Colorado Code Consulting, LLC 152
PLAN REVIEW PROTECTION OF WOOD AGAINST DECAY R317
Wood furring strips or
other wood framing
members attached
directly to the interior of
exterior masonry walls or
concrete walls below grade
except where an approved vapor retarder is applied between the wall and the furring strips or framing members.
Link to plans
©Colorado Code Consulting, LLC 2020 39
2018 IRC Plan Review
PLAN REVIEW PROTECTION AGAINST SUBTERRANEAN TERMITES R318
R318.1 Subterranean termite control methods. In areas subject to damage from termites as indicated by Table R301.2(1), methods of protection shall be one, or a combination, of the following methods:
© 2020 Colorado Code Consulting, LLC 153
PLAN REVIEW FLOOD RESISTANT CONSTRUCTION R322
R322.1 General. Buildings and structures constructed in whole or in part in flood hazard areas, including A or V Zones and Coastal A Zones, as established in Table R301.2(1), and substantial improvement and restoration of substantial damage of buildings and structures in flood hazard areas, shall be designed and constructed in accordance with the provisions contained in this section.
© 2020 Colorado Code Consulting, LLC 154
PLAN REVIEW SOLAR ENERGY SYSTEMS R324
R324.1 General. Solar energy systems shall comply with the
provisions of this section.
R324.2 Solar thermal systems. Solar thermal systems shall
be designed and installed in accordance with Chapter 23 and
the International Fire Code.
© 2020 Colorado Code Consulting, LLC 155
© 2020 Colorado Code Consulting, LLC 156
R324.4.1 ROOF LOADPortions of roof structures not covered with photovoltaic panel systems shall be designed for dead loads and roof loads in accordance with Sections R301.4 and R301.6. Portions of roof structures covered with photovoltaic panel systems shall be designed for the following load cases:
1. Dead load (including photovoltaic panel weight) plus snow load in accordance with Table R301.2(1).
2.Dead load (excluding photovoltaic panel weight) plus roof live load or snow load, whichever is greater, in accordance with Section R301.6.
©Colorado Code Consulting, LLC 2020 40
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 157
R324.6.1 PATHWAYS (2018)Two pathways, on separate roof planes from lowest roof edge to ridge and not less than 36 inches wide
One pathway shall be provided on the street or driveway side of the roof
Each roof plane with a photovoltaic array:
Pathway not less than 36 inches wide shall be provided from the lowest roof edge to ridge on the same roof plane as the photovoltaic array, on an adjacent roof plane, or straddling the same and adjacent roof planes.
Pathways shall be over areas capable of supporting fire fighters accessing the roof. Pathways shall be located in areas with minimal obstructions such as vent pipes, conduit, or mechanical equipment
R324.6 ROOF ACCESS AND PATHWAYS(2018)
Exceptions:
1. Detached non-habitable structures, carports, detached garages
2. AHJ determined no roof top operations
3. Roof pitch 2/12 and less
© 2020 Colorado Code Consulting, LLC 158
© 2020 Colorado Code Consulting, LLC 159
R324.6.2.2 EMERGENCY ESCAPE AND RESCUE OPENING
Panels and modules installed on dwellings shall not be placed on the portion of a roof that is below an emergency escape and rescue opening. A pathway not less than 36 inches wide shall be provided to the emergency escape and rescue opening
© 2020 Colorado Code Consulting, LLC 160
©Colorado Code Consulting, LLC 2020 41
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 161
R325.6 HABITABLE ATTIC (2018)A habitable attic shall not be considered a story where complying with all of the following requirements:
1. The occupiable floor area is not less than 70 square feet, in accordance with Section R304
2. The occupiable floor area has a ceiling height in accordance with Section R305
3. The occupiable space is enclosed by the roof assembly above, knee walls (if applicable) on the sides and the floor-ceiling assembly below
4. The floor of the occupiable space shall not extend beyond the exterior walls of the floor below
R327 STATIONARY STORAGE BATTERY SYSTEMS (2018)
Listed and labeled for residential use in accordance
with UL 9540.
© 2020 Colorado Code Consulting, LLC 162
PLAN REVIEW
Questions on Chapter 3???
© 2020 Colorado Code Consulting, LLC 163
© 2020 Colorado Code Consulting, LLC 164
PLAN REVIEW CHAPTER 4 FOUNDATIONS R401.4 Soil tests.
Where quantifiable data created
by accepted soil science
methodologies indicate
expansive, compressible,
shifting or other questionable
soil characteristics are likely to be present, the building official shall determine whether to require a soil test to determine the soil’s characteristics at a particular location. This test shall be done by an approved agency using an approved method.
©Colorado Code Consulting, LLC 2020 42
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 165
PLAN REVIEW-SOIL REPORT
Correct lot ?
Correct House Location?
PE Stamp?
Site Conditions?
Lab Testing?
Foundation Recommendation?
Wall Design?
Test Results?
© 2020 Colorado Code Consulting, LLC 166
PLAN REVIEW- FOUNDATION
Correct Site?Hold Downs?Sill Plate Connection?Correct Building Code and Design Loads?Does Foundation Design Match Soils Report?Footing Details? Size, Location, Voids, ReinforcementFoundation Wall Details? Size, Voids, Steps, Windows, Reinforcement
© 2020 Colorado Code Consulting, LLC 167
PLAN REVIEW FOUNDATION DRAINAGE R405
R405.1 Concrete or masonry foundations. Drains shall be provided around concrete or masonry foundations that retain earth and enclose habitable or usable spaces located below grade.
© 2020 Colorado Code Consulting, LLC 168
PLAN REVIEW FOUNDATION WATERPROOFING & DAMPPROOFING R406R406.1 Concrete and masonry foundation dampproofing.
…foundation walls that retain earth and enclose interior spaces and floors below grade shall be dampproofed from the …..top of the footing …..to the finished grade.
Link to plans
©Colorado Code Consulting, LLC 2020 43
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 169
PLAN REVIEW UNDER-FLOOR SPACE R408
R408.1 Ventilation.
The under-floor space between the bottom of the floor joists and the earth…
shall have ventilation
openings through
foundation walls or
exterior walls.
1sf per 150sf
Or 1sf per 1,500 sf with Class 1 Vapor retarder
© 2020 Colorado Code Consulting, LLC 170
PLAN REVIEW CHAPTER 4
R408.3 Unvented crawl space. Ventilation openings….
specified in Sections R408.1 and R408.2 shall not be required where the following items are provided:
© 2020 Colorado Code Consulting, LLC 171
PLAN REVIEW CHAPTER 4
…. a Class I vapor retarder is installed joints shall overlap by 6 inches and shall be sealed
The edges of the vapor retarder shall extend not less than 6 inches up the stem wall and shall be attached and sealed to the stem wall or insulation.
PLAN REVIEW CHAPTER 4
Provide ventilation:
Exhaust 1 cfm per 50 sf
or
Conditioned air at the same rate
© 2020 Colorado Code Consulting, LLC 172
©Colorado Code Consulting, LLC 2020 44
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 173
R408.3 UNVENTED CRAWL SPACE
• New option in 2018:
2.4. Dehumidification sized to provide 70 pints of moisture removal per day for every1,000 square feet of crawl space floor area
PLAN REVIEW CHAPTER 4
Questions on Chapter 4???
© 2020 Colorado Code Consulting, LLC 174
PLAN REVIEW CHAPTER 5 FLOORS
© 2020 Colorado Code Consulting, LLC 175
© 2020 Colorado Code Consulting, LLC 176
PLAN REVIEW CHAPTER 5 FLOORS
R502.3 Allowable joist spans. Spans for floor joists shall be in accordance with Tables R502.3.1(1) and R502.3.1(2).
©Colorado Code Consulting, LLC 2020 45
2018 IRC Plan Review
CONCRETE FLOORS 506
506.1 General.
• Concrete slab-on-ground floors shall be designed and constructed in accordance with the provisions of this section or ACI 332. Floors shall be a minimum 31/2 inches (89 mm) thick (for expansive soils, see Section R403.1.8). The specified compressive strength of concrete shall be as set forth in Section R402.2.
R506.2.2 Base.
• A 4-inch-thick (102 mm) base course consisting of clean graded sand, gravel, crushed stone, crushed concrete or crushed blast-furnace slag passing a 2-inch (51 mm) sieve shall be placed on the prepared subgrade where the slab is below grade. *LOOK FOR EXCEPTION
R506.2.3 Vapor retarder.
• A 6-mil (0.006 inch; 152 mm) polyethylene or approved vapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist. * LOOK FOR EXCEPTION
© 2020 Colorado Code Consulting, LLC 177
R507 EXTERIOR DECKS (2018)
R507.1 Decks
Wood-framed decks shall be in accordance with this section. For decks using materials and conditions not prescribed in this section, refer to Section R301
© 2020 Colorado Code Consulting, LLC 178
R507.3 FOOTINGS (2018)
Decks shall be supported on concrete footings or other approved structural systems
Deck footings shall be sized to carry the imposed loads from the deck structure to the ground as shown in Figure R507.3.
The footing depth shall be in accordance with Section R403.1.4.
© 2020 Colorado Code Consulting, LLC 179
R507.3.1 MINIMUM SIZE (2018)
The minimum size of concrete footings shall be in accordance with Table R507.3.1, based on the tributary area and allowable soil-bearing pressure in accordance with Table R401.4.1.
© 2020 Colorado Code Consulting, LLC 180
©Colorado Code Consulting, LLC 2020 46
2018 IRC Plan Review
R507.4 DECK POSTS
For single-level, wood-framed decks with beams sized in accordance with Table R507.5, deck post size shall be in accordance with Table R507.4
© 2020 Colorado Code Consulting, LLC 181
New table for 2018
R507.5 DECK BEAMS
Maximum allowable spans for wood deck beams, as shown in Figure R507.5, shall be in accordance with Table R507.5. Beam plies shall be fastened with two rows of 10d (3 inch by 0.128 inch) nails minimum at 16 inches on center along each edge. Beams shall be permitted to cantilever at each end up to one-fourth of the actual beam span. Deck beams of other materials shall be permitted where designed in accordance with accepted engineering practice
© 2020 Colorado Code Consulting, LLC 182
R507.5.1 DECK BEAM BEARING (2018)
The ends of beams shall have not less than 1 1/2 inches of bearing on wood or metal and not less than 3 inches of bearing on concrete or masonry for the entire width of the beam.
Where multiple-span beams bear on intermediate posts, each ply must have full bearing on the post in accordance with Figures R507.5.1(1) and R507.5.1(2)
© 2020 Colorado Code Consulting, LLC 183
NEW FOR 2018
© 2020 Colorado Code Consulting, LLC 184
©Colorado Code Consulting, LLC 2020 47
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 185
R507.6 DECK JOISTS
Maximum allowable spans for wood deck joists, as shown in Figure R507.6, shall be in accordance with Table R507.6. Deck joists shall be permitted to cantilever not greater than one-fourth of the actual, adjacent joist span.
© 2020 Colorado Code Consulting, LLC 186
© 2020 Colorado Code Consulting, LLC 187 © 2020 Colorado Code Consulting, LLC 188
New for 2018
©Colorado Code Consulting, LLC 2020 48
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 189
R507.6.2 LATERAL RESTRAINT AT SUPPORTS
Joist ends and bearing locations shall be provided with lateral restraint to prevent rotation. Where lateral restraint is provided by joist hangers or blocking between joists, their depth shall equal not less than 60 percent of the joist depth. Where lateral restraint is provided by rim joists, they shall be secured to the end of each joist with not less than (3) 10d (3 inch by 0.128 inch) nails or (3) No. 10 by 3 inch long wood screws.
No content changes for 2018
R507.7 DECKING Maximum allowable spacing for joists supporting decking shall be in accordance with Table R507.7. Wood decking shall be attached to each supporting member with not less than (2) 8d threaded nails or (2) No. 8 wood screws. Other approved decking or fastener systems shall be installed in accordance with the manufacturer’s installation requirements.
© 2020 Colorado Code Consulting, LLC 190
2018 minor changes to table
LEDGER DETAILS R507.9.11
Deck ledgers installed in accordance with Section R507.2 shall be a minimum 2-inch by 8-inch nominal, pressure-preservative-treated southern pine, incised pressure-preservative-treated Hem-fir, or approved, naturally durable, No. 2 grade or better lumber Shall not support concentrated loads from beams or girders. Deck ledgers shall not be supported on stone or masonry veneer
© 2020 Colorado Code Consulting, LLC 191 © 2020 Colorado Code Consulting, LLC 192
R507.9.2 DECK LATERAL LOAD CONNECTION Lateral loads shall be transferred to the ground or to a structure capable of transmitting them to the ground.
Where the lateral load connection is provided in accordance with Figure R507.9.2(1), hold-down tension devices shall be installed in not less than two locations per deck, within 24 inches of each end of the deck. Each device shall have an allowable stress design capacity of not less than 1,500 pounds. Where the lateral load connections are provided in accordance with Figure R507.9.2(2), the hold-down tension devices shall be installed in not less than four locations per deck, and each device shall have an allowable stress design capacity of not less than 750 pounds
©Colorado Code Consulting, LLC 2020 49
2018 IRC Plan Review
FIGURE 507.9.2(1)
© 2020 Colorado Code Consulting, LLC 193 194
FIGURE 507.9.2(2)
© 2020 Colorado Code Consulting, LLC
PLAN REVIEW CHAPTER 5 FLOORS
Questions on Chapter 5??????
© 2020 Colorado Code Consulting, LLC 195
© 2020 Colorado Code Consulting, LLC 196
PLAN REVIEW CHAPTER 6 WALLS
R602.3 Design and construction. Exterior walls of wood frame construction shall be designed and constructed in accordance with the provisions of this chapter and Figures R602.3(1) and R602.3(2), or in accordance with AWC NDS. Components of exterior walls shall be fastened in accordance with Tables R602.3(1) through R602.3(4). Wall sheathing shall be fastened directly to framing members and, where placed on the exterior side of an exterior wall, shall be capable of resisting the wind pressures listed in Table R301.2(2) adjusted for height and exposure using Table R301.2(3) and shall conform to the requirements of Table R602.3(3).
©Colorado Code Consulting, LLC 2020 50
2018 IRC Plan Review
PLAN REVIEW CHAPTER 6 WALLS
Portions of table R602.3(1)
© 2020 Colorado Code Consulting, LLC 197
PLAN REVIEW CHAPTER 6 WALLS
Table R602.3(3)
© 2020 Colorado Code Consulting, LLC 198
© 2020 Colorado Code Consulting, LLC 199
PLAN REVIEW CHAPTER 6 WALLS
R602.3.1 Stud size, height and spacing
The size, height and spacing of studs shall be in accordance with Table R602.3.(5).
PLAN REVIEW CHAPTER 6 WALLS
© 2020 Colorado Code Consulting, LLC 200
©Colorado Code Consulting, LLC 2020 51
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 201
GIRDER SPANSTABLE R602.7.1
Exterior header for 7’6” openingsupporting roof/ceiling
R602.7.2 RIM BOARD HEADERS
Rim board header size, material, and span shall be in accordance with Table R602.7(1) for rim board headers. Rim board headers shall be constructed in accordance with Figure R602.7.2 and shall be supported at each end by full height studs. The number of full height studs at each end shall be not less than the number of studs displaced by half of the header span based on the maximum stud spacing in accordance with Table R602.3(5). Rim board headers supporting concentrated loads shall be designed in accordance with accepted engineering practice
© 2020 Colorado Code Consulting, LLC 202
203
Figure R602.7.2
© 2020 Colorado Code Consulting, LLC
PLAN REVIEW CHAPTER 6 WALLS
© 2020 Colorado Code Consulting, LLC 204
©Colorado Code Consulting, LLC 2020 52
2018 IRC Plan Review
R602.9 Cripple walls
When exceeding 4 feet in
height such walls shall be framed of studs having the
size required for an
additional story….
less than 14 inches shall
be continuously sheathed
on one side with wood
structural panels
© 2020 Colorado Code Consulting, LLC 205
Link to Plan
© 2020 Colorado Code Consulting, LLC 206
PLAN REVIEW CHAPTER 6 WALLSR602.10.1 Braced wall lines.
braced wall lines shall be designated as straight lines
in the building plan placed in accordance with this section.
© 2020 Colorado Code Consulting, LLC 207
Link to plans
© 2020 Colorado Code Consulting, LLC 208
R602.10.1.2 OFFSETS ALONG A BRACED WALL LINE
• Exterior walls parallel to a braced wall line shall be offset not more than 4 feet from the designated braced wall line
• Interior walls used as bracing shall be offset not more than 4 feet from a braced wall line through the interior
©Colorado Code Consulting, LLC 2020 53
2018 IRC Plan Review
TABLE R602.10.1.3BRACED WALL LINE SPACING
© 2020 Colorado Code Consulting, LLC 209 © 2020 Colorado Code Consulting, LLC 210
• If wall line is 16’ long or less:• Two panels of any length, or
• One panel of 48” or more.
≤ 16’
© 2020 Colorado Code Consulting, LLC 211
• A braced wall line having a distance greater than 16 feet shall have a minimum of two braced wall panels.
>16’
© 2020 Colorado Code Consulting, LLC 212
©Colorado Code Consulting, LLC 2020 54
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 213
R602.10.3 Required length of bracing
1. All buildings in Seismic Design Categories A and B
shall use Table R602.10.3(1) and the applicable adjustment
factors in Table R602.10.3(2).
PLAN REVIEW CHAPTER 6 WALLS
Questions on Chapter 6???
© 2020 Colorado Code Consulting, LLC 214
© 2020 Colorado Code Consulting, LLC 215
PLAN REVIEW CHAPTER 7 WALL COVERINGS
R702.1 General
Interior coverings or
wall finishes shall be
installed in accordance
with this chapter and
Table R702.1(1), (2),(3)
and Table R702.3.5.
Interior finishes and
materials flame spread and smoke
development 200 Flame 450 Smoke
PLAN REVIEW CHAPTER 7 WALL COVERINGS
© 2020 Colorado Code Consulting, LLC 216
©Colorado Code Consulting, LLC 2020 55
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 217
PLAN REVIEW CHAPTER 7 WALL COVERINGS
R702.4 Ceramic tile.
R702.4.2 Backer boards
Materials used as backers
for wall tile in tub
shower areas and wall
panels in shower areas
shall have materials in
Table R702.4.2 installed
in accordance with the manufacturer’s recommendations.
PLAN REVIEW CHAPTER 7 WALL COVERINGS
© 2020 Colorado Code Consulting, LLC 218
© 2020 Colorado Code Consulting, LLC 219
PLAN REVIEW CHAPTER 7 WALL COVERINGS
R702.7 Vapor retarders.
Class I or II vapor retarders
Are required on the interior side of frame walls in
Climate Zones 5, 6, 7, 8 and Marine 4.
Exceptions:
1. Basement walls.
2. Below-grade portion of any wall.
3. Construction where moisture or its
freezing will not damage the materials.
© 2020 Colorado Code Consulting, LLC 220
PLAN REVIEW CHAPTER 7 WALL COVERINGS
R702.7.2 Material vapor retarder class
The vapor retarder class shall
be based on the manufacturer’s
certified testing or a tested assembly.
Class I: Sheet polyethylene,
unperforated aluminum foil.
Class II: Kraft-faced fiberglass batts.
Class III: Latex or enamel paint.
©Colorado Code Consulting, LLC 2020 56
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 221
PLAN REVIEW CHAPTER 7 WALL COVERINGS
R702.7.1 Class III vapor retarders. Class III vapor retarders shall be permitted where any one of the conditions in Table R702.7.1 is met.
© 2020 Colorado Code Consulting, LLC 222
R703.1 General
Exterior walls shall provide
the building with a
weather-resistant exterior
the exterior wall envelope
shall include flashing as
described in Section R703.4
R703.1.1 Water resistance
shall be designed and constructed that prevents the accumulation of water within the wall assembly by providing a water-resistant barrier and a means of draining to the exterior water that enters the assembly.
© 2020 Colorado Code Consulting, LLC 223
R703.2 Water-resistive barrierOne layer of No. 15 asphalt felt complying with ASTM D 226 or other approved water-resistive barrier material shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches lapped not less than 6 inches at joints shall be continuous to the top of walls and terminated at penetrations and building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section R703.1.
© 2020 Colorado Code Consulting, LLC 224
R703.4 Flashing
Approved corrosion-resistant
flashing shall be applied
shingle-fashion in a manner
to prevent entry of water
into the wall cavity
or penetration of water
to the building structural
Framing components.
shall be installed at the
following locations……
©Colorado Code Consulting, LLC 2020 57
2018 IRC Plan Review
1. EXTERIOR WINDOW AND DOOR OPENINGS
© 2020 Colorado Code Consulting, LLC 225
2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION
© 2020 Colorado Code Consulting, LLC 226
3. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS.
© 2020 Colorado Code Consulting, LLC 227
4. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM.
© 2020 Colorado Code Consulting, LLC 228
©Colorado Code Consulting, LLC 2020 58
2018 IRC Plan Review
5. WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD-FRAME CONSTRUCTION.
© 2020 Colorado Code Consulting, LLC 229
6. AT WALL AND ROOF INTERSECTIONS
© 2020 Colorado Code Consulting, LLC 230
6. AT WALL AND ROOF INTERSECTIONS
© 2020 Colorado Code Consulting, LLC 231
Link to Plans© 2020 Colorado Code Consulting, LLC 232
7. AT BUILT-IN GUTTERS.
©Colorado Code Consulting, LLC 2020 59
2018 IRC Plan Review
PLAN REVIEW CHAPTER 7 WALL COVERINGS
Questions on Chapter 7??????
© 2020 Colorado Code Consulting, LLC 233
© 2020 Colorado Code Consulting, LLC 234
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for buildings.
R801.2 Requirements. Roof and ceiling construction shall be capable of accommodating all loads imposed in accordance with Section R301 and of transmitting the resulting loads to the supporting structural elements.
R801.3 Roof drainage. In areas where expansive or collapsible soils are known to exist, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface not less than 5 feet (1524 mm) from foundation walls or to an approved drainage system.
© 2020 Colorado Code Consulting, LLC 235
R802.2 DESIGN AND CONSTRUCTION (2018)
The roof and ceiling assembly shall provide continuous ties across the structure to prevent roof thrust from being applied to the supporting walls. The assembly shall be designed and constructed in accordance with the provisions of this chapter and Figures R606.11(1), R606.11(2) and R606.11(3) or in accordance with AWC NDS.
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION
R802.10 Wood trusses.
R802.10.1 Truss design drawings
Truss design drawings, prepared in conformance to Section R802.10.1, shall be provided to the building official and approved prior to installation. Truss design drawings shall be provided with the shipment of trusses delivered to the job site. Truss design drawings shall include, at a minimum, the following information:
© 2020 Colorado Code Consulting, LLC 236
©Colorado Code Consulting, LLC 2020 60
2018 IRC Plan Review
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION
© 2020 Colorado Code Consulting, LLC 237
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION
© 2020 Colorado Code Consulting, LLC 238
Link to plansTRUSS DETAIL
© 2020 Colorado Code Consulting, LLC 239
R806.1 Ventilation required
Enclosed attics and enclosed
rafter spaces formed where
ceilings are applied directly
to the underside of roof rafters
shall have cross ventilation for
each separate space by ventilating
openings protected against the
entrance of rain or snow.
R806.5 UNVENTED ATTIC ASSEMBLIES
• Unvented conditioned attic assemblies (spaces between the ceiling joists of top story and the roof rafters) are permitted under specific conditions.
© 2020 Colorado Code Consulting, LLC 240
©Colorado Code Consulting, LLC 2020 61
2018 IRC Plan Review
R806.5 UNVENTED ATTIC ASSEMBLIES
1. Must be within the building thermal envelope.
2. No interior vapor barriers on ceiling side
3. Wood shingles/shakes – ¼ inch air between sheathing
4. Air-impermeable insulation on underside of roof deck (Climate Zones 5, 6, 7, and 8) must be a Class II vapor retarder or vapor retarder coating applied.
See 2018 IRC for climate zones 1, 2 and 3
© 2020 Colorado Code Consulting, LLC 241
R806.5 CONDITIONED ATTIC ASSEMBLIES
• Either Items 5.1, 5.2 or 5.3 shall be met, depending on the air permeability of the insulation directly under the structural roof sheathing.
© 2020 Colorado Code Consulting, LLC 242
© 2020 Colorado Code Consulting, LLC 243
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION
R807.1 Attic access
attic access opening to attic areas that have a vertical height of 30 inches or greater over an area of not less than 30 square feet
The rough-framed opening shall be not less than 22 inches by 30 inches and shall be located in a hallway or other readily accessible location.
PLAN REVIEW CHAPTER 8 ROOF CEILING CONSTRUCTION
Questions on Chapter 8?????
© 2020 Colorado Code Consulting, LLC 244
©Colorado Code Consulting, LLC 2020 62
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 245
PLAN REVIEW CHAPTER 9 ROOF ASSEMBLIES
R903.1 General
Roof decks shall be covered with
approvedroof coverings…
shall be designed and installed in
accordance with this code and the
approved manufacturer’s instructions
R903.2 Flashing
Flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints
© 2020 Colorado Code Consulting, LLC 246
PLAN REVIEW CHAPTER 9 ROOF ASSEMBLIES
R905.1.2 Ice barriers.
where there has been a history
of ice forming along the eaves
causing a backup of water as
designated in Table R301.2(1)
an ice barrier shall be installed
for asphalt shingles, metal roof shingles,
mineral- surfaced roll roofing, slate and slate-type shingles, wood shingles and wood shakes.
© 2020 Colorado Code Consulting, LLC 247
R905.2.4 Asphalt shingles
Asphalt shingles shall comply with ASTM D 3462.
R905.2.4.1 Wind resistance of asphalt shingles
Asphalt shingle packaging
shall bear a label to indicate
compliance with ASTM D 7158
and the required classification in
Table R905.2.4.1.
Exception: Asphalt shingles
not included in ASTM D 7158 shall be tested and labeled to indicate compliance with ASTM D 3161
PLAN REVIEW CHAPTER 9 ROOF ASSEMBLIES
© 2020 Colorado Code Consulting, LLC 248
©Colorado Code Consulting, LLC 2020 63
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 249
PLAN REVIEW CHAPTER 9 ROOF ASSEMBLIES
R905.2.8.5 Drip edgeA drip edge shall be provided ateaves and rake edges of shingle roofs
PLAN REVIEW CHAPTER 9 ROOF ASSEMBLIES
Questions on Chapter 9????
© 2020 Colorado Code Consulting, LLC 250
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
N1101.13 (R401.2) Compliance. Projects shall comply with one of the following:
1. Sections N1101.14 through N1104.
2. Section N1105 and the provisions of Sections N1101.14 through N1104 labeled “Mandatory.”
3. An energy rating index (ERI) approach in Section N1106.
© 2020 Colorado Code Consulting, LLC 251
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
© 2020 Colorado Code Consulting, LLC 252
©Colorado Code Consulting, LLC 2020 64
2018 IRC Plan Review
© 2020 Colorado Code Consulting, LLC 253
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
© 2020 Colorado Code Consulting, LLC 254
© 2020 Colorado Code Consulting, LLC 255
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY N1102.4.4 (R402.4.4) Rooms containing fuel-burning
appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel-burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table N1102.1.2, where the walls, floors and ceilings shall meet a minimum of the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section N1103. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8.
N1104LIGHTING SYSTEMS – LAMPS (2018)
N1104.1 (R404.1) Lighting equipment (Mandatory).
Not less than 90 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
© 2020 Colorado Code Consulting, LLC 256
©Colorado Code Consulting, LLC 2020 65
2018 IRC Plan Review
SECTION N1105 (R405)SIMULATED PERFORMANCE ALTERNATIVE(PERFORMANCE)
This section establishes criteria for compliance using simulated energy performance analysis. Such analysis shall include heating, cooling, mechanical ventilation and service water heating energy only.
© 2020 Colorado Code Consulting, LLC 257
© 2020 Colorado Code Consulting, LLC 258
© 2020 Colorado Code Consulting, LLC 259
SECTION N1106 (R406) ENERGY RATING INDEX COMPLIANCE ALTERNATIVE
N1106.2 (R406.2) Mandatory requirements.
Compliance with this section requires that the provisions identified in Sections N1101.13 through N1104 indicated as “mandatory” and in Section N1103.5.3 be met. The building thermal envelope shall be greater than or equal to levels of efficiency and Solar Heat Gain Coefficients in Table 402.1.1 or 402.1.3 of the 2009 International Energy Conservation Code.
© 2020 Colorado Code Consulting, LLC 260
©Colorado Code Consulting, LLC 2020 66
2018 IRC Plan Review
N1106.4 (R406.4) ERI-BASED COMPLIANCE 2018
© 2020 Colorado Code Consulting, LLC 261
Compliance based on an ERI analysis requires that the rated design be shown to have an ERI less than or equal to the appropriate value indicated in Table N1106.4 when compared to the ERI reference design
a. Where on-site renewable energy is included for compliance using the ERI analysis of Section N1106.4, the building shall meet the mandatory requirements of Section N1106.2, and the building thermal envelope shall be greater than or equal to the levels of efficiency and SHGC in Table N1102.1.2 or Table N1102.1.4. © 2020 Colorado Code Consulting, LLC
262
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
N1102.4 (R402.4) Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R1102.4.1 through R1102.4.4.
© 2020 Colorado Code Consulting, LLC 263
© 2020 Colorado Code Consulting, LLC 264
©Colorado Code Consulting, LLC 2020 67
2018 IRC Plan Review
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
© 2020 Colorado Code Consulting, LLC 265
© 2020 Colorado Code Consulting, LLC 266
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
© 2020 Colorado Code Consulting, LLC 267
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
© 2020 Colorado Code Consulting, LLC 268
©Colorado Code Consulting, LLC 2020 68
2018 IRC Plan Review
PLAN REVIEW CHAPTER 11 ENERGY EFFICIENCY
N1103.7 (R403.7) Equipment sizing and efficiency rating (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on building loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies.
© 2020 Colorado Code Consulting, LLC 269
© 2020 Colorado Code Consulting, LLC 270
..\..\..\..\HVAC Help\Manual J load Calc Key Elements Denver.pdf
Manual J, S and D Key Elements
© 2020 Colorado Code Consulting, LLC 271
Manual J, S and D Key Elements
..\..\..\..\HVAC Help\Manual S Key Elements.pdf
© 2020 Colorado Code Consulting, LLC 272
Manual J, S and D Key Elements
..\..\..\..\HVAC Help\Manual D Key Elements 2018.pdf
M
AN
UA
L J
LO
AD
CA
LC
UL
AT
ION
K
EY
EL
EM
EN
TS
Des
ign
Tem
pera
ture
s
Out
door
H
eati
ng
-3°
F (D
enve
r)
Coo
ling
90
° F
(Den
ver)
Indo
or
Hea
ting
70
°F @
30%
RH
Coo
ling
75
°F @
50%
RH
T
he d
esig
n gr
ains
wil
l be
abou
t
-30
to -
39 d
epen
ding
on
the
wea
ther
da
ta t
he s
oftw
are
uses
(D
enve
r)
Win
dow
s, S
kyli
ghts
and
D
oors
tha
t ar
e >
50%
G
lass
U-V
alue
s &
SH
GC
V
alue
s sh
all m
atch
the
con
stru
ctio
n pl
ans
Shad
ing
valu
es
Def
ault
for
bli
nds
shal
l be:
50%
bli
nds
at 4
5° m
ediu
m c
olor
Sc
reen
s sh
all b
e as
des
igne
d
Ove
rhan
gs
Shal
l be
reas
onab
ly c
lose
too
: as
des
igne
d an
d sh
own
on
cons
truc
tion
pla
ns
Tot
al a
rea
Shal
l be
reas
onab
ly c
lose
too
: A
s de
sign
ed a
nd s
how
n on
co
nstr
ucti
on p
lans
Exp
osur
e D
irec
tion
O
ne t
ime
buil
ds s
hall
be
orie
nted
as
plan
ned
Pro
duct
ion
hom
es s
hall
be
orie
nted
for
the
wor
st c
ase
air
cond
itio
ning
load
Ade
quat
e E
xpos
ure
Div
ersi
ty
If t
he e
xcur
sion
adj
ustm
ent
exce
eds
1000
Btu
h in
any
one
roo
m,
a se
para
te z
one
shou
ld b
e co
nsid
ered
. R
efer
to
Man
ual J
8th e
diti
on
sect
ion
A3-
3 fo
r a
mor
e de
tail
ed a
naly
sis.
Opa
que
Doo
rs
Tot
al A
rea
and
Loc
atio
n Sh
all b
e re
ason
ably
clo
se t
oo:
As
desi
gned
and
sho
wn
on
cons
truc
tion
pla
ns
U-
Val
ue
Val
ues
shal
l mat
ch t
he c
onst
ruct
ion
plan
s
A
bove
Gra
de W
alls
B
elow
Gra
de W
alls
P
arti
tion
Wal
ls
Con
stru
ctio
n T
ype
Shal
l mat
ch c
onst
ruct
ion
plan
s
Insu
lati
on
R-V
alue
s sh
all m
atch
con
stru
ctio
n pl
ans
Tot
al A
rea
Shal
l be
reas
onab
ly c
lose
too
: A
s de
sign
ed a
nd s
how
n on
co
nstr
ucti
on p
lans
Cei
ling
s
Con
stru
ctio
n T
ype
Shal
l m
atch
con
stru
ctio
n pl
ans
Insu
lati
on
R-V
alue
s sh
all m
atch
con
stru
ctio
n pl
ans
Rad
iant
Bar
rier
Sh
all m
atch
con
stru
ctio
n pl
ans
Roo
f co
lor
and
mat
eria
l ty
pe
Shal
l mat
ch c
onst
ruct
ion
plan
s
Tot
al A
rea
Shal
l be
reas
onab
ly c
lose
too
: A
s de
sign
ed a
nd s
how
n on
co
nstr
ucti
on p
lans
Floo
rs o
ver
unco
ndit
ione
d sp
aces
and
out
side
air
Con
stru
ctio
n T
ype
Shal
l mat
ch c
onst
ruct
ion
plan
s
Insu
lati
on
R-V
alue
s sh
all m
atch
con
stru
ctio
n pl
ans
Tot
al A
rea
Shal
l be
reas
onab
ly c
lose
too
: A
s de
sign
ed a
nd s
how
n on
co
nstr
ucti
on p
lans
Infi
ltra
tion
B
uild
ing
Env
elop
e T
ight
ness
Mos
t w
ill u
se t
he ‘
Ave
rage
Con
stru
ctio
n’ s
etti
ng.
Bui
lder
s w
ith
a hi
stor
y of
blo
wer
doo
r te
st r
esul
ts w
ill u
se ‘
Sem
i Tig
ht’
or ‘
Tig
ht’.
R
efer
to
Man
ual J
8th e
diti
on t
able
5A
for
a m
ore
deta
iled
ana
lysi
s.
M
AN
UA
L J
LO
AD
CA
LC
UL
AT
ION
K
EY
EL
EM
EN
TS
Abo
ve G
rade
Vol
ume
Shal
l be
reas
onab
ly c
lose
too
: A
s de
sign
ed a
nd s
how
n on
co
nstr
ucti
on p
lans
Inte
rnal
Gai
ns
App
lian
ces
1200
Btu
h is
the
def
ault
in m
ost
soft
war
e pr
ogra
ms
and
wor
ks f
or
dish
was
hers
and
ref
rige
rato
rs.
Tab
le 6
B in
Man
ual
J
8th e
diti
on,
prov
ides
load
s fo
r m
any
diff
eren
t ty
pes
of a
ppli
ance
s.
The
bui
lder
can
and
sho
uld
desi
gn f
or t
he a
ntic
ipat
ed a
ppli
ance
lo
ad.
Thi
s w
ould
incl
ude
any
hum
idif
iers
.
Occ
upan
ts
Num
ber
of o
ccup
ants
= N
umbe
r of
bed
room
s +
1 O
ccup
ants
can
be
plac
ed in
any
roo
m(s
) fo
r th
e ca
lcul
atio
n if
the
to
tal d
oes
not
exce
ed t
he a
bove
for
mul
a.
Duc
ts
Duc
t lo
cati
on
Duc
ts m
ust
be c
orre
ctly
loca
ted
eith
er in
side
or
outs
ide
the
buil
ding
s th
erm
al e
nvel
ope.
Duc
twor
k in
ven
ted
atti
cs c
an a
dd
sign
ific
ant
heat
ing
and
cool
ing
load
s. D
ucts
loca
ted
outs
ide
the
buil
ding
s th
erm
al e
nvel
ope
shal
l hav
e an
R-8
insu
lati
on
Duc
t ti
ghtn
ess
Mos
t so
ftw
are
prog
ram
s de
faul
t to
‘A
vera
ge S
eale
d’.
Wit
h th
e te
stin
g th
at is
req
uire
d in
Par
ker,
bui
lder
s co
uld
use
a hi
gher
ti
ghtn
ess
cate
gory
. R
efer
to
man
ual J
8th e
diti
on s
ecti
on 3
-12
for
a m
ore
deta
iled
ana
lysi
s.
Ven
tila
tion
Inte
rmit
tent
or
spot
ve
ntil
atio
n ex
haus
t fa
ns
Do
not
incl
ude
in c
alcu
lati
on
Ven
tila
tion
Str
ateg
y
Exh
aust
onl
y, s
uppl
y on
ly o
r a
bala
nced
sys
tem
are
all
acc
epta
ble
met
hods
.
Min
imum
cfm
for
mul
a:
(Num
ber
of b
edro
oms
+1
x 7.
5) +
(co
ndit
ione
d fl
oor
area
x .
01)
M
anu
al S
Ke
y E
lem
en
ts
Des
ign
Con
diti
ons
Was
the
cal
cula
ted
heat
ing
loss
and
gai
n tr
ansf
erre
d fr
om t
he M
anua
l J
corr
ectl
y?
The
re is
no
need
for
any
add
itio
nal ‘
safe
ty f
acto
rs’.
A c
orre
ctly
co
mpl
eted
Man
ual J
pro
vide
s ac
cura
te h
eat
loss
and
gai
ns.
Man
ufac
ture
rs
Per
form
ance
Dat
a
Hea
ting
: Fo
rced
Air
Fu
rnac
e
Out
put
capa
city
can
be
up t
o 14
0% o
f th
e ca
lcul
ated
hea
t lo
ss.
Cap
acit
y, e
ffic
ienc
y an
d al
titu
de d
erat
ion
are
from
the
per
form
ance
da
ta.
E
xam
ple
of O
utpu
t ca
paci
ty:
80
% 5
0,00
0 B
tuh
@ 5
000’
Abo
ve s
ea le
vel
.8 x
50,
000
= 4
0,00
0 B
tuh
De-
rate
2%
for
eac
h 10
00’
(fro
m M
anuf
actu
rers
dat
a) a
bove
sea
leve
l,
an a
ddit
iona
l 10%
der
atio
n fo
r al
titu
de
.9 x
40,
000
= 3
6,00
0 B
tuh
O
ver
140%
? T
his
coul
d be
nee
ded
for
a bi
gger
blo
wer
for
air
con
diti
on
perf
orm
ance
.
Air
Con
diti
onin
g:
Spli
t sy
stem
Tot
al o
utpu
t ca
paci
ty c
an b
e up
to
115%
of
the
calc
ulat
ed h
eat
gain
. C
apac
ity,
eff
icie
ncy
and
alti
tude
der
atio
n ar
e fr
om t
he p
erfo
rman
ce
data
.
Cap
acit
y w
ill
be b
ased
on
perf
orm
ance
at;
O
utdo
or d
ry b
ulb
90°
F (u
se 9
5° F
col
umn)
(D
enve
r)
Indo
or d
ry b
ulb
75°
F In
door
wet
bul
b 63
° F
O
ver
115%
? If
wit
hin
6000
BT
U w
ould
be
OK
or
the
next
siz
e sm
alle
r is
to
smal
l to
mee
t th
e lo
ad
Equ
ipm
ent
Per
form
ance
Hea
ting
: Fo
rced
Air
Fu
rnac
e
Tem
pera
ture
ris
e m
ust
be w
ithi
n m
anuf
actu
res
lim
its.
B
tuh/
cfm
/(1
.1xA
CF)
= T
empe
ratu
re R
ise
Btu
h= H
eati
ng O
utpu
t C
fm =
Air
flo
w in
cub
ic f
eet
per
min
ute
1.1
= F
orm
ula
cons
tant
at
sea
leve
l A
CF=
Alt
itud
e co
rrec
tion
fac
tor
from
Man
ual J
tab
le 1
0A
Air
Con
diti
onin
g:
Spli
t sy
stem
Whe
n ou
tput
cap
acit
y is
det
erm
ined
it w
ill b
e at
a d
efin
ed c
fm.
If
man
ufac
ture
s do
not
pro
vide
alt
itud
e de
rati
on in
form
atio
n, a
ppen
dix
6 M
anua
l S d
oes
have
tw
o m
etho
ds,
both
are
acc
epta
ble.
1.
A
djus
t ai
r fl
ow;
sinc
e ai
r at
alt
itud
e is
less
den
se,
you
need
to
mov
e m
ore
air
for
the
sam
e pe
rfor
man
ce a
t se
a le
vel.
C
FM a
t al
titu
de=
Se
a le
vel f
low
rat
e/D
ensi
ty r
atio
D
ensi
ty r
atio
for
500
0’ =
.83
2 80
0/0.
832
= 9
62 c
fm
2.
No
air
flow
adj
ustm
ent:
you
can
de-
rate
the
ent
ire
pack
age.
A
djus
tmen
t fo
r 50
00’=
T
otal
coo
ling
out
put
capa
city
x .
96
M
anu
al D
K
ey
Ele
me
nts
Man
ufac
ture
s D
ata
B
low
er p
erfo
rman
ce
at a
ran
ge o
f ex
tern
al
stat
ic p
ress
ures
The
blo
wer
sel
ecte
d m
ust
prov
ide
the
need
ed c
fm a
t th
e de
sign
sta
tic
pres
sure
. A
t th
is p
oint
the
des
igne
r ha
s a
good
idea
of
wha
t th
e he
at a
nd c
ooli
ng c
fm n
eed
to b
e fr
om t
he e
quip
men
t se
lect
ion
proc
ess.
Fric
tion
Rat
e
Ava
ilab
le S
tati
c P
ress
ure
(ASP
)
The
des
ign
stat
ic p
ress
ure
less
all
pre
ssur
e dr
ops
resu
lts
in t
he A
vaila
ble
Stat
ic
Pre
ssur
e fo
r th
e du
ctw
ork.
Pre
ssur
e dr
ops
for
all d
evis
es m
ust
be l
iste
d.
AC
Coi
ls,
filt
ers,
sup
ply
and
retu
rn o
utle
ts,
bala
ncin
g da
mpe
rs,
hum
idif
iers
, ai
r cl
eane
rs,
etc.
A
pre
ssur
e dr
op o
f 0.
03 c
an b
e us
ed f
or b
alan
cing
dam
pers
, su
pply
and
ret
urn
gril
les,
all
oth
er d
evic
es m
ust
have
man
ufac
ture
s da
ta s
peci
fyin
g th
e pr
essu
re
drop
.
Tot
al E
ffec
tive
Len
gth
(TE
L)
Thi
s is
the
long
est
supp
ly p
lus
the
long
est
retu
rn p
ath.
Thi
s in
clud
es a
ll f
itti
ngs,
re
duce
rs,
etc.
Des
ign
Fric
tion
Rat
e
Fric
tion
rat
e fo
rmul
a:
ASP
x 1
00/
TE
L
The
des
ign
fric
tion
rat
e m
ust
be b
etw
een
0.06
& 0
.18,
fri
ctio
n ra
tes
abov
e or
be
low
eff
ect
blow
er p
erfo
rman
ce.
Air
Dis
trib
utio
n Sy
stem
Des
ign
Air
vel
ocit
y fo
r su
pply
an
d re
turn
duc
twor
k
Obj
ecti
onab
le n
oise
can
be
the
resu
lt if
sys
tem
vel
ocit
y is
igno
red.
Ref
er t
o M
anua
l D s
ecti
on 1
-12
and
tabl
e A
1-1
for
a m
ore
deta
iled
ana
lysi
s.
All
duc
twor
k de
sign
ed b
ased
on
requ
ired
cfm
and
fr
icti
on r
ate
Pla
ns m
ust
indi
cate
all
duc
t lo
cati
ons,
siz
es,
trun
k re
duct
ions
, m
ater
ial a
nd f
itti
ng
type
s. P
ictu
res
of t
he a
ctua
l fit
ting
s ar
e re
quir
ed.
A d
esig
ner
may
use
tur
ning
va
nes
in t
he d
esig
n, b
ut t
he in
stal
ler
(or
buil
ding
insp
ecto
r) d
id n
ot k
now
tha
t a
5K f
itti
ng h
as t
urni
ng v
anes
.
Ret
urn
air
path
A d
ucte
d re
turn
is n
ot r
equi
red
for
each
roo
m,
but
a re
turn
air
pat
h is
req
uire
d.
Tra
nsfe
r gr
ille
s or
jum
per
duct
s w
ork,
und
ercu
ttin
g of
doo
rs w
ill
not
be
allo
wed
.
M
anu
al D
K
ey
Ele
me
nts
Duc
t ti
ghtn
ess
and
syst
em
test
ing
Tes
ting
Rou
gh-i
n te
st:
Tot
al
leak
age
shal
l be
m
easu
red
wit
h a
pres
sure
di
ffer
enti
al o
f 0.
1 in
ch w
.g.
(25
Pa)
acr
oss
the
syst
em,
incl
udin
g th
e m
anuf
actu
rer'
s ai
r ha
ndle
r en
clos
ure
if i
nsta
lled
at
the
tim
e of
the
tes
t.
All
reg
iste
rs s
hall
be
tape
d or
oth
erw
ise
seal
ed d
urin
g th
e te
st.
2. P
ost
cons
truc
tion
tes
t: T
otal
lea
kage
sha
ll b
e m
easu
red
wit
h a
pres
sure
di
ffer
enti
al o
f 0.
1 in
ch w
.g.
(25
Pa)
acr
oss
the
enti
re s
yste
m,
incl
udin
g th
e m
anuf
actu
rer'
s ai
r ha
ndle
r en
clos
ure.
Reg
iste
rs s
hall
be
tape
d or
ot
herw
ise
seal
ed d
urin
g th
e te
st.
Exc
epti
on:
1.
Duc
t ti
ghtn
ess
test
is
not
requ
ired
if
the
air
hand
ler
and
all
duct
s ar
e lo
cate
d w
ithi
n co
ndit
ione
d sp
ace.
2.
A d
uct
air-
leak
age
test
sha
ll n
ot b
e re
quir
ed f
or d
ucts
ser
ving
he
at o
r en
ergy
rec
over
y ve
ntil
ator
s th
at a
re n
ot i
nteg
rate
d w
ith
duct
s se
rvin
g he
atin
g or
coo
ling
sys
tem
s
At
roug
h pr
ior
to
inst
alla
tion
of
gyps
um
boar
d
(If
requ
ired
by
code
or
juri
sdic
tion
)
Duc
t le
akag
e R
ough
-in
test
: T
he t
otal
lea
kage
sha
ll b
e le
ss t
han
or e
qual
to
4 c
ubic
fee
t pe
r m
inut
e pe
r 10
0 sq
uare
fee
t of
con
diti
oned
flo
or a
rea
whe
re t
he a
ir h
andl
er i
s in
stal
led
at t
he t
ime
of t
he t
est.
Whe
re t
he a
ir
hand
ler
is n
ot i
nsta
lled
at
the
tim
e of
the
tes
t, t
he t
otal
lea
kage
sha
ll b
e le
ss t
han
or e
qual
to
3 cu
bic
feet
per
min
ute
per
100
squa
re f
eet
of
cond
itio
ned
floo
r ar
ea.
Stat
ic p
ress
ures
sho
uld
not
be m
ore
than
the
Man
ual D
des
ign
Tot
al s
yste
m f
low
inc
ludi
ng r
oom
to
room
flo
ws
wit
h th
e bl
ower
set
at
the
high
est
desi
gn s
peed
At
fina
l pr
ior
to
Cer
tifi
cate
of
Occ
upan
cy
(If
requ
ired
by
code
or
juri
sdic
tion
)
Tot
al l
eaka
ge s
hall
be
less
tha
n or
equ
al t
o 4
cubi
c fe
et p
er m
inut
e pe
r 10
0 sq
uare
fee
t of
con
diti
oned
flo
or a
rea.
Stat
ic p
ress
ure
at f
inal
Tot
al f
low
and
roo
m t
o ro
om f
low
s w
ith
blow
er s
et a
t th
e hi
ghes
t de
sign
sp
eed
Roo
m t
o ro
om p
ress
ure
shou
ld n
ot b
e m
ore
than
± 3
pas
cals
Wea
ther
pe
rmit
ting
: H
eat
exch
ange
r te
mpe
ratu
re
rise
, su
perh
eat
or
subc
ooli
ng f
or t
he A
ir C
ondi
tion
er
©Colorado Code Consulting, LLC 2020 69
2018 IRC Plan Review
RESIDENTIAL PLAN REVIEW
Any items you wanted to learn today and we did not cover?????
© 2020 Colorado Code Consulting, LLC 273
COLORADO CODE CONSULTING, LLC
4610 S Ulster, Suite 150Denver, CO 80237Ph. 303-400-6564Fax [email protected]
© 2020 Colorado Code Consulting, LLC 274