Pioneer Electric Cooperative, Inc. 1850 W. Oklahoma Avenue, Ulysses, KS 67880 Phone (620) 356‐1462 Fax (620) 356‐1669 Page 1 of 37 Request for Proposal (RFP) Permanent Work – Power Restoration Services RFP No. 2019001 I. Background Pioneer Electric Cooperative, Inc. (“PEC”) is seeking proposals to establish a contract with a qualified and experienced firm, herein after referred to as “Contractor,” to provide Reconductoring services and Hazard Mitigation (“Services”) to PEC relating to April 2017 Severe Winter Storm, Snowstorm, Straight‐Line Winds, and Flooding, DR‐4319. Contractor will work under the direction of PEC. Services will be based on the requirements below and the general terms and conditions set forth in a Master Services Agreement (“Agreement”) in the form substantially similar to the one found in Exhibit A to this RFP. II. General Requirements A. Services may include, but are not be limited to, damage assessment, facility restoration and assistance with federal and state reporting. B. Services shall include Contractor’s provision of all labor, supervision, transportation, tools, equipment, communications, provisions, and other services and supplies necessary for, or incidental to, the performance of such Services pursuant to the Agreement. C. Any and all Services provided by Contractor must comply fully with all applicable federal, state and local laws, regulations and guidelines, as described in the Agreement. D. Return bid sheets, bid bond and your company information no later than 10:00 am CST December 2, 2019. Unit prices must be submitted for every unit listed in the excel spread sheet. Bids will be accepted via email or hard copy. Emails submittals should be sent to storm/[email protected] Hard copies shall be sent to; Pioneer Electric Cooperative ATTN. Storm restoration 1850 west Oklahoma Ave. Ulysses, KS 67880. E. Contractor's Designated Representative shall be physically present at PEC’s Headquarters within 10 days after notification of award by PEC. Commencement of work shall begin on or before January 2, 2020 and shall be completed by December 31, 2021. F. Any Agreement(s) issued pursuant to this RFP will be based on unit prices. G. PEC reserves the right to enter into multiple Agreements as a result of this RFP. It will be PEC’s intent to select one contractor from this RFP. A minimum monthly goal should be total project in miles divided by twenty‐four (24) months. Should Contractor not meet monthly minimum construction goals for two consecutive months, PEC reserves the right to enter into multiple agreements. Additional agreement may be at different unit costs.

Transcript of Request for Proposal (RFP) Work Power Restoration Services...

Page 1: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

Page 1 of 37  

RequestforProposal(RFP)PermanentWork–PowerRestorationServices

RFPNo.2019‐001

I. BackgroundPioneer Electric Cooperative, Inc. (“PEC”) is seeking proposals to establish a contract with a qualified and 

experienced firm, herein after referred to as “Contractor,” to provide Reconductoring services and Hazard 

Mitigation (“Services”) to PEC relating to April 2017 Severe Winter Storm, Snowstorm, Straight‐Line Winds, 

and Flooding, DR‐4319.   Contractor will work under the direction of PEC.   Services will be based on the 

requirements  below  and  the  general  terms  and  conditions  set  forth  in  a  Master  Services  Agreement 

(“Agreement”) in the form substantially similar to the one found in Exhibit A to this RFP. 

II. GeneralRequirementsA. Services  may  include,  but  are  not  be  limited  to,  damage  assessment,  facility  restoration  and 

assistance with federal and state reporting. 

B. Services  shall  include  Contractor’s  provision  of  all  labor,  supervision,  transportation,  tools, 

equipment,  communications,  provisions,  and  other  services  and  supplies  necessary  for,  or 

incidental to, the performance of such Services pursuant to the Agreement. 

C. Any and all Services provided by Contractor must comply fully with all applicable federal, state and 

local laws, regulations and guidelines, as described in the Agreement. 

D. Return bid sheets, bid bond and your company information no later than 10:00 am CST December 

2, 2019. Unit prices must be submitted for every unit listed in the excel spread sheet. Bids will be 

accepted  via  email  or  hard  copy.    Emails  submittals  should  be  sent  to 

storm/[email protected]      Hard  copies  shall  be  sent  to;  Pioneer  Electric 

Cooperative ATTN.  Storm restoration 1850 west Oklahoma Ave.  Ulysses, KS 67880.   

E. Contractor's Designated Representative shall be physically present at PEC’s Headquarters within 

10 days after notification of award by PEC.  Commencement of work shall begin on or before 

January 2, 2020 and shall be completed by December 31, 2021. 

F. Any Agreement(s) issued pursuant to this RFP will be based on unit prices. 

G. PEC reserves the right to enter into multiple Agreements as a result of this RFP. It will be PEC’s 

intent to select one contractor from this RFP. A minimum monthly goal should be total project in 

miles divided by twenty‐four (24) months. Should Contractor not meet monthly minimum 

construction goals for two consecutive months, PEC reserves the right to enter into multiple 

agreements. Additional agreement may be at different unit costs.  

Page 2: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 2 of 37  

III. FederalComplianceRegulationsPEC hereby notifies all proposers that the work covered by this RFP and any resulting Agreement may be 

funded  via  Federal  grant,  including,  but  not  limited  to,  those  issued  through  the  Federal  Emergency 

Management  Agency’s  (“FEMA”)  Public  Assistance  Program  following  federally  declared  disaster  or 

emergency events.  As such, prospective contractors will be required to comply with all applicable Federal, 

laws,  regulations, executive orders, and FEMA or other Federal agency requirements  for  the  type work 

being performed.  All proposers should carefully review the Agreement found in Exhibit A to this RFP for 

more information on the required minimum clauses as these are non‐negotiable. 

IV. ScopeofWork‐WorktobeCompletedReconductoringandHazardMitigationProject

 

A.  The Services of  the project  include a  total of approximately 230 miles  that  shall  include  facility 

restoration activities including, but not limited to, the following types of tasks: 

Approximately 159 miles of single phase overhead power line reconductor/respan that will include 

retiring of existing #4 ACSR as well as poles and hardware. These projects will be rebuilt with new 

poles and #2 T2 ACSR conductor 

Approximately 14 miles of single phase overhead power line reconductor that will include replacing 

existing #1/0 ACSR conductor with #2 T2 ACSR conductor 

Approximately 19 miles of three phase overhead power line reconductor/respan that will include 

retiring of existing #4 ACSR as well as poles and hardware. These projects will be rebuilt with new 

poles and #2 T2 ACSR conductor 

Approximately 39 miles of three phase overhead power line reconductor that will include replacing 

existing #1/0 ACSR conductor with #2 T2 ACSR 

Poles that were set during the initial emergency restoration will be re‐used and will require Osmose 

butt wrap to be installed before they are reset. Any pole with newer than 2016 pole brand or if 

noted on staking sheet as “Return To Stock” (RTS) will be salvaged, including all associated material, 

and need to be re‐used within the project that it was retired from or returned to PEC’s warehouse. 

All salvaged materials shall be returned and checked into PEC’s warehouse. Quantities shown are 

approximate. Total miles and projects could be reduced or increased with no change to unit cost 

bids. 

Hazard mitigation projects  on  the  above projects  to  include  installing double  deadened,  storm 

guyed poles at a rate of 1 per mile as noted on staking sheets, each pole on single phase to have 2 

Page 3: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 3 of 37  

down guy wire and anchors. On two and three phase lines, each pole to have 4 down guy wires and 

anchors.  

Some projects may be completed as improved projects utilizing different conductor sizes, pole sizes 

and span lengths. 

Additional repair work for lines that are only being re‐conductored will include but not be limited 

to; plumping and re‐tamping poles,  tightening hardware,  replacing damaged hardware,  fix pole 

grounds, tighten guy wire.  Line sections that did not qualify for reconductor will also require repair 

work as listed above and the repair and resagging of conductor.  

The projects above will be divided into projects ranging in size from .05 miles to 6 miles. 

V. DocumentationManagement&SupportContractor shall provide data management and support to PEC during the recovery effort including but not 

limited to the following: 

A. If required, Contractor shall supply certification placards meeting FEMA requirements and place 

such placards on its vehicles. 

B. Contractor shall have a system for clearly tracking and documenting all costs associated with work 

conducted pursuant to this RFP and resulting Agreement, identifying expenditures and maintaining 

documentation of the recovery process. 

Contractor must maintain all records pertaining to work performed pursuant to this RFP consistent with 

the requirements set forth in the Agreement. 

VI. Staff&EquipmentRequirementsContractor shall ensure that its work force, including subcontractors, maintains self‐sufficiency related to 

fuel, vehicle repair/maintenance, housing, sanitation, food and related accommodations in a manner that 

is consistent with local requirements and minimizing adverse effects on the community. 

VII. ReportingContractor shall submit weekly written reports to PEC documenting the progress of project.  These reports 

shall include, but are not limited to, the following: 

A. Progress  Reports  –  Contractor  shall  provide  reports  to  PEC  to  detail  the  progress  of  power 

restoration operations.  Such reports shall include: 

1. Contractor’s Name; 

Page 4: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 4 of 37  

2. Report Date; 

3. Location of Completed Work to include work order number; 

4. A  description  of  areas  where  work  was  done,  and  a  general  overview  of  the  work 

completed  (including  a  breakdown  of  value  by  unit  or  time/materials/equipment,  as 

applicable); 

5. The number of trucks, other equipment and personnel utilized that day; and 

6. Other operational and complaint tracking information as requested by PEC. 

The format of the reports shall be provided by PEC. 

VIII. OtherOperationalConsiderationsA. Contractor may work seven (7) days per week including holidays and shall work through to 

project completion.  No outages shall be allowed on Sunday or Holidays. 

B. It will be understood that it is necessary for all work to be performed energized to keep outages 

to a minimum for the least amount of impact to PEC’s customers. Any outages must have a two‐

day notice given to PEC. All outages must be PEC approved. PEC reserves the right to deny 

allowance of all outages. 

C. Lesser Prairie habitat exist in the PEC service territory.  Contractor will need to be familiar with 

the Western Association of Fish & Wildlife Agencies (WAFWA) Lesser Prairie Chicken Range Wide 

Conservation Plan and must follow all guidelines and operational requirements. 

D. All new poles will be required to have PEC provided pole number tags installed.  Pole tags are part 

of the pole unit, no additional charge will be allowed. 

E. Prospective Contractor should visit and be familiarized with the project site prior to submitting 

bids. 

F. All materials for construction provided under the Agreement shall be furnished by PEC. 

G. Contractor must follow American Public Power Association Safety Manual. 

H. PEC is not the safety officer for the contractor. 

I. Contractor must be able to be familiarized with PEC’s construction standards. 

J. Each contract crew will only be able to have material for one job at a time. Material Vendor 

Warehouse will only be open Monday through Friday. 

K. Contractor will be responsible to note, on the staking to be turned in at the completion of each 

job, the correct pole tag number for each pole installed. 

L. Contractor will be monitored daily by an Inspector that will not have any affiliation to Contractor. 

Each project will also be inspected when each project is completed.   

M. Contractor must be familiar or be able to be familiarized with RUS construction units and 

standards. 

Page 5: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 5 of 37  

N. Contractor Superintendent and foreman will be required to meet with PEC project managers and 

coordinators at PEC offices in Ulysses, KS, within ten (10) days of acceptance of the contract.  

Contractor shall be prepared to discuss manpower, planning and scheduling for the completion of 

the contract at this meeting.  

O. Clean up of restoration site as directed by PEC; removal of damaged facilities (broken poles, 

damaged conductors, damaged hardware etc.).  Contractor should immediately report 

transformer oil spills or other environmental concerns to PEC.  

P. Contractor shall be responsible for having all foreign facilities such as rural water lines, 

underground telephone, fiber optic cables, cable TV, gas pipelines, underground electrical and 

any other facilities that may be within the area or construction located prior to doing any work. 

Contractor shall be required to contact “Kansas‐One Call: to arrange for the locating of foreign 

utilities a minimum of 48 hours in advance of the start of construction. Contact “Kansas‐One Call” 

at 800/344‐7233 or DIAL 811. Attention: Not all utilities are member of “Kansas‐One Call”.  The 

contractor shall be responsible for all costs charged by others for location of and repair of the 

foreign facilities. 

Q. Contractor is required to salvage existing transformers, reclosers, capacitors, meters, all line 

conductor, and other equipment units (both PEC owned and customer‐owned), from the area as 

noted on sheet, and bring back to warehouse and sorted as directed by PEC. 

R. When working on the traveled portion or shoulder of any public road, the Contractor shall 

conform to all State or County Requirements. The Contractor shall post warning signs in all 

directions of traffic flow, and at no time is traffic to be blocked for more than 10 minutes, during 

which time the Contractor shall furnish an employee to direct traffic. Contractor employees shall 

wear high visibility shirts or vests when working. 

S. A copy of Commercial General Liability Insurance Policy shall be submitted with Bid Proposal.  

T. Contractor will be required to submit a copy of Commercial General Liability Insurance with PEC 

as additional insured before work begins.  

U. Vendor will be required to have or obtain: liability insurance covering operations of not less than 

$5 million each occurrence, property damage not less than 5 million each occurrence, and $5 

million aggregate for accidents, liability auto insurance covering $5 million per person, $5 million 

each occurrence, and $5 million property damage each occurrence 

V. In some cases, the landowner may request the retired poles. The Contractor must coordinate with 

landowner  for  retired  pole  disposal.  It  is  required  that  the  Contractor  furnish  PEC with  a  pole 

release form signed by the  landowner(s). Release forms will be supplied by the PEC. No retired 

poles requested by the landowner shall be left along the distribution line for pickup. All other poles 

will be disposed of at a PEC approved landfill, with accompanying receipts and documentation. 

W. Invoices  for  completed  jobs  which  has  passed  inspection  will  be  processed  within  20  days  of 

receipt, unless additional time is needed to obtain all necessary information required. 

X. Time is of the essence for the completion of the work described in this contract. It is anticipated 

by the parties that all work described herein will be completed before December 31, 2021, and 

Page 6: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 6 of 37  

that any delay in the completion of the work described herein shall constitute a material breach 

of this contract. 

IX. BondingIf  at  any  time  Services  being  performed  are  deemed  to  include  construction  or  facility  improvement 

projects or subcontracts exceeding the Simplified Acquisition Threshold as defined by 48 C.F.R. Subpart 2.1 

(currently defined as $150,000), or if for any other reason PEC determines it necessary, PEC reserves the 

right to require the following: 

A. A bid guarantee from each Bidder equivalent to five percent (5%) of the bid price.  The “bid 

guarantee” must consist of a firm commitment, such as a bid bond, certified check, or other 

negotiable  instrument  accompanying  the  bid  as  assurance  that  the  bidder  will,  upon 

acceptance of the bid, execute such contractual documents as may be required within the time 

specified. 

B. A performance bond on the part of  the Contractor  for one hundred percent  (100%) of  the 

contract price.  A “performance bond” is one executed in connection with a contract to secure 

the fulfillment of all the contractor’s obligations under such contract. 

C. A payment bond on the part of the Contractor for one hundred percent (100%) of the contract 

price.  A “payment bond” is one executed in connection with a contract to assure payment as 

required  by  law  of  all  persons  supplying  labor  and  material  in  the  execution  of  the  work 

provided for in the contract. 

X. PreparationofProposals

A. QualificationsProposals must consist of the following information in the order indicated below: 

i. Cover  letter  stating  the  proposer’s  interest  in  the  project  with  signature  of  authorized 

representative. 

ii. Evidence of any and all relevant licenses and bonding. 

iii. List of at least three professional references from which PEC may determine Contractor’s record 

of past performance. 

iv. Disclosure of any actual or alleged safety violations in the last five (5) years to include DART Rate 

and OSHA 300 Log. 

Page 7: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 7 of 37  

v. Description of Contractor’s technical resources, including explanation of overall project approach 

and a listing of equipment and employees. 

vi. Description  of  Contractor’s  financial  stability,  including  an  audited  financial  statement  and 

disclosure of pending claims and litigation. 

vii. History of Contractor’s debarment or suspension from Federal contracting, including certification 

that Contractor is not currently debarred or suspended. 

viii. A copy of Commercial General Liability Insurance Policy shall be submitted with Bid Proposal.  

ix. Status as a small or minority‐owned business, women’s business enterprise, or labor surplus area 

firm. 

x. Use  of  equipment  or  provision  of  services  that  conserve  natural  resources  and  protect  the 

environment and are energy efficient. 

 

xi. Operational plan to include the use of sub‐contractors. All sub‐contractors must be PEC approved 

prior to sub‐contractor start of work. 

B. PriceProposalContractor  shall  complete  the  Price  Proposal  Form  (bid  sheet)  provided with  this  RFP  and  include  any 

additional information to provide a complete, all‐inclusive price proposal for all services to be provided as 

outlined in this RFP, including supplying all equipment, tools and labor necessary to perform the Services.  

The  documentation  and  recovery  process,  including  plan  development,  mobilization,  demobilization, 

record keeping and quality control, shall be included in the prices. 

Contractor will be given detailed work orders locating the damaged facilities. A map is provided showing 

the areas that the damages have occurred. 

Cost‐plus‐a‐percentage‐of‐cost pricing is not permitted and any bid sheets containing such pricing will be 

rejected. 

PEC is requesting pricing based on “typical” crews and Contractor should therefore include information in 

its response to this RFP regarding the composition of what it considers to be a typical power restoration 

crew, including anticipated equipment to be used by such crew. 

XI. AcceptanceorRejectionofProposalsProposals  will  be  accepted  from  contractors  whose  proposals  are  responsive  to  the  RFP  and  most 

advantageous  to  PEC,  price,  quality,  and  other  factors  considered.    PEC  reserves  the  right,  at  its  sole 

discretion,  to reject any and all proposals or  to cancel  this RFP entirely  if determined to be  in  the best 

Page 8: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 8 of 37  

interest of PEC.  PEC reserves the right, at its sole discretion, to waive any technicality in proposals provided 

such action is in the best interest of PEC. 

All proposals will be subject to a review and evaluation process.  All proposers responding to this RFP, who meet the requirements, shall be ranked in accordance with the criteria established in these documents.  PEC will  consider  all  responsive  and  responsible  proposals  received  in  its  evaluation  process.    PEC will consider the following evaluation criteria, in order of importance:  

o Contractor is appropriately licensed and bonded. 

o Contractor has an acceptable record of past performance. 

o Contractor has adequate financial and technical resources including consideration of: 

The ability, capability and skill of the proposer to perform the contract; 

The quality, availability and adaptability of the supplies or contractual services to the 

particular use required; 

The ability of the proposer to provide future service for the use of the subject of the 

contract; and 

Whether  the proposer can perform  the contract within  the  time specified, without 

delay or interference. 

o Price proposal. o Contractor has a satisfactory record of integrity and business ethics. 

o Contractor  is  not  currently  and  has  not  been  previously  suspended  or  debarred  from 

Federal  contracting;  or,  has  an  acceptable  explanation  for  any  previous  suspension  or 

debarment. 

o Contractor is adequately insured. 

o Contractor has met applicable bonding requirements. 

o Whether Contractor is a small or minority‐owned business, a women’s business enterprise, 

or a labor surplus area firm. 

o Use  of  equipment  and  services  that  conserve  natural  resources  and  protect  the environment and are energy efficient are preferred. 

o Responsiveness of the proposal. 

o The previous and existing compliance by the proposer with laws and ordinances relating 

to the contract. 

o The number and scope of conditions attached to the bid or proposal. o Responsiveness of client references. 

XII. Small&MinorityBusinesses,Women’sBusinessEnterprises,andLaborSurplusAreaFirms

All Contractors must work to ensure  fairness  in bidding and sub‐contracting procedures with small and 

minority businesses, women's business enterprises, and labor surplus area firms.  PEC will potentially use 

Page 9: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 9 of 37  

federal  funding  for  some  or  all  of  the  work  covered  by  this  RFP;  therefore,  if  Contractor  intends  to 

subcontract any portion of the Services covered by this RFP and the resulting Agreement, Contractor must 

take  all  necessary  affirmative  steps  to  assure  that  small  and  minority  businesses,  women’s  business 

enterprises,  and  labor  surplus area  firms are solicited and used when possible.   Affirmative steps must 

include: 

i. placing qualified small and minority businesses and women’s business enterprises on 

solicitation lists; 

ii. assuring  that  small  and minority businesses,  and women’s business enterprises are 

solicited whenever they are potential sources; 

iii. dividing  total  requirements,  when  economically  feasible,  into  smaller  tasks  or 

quantities  to  permit maximum participation  by  small  and minority  businesses,  and 

women’s business enterprises; 

iv. establishing  delivery  schedules,  where  the  requirement  permits,  which  encourage 

participation by small and minority businesses, and women’s business enterprises; and 

v. using the services and assistance, as appropriate, of such organizations as the Small 

Business  Administration  and  the  Minority  Business  Development  Agency  of  the 

Department of Commerce. 

XIII. TermThe  term  of  this  Agreement  shall  begin  on  the  Effective  Date  of  this  Agreement  and  shall  expire  and 

terminate 2 years after such date or when the Services are complete and final payment has been made and 

accepted. 

XIV. MiscellaneousA. Any contractor that participated in developing or drafting this RFP is excluded from competing for 

any contract under this RFP. 

B. By submitting a response to the RFP, the proposer certifies that its Proposal has not been arrived at collusively or otherwise in violation of federal, state, or local laws. Any contract or Agreement from which any agent, officer, or employee of PEC or any relative thereof, will realize a financial gain, directly or  indirectly, shall be subject to termination by PEC consistent with  its policies for review of such matters. 

C. Small and minority‐owned businesses, women’s business enterprises, and labor surplus area firms 

are encouraged to respond to this RFP. 

D. The  contents  of  this  RFP  are  incorporated  into  the  Agreement.    Where  a  conflict  exists,  the 

Agreement prevails. 

E. Contractor shall supervise and direct the work, using skillful  labor and proper equipment for all tasks.  Safety of Contractor’s personnel and equipment is the responsibility of Contractor. 

Page 10: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 10 of 37  

F. Contractor shall pay for all materials, personnel, taxes, and fees necessary to perform under the terms of the Agreement. 

G. Contractor must be duly licensed in accordance with the state and local statutory requirements to perform  the  work.    Contractor  shall  obtain  all  permits  necessary  to  complete  the  Services requested by this RFP and as covered by the resulting Agreement.  Contractor shall be responsible for determining what permits are necessary.  Copies of all permits shall be submitted to PEC for inspection. 

H. Contractor shall be responsible for removing all equipment from any public or private property.  Contractor is not permitted to store equipment or trucks on any public or private property without express permission of the owner.  

I. Contractor will ensure all necessary materials for job are provided by material vendor as noted on material list. Any additional material needed, other than for material changes that are agreed upon by PEC and Field Designer, must be purchased from Vendor at Contractor’s expense.   

 

   

Page 11: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 11 of 37  

Price Proposal 

Work Order 20175097

Assembly Unit  Assembly Unit Description 

Transaction Type  Quantity 

Unit Cost 

Extended Cost

A 5-2 1 PH TAP OFF C1, B1 Construction 1 C 1- 2-10 3PH 10' XARM CONST. Construction 3

C 1- 2RP 3PH 8' XARM CONST RAPTOR PROOF Construction 20

C 7A-HD8 8' D.E. H.D. HUGHES BRO CONST Construction 2 C 7X 3PH XARM EXISTING Construction 1 C 7XFG 3PH FG-XARM EXISTING Construction 1 D40-3 DIST. 40 FT. CLASS 3 POLE Construction 5 D40-4 DIST. 40 FT. CLASS 4 POLE Construction 20 E 2-3 SNGL.O.H.GUY THRU.BOLT TYPE Construction 1

E 9-3 SINGLE DOWN GUY W/4WAY POLE BD Construction 4

E 9-3M SINGLE DOWN GUY W/POLE BAND CONN LINK Construction 2

F1-5TF PISA ANCHOR TWIN FLITE Construction 4 F1-5TRF TRIPLE HELIX 10-12-14 ANCHOR Construction 2

G311CX 3PH TRANS. BANK 240/480 EXISTING CLSTR Construction 2

HC1-2-A1M C1-2 MINUS A1 W/10'XARM Construction 1 M 2-11#4 DRIVEN GROUND W/#4 WIRE Construction 5

M 2-12#4 GROUND W/BUTT PLATE W/#4 WIRE Construction 20

M 5- 1 HOTLINE CLAMP Construction 3 M 5- 2 POLE TOP PIN W/INSULATOR Construction 2

M 5- 9STR CUTOUT S&C W/STIRRUP LINE FUSE Construction 1

M 8- 6-17 480 100A 3PH METER LOOP FM12 Construction 2 PRI10T2 1/0 T2 CONDUCTOR Construction 21,416

Install Total

Page 12: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 12 of 37  

A 5-2 1 PH TAP OFF C1, B1 Retirement 1

C 1 3PH 8'XARM CONST PRIM SUPPORT Retirement 8

C 1-10 C1-3PH 10' XARM Retirement 3 D35-3 DIST. 35 FT. CLASS 3 POLE Retirement 2 D35-4 DIST. 35 FT. CLASS 4 POLE Retirement 15 D40-3 DIST. 40 FT. CLASS 3 POLE Retirement 1 E 2-2 SNGL.O.H. GUY THRU.BOLT TYPE Retirement 1

G311CX 3PH TRANS. BANK 240/480 EXISTING CLSTR Retirement 2

HC1-A1M C1 MINUS A1 W\10 FT ARM Retirement 8 M 2-11 DRIVEN GROUND Retirement 3 M 2-12 GROUND W/BUTT PLATE Retirement 9 M 5- 1 HOTLINE CLAMP Retirement 1

M 5- 6-3PH 3 PHASE ARRESTER BRACKET ASSEMBLY Retirement 1

M 5- 9 CUTOUT S&C X-ARM MOUNT LINE FUSE Retirement 1

M 8- 6-15 480 100A 3PH METER LOOP FM12 Retirement 2 PRI1061 1/0 6/1 ACSR Retirement 21,384

Retire Total

 

 

 

 

 

 

 

 

 

 

 

 

Page 13: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 13 of 37  

 

Work Order 20175140

Assembly Unit 

Assembly Unit Description 

Transaction Type  Quantity

Unit Cost 

Extended Cost

C 7X 3PH XARM EXISTING Construction 2 M 5- 1 HOTLINE CLAMP Construction 3 PRI02T2 #2 T2 CONDUCTOR Construction 19,976

Install Total

C 7X 3PH XARM EXISTING Retirement 2 M 5- 1 HOTLINE CLAMP Retirement 3 PRI0271 #2 7/1 ACSR Retirement 4,994 PRI1061 1/0 6/1 ACSR Retirement 14,982

Retire Total

 

 

   

Page 14: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 14 of 37  

Work Order 20175351

Assembly Unit  Assembly Unit Description Transaction Type  Quantity 

Unit Cost 

Extended Cost

A 1 1 PH. SINGLE PRIMARY SUPPORT Construction 42

A 5 1 PH DEADEND Construction 1 A 5-1 1 PH PRIMARY PHASE TAP Construction 1 D35-3 DIST. 35 FT. CLASS 3 POLE Construction 2 D35-4 DIST. 35 FT. CLASS 4 POLE Construction 41

E 1-3 SNGL. DOWN GUY THRU.BOLT TYPE Construction 3

F1-3S 15000# SCREW ANCHOR Construction 3

G 10 1PH TRANS ON D E ASSY.& CUTOUT Construction 1

M 2-11 DRIVEN GROUND Construction 8 M 2-12 GROUND W/BUTT PLATE Construction 35 M 5- 1 HOTLINE CLAMP Construction 1

M 5- 6 LIGHTNING ARRESTER W/GRND Construction 2

M 8-10-200A-15 120/240 200A 1PH D0WN LOOP FM2 Construction 1

M52-3 POLE IDENT. LETTERS & NUMBERS Construction 1

PRI02T2 #2 T2 CONDUCTOR Construction 20,834

Install Total

Page 15: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 15 of 37  

A 1 1 PH. SINGLE PRIMARY SUPPORT Retirement 11

A 5 1 PH DEADEND Retirement 1 A 5-1 1 PH PRIMARY PHASE TAP Retirement 1 D30-4X 30' USED POLE Retirement 5 D35-3 DIST. 35 FT. CLASS 3 POLE Retirement 2 D35-4 DIST. 35 FT. CLASS 4 POLE Retirement 24 D35-4X 35 FT USED POLE Retirement 2

E 1-2 SNGL. DOWN GUY THRU.BOLT TYPE Retirement 1

E 1-3 SNGL. DOWN GUY THRU.BOLT TYPE Retirement 2

F1-2 12000# ANCHOR Retirement 1 F1-3S 15000# SCREW ANCHOR Retirement 2

G 10 1PH TRANS ON D E ASSY.& CUTOUT Retirement 1

M 2-11 DRIVEN GROUND Retirement 2 M 2-12 GROUND W/BUTT PLATE Retirement 11 M 5- 1 HOTLINE CLAMP Retirement 2

M 5- 6 LIGHTNING ARRESTER W/GRND Retirement 1

M 8-10-200A-15 120/240 200A 1PH D0WN LOOP FM2 Retirement 1

PRI0471 4 7/1 ACSR Retirement 20,814

Retire Total

 

 

               

Page 16: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 16 of 37  

Work Order 20175435

Assembly Unit Assembly Unit Description Transaction Type Quantity

Unit Price

Extended Cost

A 5-2 1 PH TAP OFF C1, B1 Construction 1 C 1-10 C1-3PH 10' XARM Construction 7 C 1RP 3PH 8' XARM RAPTOR PROOF Construction 8 C 7A-FG-8 8' D.E. H.D.FIBERGLASS ARM Construction 1 C 7X 3PH XARM EXISTING Construction 1 C 7XFG 3PH FG-XARM EXISTING Construction 1 D40-3 DIST. 40 FT. CLASS 3 POLE Construction 4 D40-4 DIST. 40 FT. CLASS 4 POLE Construction 13

E 1-3 SNGL. DOWN GUY THRU.BOLT TYPE Construction 4

E 1-3M SINGLE DOWN GUY W/FLANGE CONNECTOR LINK Construction 1

F1-3S 15000# SCREW ANCHOR Construction 3

G 9 1PH TRANS. ON A1(REQ. CUTOUT) Construction 1

K15C SWINGING K-11 OFF UPSET Construction 1 M 2-11 DRIVEN GROUND Construction 3 M 2-12 GROUND W/BUTT PLATE Construction 14 M 3-25AN/10XARM

3PH OCR'S (U.A.SW'S-10'XARMS) & UPSET Construction 1

M 5- 1 HOTLINE CLAMP Construction 6 M 5- 2 POLE TOP PIN W/INSULATOR Construction 1

M 5- 9 CUTOUT S&C X-ARM MOUNT LINE FUSE Construction 1

M 5TRF SEC. SECONDARY WIRE DOWN/UP ALL SIZES Construction 1

PRI02T2 #2 T2 CONDUCTOR Construction 18,504

Install Total

Page 17: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 17 of 37  

A 5-2 1 PH TAP OFF C1, B1 Retirement 1

C 1 3PH 8'XARM CONST PRIM SUPPORT Retirement 7

C 1-10 C1-3PH 10' XARM Retirement 2 C 7X 3PH XARM EXISTING Retirement 1

C 8A- 8 C8 W/HUGHES BROTHERS 8' ARMS Retirement 1

D35-2 DIST.35 FT. CLASS 2 POLE Retirement 1 D35-3 DIST. 35 FT. CLASS 3 POLE Retirement 2 D35-4 DIST. 35 FT. CLASS 4 POLE Retirement 2 D35-4X 35 FT USED POLE Retirement 5 D40-3 DIST. 40 FT. CLASS 3 POLE Retirement 2 D40-4 DIST. 40 FT. CLASS 4 POLE Retirement 1 D40-4X 40 FT USED POLE Retirement 1

E 1-2 SNGL. DOWN GUY THRU.BOLT TYPE Retirement 1

E 1-3 SNGL. DOWN GUY THRU.BOLT TYPE Retirement 2

F1-3S 15000# SCREW ANCHOR Retirement 1

G 9X 1PH TRANS. ON A1 SPRING FORK Retirement 1

HC1-A1FR 1PH. TO 3 PH 8'X-ARM CONST.FRAMED ARM Retirement 1

HC1-A1MFR C1 MINUS A1 W\10 FT ARM FRAMED ARM Retirement 2

K15C SWINGING K-11 OFF UPSET Retirement 1 M 2-11 DRIVEN GROUND Retirement 4 M 2-12 GROUND W/BUTT PLATE Retirement 10

M 3-25AN 3PH OCR'S (U.A.SW'S-8'XARMS) & UPSET Retirement 1

M 5- 1 HOTLINE CLAMP Retirement 6 M 5- 2 POLE TOP PIN W/INSULATOR Retirement 1

M 5- 6-3PH 3 PHASE ARRESTER BRACKET ASSEMBLY Retirement 1

M 5- 9 CUTOUT S&C X-ARM MOUNT LINE FUSE Retirement 1

PRI0471 4 7/1 ACSR Retirement 18,052

Retire Total

     

Page 18: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 18 of 37  

 

Work Order 20175810 Assembly Unit Assembly Unit Description

Transaction Type Quantity

Unit Cost

Extended Cost

M 5PBF PLUMB AND BACKFILL POLE Construction 1 M 5THW 1-PH

TIGHTEN HARDWARE SINGLE PHASE STRUCTURE Construction 23

PRI02T2 #2 T2 CONDUCTOR Construction 10,888

Install Total

PRI1061 1/0 6/1 ACSR Retirement 10,872

Retire Total

                           

Page 19: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 19 of 37  

  

Project Summary

Install Retire Total WO 20175097 WO 20175140 WO 20175351 WO 20175435 WO 20175810

Total Cost  

                      

Page 20: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 20 of 37  

  

Install Unit Prices INSTALL UNITS UNIT NO

Wire UNIT DESCRIPTION UNIT COST PRI0261 #2 6/1 ACSR Per Foot PRI0271 #2 7/1 ACSR Per Foot PRI02T2 #2 T2 CONDUCTOR Per Foot PRI0461 4 6/1 ACSR Per Foot PRI0471 4 7/1 ACSR Per Foot PRI1061 1/0 6/1 ACSR Per Foot PRI10T2 1/0 T2 CONDUCTOR Per Foot PRI2061 2/0 6/1 ACSR Per Foot PRI477 477 Hawk ACSR Per Foot PRI0230 2-3 STND COPPER Per Foot PRI4061 4/0 6/1 ACSR Per Foot PRI40T2 4/0 T2 CONDUCTOR Per Foot SEC1040 1/0 QUAD Per Foot SEC1030 1/0 TRIPLEX Per Foot SEC2030 2/0 TRIPLEX Per Foot SEC2040 2/0 QUAD Per Foot SEC0240 #2 QUAD Per Foot SEC0230 #2 6/1 TRIPLEX Per Foot SEC0461 #4 6/1 ACSR OHSEC Per Foot SEC0471 #4 7/1 ACSR OHSEC Per Foot SEC4040 4/0 QUAD Per Foot SEC4030 4/0 TRIPLEX Per Foot SEC0620 6 DUPLEX Per Foot SEC0630 6 TRIPLEX Per Foot

Poles UNIT DESCRIPTION 35-2 (D35-2) DIST. 35 FT. CLASS 2 POLE 35-3 (D35-3) DIST. 35 FT. CLASS 3 POLE 35-4 (D35-4) DIST. 35 FT. CLASS 4 POLE 40-2 (D40-2) DIST. 40 FT. CLASS 2 POLE 40-3 (D40-3) DIST. 40 FT. CLASS 3 POLE 40-4 (D40-4) DIST. 40 FT. CLASS 4 POLE

Page 21: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 21 of 37  

45-2 (D45-2) DIST. 45 FT. CLASS 2 POLE 45-3 (D45-3) DIST. 45 FT. CLASS 3 POLE 45-4 (D45-4) DIST. 45 FT. CLASS 4 POLE 50-2 (D50-2) DIST. 50 FT. CLASS 2 POLE 50-3 (D50-3) DIST. 50 FT. CLASS 3 POLE 55-2 (D55-2) DIST. 55 FT. CLASS 2 POLE

Single Phase UNIT DESCRIPTION A1 (A1-RP) 1 PH. SINGLE PRIMARY SUPPORT A1-1 (A1-1RP) See RUS Specifications A1A See RUS Specifications A1-1A See RUS Specifications A1A See RUS Specifications A2 See RUS Specifications A22 See RUS Specifications A3 (A3-RP) See RUS Specifications A4 (A4-RP) See RUS Specifications A5 (A5-RP) 1 PH DEADEND A5-1 (A5-1RP) 1 PH PRIMARY PHASE TAP A5-2 (A5-2RP) 1 PH TAP OFF C1, B1 A5-2A (A5-2ARP) See RUS Specifications A5-3 See RUS Specifications A5-4 (A5-4RP) See RUS Specifications A6 (A6-RP) See RUS Specifications A7A See RUS Specifications A7X See RUS Specifications A8A See RUS Specifications A9 See RUS Specifications A9-1 See RUS Specifications

Three Phase UNIT DESCRIPTION C1 See RUS Specifications C1A See RUS Specifications C1-RP 3PH 8' XARM RAPTOR PROOF C1-8 FRAMED See RUS Specifications C1RP-FRAMED See RUS Specifications

Page 22: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 22 of 37  

C1RPM-FRAMED 10' See RUS Specifications C1-1 See RUS Specifications C1PL See RUS Specifications C1-1PL See RUS Specifications C1-10 C1-3PH 10' XARM C1-1-10 See RUS Specifications C1-1A See RUS Specifications C1-2 See RUS Specifications C1-2RP 3PH 8' XARM CONST RAPTOR PROOF C1-2-10 3PH 10' XARM CONST. C1-2-8FRAMED See RUS Specifications C1-2-10FRAMED See RUS Specifications C1-3 (C1-3RP) See RUS Specifications C1-3P-10 See RUS Specifications C1-3-10 See RUS Specifications C1-4 See RUS Specifications C2 See RUS Specifications C2-1 See RUS Specifications C2-10 See RUS Specifications C2-2PL See RUS Specifications C22 (C22-10) See RUS Specifications C2-2 See RUS Specifications C24 (C24-10) See RUS Specifications C3 See RUS Specifications C3-1 See RUS Specifications C4-1 See RUS Specifications C5-1 See RUS Specifications C5-3 See RUS Specifications C7A (C7A-10) See RUS Specifications C7A-HD8 (C7A-HD10) D.E. H.D. HUGHES BRO CONST C 7A-FG-8 8' D.E. H.D.FIBERGLASS ARM C7X 3PH XARM EXISTING C7XFG 3PH FG-XARM EXISTING C8A-8 See RUS Specifications C8A-10 See RUS Specifications C8AHB-HD (C8AHB-HD10) See RUS Specifications C 8A-FG-8 C8 D.E. W/FIBERGLASS 8' ARM C9 See RUS Specifications C9-1 See RUS Specifications C9-2 See RUS Specifications C9-2N (Lower neutral) See RUS Specifications C9-3 See RUS Specifications

Page 23: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 23 of 37  

C9M (Lower neutral) See RUS Specifications

Guys and Anchors UNIT DESCRIPTION E1-3 (INCLUDES E3-10) SNGL. DOWN GUY THRU.BOLT TYPE

E 1-3M (INCLUDES E3-10) SINGLE DOWN GUY OFF OF FIBER GLASS DE-ARM

E2-3 SNGL.O.H.GUY THRU.BOLT TYPE

E 2-3M SNGL.O.H.GUY OFF FIBER GLASS DE - ARM

E3-10 (Reflector) See RUS Specifications E3-11 (Cattle spikes) See RUS Specifications E3-3 (INCLUDES E3-10) See RUS Specifications E4-3 See RUS Specifications E5-1 See RUS Specifications E5-2 See RUS Specifications E5-3 See RUS Specifications E9-3 (Pole band) (INCLUDES E3-10) SINGLE DOWN GUY W/4WAY POLE BD E9-3M (Add guy to ex. Band) (E3-10)

SINGLE DOWN GUY W/POLE BAND CONN LINK

F1-3S 15000# SCREW ANCHOR F1-5TFS (TWIN) PISA ANCHOR TWIN FLITE F1-5TRFS (TRIPLE) TRIPLE HELIX 10-12-14 ANCHOR

Transformers UNIT DESCRIPTION G210, G211, G212(5-37.5 KVA) See RUS Specifications G310,G311,G312(5-37.5 KVA) See RUS Specifications G310,G311,G312(50 KVA & up) See RUS Specifications P310-311-312 (All Platforms) See RUS Specifications G310CX, G311CX, G312CX 3PH TRANS. BANK EXISTING CLSTR G10 (5-37.5 KVA (Combination Unit) 1PH TRANS ON D E ASSY.& CUTOUT G9 (5-37.5 KVA)(Combination Unit) 1PH TRANS. ON A1(REQ. CUTOUT) G39-(5-37.5KVA)(Combination Unit) See RUS Specifications

Misc. Units UNIT DESCRIPTION HC1-2-10-A1 C1-2 MINUS A1 W/10'XARM

Page 24: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 24 of 37  

HC1-2-A1 C1-2 MINUS A1 W/8'X-ARM HC1-2-A1M C1-2 MINUS A1 W/10'XARM HC1-2RP-A1 C1-2RP MINUS A1 W/8'X-ARM HC1-A1 1PH. TO 3 PH 8'X-ARM CONST. HC1RP-A1 1PH. TO 3 PH 8'X-ARM CONST.

HC1-A1FR 1PH. TO 3 PH 8'X-ARM CONST.FRAMED ARM

HC1-A1M C1 MINUS A1 W\10 FT ARM HC1-A1MFR C1 MINUS A1 W\10 FT ARM FRAMED ARM HC7A-A7A 1PH. D.E. TO 3PH. D.E. J & K UNITS J10 See RUS Specifications K11 See RUS Specifications K11M {Off the back existing bolt}

K15C-4FT (K15C) SWINGING K-11 OFF UPSET 4 FT EXTENSION LINK

Grounds M2-11(M2-11#4) DRIVEN GROUND W/#4 WIRE M2-12 (M2-12#4) GROUND W/BUTT PLATE W/#4 WIRE M2-9 SHORT GROUND/REPAIR GROUND

Switches and OCRS UNIT DESCRIPTION M3-10 (1-Phase OCR no sw.) See RUS Specifications M3-15 - M2-15M (Air Switch) See RUS Specifications M3-23A (OCR w/Cutout) See RUS Specifications M3-24A See RUS Specifications M3-25 See RUS Specifications M3-25A (M3-25A-10)_ See RUS Specifications

M3-25AN (M3-25A-10)_ M3-25A WITH NEUTRAL FEEDING THROUGH

M3RBS (Reg. Bypass) See RUS Specifications M3UAS (Underarm Switch) See RUS Specifications M33-1 See RUS Specifications M33-2 See RUS Specifications M33-3 See RUS Specifications M33-4 See RUS Specifications M33-5 See RUS Specifications M33-6 See RUS Specifications

Page 25: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 25 of 37  

M33-7 See RUS Specifications M33-8 See RUS Specifications M3-2A See RUS Specifications M3-3A (M3-3A-10) See RUS Specifications M43-10 {Tap Assembly} See RUS Specifications M5-1 HOTLINE CLAMP

M5-10 (STR-STND) See RUS Specifications M5-13 See RUS Specifications M5-14 See RUS Specifications M5-16 See RUS Specifications M5-17 See RUS Specifications M5-18 See RUS Specifications M5-2 POLE TOP PIN W/INSULATOR M5-20 See RUS Specifications M5-21 See RUS Specifications M5-22 See RUS Specifications M5-23 See RUS Specifications M5-24 See RUS Specifications M5-25 See RUS Specifications M5-26 See RUS Specifications M5-27 See RUS Specifications M5-28 See RUS Specifications M52-3 POLE IDENT. LETTERS & NUMBERS M52-4 See RUS Specifications M52-5 See RUS Specifications M5-3, M5-4, M5-5 See RUS Specifications M5-6 LIGHTNING ARRESTER W/GRND M5-6R See RUS Specifications M5-6-2PH See RUS Specifications M5-6-3PH See RUS Specifications M5-8 See RUS Specifications M5-9 STR & STND See RUS Specifications M6-6 See RUS Specifications POLE KEY See RUS Specifications

Regulators UNIT DESCRIPTION M 7-11 1VOLTAGE REG. POLE MOUNTED M 7-11-M514 1PH REG.LESS.1 XARM M 7-11-M514HD 1PH REG.LESS.1 XARM 1/0-4/0-T2 >

Meter Loops UNIT DESCRIPTION

Page 26: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 26 of 37  

M8-9 30 amp (All) See RUS Specifications M8-9 100 amp (All) See RUS Specifications M8-9 200 amp (All) See RUS Specifications M8-10-30A (All) See RUS Specifications M8-10 100 amp(All) See RUS Specifications M8-10 200 amp(All) 120/240 200A 1PH D0WN LOOP FM2 M8-15 See RUS Specifications M8-15M See RUS Specifications M8-6 100 amp(All) See RUS Specifications M8-6 200 amp(All) See RUS Specifications M8-6CT (All) See RUS Specifications M8-10CT (All) See RUS Specifications

Capacitors M9-11 See RUS Specifications M9-13 See RUS Specifications

URD Units UA1 See RUS Specifications UA3 See RUS Specifications UB1 See RUS Specifications UB2 See RUS Specifications UB3 See RUS Specifications UB4 See RUS Specifications UC1 See RUS Specifications UC2 See RUS Specifications UC3 See RUS Specifications UC4 See RUS Specifications UC5 See RUS Specifications UC6 See RUS Specifications UM5 See RUS Specifications UM8-2 See RUS Specifications UM12 See RUS Specifications

TRANSFER UNITS/MISC UNIT DESCRIPTION

UNIT NO M 5WRP 20"X 25'ROLLED POLE WRAP OSMOSE M 5PBF PLUMB AND BACKFILL POLE M 5TRF PRI/NEUT 1-PH PRI. AND NEUT. DOWN/UP ALL WIRES

Page 27: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 27 of 37  

M 5TRF PRI/NEUT 3-PH PRI. AND NEUT. DOWN/UP ALL WIRES M 5PERCH RAPTOR EAGLE PERCH M 5RAPTOR-GUARD RAPTOR GUARD 16" TRIANGLE M 5TRF SEC. SECONDARY WIRE DOWN/UP ALL SIZES

M 5SPLICE 1-PH SPLICE SINGLE PHASE WIRE TO RE-ATTACH

M 5SPLICE 3-PH SPLICE THREE PHASE WIRE TO RE-ATTACH

M 5TRF CAP. BANK TAKE CAPACITOR BANK DOWN & BACK UP ALL S

M 5TRF MTRLP TAKE METER LOOP DOWN & BACK UP ALL TYPES

M 5TRF 1-PH OCR TAKE OCR DOWN & BACK UP ALL SIZES

M 5TRF 3-PH OCR TAKE OCR'S DOWN & BACK UP ALL SIZES

M 5TRF 1-REG TAKE REGULATOR DOWN & BACK UP ALL SIZES

M 5TRF ROUTER TAKE ROUTER DOWN & BACK UP M 5TRF LIGHT TAKE SECURITY LITE DOWN & BACK UP

M 5TRF 1-PH TRANS TAKE TRANS. DOWN & BACK UP ALL SIZES

M 5TRF 3-PH TRANS TAKE TRANS. DOWN & BACK UP ALL SIZES

M 5TGW TIGHTEN GUY WIRE

M 5THW 1-PH TIGHTEN HARDWARE SINGLE PHASE STRUCTURE

M 5THW 3-PH TIGHTEN HARDWARE THREE PHASE STRUCTURE

M 5TRF E3-11 SPKS REMOVE AND RE-INSTALL CATTLE SPIKE

UA1 See RUS Specifications UA3 See RUS Specifications UB1 See RUS Specifications UB2 See RUS Specifications UB3 See RUS Specifications UB4 See RUS Specifications UC1 See RUS Specifications UC2 See RUS Specifications UC3 See RUS Specifications UC4 See RUS Specifications UC5 See RUS Specifications UC6 See RUS Specifications UM5 See RUS Specifications UM8-2 See RUS Specifications Cable Attachment

Page 28: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 28 of 37  

Telephone Attachment  

Removal Unit Prices

Removal Units UNIT NO

Wire UNIT DESCRIPTION UNIT COST PRI0261 #2 6/1 ACSR Per Foot PRI0271 #2 7/1 ACSR Per Foot PRI02T2 #2 T2 CONDUCTOR Per Foot PRI0461 4 6/1 ACSR Per Foot PRI0471 4 7/1 ACSR Per Foot PRI1061 1/0 6/1 ACSR Per Foot PRI10T2 1/0 T2 CONDUCTOR Per Foot PRI2061 2/0 6/1 ACSR Per Foot PRI477 477 Hawk ACSR Per Foot PRI0230 2-3 STND COPPER Per Foot PRI4061 4/0 6/1 ACSR Per Foot PRI40T2 4/0 T2 CONDUCTOR Per Foot SEC1040 1/0 QUAD Per Foot SEC1030 1/0 TRIPLEX Per Foot SEC2030 2/0 TRIPLEX Per Foot SEC2040 2/0 QUAD Per Foot SEC0240 #2 QUAD Per Foot SEC0230 #2 6/1 TRIPLEX Per Foot SEC0461 #4 6/1 ACSR OHSEC Per Foot SEC0471 #4 7/1 ACSR OHSEC Per Foot SEC4040 4/0 QUAD Per Foot SEC4030 4/0 TRIPLEX Per Foot SEC0620 6 DUPLEX Per Foot SEC0630 6 TRIPLEX Per Foot

Poles SP 8FT (Stub Pole) See RUS Specifications 35-2 (D35-2) DIST. 35 FT. CLASS 2 POLE 30-4X (D30-4X) 30' USED POLE 35-3 (D35-3) (35-3 RTS) DIST. 35 FT. CLASS 3 POLE 35-4 (D35-4) (35-4 RTS) (D35-4X) DIST. 35 FT. CLASS 4 POLE

Page 29: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 29 of 37  

40-2 (40-2) (RTS) See RUS Specifications 40-3 (D40-3) {RTS} DIST. 40 FT. CLASS 3 POLE 40-4 (D40-4) (D40-4X) {RTS} DIST. 40 FT. CLASS 4 POLE 45-2 (D45-2) See RUS Specifications 45-3 (D45-3) See RUS Specifications 45-4 (D45-4) (D45-4X) See RUS Specifications 50-2 (D50-2) See RUS Specifications 50-3 (D50-3) See RUS Specifications 50-4 (D50-4) See RUS Specifications 55-2 (D55-2) (55-1X) See RUS Specifications RTS- Return To Stock See RUS Specifications

Single Phase A1 (A1-RP) 1 PH. SINGLE PRIMARY SUPPORT A1-1 (A1-1RP) See RUS Specifications A2 See RUS Specifications A22 See RUS Specifications A3 (A3-RP) See RUS Specifications A4 (A4-RP) See RUS Specifications A5 (A5-RP) 1 PH DEADEND A5-1 (A5-1RP) 1 PH PRIMARY PHASE TAP A5-2 (A5-2RP) 1 PH TAP OFF C1, B1 A5-2A (A5-2ARP) See RUS Specifications A5-3 See RUS Specifications A5-4 (A5-4RP) See RUS Specifications A6 (A6-RP) See RUS Specifications A7 See RUS Specifications A7A See RUS Specifications A7-1 See RUS Specifications A7X See RUS Specifications A7-4 See RUS Specifications A8 See RUS Specifications A8A See RUS Specifications A9 See RUS Specifications A9-1 See RUS Specifications

B-Phase B1 See RUS Specifications B1-1 (B1-1ARP) See RUS Specifications B1-1N (B1-1NRP) See RUS Specifications

Page 30: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 30 of 37  

B1-N-10 See RUS Specifications B1N (B1-NRP) See RUS Specifications B2 (B2-RP) See RUS Specifications B22 See RUS Specifications B3 See RUS Specifications B4-1(B4-1RP) See RUS Specifications B5-1(B5-1RP) See RUS Specifications B7 See RUS Specifications B7A (B7A-NRP) See RUS Specifications B7-1 See RUS Specifications B7XN (B7X-NRP) See RUS Specifications B7-1N See RUS Specifications B7-AN See RUS Specifications B7N See RUS Specifications B7X (B7XN) See RUS Specifications B8 See RUS Specifications B8-1 (B8-1RP) See RUS Specifications B8AN See RUS Specifications B9 (B9-RP) See RUS Specifications B9-1 (B9-1RP) See RUS Specifications B9-1N (B9-1NRP) See RUS Specifications B9-2 (B9-2RP) See RUS Specifications B9-3 (B9-3RP) See RUS Specifications

Three Phase C1 (C1RP) 3PH 8'XARM CONST PRIM SUPPORT C1-8 FRAMED See RUS Specifications C1-10 FRAMED See RUS Specifications C1RP-FRAMED See RUS Specifications C1RPM-FRAMED 10' See RUS Specifications C1-1 (C1-1RP) See RUS Specifications C1PL See RUS Specifications C1-1PL See RUS Specifications C1-10 C1-3PH 10' XARM C1-1-10 See RUS Specifications C1-2 (C1-2RP) (C1-2-10) See RUS Specifications C1-2-8FRAMED See RUS Specifications C1-2-10FRAMED See RUS Specifications C1-3 (C1-3RP) See RUS Specifications C1-3P-10 See RUS Specifications

Page 31: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 31 of 37  

C1-3-10 See RUS Specifications C1-4 See RUS Specifications C2 See RUS Specifications C2-1 See RUS Specifications C2-10 See RUS Specifications C2-2PL See RUS Specifications C22 (C22-10) See RUS Specifications C2-2 See RUS Specifications C24 (C24-10) See RUS Specifications C3 See RUS Specifications C3-1 See RUS Specifications C4 See RUS Specifications C4-1 See RUS Specifications C5-1 See RUS Specifications C5-3 See RUS Specifications C7 See RUS Specifications C7-1 (C7-1-10) See RUS Specifications C7-2 See RUS Specifications C7A (C7A-10) See RUS Specifications C7A-HD8 (C7A-HD10) See RUS Specifications C7X 3PH XARM EXISTING C8 See RUS Specifications C8-1 See RUS Specifications C8-2 (C8-2-10) See RUS Specifications C8-3 See RUS Specifications C8A (C8A-8) (C8A-10) (C 8A-FG-8) See RUS Specifications C8AHB-HD (C8AHB-HD10) See RUS Specifications C9 See RUS Specifications C9-1 See RUS Specifications C9-2 See RUS Specifications C9-2N (Lower neutral) See RUS Specifications C9-3 See RUS Specifications C9M (Lower neutral) See RUS Specifications

Guys and Anchors E11 See RUS Specifications E1-1 See RUS Specifications E12 See RUS Specifications

Page 32: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 32 of 37  

E1-2 includes reflector SNGL. DOWN GUY THRU.BOLT TYPE E1-3 includes reflector SNGL. DOWN GUY THRU.BOLT TYPE

E 1-3M SINGLE DOWN GUY OFF OF FIBER GLASS DE-ARM

E2-1 See RUS Specifications E2-2 SNGL.O.H. GUY THRU.BOLT TYPE E2-3 See RUS Specifications

E 2-3M SNGL.O.H.GUY OFF FIBER GLASS DE - ARM

E3-10 GUY MARKER E3-11 cattle spike See RUS Specifications E3-3, E3-2 See RUS Specifications E4-2, E4-3 See RUS Specifications E5-1 See RUS Specifications E5-2 includes reflector See RUS Specifications E5-3 See RUS Specifications E6-2, E6-3 See RUS Specifications E7-2, E7-3 See RUS Specifications E8-2, E8-3 See RUS Specifications E9-3 (Pole band) See RUS Specifications E9-3M (Add guy to ex. Band) See RUS Specifications E9-4 See RUS Specifications F1-1 See RUS Specifications F1-2 (F1-2T) 12000# ANCHOR F1-2S See RUS Specifications F1-3 (F1-3S) (F1-3T) 15000# SCREW ANCHOR F1-4 (F1-4S) See RUS Specifications F1-5S See RUS Specifications F1-5TFS (TWIN) See RUS Specifications F1-5TRFS (TRIPLE) See RUS Specifications F5-1 See RUS Specifications F5-2 See RUS Specifications F5-3 See RUS Specifications F6-1 See RUS Specifications F6-2 See RUS Specifications F6-3 See RUS Specifications

Transformers G210, G211, G212(5-37.5 KVA) See RUS Specifications G210X, G211X, G212X(5-37.5 KVA) See RUS Specifications

Page 33: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 33 of 37  

G310,G311,G312(5-37.5 KVA) See RUS Specifications G310X,G311X,G312X(5-37.5 KVA) See RUS Specifications G310,G311,G312(50 KVA & up) See RUS Specifications G310X,G311X,G312X(50 KVA & up) See RUS Specifications G310CX, G311CX, G312CX 3PH TRANS. BANK EXISTING CLSTR P310-311-312 (All Platforms) See RUS Specifications G10 (5-37.5 KVA (Combination Unit) 1PH TRANS ON D E ASSY.& CUTOUT G10X (5-37.5 KVA (Combination Unit) See RUS Specifications G9 (5-37.5 KVA)(Combination Unit) See RUS Specifications G9X (5-37.5 KVA)(Combination Unit) 1PH TRANS. ON A1 SPRING FORK G9,10,39-(5-37.5KVA) See RUS Specifications G9X,10X,39X-(5-37.5KVA) See RUS Specifications

Misc. Units HC1-2-10-A1 C1-2 MINUS A1 W/10'XARM HC1-2-A1 C1-2 MINUS A1 W/8'X-ARM HC1-2-A1M C1-2 MINUS A1 W/10'XARM HC1-2RP-A1 C1-2RP MINUS A1 W/8'X-ARM HC1-A1 1PH. TO 3 PH 8'X-ARM CONST. HC1RP-A1 1PH. TO 3 PH 8'X-ARM CONST.

HC1-A1FR 1PH. TO 3 PH 8'X-ARM CONST.FRAMED ARM

HC1-A1M C1 MINUS A1 W\10 FT ARM HC1-A1MFR C1 MINUS A1 W\10 FT ARM FRAMED ARM HC7A-A7A 1PH. D.E. TO 3PH. D.E. J & K UNITS J8 See RUS Specifications J9 See RUS Specifications J10 See RUS Specifications K11 See RUS Specifications K11M {Off the back existing bolt}

K15C-4FT (K15C) SWINGING K-11 OFF UPSET 4 FT EXTENSION LINK

K10 See RUS Specifications

Page 34: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 34 of 37  

Grounds M2-1 See RUS Specifications M 2- 9 SHORT GROUND M2-11(M2-11#4) DRIVEN GROUND M2-12 (M2-12#4) GROUND W/BUTT PLATE M2-2 See RUS Specifications M 3-15 - M2-15M (Air Switch) See RUS Specifications

Switches and OCRS M3-2A See RUS Specifications M3-3A (M3-3A-10) See RUS Specifications M3-10 (1-Phase OCR no sw.) See RUS Specifications M3-11 (M3-11A) See RUS Specifications M3-12 (M3-12A) See RUS Specifications M3-15 - M2-15M (Air Switch) See RUS Specifications M3-23A (OCR w/Cutout) See RUS Specifications M3-24 See RUS Specifications M3-24A See RUS Specifications M3-25 See RUS Specifications M3-25A (M3-25A-10)_ See RUS Specifications

M3-25AN (M3-25A-10)_ M3-25A WITH NEUTRAL FEEDING THROUGH

M3RBS (Reg. Bypass) See RUS Specifications M3UAS (Underarm Switch) See RUS Specifications M33-1 See RUS Specifications M33-2 See RUS Specifications M33-3 See RUS Specifications M33-4 See RUS Specifications M33-5 See RUS Specifications M33-6 See RUS Specifications M33-7 See RUS Specifications M33-8 See RUS Specifications M3-41 See RUS Specifications M43-10 See RUS Specifications M43-4 See RUS Specifications M5-1 HOTLINE CLAMP M5-10 (STR-STND) See RUS Specifications M5-11 See RUS Specifications

Page 35: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 35 of 37  

M5-12 See RUS Specifications M5-13 See RUS Specifications M5-14 See RUS Specifications M5-16 See RUS Specifications M5-17 See RUS Specifications M5-18 See RUS Specifications M5-19 See RUS Specifications M5-2 See RUS Specifications M5-20 See RUS Specifications M5-21 See RUS Specifications M5-22 See RUS Specifications M5-23 See RUS Specifications M5-24 See RUS Specifications M5-25 See RUS Specifications M5-26 (M5-26A) See RUS Specifications M5-27 See RUS Specifications M52-3 See RUS Specifications M52-4 See RUS Specifications M52-5 See RUS Specifications M5-3 See RUS Specifications M5-4 See RUS Specifications M5-5 See RUS Specifications M5-6 LIGHTNING ARRESTER W/GRND M5-6R See RUS Specifications M5-6-2PH See RUS Specifications

M5-6-3PH 3 PHASE ARRESTER BRACKET ASSEMBLY

M5-8 See RUS Specifications M5-9 (STND & STR) See RUS Specifications

Regulators M 7-11 1VOLTAGE REG. POLE MOUNTED M 7-11-M514 1PH REG.LESS.1 XARM M 7-11-M514HD 1PH REG.LESS.1 XARM 1/0-4/0-T2 > M 7-13 See RUS Specifications

Meter Loops M8-9 30 amp (All) See RUS Specifications M8-9 100 amp (All) See RUS Specifications M8-9 200 amp (All) See RUS Specifications M8-10-30A (All) See RUS Specifications M8-10 100 amp(All) See RUS Specifications

Page 36: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 36 of 37  

M8-10 200 amp(All) 120/240 200A 1PH D0WN LOOP FM2 M8-15 See RUS Specifications M8-15M See RUS Specifications M8-6 100 amp(All) See RUS Specifications M8-6 200 amp(All) See RUS Specifications M8-6CT (All) See RUS Specifications M8-10CT (All) See RUS Specifications

Capacitors M9-11 See RUS Specifications M9-12 See RUS Specifications M9-13 See RUS Specifications

URD Units POLE KEY See RUS Specifications UA1 See RUS Specifications UA3 See RUS Specifications UB1 See RUS Specifications UB2 See RUS Specifications UB3 See RUS Specifications UB4 See RUS Specifications UC1 See RUS Specifications UC2 See RUS Specifications UC3 See RUS Specifications UC4 See RUS Specifications UC5 See RUS Specifications UC6 See RUS Specifications UM5 See RUS Specifications UM8-2 See RUS Specifications UM12 See RUS Specifications

         

Page 37: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

  Pioneer Electric Cooperative, Inc. 

1850 W. Oklahoma Avenue, Ulysses, KS 67880                       

Phone (620) 356‐1462      Fax (620) 356‐1669 

 

  Power Restoration Services ‐ Reconductoring and Hazard Mitigation Project 

Page 37 of 37  

  

Staking Sheets on following pages                                       

Page 38: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 1 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

.

512 0 512

SCALE IN FEET

Page 39: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 2 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 2 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

X 1 23 E D40-3 C 1-10 M 2-12 (2) E 3-10 F1-3S M 5- 9

E A 7X (2) E 1-3

E C 7A

R M42-1/0NT

R M42-1/0PH

C M42-T2PH

C M42-T2NT

TAG #78618

X 1 1 1 1 1 X 1 23 E D35-4 A 1 M 2-12

R 229 (449) PRI1061

C 229 (458) PRI02T2 M40-#2T2PH

C M 5THW 1-PH

C M40-#2T2NT

X 1 1 1 1 2 X 1 1 1 1 1 E D35-4 A 1 M 2-12

R 229 (458) PRI1061

C 229 (458) PRI02T2 M40-#2T2NT

C M 5THW 1-PH

C M40-#2T2PH

X 1 1 1 1 3 X 1 1 1 1 2 E D35-4 A 1 M 2-12

R 230 (460) PRI1061

C 230 (460) PRI02T2 M 5THW 1-PH

C M40-#2T2NT

C M40-#2T2PH

X 1 1 1 1 4 X 1 1 1 1 3 E D35-4 A 1 M 2-12

R 229 (458) PRI1061

C 229 (458) PRI02T2 M40-#2T2NT

C M40-#2T2PH

C M 5THW 1-PH

X 1 1 1 1 5 X 1 1 1 1 4 E D40-3 A 1 X1B15120/240

M 2-12 E 1-3 F1-3S K11

E G 9 E 3-10

R 231 (462) PRI1061

C 231 (462) PRI02T2 M40-#2T2PH

C M40-#2T2NT

C M 5THW 1-PH

TAG #78623

Page 40: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 3 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 3 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

X 1 1 1 1 6 X 1 1 1 1 5 E D35-4 A 1 M 2-12

R 231 (462) PRI1061

C 231 (462) PRI02T2 M40-#2T2NT

C M40-#2T2PH

C M 5THW 1-PH

X 1 1 1 1 7 X 1 1 1 1 6 E D35-4 A 1 M 2-12

R 237 (473) PRI1061

C 237 (474) PRI02T2 M 5THW 1-PH

C M40-#2T2PH

C M40-#2T2NT

X 1 1 1 1 8 X 1 1 1 1 7 E D35-4 A 1 M 2-12

R 235 (469) PRI1061

C 235 (470) PRI02T2 M40-#2T2PH

C M40-#2T2NT

C M 5THW 1-PH

X 1 1 1 1 9 X 1 1 1 1 8 E D35-4 A 1 M 2-12

R 240 (480) PRI1061

C 240 (480) PRI02T2 M40-#2T2NT

C M 5THW 1-PH

C M40-#2T2PH

X 1 1 1 1 10 X 1 1 1 1 9 E D35-4 A 1 M 2-12

R 237 (474) PRI1061

C 237 (474) PRI02T2 M 5THW 1-PH

C M40-#2T2NT

C M40-#2T2PH

X 1 1 1 1 11 X 1 1 1 1 10 E D35-4 A 1 M 2-12

R 242 (483) PRI1061

C 242 (484) PRI02T2 M40-#2T2NT

C M40-#2T2PH

C M 5THW 1-PH

X 1 1 1 1 12 X 1 1 1 1 11 E D35-4 A 1 M 2-12

R 240 (479) PRI1061

C 240 (480) PRI02T2 M40-#2T2NT

C M 5THW 1-PH

C M40-#2T2PH

Page 41: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 4 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 4 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

X 1 1 1 1 13 X 1 1 1 1 12 E D35-4 A 1 M 2-12

R 241 (482) PRI1061

C 241 (482) PRI02T2 M40-#2T2PH

C M 5THW 1-PH

C M40-#2T2NT

X 1 1 1 1 14 X 1 1 1 1 13 E D35-4 A 1 M 2-12

R 239 (477) PRI1061

C 239 (478) PRI02T2 M40-#2T2PH

C M 5THW 1-PH

C M40-#2T2NT

X 1 1 1 1 15 X 1 1 1 1 14 E D35-4 A 1 M 2-12

R 240 (480) PRI1061

C 240 (480) PRI02T2 M 5THW 1-PH

C M40-#2T2PH

C M40-#2T2NT

X 1 1 1 1 16 X 1 1 1 1 15 E D35-4 A 1 M 2-12

R 240 (480) PRI1061

C 240 (480) PRI02T2 M40-#2T2PH

C M40-#2T2NT

C M 5THW 1-PH

X 1 1 1 1 17 X 1 1 1 1 16 E D35-4 A 1 M 2-12

R 240 (480) PRI1061

C 240 (480) PRI02T2 (2) M 5THW 1-PH

C M40-#2T2NT

C M40-#2T2PH

X 1 1 1 1 18 X 1 1 1 1 17 E D35-4 A 1 M 2-12

R 241 (481) PRI1061

C 241 (482) PRI02T2 M 5THW 1-PH

C M40-#2T2NT

C M40-#2T2PH

X 1 1 1 1 19 X 1 1 1 1 18 E D35-4 A 1 M 2-12

R 241 (482) PRI1061

C 241 (482) PRI02T2 M40-#2T2PH

C M 5THW 1-PH

C M40-#2T2NT

Page 42: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 5 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 5 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

X 1 1 1 1 20 X 1 1 1 1 19 E D35-4 A 1 M 2-12

R 239 (478) PRI1061

C 239 (478) PRI02T2 M40-#2T2NT

C M 5THW 1-PH

C M40-#2T2PH

C M 5PBF

X 1 1 1 1 21 X 1 1 1 1 20 E D35-4 A 1 M 2-12

R 239 (477) PRI1061

C 239 (478) PRI02T2 M 5THW 1-PH

C M40-#2T2PH

C M40-#2T2NT

X 1 1 1 1 22 X 1 1 1 1 21 E D40-3 A 1 M 2-12

R 234 (468) PRI1061

C 234 (468) PRI02T2 M 5THW 1-PH

C M40-#2T2NT

C M40-#2T2PH

X 1 1 1 2 1 X 1 1 1 1 22 E D35-3 UA1 M 2-11 E 3-10 F1-3S UM12

E A 5 E 1-3

R 240 (480) PRI1061 M42-1/0NT

R M42-1/0PH

C 240 (480) PRI02T2 M42-T2NT

C M42-T2PH

TAG #78642

Page 43: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: GRANT COUNTY County: Grant

TWP: 28S RG.: 36W SEC: 31-NW/NE

JOB DESC: FEMA 4319- RECONDUCTOR X1-1-1-1

NAME:

ADDRESS:

SUB: 6 - ULYSSES CITY FDR: EAST 48 PHASE: B

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175810SHEET NO.: 6 OF: 6ENGINEER: JEREMY GARRISON DATE: 05/13/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 6 of 6

* UNITS REQ.

R M42-1/0NT 2

R M42-1/0PH 2

R PRI1061 10872

C M40-#2T2NT 22

C M40-#2T2PH 22

C M42-T2NT 2

C M42-T2PH 2

C M 5PBF 1

C M 5THW 1-PH 23

C PRI02T2 10888

Wire Tally

Action Conductor WireFeet

No. ofWires

Pole Line

R PRI1061 10872 2 5444

C PRI02T2 10888 2 5444

Directions:

Comments:

Page 44: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: HAMILTON COUNTY County: Hamilton

TWP: 26S RG.: 39W SEC: 30-NW/NE

JOB DESC: FEMA 4319 - REBUILD(IMP) K19-8

NAME:

ADDRESS:

SUB: 16 - BEAR CREEK FDR: SOUTH 97 PHASE: ABC

Primary Wire Size: PRI10T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175097SHEET NO.: 1 OF: 5ENGINEER: LEROY RODRIGUEZ DATE: 06/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

.

440 0 440

SCALE IN FEET

Page 45: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: HAMILTON COUNTY County: Hamilton

TWP: 26S RG.: 39W SEC: 30-NW/NE

JOB DESC: FEMA 4319 - REBUILD(IMP) K19-8

NAME:

ADDRESS:

SUB: 16 - BEAR CREEK FDR: SOUTH 97 PHASE: ABC

Primary Wire Size: PRI10T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175097SHEET NO.: 2 OF: 5ENGINEER: LEROY RODRIGUEZ DATE: 06/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 2 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

K19 9 3 E D35-4 C 1 M 2-12 FEMA RECONDUCTOR, IMPROVEDPROJECT REBUILD TO T2-1/0

K19 9 2 K19 9 3 E 100 (402) PRI1061

C D40-3 C 7A-HD8 M 2-11#4 E 9-3M 35 (2) F1-5TF M 5- 2

C C 7XFG (2) E 9-3 25/30 F1-5TRF

K19 9 1 K19 9 2 R 199 (795) PRI1061 D35-4 C 1 M 2-12 E 2-2 M 5- 1

R A 5-2 M 5- 9

C 199 (796) PRI10T2 D40-3 C 1- 2-10 M 2-12#4 E 2-3 M 5- 9STR

C A 5-2

TAG#2050

K19 8 22 K19 9 1 C 220 (880) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 21 K19 8 22 C 220 (880) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 20 K19 8 21 C 220 (880) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 19 K19 8 20 C 220 (880) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 18 K19 8 19 C 225 (900) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 17 K19 8 18 E (3) X2B05240/480

R D35-3 C 1-10 G311CX M 2-11 M 8- 6-15

C 225 (920) PRI10T2 D40-3 C 1- 2-10 G311CX M 2-11#4 M 8- 6-17

MTR;66498 LINN OPERATINGHATTRUP 1-30R NW30-26-39

K19 8 16 K19 8 17 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 15 K19 8 16 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 14 K19 8 15 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 13 K19 8 14 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 12 K19 8 13 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-11#4

K19 8 11 K19 8 12 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 10 K19 8 11 C 210 (840) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 9 K19 8 10 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 8 K19 8 9 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 7 K19 8 8 E (3) X2B05240/480

R D35-4 C 1-10 G311CX M 2-11 M 8- 6-15

C 215 (860) PRI10T2 D40-3 C 1- 2-10 G311CX M 2-11#4 M 8- 6-17

MTR;66497 LINN OPERATINGHATTRUP 2-30 NW30-26-39

K19 8 6 K19 8 7 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 5 K19 8 6 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 4 K19 8 5 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 3 K19 8 4 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

Page 46: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: HAMILTON COUNTY County: Hamilton

TWP: 26S RG.: 39W SEC: 30-NW/NE

JOB DESC: FEMA 4319 - REBUILD(IMP) K19-8

NAME:

ADDRESS:

SUB: 16 - BEAR CREEK FDR: SOUTH 97 PHASE: ABC

Primary Wire Size: PRI10T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175097SHEET NO.: 3 OF: 5ENGINEER: LEROY RODRIGUEZ DATE: 06/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 3 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

K19 8 2 K19 8 3 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 8 1 K19 8 2 C 215 (860) PRI10T2 D40-4 C 1- 2RP M 2-12#4

K19 7 18 K19 8 1 E D40-3 A 5-2 M 2-12 E 3-10 F1-3S M 5- 1

E E 1-3 27

R HC1-A1M

C 219 (876) PRI10T2 HC1-2-A1M

*NOTE:CHANGE X-ARM TO HEAVYCONSTRUCTION. TAG#34601

K19 7 17 K19 7 18 R 196 (783) PRI1061 D35-4 C 1-10 M 2-12

C 196 (784) PRI10T2 D40-3 C 7X M 2-11#4 E 9-3M 35 F1-5TRF (3) M 5- 1

C C 7A-HD8 (2) E 9-3 25/30 (2) F1-5TF M 5- 2

K19-8-16* K19 9 1 R 234 (936) PRI1061 D35-4 HC1-A1M M 2-11 M 5- 6-3PH RTS POLE & FRAMED XARM

K19-8-15* K19-8-16* E M 2-12

R 236 (944) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19-8-14* K19-8-15* E M 2-12

R 253 (1012) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19-8-13* K19-8-14* E M 2-12

R 301 (1204) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19 8 17 K19-8-13* E (3) X2B05240/480

R 306 (1224) PRI1061

MTR;66498 LINN OPERATINGHATTRUP 1-30R NW30-26-39

K19-8-11* K19 8 17 R 300 (1199) PRI1061 D35-4 C 1 M 2-12

K19-8-10* K19-8-11* R 300 (1200) PRI1061 D35-4 C 1 M 2-12

K19-8-9* K19-8-10* R 298 (1192) PRI1061 D35-4 C 1 M 2-12

K19-8-8* K19-8-9* R 303 (1212) PRI1061 D40-3 C 1 M 2-12

K19-8-7* K19-8-8* R 308 (1232) PRI1061 D35-4 C 1 M 2-12

K19-8-6* K19-8-7* R 304 (1216) PRI1061 D35-4 C 1 M 2-12

K19 8 7 K19-8-6* E (3) X2B05240/480

R 302 (1207) PRI1061

MTR;66497 LINN OPERATINGHATTRUP 2-30 NW30-26-39

K19-8-4* K19 8 7 E M 2-12

R 300 (1200) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19-8-3* K19-8-4* E M 2-12

R 297 (1188) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19-8-2* K19-8-3* E M 2-12

R 311 (1244) PRI1061 D35-4 HC1-A1M

RTS POLE & FRAMED XARM

K19-8-1* K19-8-2* R 302 (1208) PRI1061 D35-3 C 1 M 2-12

Page 47: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: HAMILTON COUNTY County: Hamilton

TWP: 26S RG.: 39W SEC: 30-NW/NE

JOB DESC: FEMA 4319 - REBUILD(IMP) K19-8

NAME:

ADDRESS:

SUB: 16 - BEAR CREEK FDR: SOUTH 97 PHASE: ABC

Primary Wire Size: PRI10T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175097SHEET NO.: 4 OF: 5ENGINEER: LEROY RODRIGUEZ DATE: 06/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 4 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

K19 7 18 K19-8-1* E D40-3 A 5-2 M 2-12 E 3-10 F1-3S M 5- 1

E E 1-3 27

R 297 (1188) PRI1061

*NOTE:CHANGE X-ARM TO HEAVYCONSTRUCTION. TAG#34601

Page 48: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: HAMILTON COUNTY County: Hamilton

TWP: 26S RG.: 39W SEC: 30-NW/NE

JOB DESC: FEMA 4319 - REBUILD(IMP) K19-8

NAME:

ADDRESS:

SUB: 16 - BEAR CREEK FDR: SOUTH 97 PHASE: ABC

Primary Wire Size: PRI10T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175097SHEET NO.: 5 OF: 5ENGINEER: LEROY RODRIGUEZ DATE: 06/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 5 of 5

* UNITS REQ.

R A 5-2 1

R C 1 8

R C 1-10 3

R D35-3 2

R D35-4 15

R D40-3 1

R E 2-2 1

R G311CX 2

R HC1-A1M 8

R M 2-11 3

R M 2-12 9

R M 5- 1 1

R M 5- 6-3PH 1

R M 5- 9 1

R M 8- 6-15 2

R PRI1061 21384

C A 5-2 1

C C 1- 2-10 3

C C 1- 2RP 20

C C 7A-HD8 2

C C 7X 1

C C 7XFG 1

C D40-3 5

C D40-4 20

C E 2-3 1

C E 9-3 4

C E 9-3M 2

C F1-5TF 4

C F1-5TRF 2

C G311CX 2

C HC1-2-A1M 1

C M 2-11#4 5

C M 2-12#4 20

C M 5- 1 3

C M 5- 2 2

C M 5- 9STR 1

C M 8- 6-17 2

C PRI10T2 21416

Wire Tally

Action Conductor WireFeet

No. ofWires

Pole Line

E PRI1061 402 4 100

R PRI1061 21384 4 5347

C PRI10T2 21416 4 5349

Directions:

Comments:

Page 49: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: Morton County: Morton

TWP: 33S RG.: 40W SEC: 24

JOB DESC: FEMA 4319- RECONDUCTOR G14-1

NAME:

ADDRESS:

SUB: 8 - ROLLA FDR: EAST 30 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175140SHEET NO.: 1 OF: 5ENGINEER: LARRY O DAVIS DATE: 03/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

.

443 0 443

SCALE IN FEET

Page 50: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: Morton County: Morton

TWP: 33S RG.: 40W SEC: 24

JOB DESC: FEMA 4319- RECONDUCTOR G14-1

NAME:

ADDRESS:

SUB: 8 - ROLLA FDR: EAST 30 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175140SHEET NO.: 2 OF: 5ENGINEER: LARRY O DAVIS DATE: 03/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 2 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G14-28 E D40-2 C 7A M 2-12 (2) E 2-3 M 5- 5

E C 1- 3-10

R C 7X (3) M 5- 1

C C 7X (3) M 5- 1

83220

G14-1-1 G14-28 E D35-4X C 1 M 2-12

R 250 (750) PRI1061

R 250 (250) PRI0271

C 250 (1000) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-2 G14-1-1 E D35-4X C 1 M 2-12

R 274 (274) PRI0271

R 274 (822) PRI1061

C 274 (1096) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-3 G14-1-2 E D40-2 C 1RP M 2-12

R 269 (807) PRI1061

R 269 (269) PRI0271

C 269 (1076) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-4 G14-1-3 E D40-2 C 1RP M 2-12

R 276 (828) PRI1061

R 276 (276) PRI0271

C 276 (1104) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-5 G14-1-4 E D40-2 C 1RP M 2-12

R 271 (271) PRI0271

R 271 (813) PRI1061

C 271 (1084) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-6 G14-1-5 E D40-4 C 1RP M 2-12

R 272 (816) PRI1061

R 272 (272) PRI0271

C 272 (1088) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

Page 51: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: Morton County: Morton

TWP: 33S RG.: 40W SEC: 24

JOB DESC: FEMA 4319- RECONDUCTOR G14-1

NAME:

ADDRESS:

SUB: 8 - ROLLA FDR: EAST 30 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175140SHEET NO.: 3 OF: 5ENGINEER: LARRY O DAVIS DATE: 03/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 3 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G14-1-7 G14-1-6 E D35-4X C 1 M 2-12

R 272 (816) PRI1061

R 272 (272) PRI0271

C 272 (1088) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-8 G14-1-7 E D40-2 C 1RP M 2-12

R 270 (810) PRI1061

R 270 (270) PRI0271

C 270 (1080) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-9 G14-1-8 E D40-2 C 1RP M 2-12

R 271 (813) PRI1061

R 271 (271) PRI0271

C 271 (1084) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-10 G14-1-9 E D40-4 C 1RP M 2-12

R 270 (810) PRI1061

R 270 (270) PRI0271

C 270 (1080) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-11 G14-1-10 E D40-4 C 1RP M 2-12

R 274 (822) PRI1061

R 274 (274) PRI0271

C 274 (1096) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-12 G14-1-11 E D40-4 C 1RP M 2-12

R 271 (271) PRI0271

R 271 (813) PRI1061

C 271 (1084) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-13 G14-1-12 E D40-4 C 1RP M 2-12

R 273 (273) PRI0271

R 273 (819) PRI1061

C 273 (1092) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

Page 52: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: Morton County: Morton

TWP: 33S RG.: 40W SEC: 24

JOB DESC: FEMA 4319- RECONDUCTOR G14-1

NAME:

ADDRESS:

SUB: 8 - ROLLA FDR: EAST 30 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175140SHEET NO.: 4 OF: 5ENGINEER: LARRY O DAVIS DATE: 03/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 4 of 5

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G14-1-14 G14-1-13 E D40-2 C 1-10 (3) X2B05240/480

M 2-11 M 8- 6-17

E G311

R 271 (271) PRI0271

R 271 (813) PRI1061

C 271 (1084) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

MTR;58470 R.H. CHAMBERS 1-2SCOUT ENERGY MNGR

G14-1-15 G14-1-14 E D40-4 C 1RP M 2-12

R 271 (271) PRI0271

R 271 (813) PRI1061

C 271 (1084) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-16 G14-1-15 E D40-4 C 1RP M 2-12

R 272 (272) PRI0271

R 272 (816) PRI1061

C 272 (1088) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

G14-1-17 G14-1-16 E D40-4 C 1RP M 2-12

R 233 (233) PRI0271

R 233 (699) PRI1061

C 233 (932) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

G14-1-18 G14-1-17 E D35-4 C 1 G 9B M 2-11 M 8-10- 30A-15

E X1B01120/240

R 229 (229) PRI0271

R 229 (687) PRI1061

C 229 (916) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

MTR;54107D N ROLLA RECTIFIERBLACK HILLS UTILITY HOLDER

G14-1-19 G14-1-18 E D35-3 C 7A M 2-11 (2) E 3-10 (2) F1-3S M 5- 1

E A 7X (2) E 1-3 27/32

R 205 (615) PRI1061 C 7X

R 205 (205) PRI0271

C 205 (820) PRI02T2 C 7X

67347

Page 53: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: Morton County: Morton

TWP: 33S RG.: 40W SEC: 24

JOB DESC: FEMA 4319- RECONDUCTOR G14-1

NAME:

ADDRESS:

SUB: 8 - ROLLA FDR: EAST 30 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175140SHEET NO.: 5 OF: 5ENGINEER: LARRY O DAVIS DATE: 03/22/2018

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 5 of 5

* UNITS REQ.

R C 7X 2

R M 5- 1 3

R PRI0271 4994

R PRI1061 14982

C C 7X 2

C M40-#2T2NT 18

C M40-#2T2PH 54

C M 5- 1 3

C PRI02T2 19976

Wire Tally

Action Conductor WireFeet

No. ofWires

Pole Line

R PRI0271 4994 1 4994

R PRI1061 14982 3 4994

C PRI02T2 19976 4 4994

Directions:

Comments:

Page 54: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 1 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

.

843 0 843

SCALE IN FEET

Page 55: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 2 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 2 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

B40D 2 18 R D35-4X A 1 M 2-12 E 3-10 F1-2 M 5- 1

R A 5-1 E 1-2

C D35-3 A 1 M 2-11 E 1-3 F1-3S M 5- 1

C A 5-1

TAG#87535

B40D 2A 1 B40D 2 18 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 2 B40D 2A 1 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 3 B40D 2A 2 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 4 B40D 2A 3 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 5 B40D 2A 4 C 250 (500) PRI02T2 D35-4 A 1 M 2-11

B40D 2A 6 B40D 2A 5 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 7 B40D 2A 6 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 8 B40D 2A 7 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 9 B40D 2A 8 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 10 B40D 2A 9 C 250 (500) PRI02T2 D35-4 A 1 M 2-11 M 5- 6

B40D 2A 11 B40D 2A 10 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 12 B40D 2A 11 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 13 B40D 2A 12 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 14 B40D 2A 13 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 15 B40D 2A 14 C 250 (500) PRI02T2 D35-4 A 1 M 2-11

B40D 2A 16 B40D 2A 15 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 17 B40D 2A 16 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 18 B40D 2A 17 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 19 B40D 2A 18 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2A 20 B40D 2A 19 C 250 (500) PRI02T2 D35-4 A 1 M 2-11 M 5- 6

B40D 2A 21 B40D 2A 20 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 1 B40D 2A 21 C 250 (500) PRI02T2 D35-4 A 1 M 2-12 M52-3 {26-31-42}

B40D 2B 2 B40D 2B 1 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 3 B40D 2B 2 C 245 (490) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 4 B40D 2B 3 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 5 B40D 2B 4 C 240 (480) PRI02T2 D35-4 A 1 M 2-11

B40D 2B 6 B40D 2B 5 C 240 (480) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 7 B40D 2B 6 C 240 (480) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 8 B40D 2B 7 C 240 (480) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 9 B40D 2B 8 C 230 (460) PRI02T2 D35-4 A 1 M 2-12

Page 56: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 3 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 3 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

B40D 2B 10 B40D 2B 9 C 200 (400) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 11 B40D 2B 10 E D40-4 A 6 G 10 M 2-11 E 1-3 F1-3 M 8-10- 15 M 5- 1

E X2B05120/240

M 5- 2

C 201 (402) PRI02T2 E 1-3 F1-3S (2) M42-#2NT

C (2) M42-#2PH

STORM GUY POLE, LEAVE IDLESERVICE TAG#122641

B40D 2B 12 B40D 2B 11 C 245 (490) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 13 B40D 2B 12 C 245 (490) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 14 B40D 2B 13 C 240 (480) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 15 B40D 2B 14 C 260 (520) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 16 B40D 2B 15 C 260 (520) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 17 B40D 2B 16 C 250 (500) PRI02T2 D35-4 A 1 M 2-11

B40D 2B 18 B40D 2B 17 C 260 (520) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 19 B40D 2B 18 C 260 (520) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 20 B40D 2B 19 C 250 (500) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 21 B40D 2B 20 C 155 (310) PRI02T2 D35-4 A 1 M 2-12

B40D 2B 22 B40D 2B 21 E X1B15120/240

R D35-3 A 5 G 10 M 2-11 E 3-10 F1-3S M 8-10-200A-15

R E 1-3

C 156 (312) PRI02T2 D35-3 A 5 G 10 M 2-11 E 1-3 F1-3S M 8-10-200A-15

EX MTR#61370D TAG#87567

B40D 2A 1* B40D 2 18 R 82 (163) PRI0471 D35-4X A 1 M 2-12

B40D 2A 2* B40D 2A 1* R 244 (488) PRI0471 D30-4X A 1 M 2-12

B40D 2A 3* B40D 2A 2* E A 1 M 2-12

R 325 (650) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 4* B40D 2A 3* E A 1 M 2-12

R 326 (651) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 5* B40D 2A 4* R 324 (647) PRI0471 D35-4 A 1 M 2-12

B40D 2A 6* B40D 2A 5* R 329 (658) PRI0471 D30-4X A 1 M 2-12

B40D 2A 7* B40D 2A 6* R 331 (661) PRI0471 D35-4 A 1 M 2-12

B40D 2A 8* B40D 2A 7* E A 1 M 2-12

R 325 (650) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 9* B40D 2A 8* R 329 (657) PRI0471 D35-4 A 1 M 2-12

B40D 2A 10* B40D 2A 9* E A 1 M 2-12

R 322 (644) PRI0471 D35-4

{RTS} NEW POLE

Page 57: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 4 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 4 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

B40D 2A 11* B40D 2A 10* E A 1 M 2-12

R 331 (661) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 12* B40D 2A 11* E A 1 M 2-12

R 325 (650) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 13* B40D 2A 12* E A 1 M 2-12

R 326 (652) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 14* B40D 2A 13* E A 1 M 2-12

R 326 (652) PRI0471 D30-4X

{RTS} NEW POLE

B40D 2A 15* B40D 2A 14* E A 1 M 2-12

R 328 (656) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 16* B40D 2A 15* E A 1 M 2-12

R 331 (662) PRI0471 D35-4

{RTS} NEW POLE

B40D 2A 17* B40D 2A 16* E A 1 M 2-12

R 329 (657) PRI0471 D35-4

{RTS} NEW POLE

B40D 2B 1* B40D 2A 17* E A 1

R 327 (653) PRI0471 D35-4 M 2-11 M 5- 6

{RTS} NEW POLE

B40D 2B 2* B40D 2B 1* E A 1 M 2-12

R 331 (661) PRI0471 D35-4

NEW POLE

3* B40D 2B 2* R 328 (656) PRI0471 D30-4X A 1 M 2-12

4* 3* E A 1 M 2-12

R 329 (658) PRI0471 D35-4

{RTS} NEW POLE

5* 4* R 333 (665) PRI0471 D35-4 A 1 M 2-12

6* 5* R 319 (638) PRI0471 D30-4X A 1 M 2-12

7* 6* E A 6 M 2-12 M 5- 2

R 203 (406) PRI0471 D35-3 E 1-3 F1-3S M 5- 1

{RTS} NEW POLE

B40D 2B 11 7* E D40-4 A 6 G 10 M 2-11 E 1-3 F1-3 M 8-10- 15 M 5- 1

E X2B05120/240

M 5- 2

R 431 (862) PRI0471

STORM GUY POLE, LEAVE IDLESERVICE TAG#122641

9* B40D 2B 11 E A 1 M 2-12

R 324 (648) PRI0471 D35-4

{RTS} NEW POLE

10* 9* E A 1 M 2-12

R 325 (650) PRI0471 D35-4

{RTS} NEW POLE

11* 10* E A 1 M 2-12

R 323 (646) PRI0471 D35-4

{RTS} NEW POLE

Page 58: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 5 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 5 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

12* 11* E A 1 M 2-12

R 327 (654) PRI0471 D35-4

{RTS} NEW POLE

13* 12* E A 1 M 2-12

R 302 (603) PRI0471 D35-4

{RTS} NEW POLE

14* 13* E A 1 M 2-12

R 310 (619) PRI0471 D35-4

{RTS} NEW POLE 2015

15* 14* R 323 (645) PRI0471 D35-4 A 1 M 2-12

B40D 2B 22 15* E X1B15120/240

R 346 (691) PRI0471

EX MTR#61370D TAG#87567

Page 59: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 31S RG.: 42W SEC: 27/26-NW-NE

JOB DESC: 4319 FEMA- REBUILD B40D2A & 2B

NAME: FEMA - REBUILD B40D 2A & 2B

ADDRESS:

SUB: 11 - MANTER FDR: SOUTH 54 PHASE: A

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175351SHEET NO.: 6 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/06/2019

CHECKED BY: DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 6 of 6

* UNITS REQ.

R A 1 11

R A 5 1

R A 5-1 1

R D30-4X 5

R D35-3 2

R D35-4 24

R D35-4X 2

R E 1-2 1

R E 1-3 2

R E 3-10 2

R F1-2 1

R F1-3S 2

R G 10 1

R M 2-11 2

R M 2-12 11

R M 5- 1 2

R M 5- 6 1

R M 8-10-200A-15 1

R PRI0471 20814

C A 1 42

C A 5 1

C A 5-1 1

C D35-3 2

C D35-4 41

C E 1-3 3

C F1-3S 3

C G 10 1

C M 2-11 8

C M 2-12 35

C M42-#2NT 2

C M42-#2PH 2

C M 5- 1 1

C M52-3 1

C M 5- 6 2

C M 8-10-200A-15 1

C PRI02T2 20834

Wire Tally

Action Conductor WireFeet

No. ofWires

Pole Line

R PRI0471 20814 2 10414

C PRI02T2 20834 2 10417

Directions:

Comments:

Page 60: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 1 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

.

416 0 416

SCALE IN FEET

Page 61: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 2 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 2 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G40A 1 G40 20 E D35-3 C 7A X2B10120/240

M 2-11 E 1-3 27 F1-3S M 8-10- 15 M 5- 1

E A 7X G 10 E 3-10 M 8-10- 30A-15 M 5- 5

R 153 (610) PRI0471 C 7X

C 153 (612) PRI02T2 C 7X E 1-3 22 F1-3S

EX MTR #61458D PION. COMM&#68626D SMITH BROS #TAG#24585

G40 20 E D40-3 C 9 M 2-12

E C 1- 1

R (3) M 5- 1

C M40-#2T2NT

C (3) M40-#2T2DBL

C (3) M 5- 1

TAG#24243

G40 1 1 G40 20 C 250 (1000) PRI02T2 D40-3 M 3-25AN/10XARM M 2-11 RE-USE BREAKERS 4H-15A

G40 1 2 G40 1 1 E X1B10120/240

F1-2T

R D35-4X C 1 G 9X M 2-11 E 1-2 K15C

C 251 (1004) PRI02T2 D40-3 C 1-10 G 9 M 2-11 E 1-3 K15C M 5TRF SEC.

TAG#103012

2A G40 1 2 E D35-4X M 2-11 E 3-10 F1-2T K11 (121) SEC0230 122 M 8-10-100A-15

E E 1-2

EX MTR#61459D SMITH BROSTRLR #3

G40 1 3 G40 1 2 C 190 (760) PRI02T2 D40-4 C 1-10 M 2-12

G40 1 4 G40 1 3 C 190 (760) PRI02T2 D40-4 C 1-10 M 2-12

G40 1 5 G40 1 4 E D40-3 A 5-2 M 2-12 M 5- 1

E C 1-10

C 185 (740) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

TAG#59018

G40 1 6 G40 1 5 C 230 (920) PRI02T2 D40-4 C 1RP M 2-12

G40 1 7 G40 1 6 C 230 (920) PRI02T2 D40-4 C 1RP M 2-12

G40 1 8 G40 1 7 C 230 (920) PRI02T2 D40-4 C 1RP M 2-12

G40 1 9 G40 1 8 C 230 (920) PRI02T2 D40-4 C 1RP M 2-12

G40 1 10 G40 1 9 C 230 (920) PRI02T2 D40-4 C 1RP M 2-12

G40 1 11 G40 1 10 E F1-3S Unknowngs_overcurrent_device

R D40-3 C 1-10 M 2-11 E 1-3 M 5- 9

R A 5-2

C 232 (928) PRI02T2 D40-3 A 5-2 M 2-11 E 1-3 M 5- 9

C C 1-10

15K TAG#103019

Page 62: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 3 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 3 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G40 1 12 G40 1 11 C 235 (940) PRI02T2 D40-4 C 1-10 M 2-12

G40 1 13 G40 1 12 C 235 (940) PRI02T2 D40-4 C 1RP M 2-12

G40 1 14 G40 1 13 C 235 (940) PRI02T2 D40-4 C 1RP M 2-12

G40 1 15 G40 1 14 C 235 (940) PRI02T2 D40-4 C 1RP M 2-12

G40 1 16 G40 1 15 C 230 (920) PRI02T2 D40-4 C 1-10 M 2-12

G40 1 17 G40 1 16 C 230 (920) PRI02T2 D40-4 C 1-10 M 2-12

G40 1 18 G40 1 17 E D40-3 C 1-10 (2) X2B10120/240

M 2-11 M 8- 6- 4-17-20

E G310

E X2B15120/240

C 229 (916) PRI02T2 (3) M40-#2T2PH

C M40-#2T2NT

EX MTR#64755

G40 1 19 G40 1 18 E D40-3 C 1-10 G310 M 2-11 E 1-3 F1-3S J10

E (3) X2B15120/240

R 250 (1001) PRI0471

C 250 (1000) PRI02T2 M40-#2T2NT

C (3) M40-#2T2PH

TAG #103035

19A G40 1 19 E D35-4 M 2-11 E 1-3 F1-3S J10 (48) SEC1040 48 M 8- 6- 4-20-20 M 5-28 EX MTR#64633

G40 1 20 G40 1 19 R 146 (146) PRI0471 D40-3 C 8A- 8 M 2-12 E 3-10 F1-3S (3) M 5- 1

R E 1-3 M 5- 2

C 146 (584) PRI02T2 D40-3 C 7XFG M 2-12 E 1-3M (2) F1-3S (3) M 5- 1

C C 7A-FG-8 E 1-3 M 5- 2

G40 1 1* G40 20 R 225 (899) PRI0471 D35-4X M 3-25AN M 2-11 *NOTE: RE-USE BREAKERS 4H-15A

G40 1 2 G40 1 1* E X1B10120/240

F1-2T

R 276 (1103) PRI0471

TAG#103012

G40 1 3* G40 1 2 R 278 (1110) PRI0471 D35-4X C 1 M 2-12

G40 1 5 G40 1 3* E D40-3 A 5-2 M 2-12 M 5- 1

E C 1-10

R 288 (1150) PRI0471

TAG#59018

G40 1 5* G40 1 5 R 294 (1175) PRI0471 D40-4 HC1-A1FR M 2-12 NEW POLE, RETURN POLE ANDFRAMED X-ARM TO STOCK

G40 1 6* G40 1 5* R 283 (1132) PRI0471 D35-2 HC1-A1MFR M 2-12 NEW POLE, RETURN POLE ANDFRAMED X-ARM TO STOCK

Page 63: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 4 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 4 of 6

PRIMARY GUY & ANCHOR SECONDARY

POLE NUMBER PREVIOUSSTATION

E ROR C

BACKSPAN(FT.)

WIRE SIZE POLEHEIGHT

& CLASS

PRIMARY UNIT XFMR UNIT GRND UNIT GUY UNIT LEAD ANCHOR UNIT UNIT "JOR K"

WIRE SIZE SPANFEET

METER OR LOOP MISC UNIT MISCELLANEOUS AND REMARKS

G40 1 7* G40 1 6* R 286 (1142) PRI0471 D35-4X C 1 M 2-12

G40 1 8* G40 1 7* R 281 (1124) PRI0471 D40-4X C 1 M 2-12

G40 1 11 G40 1 8* E F1-3S Unknowngs_overcurrent_device

R 238 (950) PRI0471

15K TAG#103019

G40 1 10* G40 1 11 R 318 (1271) PRI0471 D35-4 HC1-A1MFR M 2-11 M 5- 6-3PH NEW POLE, RETURN POLE ANDFRAMED X-ARM TO STOCK

G40 1 11* G40 1 10* R 271 (1083) PRI0471 D35-3 C 1 M 2-12

G40 1 12* G40 1 11* R 276 (1105) PRI0471 D35-3 C 1-10 M 2-12

G40 1 13* G40 1 12* R 287 (1149) PRI0471 D35-4 C 1 M 2-12

G40 1 14* G40 1 13* R 235 (941) PRI0471 D35-4X C 1 M 2-12

G40 1 18 G40 1 14* E D40-3 C 1-10 (2) X2B10120/240

M 2-11 M 8- 6- 4-17-20

E G310

E X2B15120/240

R 240 (961) PRI0471

EX MTR#64755

Page 64: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 5 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 5 of 6

* UNITS REQ.

R A 5-2 1

R C 1 7

R C 1-10 2

R C 7X 1

R C 8A- 8 1

R D35-2 1

R D35-3 2

R D35-4 2

R D35-4X 5

R D40-3 2

R D40-4 1

R D40-4X 1

R E 1-2 1

R E 1-3 2

R E 3-10 1

R F1-3S 1

R G 9X 1

R HC1-A1FR 1

R HC1-A1MFR 2

R K15C 1

R M 2-11 4

R M 2-12 10

R M 3-25AN 1

R M 5- 1 6

R M 5- 2 1

R M 5- 6-3PH 1

R M 5- 9 1

R PRI0471 18052

C A 5-2 1

C C 1-10 7

C C 1RP 8

C C 7A-FG-8 1

C C 7X 1

C C 7XFG 1

C D40-3 4

C D40-4 13

C E 1-3 4

C E 1-3M 1

C F1-3S 3

Wire Tally

Action Conductor WireFeet

No. ofWires

Pole Line

E SEC0230 121 1 122

E SEC1040 48 1 48

R PRI0471 17906 4 4479

R PRI0471 146 1 146

C PRI02T2 18504 4 4626

Directions:

Comments:

Page 65: Request for Proposal (RFP) Work Power Restoration Services ...pioneerelectric.coop/wp-content/uploads/2019/11/RFP-2019-001-final… · underground telephone, fiber optic cables, cable

LOCATION: MORTON COUNTY County: Morton

TWP: 32s RG.: 43w SEC: 25-SE/SW

JOB DESC: FEMA 4319- REBUILD G40-1 IMPROVED

NAME:

ADDRESS:

SUB: 15 - RICHFIELD FDR: SOUTH 93 PHASE: ABC

Primary Wire Size: PRI02T2 Ruling Span:

STAKING SHEET

W.O. NUMBER: 20175435SHEET NO.: 6 OF: 6ENGINEER: LEROY RODRIGUEZ DATE: 08/05/2019

CHECKED BY: 0 DATE:

Call Before Dig: Ticket #:

Loan Project: 300-IMP

Page 6 of 6

* UNITS REQ.

C G 9 1

C K15C 1

C M 2-11 3

C M 2-12 14

C M 3-25AN/10XARM 1

C M40-#2T2DBL 3

C M40-#2T2NT 4

C M40-#2T2PH 9

C M 5- 1 6

C M 5- 2 1

C M 5- 9 1

C M 5TRF SEC. 1

C PRI02T2 18504