Kinetics Noise Control, Inc Confidential 3/14/2012 Effectiveness of UniBrace: Isolation of the Drive Unit of a Garage Door Opener Purpose for experiment: To measure effectiveness of the UniBrace for Isolating structure-borne noise from a garage door drive unit. Conducted by: Matt Golden Basis experimental setup: A single family residence was located with a bedroom directly above the garage. The garage had an automatic garage door opener installed. Acoustical measurements were obtained in the bedroom while the garage door was opened when the garage door opener was directly attached to the structure and when it was isolated by two Kinetics Noise Control IsoMax UniBrace-L brackets. Measurements were obtained with: BSWA MP253 – ½” free field microphone BSWA MA211 – ICP preamplifier OROS 34 – 4 channel analyzer The analyzer was set to record 1/3 octave band sound pressure levels once every second. The L eq for each event was then calculated. Pictures: Figure 1: Direct - attached garage door opener

Transcript of Report on Isolation of grage door with UniBrace · a garage door drive unit. Conducted by: Matt...

Page 1: Report on Isolation of grage door with UniBrace · a garage door drive unit. Conducted by: Matt Golden Basis experimental setup: A single family residence was located with a bedroom

Kinetics Noise Control, Inc Confidential 3/14/2012

Effectiveness of UniBrace:

Isolation of the Drive Unit of a Garage Door Opener

Purpose for experiment: To measure effectiveness of the UniBrace for Isolating structure-borne noise from a garage door drive unit.

Conducted by: Matt Golden

Basis experimental setup: A single family residence was located with a bedroom directly above the garage. The garage had an automatic garage door opener installed. Acoustical measurements were obtained in the bedroom while the garage door was opened when the garage door opener was directly attached to the structure and when it was isolated by two Kinetics Noise Control IsoMax UniBrace-L brackets.

Measurements were obtained with:

� BSWA MP253 – ½” free field microphone � BSWA MA211 – ICP preamplifier � OROS 34 – 4 channel analyzer

The analyzer was set to record 1/3 octave band sound pressure levels once every second. The Leq for each event was then calculated.

Pictures:

Figure 1: Direct - attached garage door opener

Page 2: Report on Isolation of grage door with UniBrace · a garage door drive unit. Conducted by: Matt Golden Basis experimental setup: A single family residence was located with a bedroom

– 2 – March 14, 2012

Figure 2: Isolated garage door opener by IsoMax UniBrace L brackets

Data:

Garage Door Isolation by UniBrace in Bedroom Directly Above Garage

1/3 Octave Band Data

20

25

30

35

40

45

50

55

60

20

25

32

40

50

63

80

100

125

160

200

250

315

400

500

630

800

1000

1250

1600

2000

dBA

Freq (Hz)

SPL (dB)

Hard Attached

Drive Unit Isolated

Page 3: Report on Isolation of grage door with UniBrace · a garage door drive unit. Conducted by: Matt Golden Basis experimental setup: A single family residence was located with a bedroom

– 3 – March 14, 2012

Garage Door Isolation by UniBrace in Bedroom Directly Above Garage

Ocatave Band Data

20

25

30

35

40

45

50

55

60

6532

63

125

250

500

1000

2000

dBA

Freq (Hz)

SPL (dB)

Hard Attached

Drive Unit Isolated

Octave Band

Center Freq

(Hz) Hard Attached

Drive Unit

Isolated Max Backgroud Improvement

32 61.7 55.8 43.9 5.9

63 56.7 53.5 44.9 3.3

125 59.7 53.9 44.9 5.8

250 53.9 43.6 35.5 10.2

500 42.3 38.1 32.2 4.2

1000 31.8 29.7 27.0 2.1

2000 26.8 27.5 27.2 -0.7

dBA 48.3 41.6 35.2 6.7

Page 4: Report on Isolation of grage door with UniBrace · a garage door drive unit. Conducted by: Matt Golden Basis experimental setup: A single family residence was located with a bedroom

– 4 – March 14, 2012

1/3 Octave

Band Center

Freq (Hz) Hard Attached

Drive Unit

Isolated Max Backgroud Improvement

20 58.6 56.0 45.1 2.6

25 59.1 50.4 40.1 8.7

32 52.7 50.9 40.7 1.8

40 56.8 51.7 35.3 5.1

50 46.8 44.9 33.6 2.0

63 51.4 47.1 35.8 4.3

80 54.5 51.5 44.0 3.1

100 50.9 46.3 41.8 4.7

125 58.6 52.0 40.8 6.6

160 48.9 46.5 35.3 2.5

200 46.2 42.1 31.1 4.1

250 52.7 35.7 29.0 17.0

315 42.3 34.9 31.7 7.4

400 41.0 33.8 28.9 7.2

500 34.1 33.3 29.1 0.8

630 32.8 32.9 27.0 -0.1

800 29.6 26.0 21.8 3.7

1000 25.5 26.1 22.6 -0.6

1250 23.5 21.2 22.1 2.3

1600 21.7 23.4 22.2 -1.6

2000 21.4 21.5 22.6 -0.1

dBA 48.2 41.6 35.1 6.6

Conclusion:

• The Kinetics Noise Control IsoMax UniBrace-L can be effectively used to isolate structure-borne noise from a garage door opener.