Report in Eee
-
Upload
villegreen910 -
Category
Documents
-
view
215 -
download
0
Transcript of Report in Eee
-
8/2/2019 Report in Eee
1/42
Click to edit Master subtitle style
4/8/12
by:
Switching and ControlDevices
-
8/2/2019 Report in Eee
2/42
4/8/12
Are included all types of switches, fuses,circuit breakers and a large number of otherdevices, the purposes of which are to make orbreak, or change the connections in an electric
circuit, under either normal or abnormalconditions.
Switching and ControlDevices
-
8/2/2019 Report in Eee
3/42
4/8/12
SWITCHESFUSES
BREAKERS
-
8/2/2019 Report in Eee
4/42
4/8/12
The most familiar form of switch is a manuallyoperated electromechanical device with oneor more sets of electrical contacts. Each set ofcontacts can be in one of two states: either
'closed' meaning the contacts are touchingand electricity can flow between them, or'open', meaning the contacts are separatedand non-conducting.
SWITCHES
-
8/2/2019 Report in Eee
5/42
4/8/12
Electrical Switches.
-
8/2/2019 Report in Eee
6/42
4/8/12
Knife switches
A knife switch is a type of switch used to control the
flow of electricity in a circuit. It is composed of a hinge whichallows a metal lever, or knife, to be lifted from or inserted into
a slot or jaw.
CLASSES OF SWITCHES
-
8/2/2019 Report in Eee
7/42
4/8/12
Disconnecting Switches
for power circuits it is necessary to use some type ofcircuit breaker to open or close the circuit. In order to isolatethe circuit breakers, it is generally considered good practice toconnect the knife switches in series with the circuit breakers.
-
8/2/2019 Report in Eee
8/42
4/8/12
Air-break Switches
An air break switch comprising one or more fixedcontacts and one or more movable contacts which aremovable between open and closed positions, and a coilwhich, preferably in conjunction with magneticallysusceptible material acting as a flux director.
-
8/2/2019 Report in Eee
9/42
4/8/12
Control Switches
This class include all switches that are used to controlthe operation of other equipment.
A clothes dryer using a load control switch to reduce peak
-
8/2/2019 Report in Eee
10/42
4/8/12
Auxiliary Switches
A switch actuated by the main device (such as a circuitbreaker) for signaling, interlocking, or other purposes. In thisclass are included all switches or contactors that are actuatedby some other control switch or device.
-
8/2/2019 Report in Eee
11/42
4/8/12
Oil Switches
An oil switch is a high-voltage switch whose contactsare opened and closed in oil. The switch is actually immersedin an oil bath and contained in a steel tank.
-
8/2/2019 Report in Eee
12/42
4/8/12
Magnetic-impulse Switches
This type of switch, the arc is extinguished by blowingit magnetically into arc chutes where it is lengthened cooled,and interrupted. The magnetic effect is produced by the circuitcurrent which is passed through suitable coils, setting up astrong magnetic field across the space between the switchcontacts as they are opened.
-
8/2/2019 Report in Eee
13/42
4/8/12
In electronics and electrical engineering a fuse (from theLatin "fusus" meaning to melt) is a type of sacrificialovercurrent protection device. Its essential component is ametal wire or strip that melts when too much current flows,which interrupts the circuit in which it is connected. Short
circuit, overload or device failure is often the reason forexcessive current.
A fuse interrupts excessive current (blows) so that furtherdamage by overheating or fire is prevented. Wiringregulations often define a maximum fuse current rating forparticular circuits. Overcurrent protection devices areessential in electrical systems to limit threats to human lifeand property damage. Fuses are selected to allow passageof normal current and of excessive current only for short
periods.
FUSES
-
8/2/2019 Report in Eee
14/42
4/8/12
Cartridge Fuses
Come in a cylindrical shape and have contacts points ateach end. They have a fuse link connected to the two endsand protect the circuit from over-current. It is composed ofstrong fiber casing inside of which is enclosed a fuse wiregenerally an alloy of lead.
CLASSES OF FUSES
-
8/2/2019 Report in Eee
15/42
4/8/12
Transformer Fuse Block and Cutout
The proper protection of distribution circuits has for yearsbeen recognized as best fulfilled by means of fuses.Distribution transformers are as a general rule placed onpoles, towers, or in manholes and in any automatic protectionwould be too entirely complicated and expensive. Fuses offera simple and cheap method of protection, It is common
practice tom place these fuses in the secondary of suchtransformers, thereby protecting the transformers againstshort circuits or overloads. There are two types of fuses that
are generally used for these purpose.
-
8/2/2019 Report in Eee
16/42
4/8/12
Expulsion Fuse
For higher voltages such as found in power circuits ormain feeders, there is often a demand for a fuse, on accountof its simplicity. The expulsion type-fuse has been developedfor such service. This device is consists of a hollow tube, madeof some heat-resisting substance such as fiber with a lining ofasbestos or some other material, through which is passed a
fuse wire. One end of the tube is closed and connected to theline; the other end is opened and allows the fuse wire toproject out and connect to the other terminal.
-
8/2/2019 Report in Eee
17/42
4/8/12
A circuit breaker is a complex circuit-breaking device withthe following duties:
a. Makes or breaks both normal and abnormal currents.
b. Appropriately manages the high-energy arc associated
with current interruption. The problem has become moreacute due to interconnection of power stations resulting invery high fault levels.\
c. Effects current interruption only when it is called upon todo so by the relay circuits. In fact they are required to trip
for a minimum of the internal fault current and remaininoperative for a maximum of through fault current.
d. Rapid and successive automatic breaking and making toaid stable system operation
e. Three pole (3-pole) and single pole (1-pole) auto-reclosingarrangement
Circuit Breakers
-
8/2/2019 Report in Eee
18/42
4/8/12
In addition to the making and breaking capabilities, acircuit breaker is required to do following tasks under the
following typical conditions:
a. Short-circuit interruption
b. Interruption of small inductive currents
c. Capacitor switching
d. Interruption of short-line faulte. Asynchronous switching
-
8/2/2019 Report in Eee
19/42
4/8/12
A circuit breaker is a switching i.e. current interruptingor making device in switchgear. In more proper words, a
circuit breaker is defined as a piece of equipment whichcan do any one of the following tasks:
a. Makes or breaks a circuit either manually or byremote control under normal conditions
b. Breaks a circuit automatically under faultconditions
c. Makes a circuit either manually or by remotecontrol under fault conditions
-
8/2/2019 Report in Eee
20/42
4/8/12
A Circuit Breaker with InternalStructure
-
8/2/2019 Report in Eee
21/42
4/8/12
The primary function of the circuit breakers mechanism is toprovide the means for opening and closing the contacts.Initially, this seems to be a rather simple andstraightforward requirement. However, when one considersthe fact that most circuit breakers, once placed into service,
will remain in the closed position for long periods of time,and yet on the few occasions when they are called upon toopen or close, they must do so reliably, without any delay orsluggishness, then one realizes that the demands on the
mechanisms are not as simple as was first thought.
Operating Principle
Arc Phenomenon
-
8/2/2019 Report in Eee
22/42
4/8/12
Based on Voltage
Low
Medium High/Extra High
Ultra High
Classification of CircuitBreakers
Arc Phenomenon
-
8/2/2019 Report in Eee
23/42
4/8/12
Based on Location
Indoor
Outdoor
Based on External Design
Dead Tank
Live Tank
Based on Interrupting media
Air Break
Air Blast
Oil
SF6
-
8/2/2019 Report in Eee
24/42
4/8/12
In such circuit breakers, some insulating oil (i.e., transformeroil) is used as an arc quenching medium. The contacts areopened under oil and an arc is struck between them. Theheat of the arc evaporates the surrounding oil anddissociates it into a substantial volume of hydrogen gas at a
high pressure. This large volume of the hydrogen gaspushes the oil away from the arc.
Oil Circuit Breakers
-
8/2/2019 Report in Eee
25/42
4/8/12
Advantages:
1. Oil absorbs the arc energy to produceshydrogen gas during arcing. The hydrogen hasexcellent cooling properties and helps
extinguish the arc. (In addition to hydrogen gas,a small proportion of methane, ethylene, andacetylene are also generated in oildecomposition.)
2. The oil provides insulation for the liveexposed contacts from the earthed portions ofthe container.
3. Oil provides insulation between the contactsafter the arc has been extinguished
-
8/2/2019 Report in Eee
26/42
4/8/12
Disadvantages:
1. Oil is inflammable and may cause firehazards. When a defective circuit breaker failsunder pressure, it may cause an explosion.
2. The hydrogen generated during arcing, whencombined with air, may form an explosive
mixture.
3. During arcing, oil decomposes and becomespolluted by carbon particles, which reduces itsdielectric strength. Hence, it requires periodic
-
8/2/2019 Report in Eee
27/42
4/8/12
Bulk Oil Circuit Breakers
These circuit breakers use a large quantityof oil. The oil has to serve two purposes:
1. It extinguishes the arc during opening ofcontacts.
2. It insulates the current conducting parts fromone another and from the earthed tank.
Types of Oil CircuitBreakers
-
8/2/2019 Report in Eee
28/42
4/8/12
Minimum Oil Circuit Breakers
These circuit breakers use a small quantityof oil. In such circuit breakers, oil is used onlyfor arc extinction; the current conducting parts
insulated by air or porcelain or organicinsulating material.
In these circuit breakers, the oilrequirement can be minimized by placing the
interrupting units, in insulating chambers at livepotential, on an insulator column.
-
8/2/2019 Report in Eee
29/42
4/8/12
These circuit breakers employ a high pressure air-blast as an arc quenching medium. The contactsare opened in a flow of air-blast established by theopening of the blast valve. The air-blast cools thearc and sweeps away the arcing products of theatmosphere. Consequently, the arc is extinguishedand flow of current is interrupted.
Whenever current at high voltages needs to beinterrupted, more breaking units are used, inseries. Dry and clean air supply is one of the mostessential requirements for the operation of the air-blast circuit breakers.
Air-Blast Circuit Breakers
-
8/2/2019 Report in Eee
30/42
4/8/12
-
8/2/2019 Report in Eee
31/42
4/8/12
Advantages:
1. The risk of fire is eliminated in these circuitbreakers.
2. The arcing products are completely removed
by the blast whereas the oil deteriorates withsuccessive operations. So the expenditure of oilreplacement is avoided in air-blast circuitbreakers.
3. The size of these breakers is reduced, as thedielectric strength grows so rapidly that finalcontact gap for the arc extinction is very small.
4. Due to the rapid growth of the dielectric
-
8/2/2019 Report in Eee
32/42
4/8/12
Disadvantages:
1. These circuit breakers are very sensitive to thevariation s in the rate of rise of restriking voltage.
2. The air-blast is supplied by the compressor plantthat needs considerable maintenance tages:
-
8/2/2019 Report in Eee
33/42
4/8/12
In these circuit breakers, Sulphurhexafluoride gas (SF6) is used as the arcquenching medium. The SF6is anelectronegative gas and has a strong tendency
to absorb free electrons.
Applications
SF6 circuit breakers find use in systemswith voltages ranging in 115 kV to 230 kV,as they are designed for this range withpower ratings of 10 MVA to 20 MVA and
interrupting time less than 3 cycles.
Sulphur Hexafluoride (SF6)Circuit Breakers
-
8/2/2019 Report in Eee
34/42
4/8/12
Advantages:
1. Because of the high conductivity of the arc in theSF6 gas, the arc energy is low. (Arc voltage isbetween 150 and 200V.)
2. Due to the low energy the contact erosion is small.3. The gaseous medium SF6 possesses excellentdielectric and arc quenching properties. After arcextinction, the dissociated gas molecules recombine
almost completely to reform SF6. This means thatpractically no loss/consumption of the quenchingmedium occurs.
-
8/2/2019 Report in Eee
35/42
4/8/12
4. Due to the superior arc quenching property of theSF6 gas, such circuit breakers have very short arcing
time. Furthermore, they can interrupt much largercurrent.
5. These breakers give noiseless operation due to itsclosed gas circuit and no exhaust to atmosphere
unlike the air-blast circuit breaker.
6. The SF6 gas is not inflammable, so there is no riskof fire in SF6 breakers.
7. Since SF6 breakers are totally enclosed and sealedfrom the atmosphere, they are particularly suitable
where explosion hazards exist, i.e. in coal mines.
-
8/2/2019 Report in Eee
36/42
4/8/12
Disadvantages:
1.These circuit breakers are expensive due tothe high cost of SF6 gas.
2. Since SF6 gas has to be reconditioned after
every operation of the breaker, additionalequipment is required for this purpose.
3.The SF6gas has been identified as a
greenhouse gas, and safety regulations arebeing introduced in many countries in orderto prevent its release into the atmosphere.
-
8/2/2019 Report in Eee
37/42
4/8/12
In such circuit breakers, the vacuum is used as thearc quenching medium. The vacuum circuit breakertakes the advantage of non-sustainability ofelectric arc in vacuum, and employs the principleof contact separation under vacuum where there isno ionization due to medium. The initial arc causedby field and thermionic emissions during thecontacts separation, will die away soon, as there isno further ionization because of vacuum.
Vacuum Circuit Breakers
-
8/2/2019 Report in Eee
38/42
4/8/12
-
8/2/2019 Report in Eee
39/42
-
8/2/2019 Report in Eee
40/42
4/8/12
Advantages:
1. The vacuum circuit breakers are compact insize and have longer lives.
2. Operating energy requirements are low,
because the mechanism must move onlyrelatively small masses at moderate speed,over very short distances.
3. Because of the very low voltage across themetal vapor arc, energy is very low. (Arc voltageis between 50 and 100V.)
4. Due to the very low arc energy, the rapid
movement of the arc root over the contact and-
-
8/2/2019 Report in Eee
41/42
4/8/12
5. There is no generation of gases during andafter the circuit breaker operation.
6. The outstanding feature of these breakers isthat it can break any heavy fault current
perfectly just before the contacts reach adefinite open position.
7. They can successfully withstand lightningsurges.
8. It is now possible to produce cost-effective VI(vacuum interrupter) designs with electrical
lives that exceed the required mechanical life ofthe circuit breakers and that will even be able
-
8/2/2019 Report in Eee
42/42
Air circuit breaker is defined as a circuit breaker, inwhich the contacts open and close in air atatmospheric pressure. In general, the use of thistype of circuit breakers is restricted to low voltageapplications or high security installations where therisk of an oil fire or oil contamination of theenvironment is too high to be tolerated. Countriesfollowing the American practice used air circuitbreakers almost exclusively for systems up to 15
kV until the advent of the new vacuum and SF6technologies.
Air Circuit Breakers