REPAIR / ADDITION TO AIR CONDITIONING - IMCOM ... Ft Sam...1102 CONFERENCE ROOM 1652 ELEC 1651 FIRE...
Transcript of REPAIR / ADDITION TO AIR CONDITIONING - IMCOM ... Ft Sam...1102 CONFERENCE ROOM 1652 ELEC 1651 FIRE...
DRS
CLC
TITLE SHEET
AS SHOWN G1.1
CLC
JBSA SAM HOUSTON, TX
DRAWING LIST
REPAIR / ADDITION TO AIR
EXPIRATIONDATE SIGNED
EXPIRATIONDATE SIGNED
MECHANICAL ENGINEER'S SEALELECTRICAL ENGINEER'S SEAL
GENERALG1.1
MECHANICALMD1.1M1.1
ELECTRICALE1.1
TITLE SHEET
PARTIAL FLOOR PLAN - DEMOLITION - MECHANICALPARTIAL FLOOR PLAN - MECHANICAL
PARTIAL FIRST FLOOR PLAN - ELECTRICAL
CHARLES L . CALVERT
I L L I NO I S
ENGINEERPROFESSIONALREGISTERED62046964
OF
LARRY D . HOWARDLARRY D . HOWARD
I L L I NO I S
ENGINEERPROFESSIONALREGISTERED
6235161
OF
McCOY AND HOWARD CONSULTING ENGINEERS, INC
ELECTRICAL & MECHANICALENGINEERS
413 MAIN STREETMT. VERNON, IL. 62864
CONDITIONING - IMCOM
7 FEBRUARY 2017SOLICITATION ISSUE
3720-16-000004
JBSA SAM HOUSTON, TX
IMCOMTO AIR CONDITIONING -
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main St ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
35% DESIGN SUBMITTAL 23 SEPT 2016
7 FEB 2017
REPAIR / ADDITION
95% DESIGN SUBMITTAL 6 JAN 2017
100% DESIGN SUBMITTAL 31 JAN 2017
SOLICITATION ISSUE7 FEB 2017
LOCATION MAP
PROJECT LOCATION
1102CONFERENCE ROOM
1652ELEC
1651FIRE PUIMP
1653MECH
1501ADMIN1502
SECURITY
1503ELECTRICAL RM.
1901STAIR 'A'
1801MEN
1902ELEV 1
1002ELEV 1 LOBBY
1001ENTRY
1101OFFICE
L
C
PARTIALFIRST FLOOR PLAN - ELECTRICALSCALE:1/8" = 1'-0"NORTH
DRS
LDH
PARTIALFIRST FLOOR PLAN -
ELECTRICAL
1/8"=1'-0" E1.1
LDH
3720-16-000004
JBSA SAM HOUSTON, TX
IMCOMTO AIR CONDITIONING -
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main St ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
LARRY D . HOWARDLARRY D . HOWARD
I L L I NO I S
ENGINEERPROFESSIONALREGISTERED
6235161
OF
35% DESIGN SUBMITTAL 23 SEPT 2016
7 FEB 2017
REPAIR / ADDITION
95% DESIGN SUBMITTAL 6 JAN 2017
100% DESIGN SUBMITTAL 31 JAN 2017
SOLICITATION ISSUE7 FEB 2017
SD
D2
DEMOLITION NOTES:DISCONNECT ELECTRIC DUCT HEATER FROM POWER SUPPLY. COMPLETELY REMOVESAFETY SWITCH AND BRANCH CIRCUIT WIRE AND CONDUIT.
DISCONNECT FAN COIL UNIT FROM POWER SUPPLY. COMPLETELY REMOVE SAFETY SWITCHAND BRANCH CIRCUIT WIRE AND CONDUIT. REUSE 30A/3P CIRCUIT BREAKER IN EXISTINGPANEL L4N TO SUPPLY NEW FAN COIL UNIT.
DISCONNECT AND REMOVE DUCT SMOKE DETECTORS FROM DUCTS SUPPLIED BY FAN COILUNIT TO BE REMOVED. RECONNECT EXISTING SIGNALLING LINE CIRCUIT TO NEW DUCTSMOKE DETECTORS.
PLAN NOTES:PROVIDE 50A/3P CIRCUIT BREAKER IN EXISTING 480V/3PH PANELBOARD. LABEL “OUTDOORHEAT PUMP HP1.”
NEW INDOOR FAN COIL UNIT FC-1. 208V/3PH, 14 RLA. PROVIDE 30A/3P NON-FUSED SAFETYSWITCH ON UNIT AND MAKE FINAL CONNECTION. RUN 3 # 10, # 10 GND, ¾”C. TOEXISTING 30A/3P CIRCUIT BREAKER IN EXISTING PANEL L4N. MODIFY PANEL SCHEDULE.
NEW OUTDOOR HEAT PUMP HP-1. 480V/3PH, 41 RLA. PROVIDE 60A/3P NON-FUSED NEMA 3RSAFETY SWITCH. MOUNT ON UNISTRUT STEEL CHANNEL ADJACENT TO HEAT PUMP. MAKEFINAL CONNECTION. RUN 3 # 6, # 8 GND, 1”C. TO NEW 50A/3P CIRCUIT BREAKER INEXISTING 480V PANEL. RUN CIRCUIT IN PIPE TRENCH OUTSIDE BUILDING. MODIFY PANELSCHEDULE.
PROVIDE ADDRESSABLE 2-WIRE DUCT SMOKE DETECTORS IN SUPPLY DUCT AND RETURNAIR PLENUM.
PROVIDE ADDRESSABLE RELAY BASE CONTROL MODULE AND CONNECT TO FAN COIL UNITCONTROL CIRCUIT TO SHUT DOWN UNIT UPON ACTUATION OF FIRE ALARM SYSTEM.
CONNECT NEW FIRE ALARM DEVICES TO EXISTING SLC CIRCUIT IN CLASS A CONFIGURATION.ALL WIRING SHALL BE IN CONDUIT.
PROVIDE GFCI RECEPTACLE IN CAST BOX WITH WEATHERPROOF-WHILE-IN-USECOVER. MOUNT ON UNISTRUT STEEL CHANNEL ADJACENT TO HEAT PUMP. RUN 2 # 12,# 12 GND, 3/4”C. TO EXISTING RECEPTACLE CIRCUIT IN PANEL L4N. RUN CIRCUIT IN PIPETRENCH OUTSIDE BUILDING.
D1
D2
D3
1
2
3
4
5
6
7
480 VOLT PANELBOARD
208 VOLT PANELBOARD
SAFETY SWITCH
GFCI RECEPTACLE
DUCT SMOKE DETECTOR
RELAY BASE ADDRESSABLE CONTROL MODULE.
ELECTRICAL OR FIRE ALARM CIRCUIT IN CONDUIT CONCEALED ABOVE LAY-IN CEILING.
ELECTRICAL CIRCUIT IN CONDUIT IN PIPE TRENCH.
FLEXIBLE METALLIC CONDUIT CONNECTION TO EQUIPMENT. USE LFMC FOR CONNECTIONTO HEAT PUMP.
SD
CM
EXISTING PANEL "L4N"
EXISTING 480V PANEL1
CM
SD
2
4
5
4
6
TO 480V PANEL
TO PANEL L4N
3
7GFCI
GFCI
TO PANEL L4N
FC-1
SD
HP-1
6
D1 D3
1102CONFERENCE ROOM
1652ELEC
1651FIRE PUIMP
1653MECH
1501ADMIN1502
SECURITY
1503ELECTRICAL RM.
1901STAIR 'A'
1801MEN
1902ELEV 1
1002ELEV 1 LOBBY
1001ENTRY
1101OFFICE
L
C
PARTIAL FLOOR PLAN - MECHANICALSCALE:1/8" = 1'-0"NORTH
3720-16-000004
JBSA SAM HOUSTON, TX
IMCOMTO AIR CONDITIONING -
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main St ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
CHARLES L . CALVERT
I L L I NO I S
ENGINEERPROFESSIONALREGISTERED62046964
OF
35% DESIGN SUBMITTAL 23 SEPT 2016
7 FEB 2017
REPAIR / ADDITION
95% DESIGN SUBMITTAL 6 JAN 2017
100% DESIGN SUBMITTAL 31 JAN 2017
SOLICITATION ISSUE7 FEB 2017
X
PT
P T
CONDENSATE DRAIN
BUTTERFLY VALVEGATE VALVEGLOBE VALVECHECK VALVECALIBRATED BALANCE VALVEAUTOMATIC THREE WAY CONTROL VALVEAUTOMATIC TWO WAY CONTROL VALVEPRESSURE REDUCING VALVEPLUG VALVEELBOW TURNED UPELBOW TURNED DOWNTEE - 45 DEG BOTTOM OUTLETTEE - 45 DEG TOP OUTLETUNION OR FLANGEFLEXIBLE PUMP OR PIPE CONNECTIONPIPE ANCHORPRESSURE AND TEMPERATURE TEST STATIONPRESSURE GUAGE AND THERMOMETERMANUAL AIR VENT
REFRIGERANT LIQUIDREFRIGERANT SUCTION
SUPPLY AIR DUCTWORK (SA)RETURN, EXHAUST, OR OUTDOOR AIR DUCTWORK (RA,EA,OA)SUPPLYRETURN OR EXHAUSTINCLINE RISE (IN DIRECTION OF FLOW)INCLINE DROP (IN DIRECTION OF FLOW)FLEXIBLE DUCTWORKFLEXIBLE DUCT CONNECTIONFIRE DAMPER
ACCESS DOOR IN DUCTWORK
R
D
FD
VD VOLUME DAMPERAD
SG
DRLRS
12x12
12x12
SECURITY GRILLEAP18x18 ACCESS PANEL IN BUILDING CONSTRUCTION - SIZE
ADJUSTABLE VOLUME EXTRACTORSPLITTER DAMPERTURNING VANESTHERMOSTAT - MOUNT 48" AFF, G INDICATES GUARD, N INDICATES NIGHTT
GRILLE OR DIFFUSER SYMBOL - SEE SCHEDULE, THROAT SIZE INDICATED2
AHU-1 EQUIPMENT DESIGNATION - SEE SCHEDULEVARIABLE VOLUME TERMINAL UNITV-2
DOOR GRILL AND SIZEDOOR UNDERCUT
DUC
DG18x12
WATER PIPING NOTES
MOTORIZED DAMPERMD
RHG REFRIGERANT HOT GAS
PITCH UP IN DIRECTION OF FLOW 1" IN40'-0" IF POSSIBLE. PROVIDE MANUALAIR VENTS AT ALL HIGH POINTS ANDDRAIN VALVES AT ALL LOW POINTS INPIPING SYSTEM.
CARBON DIOXIDE SENSORC
HP-1
FC-1
CFMX2 720
18 1814"Ø, TYP OF 10
CFMX1 1450
24 2418"Ø
CFMX1 1450
24 2418"Ø
40x20 SA
VD VDVD VD
VD
24x20 SAVD
VD
16x16 SA VD
VD
HEATING
VOLT/PHASE
SUPPLY FAN SHALL BE CAPABLE OF PROVIDING 1" EXTERNAL STATIC PRESSURE.
PROVIDE OUTDOOR UNIT WITH HAIL GUARDS, SHORT CYCLE PROTECTION, LOW AMBIENT OPERATION (0 F), COMPRESSOR SOUND BLANKETS, FILTER DRIERS, CRANKCASE HEATERS, AND PROVIDE INDOOR UNIT WITH PROGRAMMABLE THERMOSTAT.
PROVIDE UL 508 WATER LEVEL DETECTION DEVICE TO SHUT DOWN UNIT IF CONDENSATE DRAIN IS PLUGGED.
TOTAL
CFMMODEL NO.INDOOR OUTDOOR
SYMBOLPLAN TRANE
SEERCFM TOTAL SENSBTUH BTUH
MINOA
COOLINGCOMPRELECTRICAL DATA
BTU/HR COP BTU/HR RLACOPHI-TEMP CAP. LO-TEMP CAP. MCA/EVAPCOND
FANFLA
FANFLA
MOCP
1.NOTES:
4.
2.3.
FC-1 TWE240E 7200 1200 226,200 172,000 10 208/3 236,000 3.2 168,000 2 -- -- 14 17.5/30HP-1 TWA240E4 480/3 2 @ 18 2 @ 2.5 -- 45.5/50
THE CONTRACTOR SHALL VISIT THE JOB SITE BEFORE BIDDING TO ACQUAINT HIMSELFWITH THE CONDITIONS UNDER WHICH THE WORK MUST BE CARRIED OUT.
THE CONTRACTOR SHALL DO ALL CUTTING, PATCHING AND REFINISHING REQUIRED FORTHE INSTALLATION OF HIS WORK. HE SHALL CUT, PATCH AND REFINISH TO MATCHADJACENT SURFACES.
MAXIMUM LENGTH OF ALL FLEXIBLE DUCTWORK SHALL BE 8'-0".
ALL SUSPENDED DUCTWORK, PIPING, EQUIPMENT, ETC. SHALL BE HUNG FROMSTRUCTURAL BEAMS AND TOP CHORD OF FLOOR JOISTS. NOTHING SHALL BE HUNGFROM FLOOR DECKING.
KEEP ALL EQUIPMENT SERVICE ACCESS AREAS CLEAR OF ALL ELECTRICAL CONDUITS,CONTROL WIRING, DUCTWORK, WATER PIPING, ETC. SO AS NOT TO HINDER SERVICEACCESS TO EQUIPMENT FOR MAINTENANCE AND REPAIR.
COORDINATE LOCATION OF ALL DUCTWORK WITH EXISTING CONDITIONS BEFOREFABRICATION TO AVOID INTERFERENCES.
PROVIDE 1" THICK, 112" LB DENSITY DUCT LINING FOR THE FOLLOWING DUCTWORK: 1. ALL RECTANGULAR RETURN AIR AND MIXED AIR DUCTS.
CONDENSATE DRAIN PIPING SHALL BE PVC-DWV, SCHEDULE 40.
ALL REMOVED EQUIPMENT (UNLESS NOTED OTHERWISE), PIPING, FITTINGS, VALVES,HANGERS, INSULATION, DUCTWORK REGISTERS, WIRING, CONTROLS, ETC. SHALLBECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THESITE AND DISPOSED OF LEGALLY BY THE CONTRACTOR.
CONTRACTOR SHALL REMOVE EXISTING PORTIONS OF LAY-IN CEILINGS INCLUDINGLIGHT FIXTURES AS REQUIRED FOR INSTALLATION OF NEW HVAC SYSTEM. STORE ANDPROTECT REMOVED PORTIONS OF CEILINGS. REINSTALL CEILINGS WHEN WORK ONHVAC SYSTEM IS COMPLETE. ANY CEILING TILES OR RUNNERS DAMAGED DURINGREMOVAL, STORAGE, OR REINSTALLATION SHALL BE REPLACED BY THE CONTRACTOR.
INDICATED LOCATIONS OF CEILING MOUNTED DIFFUSERS, REGISTERS, EXHAUST FANS,ETC. ARE APPROXIMATED. COORDINATE ACTUAL LOCATION WITH EXISTING LIGHTFIXTURES AND SPRINKLERS.
REFRIGERANT PIPING SIZES INDICATED ARE BASED ON ASHRAE REFRIGERATIONHANDBOOK. PIPING SIZES MAY BE CHANGED TO COMPLY WITH CONDENSING UNITMANUFACTURERS PUBLISHED REQUIREMENTS AND RECOMMENDATIONS.
ALL TEMPERATURE CONTROL WIRING AND DEVICES SHALL BE BY THIS CONTRACTOR INCOMPLIANCE WITH DIVISION 26 REQUIREMENTS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
NOTES (THIS SHEET ONLY):1. CONTRACTOR SHALL PROVIDE 4 INCH HIGH CONCRETE PAD FOR HEAT PUMP UNIT. PAD SHALL BE
CONSTRUCTED OF 3500 PSI CONCRETE WITH WIRE MESH REINFORCING.
2. CONTRACTOR SHALL PROVIDE 96" HIGH CHAIN-LINK FENCE WITH VINYL SLATS IN COLOR SELECTED BYBASE ARCHITECT AND AAFES PROJECT MANAGER.
3. SEE DETAIL THIS SHEET FOR REINFORCING AT CORNERS OF FENCING TYPICAL.
4. TWO PIPE RISES TO 12" ABOVE GRADE AND THRU WALL INTO ELECTRICAL ROOM.
5. PIPE RISES TIGHT TO WALL.
6. INSTALL 2 SETS OF REFRIGERANT PIPING, CONTROL WIRING AND POWER WIRING IN 20" WIDE x 16"DEEP PRECAST CONCRETE PIPE TRENCH WITH 3" THICK CONCRETE COVER FULL WIDTH OF SIDEWALK.
7. INSTALL NEW FAN COIL UNIT ABOVE EXISTING CEILING. SUPPORT FROM STRUCTURE IN COMPLIANCEWITH UFC 4-010-1. SUPPORTS SHALL SUPPORT 150% OF UNIT WEIGHT VERTICALLY AND 50% OF UNITWEIGHT HORIZONTALLY.
8. CONNECT NEW 18" DIA. OUTSIDE AIR INTAKE DUCT TO WALL LOUVER WITH SMOOTH TRANSITION.
9. 3 4" CONDENSATE DRAIN PIPING DOWN TO FLOOR SINK BRACKETED TO WALL. INSULATE WITH 12" THICKELASTOMERIC INSULATION.
10. INSTALL NEW TEMPERATURE SENSOR ON NEW SURFACE J-BOX. PROVIDE NEW RACEWAY TO ABOVECEILING.
11. COORDINATE DUCT ROUTING WITH EXISTING PIPES AND DUCTS IN MECHANICAL ROOM.
12. TWO SETS OF 3 4" OD RL & 138" OD RS PIPING ABOVE CEILING.
13. SUPPORT FC-1 FROM SUPPORTS SPANNING BETWEEN EXISTING BEAMS.
14. INSTALL NEW LOUVER WITH BOTTOM 10'-0" AFF ABOVE DOOR. INSTALL 12" DEEP PLENUM FULL SIZE OFLOUVER WITH 1" THICK DUCT LINER WITH PROTECTANT FINISH.
15. TRANSFER GRILLE FOR MAKE-UP AIR FOR CONDENSER EXHAUST FAN. SEE MD1.1.
16. PROVIDE FILTER RACK FOR 20x24x2 MERV 8 OUTDOOR AIR FILTER IN 20x12 OA DUCT. PROVIDE CEILINGTAG LOCATING ACCESS FOR FILTERS.
17. REINSTALL EXISTING SPRINKLER HEAD AFTER INSTALLATION OF FC-1. RECONNECT TO EXISTINGBRANCH PIPING. MAINTAIN SERVICE CLEARANCES FOR FC-1.
18. PROVIDE 20x12 24VAC LOW LEAKAGE MOTORIZED OUTSIDE AIR DAMPER. INTERLOCK WITH FC-1 FANMOTOR. 3 CFM/SF MAX LEAKAGE AT 1" W.C.
19. INTERLOCK EXISTING EMERGENCY SHUT DOWN SWITCH WITH NEW CONTROLS.
20. CORE DRILL WALL FOR INSTALLATION OF NEW PIPING. SEAL WEATHERTIGHT AROUND PIPING.
X
CONTROL TRANSFORMER.
50010002000
250125
4000
OCTAVE BANDHZ
SOUND POWER
8000OVERALL DBA
63DB
918885
9297
817694
99
PROVIDE UNIT WITH 1/2" ALUM. BIRDSCREEN AND ENAMEL FINISH TO MATCH EXISTING DOOR FRAMES.
MARKMAX.
IN. WC.SP.TYPE
MODEL NO.GREENHECK MAX.
CFMDIMENSIONS (IN)
HEIGHT WIDTH
AREA SQ. FT.
NET FREE DEPTH REMARKS
1.NOTES:WLS-1 EDD-601 INTAKE 1210 0.08 18 36 6 1.8
WLS-1
20x12 OA
D
RL&RS
RL&RS
FRAMEMOUNTING
B.W.E. INDICATES BAKED WHITE ENAMEL FINISH.PAINT ALL BARE METAL SURFACES EXPOSED TO VIEW THRU GRILLE, REGISTER OR DIFFUSER WITH FLAT BLACK PAINT.
1 50 FF RETURN LAY-IN CLG LAY-IN ---- BWE FILTER RETURN WITH OBD AND MERV 8 FILTERS
3.2.
OBD (OPPOSED BLADE DAMPER).
MODEL NO.
1.NOTES:
MARK TITUSUSE
MOUNTINGLOCATION PATTERN
AIRFINISH REMARKS
2 MCD SUPPLY LAY-IN CLG LAY-IN ADJUSTABLE BWE WITH OBD
4'-0"
4'-0"
2'-0"
18" DIA.
1
11
7
9
VD
OUTDOOR UNIT SHALL HAVE EQUIVALENT ACOUSTIC DATA TO TABLE BELOW.5.
5
16
T
10
12
4
6
3 50 F TRANSFER LAY-IN CLG LAY-IN ---- BWE COOLING SELECTION CRITERIA - 105 DEG AIR ENTERING CONDENSER; 78/64 MIXED AIR ENTERING COIL.6.HEATING SELECTION CRITERIA - 30 DEG AIR ENTERING CONDENSER; 63 DEG MIXED AIR ENTERING COIL.7.MIXED AIR TEMPERATURES BASED ON 96/73 OUTDOOR COOLING; 30 DEG OUTDOOR HEATING; 74 DEG 50% RH INDOOR COOLING; 70 DEG INDOOR HEATING.8.
14
8
M
18
CFMX3 1200
22 2215
20x12 OA
S19VD
VDVD
13
17
13
17
20
3
2
1102CONFERENCE ROOM
1652ELEC
1651FIRE PUIMP
1653MECH
1501ADMIN
OFFICE
1502SECURITY
1503ELECTRICAL RM.
1901STAIR 'A'
1801MEN
1902ELEV 1
1002ELEV 1 LOBBY
1001ENTRY
1101OFFICE
L
C
PARTIAL FLOOR PLAN - DEMOLITION - MECHANICALSCALE:1/8" = 1'-0"NORTH
3720-16-000004
JBSA SAM HOUSTON, TX
IMCOMTO AIR CONDITIONING -
ILLINOIS DESIGN FIRM REGISTRATION NO. 184-001152P.O. Box 581 ▪ 413 Main St ▪ Mt. Vernon, IL 62864
[email protected] ▪ (p)618-242-0473 (f)618-242-2330
McCOY and HOWARDCONSULTING ENGINEERS INC.
CHARLES L . CALVERT
I L L I NO I S
ENGINEERPROFESSIONALREGISTERED62046964
OF
35% DESIGN SUBMITTAL 23 SEPT 2016
7 FEB 2017
REPAIR / ADDITION
95% DESIGN SUBMITTAL 6 JAN 2017
100% DESIGN SUBMITTAL 31 JAN 2017
SOLICITATION ISSUE7 FEB 2017
EXISTING RETURN/EXHAUST GRILLE TO BE REMOVED
EXISTING DUCTWORK TO BE REMOVEDSA = SUPPLY AIR, RA = RETURN AIR,OA = OUTSIDE AIR, EA = EXHAUST AIR
EXISTING ROOF MOUNTED EXHAUST FAN OR VENT TO BE REMOVED
EXISTING PIPING TO BE REMOVED
CAP EXISTING DUCTWORK OR PIPINGEXISTING DUCTWORK OR PIPING TO REMAIN
EXISTING THERMOSTAT TO BE REMOVED
HWS = HOT WATER SUPPLYHWR = HOT WATER RETURN
EXISTING DIFFUSER TO BE REMOVED
CWR = CONDENSER WATER RETURN
SA
HWS
CHS = CHILLED WATER SUPPLY
CWS = CONDENSER WATER SUPPLYCHR = CHILLED WATER RETURN
T
EEA = EXISTING EXHAUST AIR DUCTWORKERA = EXISTING RETURN AIR DUCTWORKESA = EXISTING SUPPLY AIR DUCTWORK
EOA = EXISTING OUTSIDE AIR DUCTWORK
NOTES (THIS SHEET ONLY):1. REMOVE EXISTING DIFFUSER/GRILLE AND ASSOCIATED BRANCH DUCTWORK.
2. REMOVE EXISTING CHILLED WATER FAN-COIL UNIT AND ALL ASSOCIATED DUCTWORK, PIPING, ANDCONTROLS. CAP PIPING AT COIL CONNECTIONS.
3. REMOVE EXISTING DUCTWORK AS INDICATED.
4. EXISTING DUCTWORK TO REMAIN.
5. EXISTING LOUVER TO REMAIN.
6. REMOVE EXISTING VAV BOX INCLUDING ALL ASSOCIATED PIPING AND CONTROLS. CAP PIPING ATCOIL CONNECTIONS.
7. EXISTING IN-LINE EXHAUST FAN TO REMAIN.
8. REMOVE EXISTING SENSOR/THERMOSTAT AND ALL ASSOCIATED CONTROL WIRING. INSTALL BLANKCHROME COVER PLATE ON BOX.
9. CAP EXISTING SUPPLY DUCTWORK AIR TIGHT AT WALL.
10. CAP EXISTING TRANSFER DUCT AIR TIGHT AT WALL.
11. REMOVE CHILLED WATER PIPING COMPLETELY. CAP AT WALL. VALVE OFF FROM CHILLED WATERMAINS USING VALVES LOCATED IN THIRD FLOOR MECHANICAL ROOM.
12. EXISTING SPRINKLER HEAD TO REMAIN. TEMPORARILY REMOVE FOR INSTALLATION OF NEW HVAC.REINSTALL IN SAME LOCATION. REVISE PIPING AS REQUIRED. TYPICAL.
13. HVAC SHUT-DOWN SWITCH TO REMAIN FOR CONNECTION TO NEW SYSTEM.
14. REMOVE ELECTRIC DUCT HEATER.
2
X
1
1
3
1
6
6
10
88
7
7
4
4
3
1
8
99
4
5
CEILING RETURN OR EXHAUST
RETURN DUCTPLAN VIEW
DAMPEROPPOSED BLADE
RETURN REGISTERELEVATION
DUCT LINER RETAINER
AIR FLOW
OF FAN.LINER DOWNSTREAMFIRST PIECE OF DUCTLEADING EDGE OF METAL NOSING ON
DUCT LINER
DUCTWORK
SUPPLY DUCT BRANCH TAKE-OFF
D
L = 1/2 W W
DUCTBRANCH
AIR FLOWMAIN DUCT
L 45
W
2 1/4"
1 1/8"
2"4"
1"2"DBA
LARGER36" AND
20" TO 36"W
W/ GREATER THAN 20"DOUBLE VANE ELBOW
AB
90
S
.73 R
.80 R
.87 R
.96 R
1.08 R
1.24 R
1.45 R
1.77 R
2.31 R
3.59 R
.50
.45
.40
.35
.30
.25
.20
.15
.10
.05
R/W
W/ LESS THAN 20"SINGLE VANE ELBOW
4 1/2"
90
2 1/4"
W
ELBOWSHORT RADIUS
R
SW
ELBOWSTANDARD RADIUS
R
W
R=W
MANUAL VOLUME DAMPER
CEILING SUPPLY DIFFUSER
TAKE-OFF
ADAPTER
ROUND TO
NYLON STRAPS
SQUARE
SPIN-IN
ELEVATION
FLEXIBLE DUCT
OPPOSED BLADE
SUPPLY DUCT
6'-0" MAX. LENGTH
MANUAL VOLUME DAMPER
DAMPER
RIGID BRANCH DUCT WITHEXT INSULATION, NOT SHOWN
OUTLET ON AHU DRAIN
1 1/2" CONDENSATE DRAINPVC - DWV
PROVIDE CLEANOUT PLUGSAT ALL CHANGES OF
W/ 1/2" THICK FLEX. FOAMINSULATION.
DIRECTION
AIR GAP
PIPING SCH. 40
PAN
D
D
DEEP SEAL TRAP
DISCHARGE OPEN SITE
FLOOR DRAIN
CLEANOUT PLUG - TYPICAL
SEAL ON TRAP SHALL BETOTAL FAN STATIC PRESSUREPLUS 1"
12 1 1
CHS CHR
11
S
13
3 3
14