Regulator – inspection & testing
-
Upload
gasutility -
Category
Education
-
view
3.445 -
download
2
Transcript of Regulator – inspection & testing
![Page 1: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/1.jpg)
Regulator – Inspection & Testing
Service Regulator
• Service Regulator & Meter Set
Inspection
• Regulator Flow, Lock-up and Leak Tests
![Page 2: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/2.jpg)
Regulator – Inspection & Testing
Service Regulator
A device that controls the pressure
of gas from the service line pressure
(usually 60 psig) to the reduced
pressure ultimately delivered to the
customer.
(usually 7” W.C. or 2 psig)
![Page 3: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/3.jpg)
Regulator – Inspection & TestingLock-up
The pressure at which a regulator
remains under a no-flow or no-load
condition. This lock-up pressure is
always slightly above the set
pressure.
![Page 4: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/4.jpg)
Regulator – Inspection & Testing
Set Pressure
The pressure a regulator is adjusted
to deliver for the required pressure
for the specific load or system. This
pressure is measured between the
outlet connection of the regulator
and the inlet connection of the
meter.
![Page 5: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/5.jpg)
Regulator – Inspection & Testing
Common Set Pressures
• 7” W.C. (1/4” psig)
• 14: W.C. (1/2 psig) < WPS only
• *2 psig (56” W.C.)
• *5 psig (commercial customers)
* requires additional regulator on
customer piping system
![Page 6: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/6.jpg)
Regulator – Inspection & Testing
When are they required?
• When meter is newly installed, tested,
or changed (periodic meter change)
• When replacing meter assembly(meter
set)
![Page 7: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/7.jpg)
Regulator – Inspection & Testing
Inspection
• Inspect general overall condition of
entire meter set
• Inspect discharge vent on outside
regulators
and discharge vent piping from inside
meter sets
![Page 8: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/8.jpg)
Regulator – Inspection & Testing
Test Procedures
Perform flow, lock-up and leak test
per
company procedures and
manufacturers
requirements.
![Page 9: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/9.jpg)
Regulator – Inspection & Testing
Remove Meter
Note: This step does not apply to a new
meter installation.
Close riser valve and using a 14” pipe
wrench remove the meter from the meter
connections on your meter set. Discard
meter gaskets.
![Page 10: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/10.jpg)
Regulator – Inspection & Testing
Flow Testing 1. Select the appropriate test device to use on
your system depending on your
set/delivery
pressure.
2. Attach the test device to the inlet meter
swivel.
Make sure the test device’s valve is closed.
The seal at the meter collar/swivel must be
gas tight, as this will affect the leak test.
![Page 11: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/11.jpg)
Regulator – Inspection & Testing
Flow Testing 3. SLOWLY open the riser valve to the full open
position.
4. Open the test device’s valve. Adjust the set
pressure per company requirements.
Note: Adjust the regulator clockwise to increase
flow pressure, and adjust counter-clockwise
to decrease flow pressure.
![Page 12: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/12.jpg)
Regulator – Inspection & Testing
Set Flow Pressure to the following:
• 7” W.C. system: 7” @ 50 SCFH
• 14” W.C. system: 14” @ 50 SCFH
• 2 PSIG system: 2psig (56”) @ 50 SCFH
Note: 50 SCFH = 50,000 BTU/HR
![Page 13: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/13.jpg)
Regulator – Inspection & Testing
Lock-up Testing
Close the test device’s valve. The riser
valve should still be in the fully opened
position. Continue to observe the test
device for a 3 minute period. The
regulator lock-up pressure should not
exceed your company’s requirements.
![Page 14: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/14.jpg)
Regulator – Inspection & Testing
Lock-up Pressure should not exceed:
• 7” W.C. system: Lock-up @ 10” W.C.
• 14” W.C. system: Lock-up @ 17” W.C.
• 2 psig system: Lock-up @ 2.3 psig (64’ W.C.)
![Page 15: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/15.jpg)
Regulator – Inspection & Testing
Meter Assembly Leak TestingShut off the riser valve. While observing the
test device, bleed a small amount of gas at the
test device’s valve until an acceptable pressure
is reached. Observe the test device for at least
1 minute. A drop in pressure indicates leakage
between the test device and the riser valve. An
increase in pressure indicates a leak through
the riser valve.
![Page 16: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/16.jpg)
Regulator – Inspection & Testing
Acceptable Pressure Reached• 7” W.C. system: pressure should remain
@ 5-6” W.C.
• 14” W.C. system: pressure should remain
@ 9-10” W.C.
• 2 psig system: pressure should remain
@ 30-40” W.C.
![Page 17: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/17.jpg)
Regulator – Inspection & Testing
Riser Valve Leak Testing
The riser valve must remain closed. Bleed
the remaining gas out of test device until
the test device is zero. Observe the test
device for at least 1 minute. If pressure
stays constant, the riser valve is not
leaking. If the pressure increases, the
riser valve is defective and needs repair
or replacement.
![Page 18: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/18.jpg)
Regulator – Inspection & Testing
Internal Relief Valve Testing(WPS only)
The riser valve must remain closed. Blow
pressure back into the outlet of the regulator.
Two tests are required on regulators set for 14”
W.C. or less. On the first try, the internal relief
should open at 35” W.C. or less. This is the ‘as
found’ condition. On the second try, the
internal relief should open at 23” W.C. or lower.
This is the ‘as left’ condition.
![Page 19: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/19.jpg)
Regulator – Inspection & Testing
Restoration of Customer ServiceAfter completion of all tests, replace the old
meter gaskets and reconnect meter to
assembly. Always apply anti-seize compound to
the meter threads prior to connection. Purge air
out of meter prior to making the outlet meter
connection. Tighten meter connections with a
14” pipe wrench and soap test all connections
for possible leakage.
![Page 20: Regulator – inspection & testing](https://reader036.fdocuments.in/reader036/viewer/2022082513/55648578d8b42a73418b4919/html5/thumbnails/20.jpg)
Regulator – Inspection & Testing
Records Completion
• Complete Regulator & Safety Device
Inspection Record
• Complete Gas Meter Record